Power and energy meter (panel meter) · BACnet points list
Delta Electronics DPM-C530A power meter (BACnet MS/TP) BACnet points list
Updated 7 November 2026Unofficial source
The DPM-C530A serves its measurements as Analog Values on BACnet MS/TP. AV 0-10 are commandable setup objects (wiring system, CT and PT ratios, demand settings, language, energy reset); AV 11-85 are read-only voltage, current, unbalance, power factor, power, energy, THD and demand values.
This page lists 86 BACnet objects for the Delta Electronics DPM-C530A power meter (BACnet MS/TP) — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Delta Electronics’s documentation hosted by BACnet International catalog, not by Delta Electronics itself, so treat it as unofficial.
- Manufacturer
- Delta Electronics
- Model
- DPM-C530A power meter (BACnet MS/TP)
- Equipment
- Power and energy meter (panel meter)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 86 (11 writable)
- Transport
- BACnet MS/TP
- Firmware
- Ver 01.1820
- Also known as
- DPM-C530A, Delta DPM-C530, Delta multifunction power meter BACnet
- Source document
- DPM-C530A BACnet Protocol Implementation Conformance Statement · rev. 2016-01-07 (unofficial copy, hosted by BACnet International catalog)
Reference only, provided as-is: verify against Delta Electronics’s current documentation and the live device before use. Not official Delta Electronics information. Terms of use.
BMS integration notes: Delta Electronics DPM-C530A power meter (BACnet MS/TP)
Set CT/PT ratios and the wiring system at the meter (or AV 0-5) once, then read the read-only power, energy, demand, PF, current and voltage AVs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 49 | AV_049_Active_Power_Total | Total real power, kW | Read |
| AV 61 | AV_061_Active_Energy-delivered | Delivered energy, kWh | Read |
| AV 80 | AV_080_Present_Demand_Active_Power | Present real power demand, kW | Read |
| AV 40 | AV_040_Power_Factor_Total | Total power factor (sign = lead/lag) | Read |
| AV 34 | AV_034_Current_AVG | Average current, A | Read |
| AV 18 | AV_018_Voltage_L-N_AVG | Average L-N voltage, V | Read |
| AV 48 | AV_048_Frequency | Frequency, Hz | Read |
Network setup
- BACnet MS/TP master at 9600, 19200 or 38400 baud.
- Device object instance and name are writable over BACnet.
Watch out for
- AV 0-10 are configuration values (commandable); don't write them cyclically from the BMS.
- AV 10 Reset_Parameter resets energy when written with 0x5768.
Delta Electronics DPM-C530A power meter (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 0 | AV_000_Power_System | Command | 0=3φ4W 1=3φ3W 2=1φ2W 3=1φ3W | ||
| AV | 1 | AV_001_Primary_CT | Range 1 ~ 9999 A | A | Command | |
| AV | 2 | AV_002_Secondary_CT | A | Command | 0=1A 1=5A 2=2.5A | |
| AV | 3 | AV_003_Primary_PT | Range 1 ~ 9999 V | V | Command | |
