Industrial dehumidifier (air handler) controller · BACnet points list

Desert Aire ExpertAire LW (Wide Temperature Range) - program 2.0.6 BACnet points list

Updated 28 October 2026

Short answer

The ExpertAire LW is a single-compressor dehumidifier for low and wide temperature ranges. Over BACnet the BMS can switch the unit off, command occupancy, write occupied and unoccupied space temperature and RH setpoints, and send its own zone temperature and RH readings. An optional heartbeat (enable, toggle point and delay) supervises the BMS link. Status and alarms are binary values; unit status and zone-sensor source are integer codes.

This page lists 65 BACnet objects for the Desert Aire ExpertAire LW (Wide Temperature Range) - program 2.0.6 — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Desert Aire’s own free documentation, linked below.

Manufacturer
Desert Aire
Model
ExpertAire LW (Wide Temperature Range) - program 2.0.6
Equipment
Industrial dehumidifier (air handler) controller
Equipment type
Dehumidifiers
BACnet objects
65 (13 writable)
Transport
—
Firmware
Program version 2.0.6
Also known as
ExpertAire LW, LW Series, Desert Aire LW, LW 2.0.6
Source document
BACnet Points List - Unit Type LW For Program Version 2.0.6 · ECN 10971 (Rev. 03) · rev. 2023-10-10
Download CSV 65 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Desert Aire ExpertAire LW (Wide Temperature Range) - program 2.0.6

Integration in brief

Command occupancy (BV 23) and, if the BMS owns start/stop, Remote Off (BV 22). Write the occupied space temperature and RH setpoints (AV 24, AV 23) and the unoccupied ones if used (AV 26, AV 25). If the heartbeat is enabled (BV 26), toggle BV 27 within the delay set in AV 29. Monitor Unit Status (AV 1001), space conditions and Active Alarm (BV 8, inverted).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 22Remote OffUnit off command (1 = off, 0 = on)Write
BV 23Network Occupied InputOccupancy command (1 = occupied)Write
AV 24Network Zone Temperature SetpointOccupied space temperature setpoint, °FWrite
AV 23Network Zone RH SetpointOccupied space RH setpoint, %Write
BV 27Network HeartbeatToggle within AV 29 delay when heartbeat is onWrite
BV 24Remote ResetWrite 1 to resetWrite
AV 1001Unit StatusOperating state code (0-11)Read
AV 4Zone Air Relative HumidityMeasured space RH, %Read
AV 5Zone Air TemperatureMeasured space temperature, °FRead
BV 8Active AlarmUnit alarm; 0 = alarm, 1 = normalRead

Enable & remote start

BV 22 Remote Off turns the unit off when set to 1 and back on at 0. BV 23 Network Occupied Input selects occupied (1) or unoccupied (0); BV 7 confirms the occupied state. BV 25 Blower Continuous switches the blower between automatic and continuous.

Heartbeat & communication loss

Optional. Write BV 26 Network Heartbeat Enable = 1 to turn it on, then toggle BV 27 Network Heartbeat between 1 and 0 within the delay in AV 29 (1-999 s, default 120 s). The list does not say what the unit does when the heartbeat stops.

Sensors & values from the BMS

The BMS can send zone temperature (AV 27) and zone RH (AV 28). AV 1002 Zone Sensor Status shows which sensor is in use (0 = unit sensor, 1 = BMS, 2 = lead unit).

Network setup

Watch out for

Desert Aire ExpertAire LW (Wide Temperature Range) - program 2.0.6 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

