 "manufacturer": "Delta Electronics",
 "manufacturer_slug": "delta-electronics",
 "model": "DPM-C530A power meter (BACnet MS/TP)",
 "model_slug": "dpm-c530a",
 "aliases": [
  "DPM-C530A",
  "Delta DPM-C530",
  "Delta multifunction power meter BACnet"
 ],
 "equipment_type": "Power and energy meter (panel meter)",
 "applies_to": "Delta Electronics DPM-C530A multifunction power meters on BACnet MS/TP.",
 "summary": "The DPM-C530A serves its measurements as Analog Values on BACnet MS/TP. AV 0-10 are commandable setup objects (wiring system, CT and PT ratios, demand settings, language, energy reset); AV 11-85 are read-only voltage, current, unbalance, power factor, power, energy, THD and demand values.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "Ver 01.1820",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "AV 11-14 are reserved.",
  "Reactive and apparent energy (AV 63-66) report the unit kWh because BACnet has no kvarh / kVAh unit; the values are kvarh and kVAh.",
  "The PICS prints AV 64 as 'AV_064Reactive_Energy-received' (no underscore after the number); kept as printed.",
  "Device Object_Identifier and Object_Name are writable.",
  "Source: BACnet International catalog copy of Delta's PICS dated 2016-01-07."
 ],
 "source": {
  "title": "DPM-C530A BACnet Protocol Implementation Conformance Statement",
  "doc_number": null,
  "revision_date": "2016-01-07",
  "url": "https://www.bacnetinternational.net/catalog/manu/delta%20electronics,%20inc./DPM-C530A_BACnet_PICS_20160107.pdf",
  "unofficial": true,
  "host": "BACnet International catalog"
 },
 "integration": {
  "summary": "Set CT/PT ratios and the wiring system at the meter (or AV 0-5) once, then read the read-only power, energy, demand, PF, current and voltage AVs.",
  "minimum_points": [
   {
    "ref": "AV 49",
    "name": "AV_049_Active_Power_Total",
    "why": "Total real power, kW"
   },
   {
    "ref": "AV 61",
    "name": "AV_061_Active_Energy-delivered",
    "why": "Delivered energy, kWh"
   },
   {
    "ref": "AV 80",
    "name": "AV_080_Present_Demand_Active_Power",
    "why": "Present real power demand, kW"
   },
   {
    "ref": "AV 40",
    "name": "AV_040_Power_Factor_Total",
    "why": "Total power factor (sign = lead/lag)"
   },
   {
    "ref": "AV 34",
    "name": "AV_034_Current_AVG",
    "why": "Average current, A"
   },
   {
    "ref": "AV 18",
    "name": "AV_018_Voltage_L-N_AVG",
    "why": "Average L-N voltage, V"
   },
   {
    "ref": "AV 48",
    "name": "AV_048_Frequency",
    "why": "Frequency, Hz"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "BACnet MS/TP master at 9600, 19200 or 38400 baud.",
   "Device object instance and name are writable over BACnet."
  ],
  "gotchas": [
   "AV 0-10 are configuration values (commandable); don't write them cyclically from the BMS.",
   "AV 10 Reset_Parameter resets energy when written with 0x5768."