| AV | 4 | AV_004_Secondary_PT | Range 1 ~ 9999 V | V | Command | |
| AV | 5 | AV_005_Number_of_Transformer | Command | 0=3CT3PT 1=3CT2PT 2=3CT0PT 3=2CT3PT 4=2CT2PT 5=2CT0PT 6=1CT3PT 7=1CT2PT 8=1CT0PT | ||
| AV | 6 | AV_006_Demand_Mode | Command | 0=block | ||
| AV | 7 | AV_007_Demand_Interval | Range 1 ~ 60 min | min | Command | |
| AV | 8 | AV_008_Phase Rotation | Command | 0=ABC 1=CBA | ||
| AV | 9 | AV_009_UI_Language | Command | 0=English 1=Traditional Chinese 2=Simplify Chinese | ||
| AV | 10 | AV_010_Reset_Parameter | 0x5768=kWh | Command | ||
| AV | 11 | AV_011_Reserved | Read | |||
| AV | 12 | AV_012_Reserved | Read | |||
| AV | 13 | AV_013_Reserved | Read | |||
| AV | 14 | AV_014_Reserved | Read | |||
| AV | 15 | AV_015_Voltage_L-N_AN | Range 0.000 ~ 99999.999 V | V | Read | |
| AV | 16 | AV_016_Voltage_L-N_BN | Range 0.000 ~ 99999.999 V | V | Read | |
| AV | 17 | AV_017_Voltage_L-N_CN | Range 0.000 ~ 99999.999 V | V | Read | |
| AVmin | 18 | AV_018_Voltage_L-N_AVG | Range 0.000 ~ 99999.999 V | V | Read | |
| AV | 19 | AV_019_Voltage_L-L_AB | Range 0.000 ~ 99999.999 V | V | Read | |
| AV | 20 | AV_020_Voltage_L-L_BC | Range 0.000 ~ 99999.999 V | V | Read | |
| AV | 21 | AV_021_Voltage_L-L_CA | Range 0.000 ~ 99999.999 V | V | Read | |
| AV | 22 | AV_022_Voltage_L-L_AVG | Range 0.000 ~ 99999.999 V | V | Read | |
| AV | 23 | AV_023_Unbalance_Voltage_L-N_AN | Range 0.00 ~ 99.99 % | % | Read | |
| AV | 24 | AV_024_Unbalance_Voltage_L-N_BN | Range 0.00 ~ 99.99 % | % | Read | |
| AV | 25 | AV_025_Unbalance_Voltage_L-N_CN | Range 0.00 ~ 99.99 % | % | Read | |
| AV | 26 | AV_026_Unbalance_Voltage_L-N_AVG | Range 0.00 ~ 99.99 % | % | Read | |
| AV | 27 | AV_027_Unbalance_Voltage_L-L_AB | Range 0.00 ~ 99.99 % | % | Read | |
| AV | 28 | AV_028_Unbalance_Voltage_L-L_BC | Range 0.00 ~ 99.99 % | % | Read | |
| AV | 29 | AV_029_Unbalance_Voltage_L-L_CA | Range 0.00 ~ 99.99 % | % | Read | |
| AV | 30 | AV_030_Unbalance_Voltage_L-L_AVG | Range 0.00 ~ 99.99 % | % | Read | |
| AV | 31 | AV_031_Current_A | Range 0.000 ~ 99999.999 A | A | Read | |
| AV | 32 | AV_032_Current_B | Range 0.000 ~ 99999.999 A | A | Read | |
| AV | 33 | AV_033_Current_C | Range 0.000 ~ 99999.999 A | A | Read | |
| AVmin | 34 | AV_034_Current_AVG | Range 0.000 ~ 99999.999 A | A | Read | |
| AV | 35 | AV_035_Current_Neutral | Range 0.000 ~ 99999.999 A | A | Read | |
| AV | 36 | AV_036_Unbalance_Current_A | Range 0.00 ~ 99.99 % | % | Read | |
| AV | 37 | AV_037_Unbalance_Current_B | Range 0.00 ~ 99.99 % | % | Read | |
| AV | 38 | AV_038_Unbalance_Current_C | Range 0.00 ~ 99.99 % | % | Read | |
| AV | 39 | AV_039_Unbalance_Current_AVG | Range 0.00 ~ 99.99 % | % | Read | |
| AVmin | 40 | AV_040_Power_Factor_Total | Range 0 to 1; negative = leading, positive = lagging | PF | Read | |
| AV | 41 | AV_041_Power_Factor_A | Range 0 to 1; negative = leading, positive = lagging | PF | Read | |