65 of 65 shown
Type
AnalogBinary
Access
Show
Desert Aire ExpertAire LW (Wide Temperature Range) - program 2.0.6 BACnet Points List
DescriptionStates
AV1Suction PressureRange 0.0 to 250.0 psig (sent in tenths)psigRead
AV2Discharge PressureRange 0.0 to 650.0 psig (sent in tenths)psigRead
AV3Liquid PressureRange 0.0 to 650.0 psig (sent in tenths)psigRead
AVmin4Zone Air Relative HumidityRange 0.0 to 100.0 % (sent in tenths)%Read
AVmin5Zone Air TemperatureRange -42.0 to 137.0 °F (sent in tenths)°FRead
AV6Zone DewpointRange -42.0 to 137.0 °F (sent in tenths)°FRead
AV7Suction Line TemperatureRange -58.0 to 212.0 °F (sent in tenths)°FRead
AV8Liquid Line TemperatureRange -58.0 to 212.0 °F (sent in tenths)°FRead
AV9Return Air TemperatureRange -58.0 to 212.0 °F (sent in tenths)°FRead
AV10Reheat Condenser Differential Air PressureRange 0.000 to 2.000 in. w.c. (sent in thousandths)in. w.c.Read
AV11Refrigerant SuperheatRange -58.0 to 212.0 °F (sent in tenths)°FRead
AV12Refrigerant SubcoolingRange -58.0 to 212.0 °F (sent in tenths)°FRead
AV13Unit AirflowRange 0 to 1000 cfm (sent in tenths)cfmRead
AV14Air Heating CommandRange 0.0 to 100.0 % (sent in tenths)%Read
AV15Evaporator Bypass Damper CommandRange 0.0 to 100.0 % (sent in tenths)%Read
AV16Outdoor Air Damper CommandRange 0.0 to 100.0 % (sent in tenths)%Read
AV17Evaporator Differential Air PressureRange 0.000 to 2.000 in. w.c. (sent in thousandths)in. w.c.Read
AV18Surface Temperature Sensor 1Range -42.0 to 137.0 °F (sent in tenths)°FRead
AV19Surface Temperature Sensor 2Range -42.0 to 137.0 °F (sent in tenths)°FRead
AV20Surface Temperature Sensor 3Range -42.0 to 137.0 °F (sent in tenths)°FRead
AV21Surface Temperature Sensor 4Range -42.0 to 137.0 °F (sent in tenths)°FRead
AV22Electronic Expansion Valve PositionRange 0.0 to 100.0 % (sent in tenths)%Read
AVmin23Network Zone RH SetpointSettable 0.0 to 99.9 % (sent in tenths)%Write
AVmin24Network Zone Temperature SetpointSettable 32.0 to 99.9 °F (sent in tenths)°FWrite
AV25Network Un-Occupied Zone RH SetpointSettable 0.0 to 99.9 % (sent in tenths)%Write
AV26Network Un-Occupied Zone Temperature SetpointSettable 32.0 to 99.9 °F (sent in tenths)°FWrite
AV27Network Zone TemperatureBMS zone temperature input, 32.0-99.9 °F°FWrite
AV28Network Zone Relative HumidityBMS zone RH input, 0.0-99.9 %%Write
AV29Network Heartbeat DelayHeartbeat timeout, 1-999 s, default 120 ssWrite
AV30Active Zone RH SetpointRange 0.0 to 100.0 % (sent in tenths)%Read
AV31Active Zone Temperature SetpointRange -42.0 to 137.0 °F (sent in tenths)°FRead
AVmin1001Unit StatusCurrent operating state code (listed as INT)Read0=Zone Satisfied, 1=Heating Required, 2=Cooling Required, 3=Dehumidification Required, 4=Dehum/Heat, 5=Dehum/Cool, 6=Low Airflow, 7=Defrost Cycle, 8=Low R/A Temp, 9=ExV Initialize, 10=Surface Dehum, 11=Factory Test Running
AV1002Zone Sensor StatusWhich zone sensor is in use (listed as INT)Read0=Zone Sensor, 1=BMS Zone Sensor, 2=Lead Unit Zone Sensor
BV1Supply FanRead0=Off, 1=On
BV2CompressorRead0=Off, 1=On
BV3Liquid SolenoidRead0=Off, 1=On
BV4Defrost SolenoidRead0=Off, 1=On
BV5Reheat SolenoidRead0=Off, 1=On
BV6Heating RequiredRead0=Off, 1=On
BV7Occupied StatusRead0=Unoccupied, 1=Occupied
BVmin8Active AlarmUnit alarm state (inverted)Read0=Alarm, 1=Normal
BV9Retain Memory AlarmRead0=No Alarm, 1=Alarm
BV10Retain Memory Write AlarmRead0=No Alarm, 1=Alarm
BV11Blower Overload AlarmRead0=No Overload, 1=Overload
BV12Compressor Overload AlarmRead0=No Overload, 1=Overload
BV13Smoke/ General AlarmRead0=No Alarm, 1=Alarm
BV14Low Suction Pressure AlarmRead0=No Alarm, 1=Alarm
BV15Discharge Pressure AlarmRead0=No Alarm, 1=Alarm
BV16Zone Sensor FaultRead0=No Fault, 1=Fault
BV17c.PCOe Configuration Error AlarmRead0=No Error, 1=Error
BV18c.PCOe Offline AlarmExpansion module offlineRead0=Online, 1=Offline
BV19ExV Motor AlarmRead0=No Error, 1=Error
BV20ExV Control AlarmRead0=No Error, 1=Error
BV21ExV Emergency Closing AlarmRead0=No Action, 1=Emergency Closing
BVmin22Remote OffUnit off commandWrite0=On, 1=Off
BVmin23Network Occupied InputOccupancy commandWrite0=Unoccupied, 1=Occupied
BVmin24Remote ResetWrite 1 to reset; clears itself after a scanWrite
BV25Blower ContinuousBlower mode commandWrite0=Automatic, 1=Continuous
BV26Network Heartbeat EnableEnables the BMS heartbeat checkWrite0=Disabled, 1=Enabled
BVmin27Network HeartbeatToggle 1/0 within the heartbeat delayWrite
BV28Discharge Pressure Sensor AlarmRead0=No Alarm, 1=Alarm
BV29Network Sensor AlarmRead0=No Alarm, 1=Alarm
BV30Lead Sensor AlarmRead0=No Alarm, 1=Alarm
BV31Very Low Suction Pressure AlarmRead0=No Alarm, 1=Alarm
BV32Suction Temperature Sensor AlarmRead0=No Alarm, 1=Alarm