  ]
 },
 "points": [
  {
   "type": "AV",
   "instance": 0,
   "name": "AV_000_Power_System",
   "description": "",
   "units": "",
   "access": "C",
   "states": "0=3φ4W 1=3φ3W 2=1φ2W 3=1φ3W"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "AV_001_Primary_CT",
   "description": "Range 1 ~ 9999 A",
   "units": "A",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "AV_002_Secondary_CT",
   "description": "",
   "units": "A",
   "access": "C",
   "states": "0=1A 1=5A 2=2.5A"
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "AV_003_Primary_PT",
   "description": "Range 1 ~ 9999 V",
   "units": "V",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "AV_004_Secondary_PT",
   "description": "Range 1 ~ 9999 V",
   "units": "V",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "AV_005_Number_of_Transformer",
   "description": "",
   "units": "",
   "access": "C",
   "states": "0=3CT3PT 1=3CT2PT 2=3CT0PT 3=2CT3PT 4=2CT2PT 5=2CT0PT 6=1CT3PT 7=1CT2PT 8=1CT0PT"
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "AV_006_Demand_Mode",
   "description": "",
   "units": "",
   "access": "C",
   "states": "0=block"
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "AV_007_Demand_Interval",
   "description": "Range 1 ~ 60 min",
   "units": "min",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "AV_008_Phase Rotation",
   "description": "",
   "units": "",
   "access": "C",
   "states": "0=ABC 1=CBA"
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "AV_009_UI_Language",
   "description": "",
   "units": "",
   "access": "C",
   "states": "0=English 1=Traditional Chinese 2=Simplify Chinese"
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "AV_010_Reset_Parameter",
   "description": "0x5768=kWh",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "AV_011_Reserved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "AV_012_Reserved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "AV_013_Reserved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "AV_014_Reserved",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "AV_015_Voltage_L-N_AN",
   "description": "Range 0.000 ~ 99999.999 V",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "AV_016_Voltage_L-N_BN",
   "description": "Range 0.000 ~ 99999.999 V",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "AV_017_Voltage_L-N_CN",
   "description": "Range 0.000 ~ 99999.999 V",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "AV_018_Voltage_L-N_AVG",
   "description": "Range 0.000 ~ 99999.999 V",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "AV_019_Voltage_L-L_AB",
   "description": "Range 0.000 ~ 99999.999 V",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "AV_020_Voltage_L-L_BC",
   "description": "Range 0.000 ~ 99999.999 V",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "AV_021_Voltage_L-L_CA",
   "description": "Range 0.000 ~ 99999.999 V",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "AV_022_Voltage_L-L_AVG",
   "description": "Range 0.000 ~ 99999.999 V",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "AV_023_Unbalance_Voltage_L-N_AN",
   "description": "Range 0.00 ~ 99.99 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "AV_024_Unbalance_Voltage_L-N_BN",
   "description": "Range 0.00 ~ 99.99 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "AV_025_Unbalance_Voltage_L-N_CN",
   "description": "Range 0.00 ~ 99.99 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "AV_026_Unbalance_Voltage_L-N_AVG",
   "description": "Range 0.00 ~ 99.99 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "AV_027_Unbalance_Voltage_L-L_AB",
   "description": "Range 0.00 ~ 99.99 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "AV_028_Unbalance_Voltage_L-L_BC",
   "description": "Range 0.00 ~ 99.99 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "AV_029_Unbalance_Voltage_L-L_CA",
   "description": "Range 0.00 ~ 99.99 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "AV_030_Unbalance_Voltage_L-L_AVG",
   "description": "Range 0.00 ~ 99.99 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "AV_031_Current_A",
   "description": "Range 0.000 ~ 99999.999 A",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "AV_032_Current_B",
   "description": "Range 0.000 ~ 99999.999 A",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "AV_033_Current_C",
   "description": "Range 0.000 ~ 99999.999 A",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "AV_034_Current_AVG",
   "description": "Range 0.000 ~ 99999.999 A",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "AV_035_Current_Neutral",
   "description": "Range 0.000 ~ 99999.999 A",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "AV_036_Unbalance_Current_A",
   "description": "Range 0.00 ~ 99.99 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "AV_037_Unbalance_Current_B",
   "description": "Range 0.00 ~ 99.99 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "AV_038_Unbalance_Current_C",
   "description": "Range 0.00 ~ 99.99 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "AV_039_Unbalance_Current_AVG",
   "description": "Range 0.00 ~ 99.99 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "AV_040_Power_Factor_Total",
   "description": "Range 0 to 1; negative = leading, positive = lagging",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "AV_041_Power_Factor_A",
   "description": "Range 0 to 1; negative = leading, positive = lagging",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "AV_042_Power_Factor_B",
   "description": "Range 0 to 1; negative = leading, positive = lagging",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "AV_043_Power_Factor_C",
   "description": "Range 0 to 1; negative = leading, positive = lagging",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "AV_044_Displacement_Power_Factor_Total",