| AV | 42 | AV_042_Power_Factor_B | Range 0 to 1; negative = leading, positive = lagging | PF | Read | |
| AV | 43 | AV_043_Power_Factor_C | Range 0 to 1; negative = leading, positive = lagging | PF | Read | |
| AV | 44 | AV_044_Displacement_Power_Factor_Total | Range 0 to 1; negative = leading, positive = lagging | PF | Read | |
| AV | 45 | AV_045_Displacement_Power_Factor_A | Range 0 to 1; negative = leading, positive = lagging | PF | Read | |
| AV | 46 | AV_046_Displacement_Power_Factor_B | Range 0 to 1; negative = leading, positive = lagging | PF | Read | |
| AV | 47 | AV_047_Displacement_Power_Factor_C | Range 0 to 1; negative = leading, positive = lagging | PF | Read | |
| AVmin | 48 | AV_048_Frequency | Range 0.0000 ~ 99.9999 Hz | Hz | Read | |
| AVmin | 49 | AV_049_Active_Power_Total | Range -99999.999 ~ 99999.999 kW | kW | Read | |
| AV | 50 | AV_050_Active_Power_A | Range -99999.999 ~ 99999.999 kW | kW | Read | |
| AV | 51 | AV_051_Active_Power_B | Range -99999.999 ~ 99999.999 kW | kW | Read | |
| AV | 52 | AV_052_Active_Power_C | Range -99999.999 ~ 99999.999 kW | kW | Read | |
| AV | 53 | AV_053_Reactive_Power_Total | Range -99999.999 ~ 99999.999 kVAR | kvar | Read | |
| AV | 54 | AV_054_Reactive_Power_A | Range -99999.999 ~ 99999.999 kVAR | kvar | Read | |
| AV | 55 | AV_055_Reactive_Power_B | Range -99999.999 ~ 99999.999 kVAR | kvar | Read | |
| AV | 56 | AV_056_Reactive_Power_C | Range -99999.999 ~ 99999.999 kVAR | kvar | Read | |
| AV | 57 | AV_057_Apparent_Power_Total | Range 0.000 ~ 99999.999 kVA | kVA | Read | |
| AV | 58 | AV_058_Apparent_Power_A | Range 0.000 ~ 99999.999 kVA | kVA | Read | |
| AV | 59 | AV_059_Apparent_Power_B | Range 0.000 ~ 99999.999 kVA | kVA | Read | |
| AV | 60 | AV_060_Apparent_Power_C | Range 0.000 ~ 99999.999 kVA | kVA | Read | |
| AVmin | 61 | AV_061_Active_Energy-delivered | Range 0.000 ~ 4294967.295 kWh | kWh | Read | |
| AV | 62 | AV_062_Active_Energy-received | Range 0.000 ~ 4294967.295 kWh | kWh | Read | |
| AV | 63 | AV_063_Reactive_Energy-delivered | Range 0.000 ~ 4294967.295 kVARh | kvarh | Read | |
| AV | 64 | AV_064Reactive_Energy-received | Range 0.000 ~ 4294967.295 kVARh | kvarh | Read | |
| AV | 65 | AV_065_Apparent_Energy-delivered | Range 0.000 ~ 4294967.295 kVAh | kVAh | Read | |
| AV | 66 | AV_066_Apparent_Energy-received | Range 0.000 ~ 4294967.295 kVAh | kVAh | Read | |
| AV | 67 | AV_067_THD_Current_A | Range 0.000 ~ 999.999 % | % | Read | |
| AV | 68 | AV_068_THD_Current_B | Range 0.000 ~ 999.999 % | % | Read | |
| AV | 69 | AV_069_THD_Current_C | Range 0.000 ~ 999.999 % | % | Read | |
| AV | 70 | AV_070_THD_Voltage_L-N_AN | Range 0.000 ~ 999.999 % | % | Read | |
| AV | 71 | AV_071_THD_Voltage_L-N_BN | Range 0.000 ~ 999.999 % | % | Read | |
| AV | 72 | AV_072_THD_Voltage_L-N_CN | Range 0.000 ~ 999.999 % | % | Read | |
