Indoor air quality sensor (room) · BACnet points list

Delta Electronics UNOlite indoor air quality monitor (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The UNOlite is a room air quality monitor with an RS-485 port that runs Modbus or BACnet MS/TP (DIP switch 7 ON). Over BACnet it reports temperature, humidity, PM1/PM2.5/PM10, CO2, TVOC, an IAQ index and the RESET viral index (RVI), and has writable values for MAC address, sensor calibration, CO2 self-calibration, display and IAQ LED thresholds.

This page lists 29 BACnet objects for the Delta Electronics UNOlite indoor air quality monitor (BACnet MS/TP) — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Delta Electronics’s own free documentation, linked below.

Manufacturer
Delta Electronics
Model
UNOlite indoor air quality monitor (BACnet MS/TP)
Equipment
Indoor air quality sensor (room)
Equipment type
Thermostats, sensors & meters
BACnet objects
29 (15 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
From the serial number (e.g. SN 2301L0170040 gives 010040)
Also known as
UNOlite, UNOlite LWD, Delta UNOlite, UNOLite BACnet
Source document
UNOlite BACnet User Guide · rev. VER 0.5
Download CSV 29 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Delta Electronics’s current documentation and the live device before use. Not official Delta Electronics information. Terms of use.

BMS integration notes: Delta Electronics UNOlite indoor air quality monitor (BACnet MS/TP)

Integration in brief

Set DIP 7 ON for BACnet, DIP 1-4 for the MAC address (0-15) and DIP 5-6 for the baud rate, then read the measurements. Use AV 0 for MAC addresses above 15.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 5CO2CO2, ppmRead
AI 0TemperatureRoom temperature, °CRead
AI 1HumidityRelative humidity, %Read
AI 2PM2.5PM2.5, µg/m³Read
AI 7TVOCTVOC, ppmRead
AI 8IAQAir quality index (green 0-80, red above 100)Read

Network setup

Watch out for

Delta Electronics UNOlite indoor air quality monitor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

29 of 29 shown
Type
Access
Show
Delta Electronics UNOlite indoor air quality monitor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin0TemperatureTemperature, 0-50°CRead
AImin1HumidityRelative humidity, 10-80%Read
AImin2PM2.5PM2.5, 0-1000µg/m³Read
AI3PM10PM10, 0-1000µg/m³Read
AI4PM1PM1, 0-1000µg/m³Read
AImin5CO2CO2, 400-5000ppmRead
AI6Temperature_FTemperature in Fahrenheit°FRead
AImin7TVOCTVOC, 0-30ppmRead
AImin8IAQAir quality index from PM and CO2 (drives IAQ LED)Read
AI9TVOC_ugm3TVOC, 0-7000µg/m³Read
AI10RVIViral infection risk index, 0-99 (higher is better)%Read
AI11RVI_LabelRVI categoryRead0=Poor; 1=Unsatisfactory; 2=Needs Improvement; 3=Fair; 4=Good; 5=Excellent
AV0MAC AddressMS/TP MAC 0-127; overrides DIP; 255 clears; rebootsWrite
AV1Temperature_CaliWrite actual temperature x100 to calibrate°CWrite
AV2CO2_CaliWrite actual CO2 (400-1500) to calibrate; disables ASCppmWrite
AV3CO2_ASCCO2 automatic self-calibration on/offWrite0=Off; 1=On
AV4Dim ModeLED/screen dimming modeWrite0=Auto-Dim (LWD only); 1=Dim disabled; 2=Dim
AV5PM_CaliPM2.5 reference 20-1000 for calibration; 9999 resetsWrite
AV6RESET_TVOCWrite 1 to reset the TVOC baselineWrite
AV7EN_CUS_IAQEnable custom IAQ LED thresholdsWrite
AV8IAQ_PM25IAQ LED threshold for PM2.5Write
AV9IAQ_PM10IAQ LED threshold for PM10Write
AV10IAQ_CO2IAQ LED threshold for CO2Write
AV11ECO_PWRUNOeco ventilation power suggestionRead
AV12ECO_SPDUNOeco ventilation speed suggestionRead
AV13Set_OLED_FahrenheitDisplay temperature unitWrite0=Celsius; 1=Fahrenheit
AV14Set_Low_PowerSensor power modeWrite0=Normal; 1=Low power
AV15HUMI_CaliHumidity calibration, 1000-9000 (x100); 9999 resets%Write
AV16TVOC_CaliTVOC reference 1-500 ppb for calibration; 9999 resetsppbWrite
Object ID lookup: Delta Electronics UNOlite indoor air quality monitor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the UNOlite indoor air quality monitor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Delta Electronics UNOlite indoor air quality monitor (BACnet MS/TP)

How many BACnet points does the Delta Electronics UNOlite indoor air quality monitor (BACnet MS/TP) have?

This list has 29 BACnet objects: 12 analog inputs, 17 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Delta Electronics UNOlite indoor air quality monitor (BACnet MS/TP) BACnet points are writable?

15 of the 29 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Delta Electronics UNOlite indoor air quality monitor (BACnet MS/TP) BACnet documentation?

The source is UNOlite BACnet User Guide, revision VER 0.5, published free by Delta Electronics at https://isdweb.deltaww.com/resources/files/UNOlite_bacnet_user_guide.pdf.

What are the minimum BACnet points to integrate the Delta Electronics UNOlite indoor air quality monitor (BACnet MS/TP)?

Start with AI 5 CO2 (CO2, ppm); AI 0 Temperature (Room temperature, °C); AI 1 Humidity (Relative humidity, %); AI 2 PM2.5 (PM2.5, µg/m³); AI 7 TVOC (TVOC, ppm); AI 8 IAQ (Air quality index (green 0-80, red above 100)).

How do I check these points on the real UNOlite indoor air quality monitor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.