Evaporative cooling air handling unit controller · BACnet points list
Cambridge Air Solutions BACnet Controller - EVAP BACnet points list
Updated 11 November 2026
The EVAP version of Cambridge's BACnet Controller is a BTL-listed, programmable BACnet MS/TP controller that runs the supply fan, pumps, fill and drain valves and the optional burner of an evaporative cooling unit. Commands, HOA modes, statuses and alarms are mostly multistate values; temperatures, setpoints, delays and water conductivity are analog values, with a few binary values for system enable, water flush and runtime resets. It runs on its own defaults without the network if a zone sensor is connected.
This page lists 101 BACnet objects for the Cambridge Air Solutions BACnet Controller - EVAP — 57 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Cambridge Air Solutions’s own free documentation, linked below.
- Manufacturer
- Cambridge Air Solutions
- Model
- BACnet Controller - EVAP
- Equipment
- Evaporative cooling air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 101 (57 writable)
- Transport
- BACnet MS/TP
- Firmware
- 4.0.2.0003
- Also known as
- Cambridge EVAP controller, Cambridge evaporative cooler BACnet, EVAP Technical Manual 4.0.2.0003
Reference only, provided as-is: verify against Cambridge Air Solutions’s current documentation and the live device before use. Not official Cambridge Air Solutions information. Terms of use.
BMS integration notes: Cambridge Air Solutions BACnet Controller - EVAP
Enable the unit with BV 29501 System Enable and command occupancy with MV 29548 Occupancy Override. Set the zone cooling and heating setpoints (AV 29541/29555), and choose fan and cooling behaviour per occupancy with the Occupied/Unoccupied Fan and Cooling Mode MVs. Read MV 29501 Unit Status, the supply fan status and fault, discharge air temperature and the alarm MVs. Without the network the controller runs on its own defaults as long as a zone sensor is connected.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 29501 | System Enable | Unit enable (1 = enable) | Write |
| MV 29548 | Occupancy Override | Occupied / unoccupied / bypass / standby from the BAS | Write |
| MV 29546 | Occupied Cooling Mode | Occupied cooling: auto / off / on | Write |
| AV 29541 | Occupied Zone Cooling Set Point | Occupied zone cooling setpoint, °F | Write |
| AV 29555 | Occupied Zone Heating Set Point | Occupied zone heating setpoint, °F | Write |
| MV 29501 | Unit Status | Heating / satisfied / cooling / sensor unreliable | Read |
| MV 29507 | Supply Fan Status | Supply fan proven on | Read |
| AV 29504 | Discharge air temperature | Discharge air temperature, °F | Read |
| MV 29534 | Supply Fan Fault | Supply fan alarm | Read |
| MV 29535 | Sensor 1 Alarms | Low water switch 1 alarm (1 = alarm) | Read |
Enable & remote start
BV 29501 System Enable (0 = disable, 1 = enable). Fan, pump and burner Hand/Off/Auto overrides (MV 29539, 29540, 29562, 29566) and the valve control modes (MV 29541, 29542) should stay in Auto for normal control.
Network setup
- BACnet MS/TP only, up to 76.8 kbaud. MAC address 4-127 (default 4), set from the local display (Controller > Network) or a MAP gateway; also exposed as AV 29501.
- Baud defaults to Auto (follows the bus supervisor); the manual suggests 38400 with a Smart Building Hub.
- Device Object ID (AV 29502) must be unique on the network.
- Disconnect the controller from the bus while changing network settings, then cycle power before reconnecting.
- An EOL terminator is needed when the controller is at either end of the MS/TP trunk.
Watch out for
- Two MV rows in the manual (valve 2 control modes) reuse the valve 1 instances; confirm on site which object the valves actually use.
- The DAT low temperature alarm needs a manual reset; the other listed alarms reset automatically.
- Confirm the filter alarm objects on site: MV 25973/25974 (points table) vs MV 29573/29574 (alarm table).
- Points table defaults and the Default Settings list disagree for some setpoints; read the live values before writing.