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ExpertAire LW (Wide Temperature Range) - program 2.0.6 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Desert Aire ExpertAire LW (Wide Temperature Range) - program 2.0.6

How many BACnet points does the Desert Aire ExpertAire LW (Wide Temperature Range) - program 2.0.6 have?

This list has 65 BACnet objects: 33 analog values, 32 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Desert Aire ExpertAire LW (Wide Temperature Range) - program 2.0.6 BACnet points are writable?

13 of the 65 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Desert Aire ExpertAire LW (Wide Temperature Range) - program 2.0.6 BACnet documentation?

The source is BACnet Points List - Unit Type LW For Program Version 2.0.6 (ECN 10971 (Rev. 03)), revision 2023-10-10, published free by Desert Aire at https://www.desert-aire.com/wp-content/uploads/2025/04/LW-BACnet-Points-Ver-2_0_6.pdf.

What are the minimum BACnet points to integrate the Desert Aire ExpertAire LW (Wide Temperature Range) - program 2.0.6?

Start with BV 22 Remote Off (Unit off command (1 = off, 0 = on)); BV 23 Network Occupied Input (Occupancy command (1 = occupied)); AV 24 Network Zone Temperature Setpoint (Occupied space temperature setpoint, °F); AV 23 Network Zone RH Setpoint (Occupied space RH setpoint, %); BV 27 Network Heartbeat (Toggle within AV 29 delay when heartbeat is on); BV 24 Remote Reset (Write 1 to reset); AV 1001 Unit Status (Operating state code (0-11)); AV 4 Zone Air Relative Humidity (Measured space RH, %); AV 5 Zone Air Temperature (Measured space temperature, °F); BV 8 Active Alarm (Unit alarm; 0 = alarm, 1 = normal).

How do I enable BMS control of the Desert Aire ExpertAire LW (Wide Temperature Range) - program 2.0.6?

BV 22 Remote Off turns the unit off when set to 1 and back on at 0. BV 23 Network Occupied Input selects occupied (1) or unoccupied (0); BV 7 confirms the occupied state. BV 25 Blower Continuous switches the blower between automatic and continuous.

Does the Desert Aire ExpertAire LW (Wide Temperature Range) - program 2.0.6 need a BACnet heartbeat or have a communication timeout?

Optional. Write BV 26 Network Heartbeat Enable = 1 to turn it on, then toggle BV 27 Network Heartbeat between 1 and 0 within the delay in AV 29 (1-999 s, default 120 s). The list does not say what the unit does when the heartbeat stops.

Can the BMS supply sensor values to the Desert Aire ExpertAire LW (Wide Temperature Range) - program 2.0.6?

The BMS can send zone temperature (AV 27) and zone RH (AV 28). AV 1002 Zone Sensor Status shows which sensor is in use (0 = unit sensor, 1 = BMS, 2 = lead unit).

How do I check these points on the real ExpertAire LW (Wide Temperature Range) - program 2.0.6?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Desert Aire BACnet points lists

Source: BACnet Points List - Unit Type LW For Program Version 2.0.6 · ECN 10971 (Rev. 03) · rev. 2023-10-10. Object names, instances and units are reproduced as published; descriptions are our own.