| AV | 73 | AV_073_THD_Voltage_L-L_AB | Range 0.000 ~ 999.999 % | % | Read | |
| AV | 74 | AV_074_THD_Voltage_L-L_BC | Range 0.000 ~ 999.999 % | % | Read | |
| AV | 75 | AV_075_THD_Voltage_L-L_CA | Range 0.000 ~ 999.999 % | % | Read | |
| AV | 76 | AV_076_THD_Current | Range 0.000 ~ 999.999 % | % | Read | |
| AV | 77 | AV_077_THD_Voltage | Range 0.000 ~ 999.999 % | % | Read | |
| AV | 78 | AV_078_Present_Demand_Current | Range 0.000 ~ 99999.999 A | A | Read | |
| AV | 79 | AV_079_Previous_Demand_Current | Range 0.000 ~ 99999.999 A | A | Read | |
| AVmin | 80 | AV_080_Present_Demand_Active_Power | Range 0.000 ~ 99999.999 kW | kW | Read | |
| AV | 81 | AV_081_Previous_Demand_Active_Power | Range 0.000 ~ 99999.999 kW | kW | Read | |
| AV | 82 | AV_082_Present_Demand_Reactive_Power | Range 0.000 ~ 99999.999 kVAR | kvar | Read | |
| AV | 83 | AV_083_Previous_Demand_Reactive_Power | Range 0.000 ~ 99999.999 kVAR | kvar | Read | |
| AV | 84 | AV_084_Present_Demand_Apparent_Power | Range 0.000 ~ 99999.999 kVA | kVA | Read | |
| AV | 85 | AV_085_Previous_Demand_Apparent_Power | Range 0.000 ~ 99999.999 kVA | kVA | Read |
No points match these filters.
Object ID lookup: Delta Electronics DPM-C530A power meter point IDs by name
AV0AV_000_Power_SystemAV1AV_001_Primary_CTAV2AV_002_Secondary_CTAV3AV_003_Primary_PTAV4AV_004_Secondary_PTAV5AV_005_Number_of_TransformerAV6AV_006_Demand_ModeAV7AV_007_Demand_IntervalAV8AV_008_Phase RotationAV9AV_009_UI_LanguageAV10AV_010_Reset_ParameterAV11AV_011_ReservedAV12AV_012_ReservedAV13AV_013_ReservedAV14AV_014_ReservedAV15AV_015_Voltage_L-N_ANAV16AV_016_Voltage_L-N_BNAV17AV_017_Voltage_L-N_CNAV18AV_018_Voltage_L-N_AVGAV19AV_019_Voltage_L-L_ABAV20AV_020_Voltage_L-L_BCAV21AV_021_Voltage_L-L_CAAV22AV_022_Voltage_L-L_AVGAV23AV_023_Unbalance_Voltage_L-N_ANAV24AV_024_Unbalance_Voltage_L-N_BNAV25AV_025_Unbalance_Voltage_L-N_CNAV26AV_026_Unbalance_Voltage_L-N_AVGAV27AV_027_Unbalance_Voltage_L-L_ABAV28AV_028_Unbalance_Voltage_L-L_BCAV29AV_029_Unbalance_Voltage_L-L_CAAV30AV_030_Unbalance_Voltage_L-L_AVGAV31AV_031_Current_AAV32AV_032_Current_BAV33AV_033_Current_CAV34AV_034_Current_AVGAV35AV_035_Current_NeutralAV36AV_036_Unbalance_Current_AAV37AV_037_Unbalance_Current_BAV38AV_038_Unbalance_Current_CAV39AV_039_Unbalance_Current_AVGAV40AV_040_Power_Factor_TotalAV41AV_041_Power_Factor_AAV42AV_042_Power_Factor_BAV43AV_043_Power_Factor_CAV44AV_044_Displacement_Power_Factor_TotalAV45AV_045_Displacement_Power_Factor_AAV46AV_046_Displacement_Power_Factor_BAV47AV_047_Displacement_Power_Factor_CAV48AV_048_FrequencyAV49AV_049_Active_Power_TotalAV50AV_050_Active_Power_AAV51AV_051_Active_Power_BAV52AV_052_Active_Power_CAV53AV_053_Reactive_Power_TotalAV54AV_054_Reactive_Power_AAV55AV_055_Reactive_Power_BAV56AV_056_Reactive_Power_CAV57AV_057_Apparent_Power_TotalAV58AV_058_Apparent_Power_AAV59AV_059_Apparent_Power_BAV60AV_060_Apparent