Indoor air quality sensor (room) · BACnet points list

Delta Electronics UNOslim IAQ sensor (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The UNOslim is a slim room air quality sensor with RS-485 for Modbus RTU or BACnet MS/TP and an optional external thermistor. Over BACnet it reports temperature, humidity, CO2, VOC, PM1/PM2.5/PM10, the RESET air and viral indexes, built-in and external temperature/humidity and dew point, and has writable calibration, display, relay and NFC-lock values.

This page lists 31 BACnet objects for the Delta Electronics UNOslim IAQ sensor (BACnet MS/TP) — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Delta Electronics’s own free documentation, linked below.

Manufacturer
Delta Electronics
Model
UNOslim IAQ sensor (BACnet MS/TP)
Equipment
Indoor air quality sensor (room)
Equipment type
Thermostats, sensors & meters
BACnet objects
31 (12 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
From the serial number (e.g. SN 2512M0170040 gives 120040)
Also known as
UNOslim, UNO-M, Delta UNOslim, UNOslim RS485
Source document
UNOslim Modbus/BACnet User Guide · rev. VER 0.7
Download CSV 31 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Delta Electronics’s current documentation and the live device before use. Not official Delta Electronics information. Terms of use.

BMS integration notes: Delta Electronics UNOslim IAQ sensor (BACnet MS/TP)

Integration in brief

Select BACnet mode, set the MS/TP MAC (or write AV 5) and baud, then read the measurements. AV 10 lets the BMS drive the on-board relay.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 10Relay_out_refRelay command: 1 = COM-NO closedWrite
AI 3CO2CO2, ppmRead
AI 0TemperatureRoom temperature, °CRead
AI 2HumidityRelative humidity, %Read
AI 5PM2.5PM2.5, µg/m³Read
AI 4VOCTotal VOC, µg/m³Read
AI 8AQIRESET air index, %Read

Network setup

Delta Electronics UNOslim IAQ sensor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

31 of 31 shown
Type
Access
Show
Delta Electronics UNOslim IAQ sensor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin0TemperatureTemperature (thermistor if fitted, else built-in)°CRead
AI1Temperature_FTemperature in Fahrenheit°FRead
AImin2HumidityRelative humidity (thermistor-compensated if fitted)%Read
AImin3CO2CO2 concentrationppmRead
AImin4VOCTotal VOCµg/m³Read
AImin5PM2.5PM2.5µg/m³Read
AI6PM10PM10µg/m³Read
AI7PM1PM1µg/m³Read
AImin8AQIRESET air index, 0-100%Read
AI9RVIRESET viral index, 0-99 (higher is better)%Read
AI10RVI_LabelRVI categoryRead0=Poor; 1=Unsatisfactory; 2=Needs Improvement; 3=Fair; 4=Good; 5=Excellent
AI11Int_TemperatureBuilt-in sensor temperature°CRead
AI12Int_Temperature_FBuilt-in sensor temperature°FRead
AI13Ext_TemperatureThermistor temperature (if fitted)°CRead
AI14Ext_Temeprature_FThermistor temperature (if fitted)°FRead
AI15Int_HumidityBuilt-in sensor humidity%Read
AI16Ext_HumidityHumidity using thermistor temperature (if fitted)%Read
AI17Dew_TemepratureDew point temperature°CRead
AV0Temperature_CaliTemperature reference 0-50 in 0.01 °C; 9999 resets°CWrite
AV1Humidity_CaliHumidity reference 10-90 %RH; 9999 resets%Write
AV2CO2_CaliCO2 reference 400-1500 ppm%Write
AV3PM_CaliPM2.5 reference 1-500; 9999 resetsµg/m³Write
AV4VOC_CaliTVOC reference 1-500; 9999 resetsµg/m³Write
AV5MAC_AddressMS/TP MAC 0-127; 255 clears; rebootsWrite
AV6CO2_ASCCO2 automatic self-calibrationWrite0=Disable; 1=Enable
AV7Temp_UnitDisplay temperature unitWrite0=Celsius; 1=Fahrenheit
AV8Low_Power_ModeSensor low power modeWrite0=Disable; 1=Enable
AV9Disp_modeDisplay modeWrite0=Auto off (ToF); 1=Always on; 2=Always off
AVmin10Relay_out_refRelay commandWrite0=COM-NC closed; 1=COM-NO closed
AV11Relay_valRelay stateRead0=COM-NC closed; 1=COM-NO closed
AV12NFC_LockBlocks configuration writes over NFCWrite0=Unlocked; 1=Locked
Object ID lookup: Delta Electronics UNOslim IAQ sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the UNOslim IAQ sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Delta Electronics UNOslim IAQ sensor (BACnet MS/TP)

How many BACnet points does the Delta Electronics UNOslim IAQ sensor (BACnet MS/TP) have?

This list has 31 BACnet objects: 18 analog inputs, 13 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Delta Electronics UNOslim IAQ sensor (BACnet MS/TP) BACnet points are writable?

12 of the 31 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Delta Electronics UNOslim IAQ sensor (BACnet MS/TP) BACnet documentation?

The source is UNOslim Modbus/BACnet User Guide, revision VER 0.7, published free by Delta Electronics at https://isdweb.deltaww.com/resources/files/UNOslim_RS485_User_Guide.pdf.

What are the minimum BACnet points to integrate the Delta Electronics UNOslim IAQ sensor (BACnet MS/TP)?

Start with AV 10 Relay_out_ref (Relay command: 1 = COM-NO closed); AI 3 CO2 (CO2, ppm); AI 0 Temperature (Room temperature, °C); AI 2 Humidity (Relative humidity, %); AI 5 PM2.5 (PM2.5, µg/m³); AI 4 VOC (Total VOC, µg/m³); AI 8 AQI (RESET air index, %).

How do I check these points on the real UNOslim IAQ sensor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Delta Electronics BACnet points lists

Source: UNOslim Modbus/BACnet User Guide · rev. VER 0.7. Object names, instances and units are reproduced as published; descriptions are our own.