Evaporative cooling air handling unit controller · BACnet points list

Cambridge Air Solutions BACnet Controller - EVAP BACnet points list

Updated 11 November 2026

Short answer

The EVAP version of Cambridge's BACnet Controller is a BTL-listed, programmable BACnet MS/TP controller that runs the supply fan, pumps, fill and drain valves and the optional burner of an evaporative cooling unit. Commands, HOA modes, statuses and alarms are mostly multistate values; temperatures, setpoints, delays and water conductivity are analog values, with a few binary values for system enable, water flush and runtime resets. It runs on its own defaults without the network if a zone sensor is connected.

This page lists 101 BACnet objects for the Cambridge Air Solutions BACnet Controller - EVAP — 57 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Cambridge Air Solutions’s own free documentation, linked below.

Manufacturer
Cambridge Air Solutions
Model
BACnet Controller - EVAP
Equipment
Evaporative cooling air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
101 (57 writable)
Transport
BACnet MS/TP
Firmware
4.0.2.0003
Also known as
Cambridge EVAP controller, Cambridge evaporative cooler BACnet, EVAP Technical Manual 4.0.2.0003
Source document
Operating Instructions - BACnet Controller - EVAP (BACnet Controller EVAP Technical Manual) · Version 4.0.2.0003 · rev. 2023-01-31
Download CSV 101 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cambridge Air Solutions’s current documentation and the live device before use. Not official Cambridge Air Solutions information. Terms of use.

BMS integration notes: Cambridge Air Solutions BACnet Controller - EVAP

Integration in brief

Enable the unit with BV 29501 System Enable and command occupancy with MV 29548 Occupancy Override. Set the zone cooling and heating setpoints (AV 29541/29555), and choose fan and cooling behaviour per occupancy with the Occupied/Unoccupied Fan and Cooling Mode MVs. Read MV 29501 Unit Status, the supply fan status and fault, discharge air temperature and the alarm MVs. Without the network the controller runs on its own defaults as long as a zone sensor is connected.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 29501System EnableUnit enable (1 = enable)Write
MV 29548Occupancy OverrideOccupied / unoccupied / bypass / standby from the BASWrite
MV 29546Occupied Cooling ModeOccupied cooling: auto / off / onWrite
AV 29541Occupied Zone Cooling Set PointOccupied zone cooling setpoint, °FWrite
AV 29555Occupied Zone Heating Set PointOccupied zone heating setpoint, °FWrite
MV 29501Unit StatusHeating / satisfied / cooling / sensor unreliableRead
MV 29507Supply Fan StatusSupply fan proven onRead
AV 29504Discharge air temperatureDischarge air temperature, °FRead
MV 29534Supply Fan FaultSupply fan alarmRead
MV 29535Sensor 1 AlarmsLow water switch 1 alarm (1 = alarm)Read

Enable & remote start

BV 29501 System Enable (0 = disable, 1 = enable). Fan, pump and burner Hand/Off/Auto overrides (MV 29539, 29540, 29562, 29566) and the valve control modes (MV 29541, 29542) should stay in Auto for normal control.

Network setup

Watch out for

Cambridge Air Solutions BACnet Controller - EVAP BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