   "description": "Range 0 to 1; negative = leading, positive = lagging",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "AV_045_Displacement_Power_Factor_A",
   "description": "Range 0 to 1; negative = leading, positive = lagging",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "AV_046_Displacement_Power_Factor_B",
   "description": "Range 0 to 1; negative = leading, positive = lagging",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "AV_047_Displacement_Power_Factor_C",
   "description": "Range 0 to 1; negative = leading, positive = lagging",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "AV_048_Frequency",
   "description": "Range 0.0000 ~ 99.9999 Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "AV_049_Active_Power_Total",
   "description": "Range -99999.999 ~ 99999.999 kW",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "AV_050_Active_Power_A",
   "description": "Range -99999.999 ~ 99999.999 kW",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "AV_051_Active_Power_B",
   "description": "Range -99999.999 ~ 99999.999 kW",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "AV_052_Active_Power_C",
   "description": "Range -99999.999 ~ 99999.999 kW",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "AV_053_Reactive_Power_Total",
   "description": "Range -99999.999 ~ 99999.999 kVAR",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "AV_054_Reactive_Power_A",
   "description": "Range -99999.999 ~ 99999.999 kVAR",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "AV_055_Reactive_Power_B",
   "description": "Range -99999.999 ~ 99999.999 kVAR",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "AV_056_Reactive_Power_C",
   "description": "Range -99999.999 ~ 99999.999 kVAR",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "AV_057_Apparent_Power_Total",
   "description": "Range 0.000 ~ 99999.999 kVA",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "AV_058_Apparent_Power_A",
   "description": "Range 0.000 ~ 99999.999 kVA",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "AV_059_Apparent_Power_B",
   "description": "Range 0.000 ~ 99999.999 kVA",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "AV_060_Apparent_Power_C",
   "description": "Range 0.000 ~ 99999.999 kVA",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "AV_061_Active_Energy-delivered",
   "description": "Range 0.000 ~ 4294967.295 kWh",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "AV_062_Active_Energy-received",
   "description": "Range 0.000 ~ 4294967.295 kWh",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "AV_063_Reactive_Energy-delivered",
   "description": "Range 0.000 ~ 4294967.295 kVARh",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "AV_064Reactive_Energy-received",
   "description": "Range 0.000 ~ 4294967.295 kVARh",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "AV_065_Apparent_Energy-delivered",
   "description": "Range 0.000 ~ 4294967.295 kVAh",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "AV_066_Apparent_Energy-received",
   "description": "Range 0.000 ~ 4294967.295 kVAh",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "AV_067_THD_Current_A",
   "description": "Range 0.000 ~ 999.999 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "AV_068_THD_Current_B",
   "description": "Range 0.000 ~ 999.999 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "AV_069_THD_Current_C",
   "description": "Range 0.000 ~ 999.999 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "AV_070_THD_Voltage_L-N_AN",
   "description": "Range 0.000 ~ 999.999 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "AV_071_THD_Voltage_L-N_BN",
   "description": "Range 0.000 ~ 999.999 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "AV_072_THD_Voltage_L-N_CN",
   "description": "Range 0.000 ~ 999.999 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "AV_073_THD_Voltage_L-L_AB",
   "description": "Range 0.000 ~ 999.999 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "AV_074_THD_Voltage_L-L_BC",
   "description": "Range 0.000 ~ 999.999 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "AV_075_THD_Voltage_L-L_CA",
   "description": "Range 0.000 ~ 999.999 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 76,
   "name": "AV_076_THD_Current",
   "description": "Range 0.000 ~ 999.999 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "AV_077_THD_Voltage",
   "description": "Range 0.000 ~ 999.999 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "AV_078_Present_Demand_Current",
   "description": "Range 0.000 ~ 99999.999 A",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "AV_079_Previous_Demand_Current",
   "description": "Range 0.000 ~ 99999.999 A",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "AV_080_Present_Demand_Active_Power",
   "description": "Range 0.000 ~ 99999.999 kW",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "AV_081_Previous_Demand_Active_Power",
   "description": "Range 0.000 ~ 99999.999 kW",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "AV_082_Present_Demand_Reactive_Power",
   "description": "Range 0.000 ~ 99999.999 kVAR",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "AV_083_Previous_Demand_Reactive_Power",
   "description": "Range 0.000 ~ 99999.999 kVAR",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "AV_084_Present_Demand_Apparent_Power",
   "description": "Range 0.000 ~ 99999.999 kVA",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "AV_085_Previous_Demand_Apparent_Power",
   "description": "Range 0.000 ~ 99999.999 kVA",
   "units": "kVA",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/delta-electronics/dpm-c530a",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}