_Power_CAV61AV_061_Active_Energy-deliveredAV62AV_062_Active_Energy-receivedAV63AV_063_Reactive_Energy-deliveredAV64AV_064Reactive_Energy-receivedAV65AV_065_Apparent_Energy-deliveredAV66AV_066_Apparent_Energy-receivedAV67AV_067_THD_Current_AAV68AV_068_THD_Current_BAV69AV_069_THD_Current_CAV70AV_070_THD_Voltage_L-N_ANAV71AV_071_THD_Voltage_L-N_BNAV72AV_072_THD_Voltage_L-N_CNAV73AV_073_THD_Voltage_L-L_ABAV74AV_074_THD_Voltage_L-L_BCAV75AV_075_THD_Voltage_L-L_CAAV76AV_076_THD_CurrentAV77AV_077_THD_VoltageAV78AV_078_Present_Demand_CurrentAV79AV_079_Previous_Demand_CurrentAV80AV_080_Present_Demand_Active_PowerAV81AV_081_Previous_Demand_Active_PowerAV82AV_082_Present_Demand_Reactive_PowerAV83AV_083_Previous_Demand_Reactive_PowerAV84AV_084_Present_Demand_Apparent_PowerAV85AV_085_Previous_Demand_Apparent_Power
Integration notes
- AV 11-14 are reserved.
- Reactive and apparent energy (AV 63-66) report the unit kWh because BACnet has no kvarh / kVAh unit; the values are kvarh and kVAh.
- The PICS prints AV 64 as 'AV_064Reactive_Energy-received' (no underscore after the number); kept as printed.
- Device Object_Identifier and Object_Name are writable.
- Source: BACnet International catalog copy of Delta's PICS dated 2016-01-07.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DPM-C530A power meter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Delta Electronics DPM-C530A power meter (BACnet MS/TP)
How many BACnet points does the Delta Electronics DPM-C530A power meter (BACnet MS/TP) have?
This list has 86 BACnet objects: 86 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Delta Electronics DPM-C530A power meter (BACnet MS/TP) BACnet points are writable?
11 of the 86 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Delta Electronics DPM-C530A power meter (BACnet MS/TP) BACnet documentation?
Delta Electronics does not publish it on its own website. This list comes from DPM-C530A BACnet Protocol Implementation Conformance Statement, revision 2016-01-07, a copy hosted by BACnet International catalog at https://www.bacnetinternational.net/catalog/manu/delta%20electronics,%20inc./DPM-C530A_BACnet_PICS_20160107.pdf. Ask Delta Electronics or its representative for the current revision.
What are the minimum BACnet points to integrate the Delta Electronics DPM-C530A power meter (BACnet MS/TP)?
Start with AV 49 AV_049_Active_Power_Total (Total real power, kW); AV 61 AV_061_Active_Energy-delivered (Delivered energy, kWh); AV 80 AV_080_Present_Demand_Active_Power (Present real power demand, kW); AV 40 AV_040_Power_Factor_Total (Total power factor (sign = lead/lag)); AV 34 AV_034_Current_AVG (Average current, A); AV 18 AV_018_Voltage_L-N_AVG (Average L-N voltage, V); AV 48 AV_048_Frequency (Frequency, Hz).
How do I check these points on the real DPM-C530A power meter (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.