101 of 101 shown
Type
AnalogBinaryMulti-state
Access
Show
Cambridge Air Solutions BACnet Controller - EVAP BACnet Points List
DescriptionStates
BVmin29501System EnableWrite0=Disable, 1=Enable
BV29502Water System FlushWrite0=Off, 1=On
BV29512Supply Fan Runtime ResetWrite0=Off, 1=Reset
BV29516Humidity Lockout EnableWrite0=Disable, 1=Enable
BV29517Burner Runtime Reset (optional)Write0=Off, 1=Reset
MVmin29501Unit StatusRead1=Heating, 2=Satisfied, 3=Cooling, 4=Temperature Unreliable
MV29505FCB Baud RateWrite1=Auto, 2=1200, 3=9600, 4=19200, 5=38400, 6=76800
MV29506Operating Baud RateRead1=Auto, 2=1200, 3=9600, 4=19200, 5=38400, 6=76800
MVmin29507Supply Fan StatusHardware point BI:2Read1=Off, 2=On
MV29525Control PointsWrite1=State 0, 2=State 1
MVmin29534Supply Fan FaultRead1=Normal, 2=Alarm
MVmin29535Sensor 1 AlarmsHardware point BI:5; I/O table name 'Low Water Switch #1'Read1=Alarm, 2=Normal
MV29536Supply Air Temperature Sensor FailureRead1=Normal, 2=Alarm
MV29537Outdoor Air Temperature Sensor FailureRead1=Normal, 2=Alarm
MV29538Zone Temperature Sensor FailureRead1=Normal, 2=Alarm
MV29539Supply Fan Control ModeWrite1=Hand, 2=Off, 3=Auto
MV29540Indirect Pump Control Mode (optional)Write1=Hand, 2=Off, 3=Auto
MV29541Drain Valve 1 Control ModeWrite1=Auto, 2=Close, 3=Open
MV29542Fill Valve 1 Control ModeWrite1=Auto, 2=Close, 3=Open
MV29543Effective OccupancyReadOccupied / Unoccupied
MV29544Occupied Fan ModeWrite1=Auto, 2=Off, 3=On
MV29545Unoccupied Fan ModeWrite1=Auto, 2=Off, 3=On
MVmin29546Occupied Cooling ModeWrite1=Auto, 2=Off, 3=On
MV29547Unoccupied Cooling ModeWrite1=Auto, 2=Off, 3=On
MVmin29548Occupancy OverrideWrite1=Occupied, 2=UnOccupied, 3=Bypass, 4=Standby, 5=Not Set
MV29549Occupancy ScheduleWrite1=Occupied, 2=UnOccupied, 3=Bypass, 4=Standby, 5=Not Set
MV29555Sensor 2 AlarmsHardware point BI:6; I/O table name 'Low Water Switch #2 (optional)'Read1=Alarm, 2=Normal
MV29557Cooling TypeWrite1=X, 2=Y, 3=Z
MV29562Direct Pump Control Mode (optional)Write1=Hand, 2=Off, 3=Auto
MV29563Burner StatusHardware point BI:1Read1=Off, 2=On
MV29565Burner Modulation ModeWrite1=Auto, 2=Manual
MV29566Burner Control ModeWrite1=Hand, 2=Off, 3=Auto
MV29567Burner Alarm ResetWrite1=Off, 2=Reset
MV29568Heat/Cool ModeWrite1=Heating, 2=Cooling
MV29569Burner FaultRead1=Normal, 2=Alarm
MV29570DAT Low Temperature AlarmRead1=Normal, 2=Lockout
MV29571Heater Lockout AlarmRead1=Normal, 2=Lockout
MV29572System ModeRead1=Heat, 2=Cool, 3=Fan Only, 4=Auto, 5=Off
MV25973Filter ARead1=Normal, 2=Alarm
MV25974Filter BRead1=Normal, 2=Alarm
AV29501Device AddressRange 4 to 127, default 4Write
AV29502Device Object IDRange 0 to 4194302Write
AV29510DAT Sensor OffsetRange -10 to 10, default 0°F°FWrite
AV29512DeadbandRange 0 to 20, default 0°F°FWrite
AV29513High Drain ThresholdRange 0-10,000μS/cmWrite
AV29514Drain Delay TimeRange 0 to 120MinutesWrite
AV29515Drying TimeRange 0 to 120MinutesWrite
AV29516Valve DelayRange 0 to 120MinutesWrite
AV29517Fan Fault DelayRange 0 to 300, default 60 secsecondsWrite
AV29518Water Flush SystemRange 0-10,000μS/cmWrite
AV29519OAT Sensor OffsetRange -10 to 10, default 0°F°FWrite
AV29520Low OA Lockout SetpointRange 40 to 160, default 40°F°FWrite
AV29521Pump Down TimeRange 0 to 120MinutesWrite
AV29522Fan Start DelayRange 0 to 120MinutesWrite
AV29524ZNT Sensor OffsetRange -10 to 10, default 0°F°FWrite
AV29534Supply Fan Cycle CountCountsRead
AV29535Supply Fan RuntimehoursRead
AV29536Supply Fan Speed (optional)Range 0 to 100, default 100%%Write
AV29537Effective Cooling Setpoint°FRead
AV29538OA Econ Lockout SetpointRange 40 to 160, default 65°F°FWrite
AV29539Unoccupied Discharge Air Flow SetpointRange 40 to 160, default 65°F°FWrite
AV29540Occupied Discharge Air Flow SetpointRange 40 to 160, default 65°F°FWrite
AVmin29541Occupied Zone Cooling Set PointRange 40 to 160, default 75°F°FWrite
AV29542Unoccupied Zone Cooling Set PointRange 40 to 160, default 85°F°FWrite
AV29543Freeze Stat SetpointRange 40 to 160, default 65°F°FWrite
AV29544Netsensor TempRange 32 to 104°FRead
AV29545Netsensor HumidityRange 0 to 100%Read
AV29546RH SetpointRange 0-100, default 60%%Write
AV29547Inlet Air CoolerRange 1-2Write
AV29548Number of PumpsRange 1-2Write
AV29549Stage Up DelayRange 0 to 30MinutesWrite
AV29552OA Heating Lockout SetpointRange 0 to 130, default 65°F°FWrite
AV29553Discharge Air High Set PointRange 40 to 160, default 160°F°FWrite
AV29554Discharge Air Low Set PointRange 40 to 160, default 70°F°FWrite
AVmin29555Occupied Zone Heating Set PointRange 60 to 90, default 60°F°FWrite
AV29556Unoccupied Zone Heating Set PointRange 40 to 80, default 55°F°FWrite
AV29557Burner Modulation Set Point%Read
AV29560Burner Fault DelayRange 0 to 300, default 60 secsecondsWrite
AV29561Low Temperature Cutout SetpointRange 45 to 55, default 45°F°FWrite
AV29562Low Temperature Cutout DelayRange 0 to 300, default 60 secsecondsWrite
AV29563Effective Heating Set Point°FRead
AV29564Effective Discharge Air Set Point°FRead
AV29565Burner RuntimehoursRead
AV29566Burner Cycle CountCountsRead
MV29573Clogged Filter Switch 1 (Optional)Hardware point BI:3Read0=Normal, 1=Alarm
MV29574Clogged Filter Switch 2 (Optional)Hardware point BI:4Read0=Normal, 1=Alarm
AVmin29504Discharge air temperatureHardware point UI:14, range -50 - 250°FRead
AV29550Water Conductivity #2 (optional)Hardware point UI:15, range 0-10,000μS/cmRead
AV29506Outdoor air temperatureHardware point UI:16, range -50 - 250°FRead
AV29507Zone temperature (optional)Hardware point UI:17, range -50 - 250°FRead
AV29508Water Conductivity #1 (optional)Hardware point UI:18, range 0-10,000μS/cmRead
MV29564Burner command (optional)Hardware point BO:4Read0=Off, 1=On
MV29516Indirect Pump command (optional)Hardware point BO:6Read0=Off, 1=On
MV29550Direct Pump command (optional)Hardware point BO:8Read0=Off, 1=On
MV29520Supply Fan commandHardware point BO:10Read0=Off, 1=On
MV29521Drain Valve #1 commandHardware point BO:11Read0=Open, 1=Closed
MV29522Fill Valve #1 commandHardware point BO:12Read0=Closed, 1=Open
MV29553Drain Valve #2 command (optional)Hardware point BO:13Read0=Open, 1=Closed
MV29554Fill Valve #2 command (optional)Hardware point BO:14Read0=Closed, 1=Open
AV29551Burner Modulation (optional)Hardware point AO:1, range 0 - 100%Read
AV29509Supply Fan Output (optional)Hardware point AO:2, range 0 - 100%Read
Object ID lookup: Cambridge Air Solutions EVAP Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BACnet Controller - EVAP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cambridge Air Solutions BACnet Controller - EVAP

How many BACnet points does the Cambridge Air Solutions BACnet Controller - EVAP have?

This list has 101 BACnet objects: 51 analog values, 5 binary values, 45 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cambridge Air Solutions BACnet Controller - EVAP BACnet points are writable?

57 of the 101 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Cambridge Air Solutions BACnet Controller - EVAP BACnet documentation?

The source is Operating Instructions - BACnet Controller - EVAP (BACnet Controller EVAP Technical Manual) (Version 4.0.2.0003), revision 2023-01-31, published free by Cambridge Air Solutions at https://www.cambridge-eng.com/Portals/0/Operating%20Instructions%204_0_2_0003.pdf.

What are the minimum BACnet points to integrate the Cambridge Air Solutions BACnet Controller - EVAP?

Start with BV 29501 System Enable (Unit enable (1 = enable)); MV 29548 Occupancy Override (Occupied / unoccupied / bypass / standby from the BAS); MV 29546 Occupied Cooling Mode (Occupied cooling: auto / off / on); AV 29541 Occupied Zone Cooling Set Point (Occupied zone cooling setpoint, °F); AV 29555 Occupied Zone Heating Set Point (Occupied zone heating setpoint, °F); MV 29501 Unit Status (Heating / satisfied / cooling / sensor unreliable); MV 29507 Supply Fan Status (Supply fan proven on); AV 29504 Discharge air temperature (Discharge air temperature, °F); MV 29534 Supply Fan Fault (Supply fan alarm); MV 29535 Sensor 1 Alarms (Low water switch 1 alarm (1 = alarm)).

How do I enable BMS control of the Cambridge Air Solutions BACnet Controller - EVAP?

BV 29501 System Enable (0 = disable, 1 = enable). Fan, pump and burner Hand/Off/Auto overrides (MV 29539, 29540, 29562, 29566) and the valve control modes (MV 29541, 29542) should stay in Auto for normal control.

How do I check these points on the real BACnet Controller - EVAP?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cambridge Air Solutions BACnet points lists

Source: Operating Instructions - BACnet Controller - EVAP (BACnet Controller EVAP Technical Manual) · Version 4.0.2.0003 · rev. 2023-01-31. Object names, instances and units are reproduced as published; descriptions are our own.