Cambridge Air Solutions BACnet Controller - EVAP BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 29501 | System Enable | Write | 0=Disable, 1=Enable | ||
| BV | 29502 | Water System Flush | Write | 0=Off, 1=On | ||
| BV | 29512 | Supply Fan Runtime Reset | Write | 0=Off, 1=Reset | ||
| BV | 29516 | Humidity Lockout Enable | Write | 0=Disable, 1=Enable | ||
| BV | 29517 | Burner Runtime Reset (optional) | Write | 0=Off, 1=Reset | ||
| MVmin | 29501 | Unit Status | Read | 1=Heating, 2=Satisfied, 3=Cooling, 4=Temperature Unreliable | ||
| MV | 29505 | FCB Baud Rate | Write | 1=Auto, 2=1200, 3=9600, 4=19200, 5=38400, 6=76800 | ||
| MV | 29506 | Operating Baud Rate | Read | 1=Auto, 2=1200, 3=9600, 4=19200, 5=38400, 6=76800 | ||
| MVmin | 29507 | Supply Fan Status | Hardware point BI:2 | Read | 1=Off, 2=On | |
| MV | 29525 | Control Points | Write | 1=State 0, 2=State 1 | ||
| MVmin | 29534 | Supply Fan Fault | Read | 1=Normal, 2=Alarm | ||
| MVmin | 29535 | Sensor 1 Alarms | Hardware point BI:5; I/O table name 'Low Water Switch #1' | Read | 1=Alarm, 2=Normal | |
| MV | 29536 | Supply Air Temperature Sensor Failure | Read | 1=Normal, 2=Alarm | ||
| MV | 29537 | Outdoor Air Temperature Sensor Failure | Read | 1=Normal, 2=Alarm | ||
| MV | 29538 | Zone Temperature Sensor Failure | Read | 1=Normal, 2=Alarm | ||
| MV | 29539 | Supply Fan Control Mode | Write | 1=Hand, 2=Off, 3=Auto | ||
| MV | 29540 | Indirect Pump Control Mode (optional) | Write | 1=Hand, 2=Off, 3=Auto | ||
| MV | 29541 | Drain Valve 1 Control Mode | Write | 1=Auto, 2=Close, 3=Open | ||
| MV | 29542 | Fill Valve 1 Control Mode | Write | 1=Auto, 2=Close, 3=Open | ||
| MV | 29543 | Effective Occupancy | Read | Occupied / Unoccupied | ||
| MV | 29544 | Occupied Fan Mode | Write | 1=Auto, 2=Off, 3=On | ||
| MV | 29545 | Unoccupied Fan Mode | Write | 1=Auto, 2=Off, 3=On | ||
| MVmin | 29546 | Occupied Cooling Mode | Write | 1=Auto, 2=Off, 3=On | ||
| MV | 29547 | Unoccupied Cooling Mode | Write | 1=Auto, 2=Off, 3=On | ||
| MVmin | 29548 | Occupancy Override | Write | 1=Occupied, 2=UnOccupied, 3=Bypass, 4=Standby, 5=Not Set | ||
| MV | 29549 | Occupancy Schedule | Write | 1=Occupied, 2=UnOccupied, 3=Bypass, 4=Standby, 5=Not Set | ||
| MV | 29555 | Sensor 2 Alarms | Hardware point BI:6; I/O table name 'Low Water Switch #2 (optional)' | Read | 1=Alarm, 2=Normal | |
| MV | 29557 | Cooling Type | Write | 1=X, 2=Y, 3=Z | ||
| MV | 29562 | Direct Pump Control Mode (optional) | Write | 1=Hand, 2=Off, 3=Auto | ||
| MV | 29563 | Burner Status | Hardware point BI:1 | Read | 1=Off, 2=On | |
| MV | 29565 | Burner Modulation Mode | Write | 1=Auto, 2=Manual | ||
| MV | 29566 | Burner Control Mode | Write | 1=Hand, 2=Off, 3=Auto | ||
| MV | 29567 | Burner Alarm Reset | Write | 1=Off, 2=Reset | ||
| MV | 29568 | Heat/Cool Mode | Write | 1=Heating, 2=Cooling | ||
| MV | 29569 | Burner Fault | Read | 1=Normal, 2=Alarm | ||
| MV | 29570 | DAT Low Temperature Alarm | Read | 1=Normal, 2=Lockout | ||
| MV | 29571 | Heater Lockout Alarm | Read | 1=Normal, 2=Lockout | ||
| MV | 29572 | System Mode | Read | 1=Heat, 2=Cool, 3=Fan Only, 4=Auto, 5=Off | ||
| MV | 25973 | Filter A | Read | 1=Normal, 2=Alarm | ||
| MV | 25974 | Filter B | Read | 1=Normal, 2=Alarm | ||
| AV | 29501 | Device Address | Range 4 to 127, default 4 | Write | ||
| AV | 29502 | Device Object ID | Range 0 to 4194302 | Write | ||
| AV | 29510 | DAT Sensor Offset | Range -10 to 10, default 0°F | °F | Write | |
| AV | 29512 | Deadband | Range 0 to 20, default 0°F | °F | Write | |
| AV | 29513 | High Drain Threshold | Range 0-10,000 | μS/cm | Write | |
| AV | 29514 | Drain Delay Time | Range 0 to 120 | Minutes | Write | |
| AV | 29515 | Drying Time | Range 0 to 120 | Minutes | Write | |
| AV | 29516 | Valve Delay | Range 0 to 120 | Minutes | Write | |
| AV | 29517 | Fan Fault Delay | Range 0 to 300, default 60 sec | seconds | Write | |
| AV | 29518 | Water Flush System | Range 0-10,000 | μS/cm | Write | |
| AV | 29519 | OAT Sensor Offset | Range -10 to 10, default 0°F | °F | Write | |
| AV | 29520 | Low OA Lockout Setpoint | Range 40 to 160, default 40°F | °F | Write | |
| AV | 29521 | Pump Down Time | Range 0 to 120 | Minutes | Write | |
| AV | 29522 | Fan Start Delay | Range 0 to 120 | Minutes | Write | |
| AV | 29524 | ZNT Sensor Offset | Range -10 to 10, default 0°F | °F | Write | |
| AV | 29534 | Supply Fan Cycle Count | Counts | Read | ||
| AV | 29535 | Supply Fan Runtime | hours | Read | ||
| AV | 29536 | Supply Fan Speed (optional) | Range 0 to 100, default 100% | % | Write | |
| AV | 29537 | Effective Cooling Setpoint | °F | Read | ||
| AV | 29538 | OA Econ Lockout Setpoint | Range 40 to 160, default 65°F | °F | Write | |
| AV | 29539 | Unoccupied Discharge Air Flow Setpoint | Range 40 to 160, default 65°F | °F | Write | |
| AV | 29540 | Occupied Discharge Air Flow Setpoint | Range 40 to 160, default 65°F | °F | Write | |
| AVmin | 29541 | Occupied Zone Cooling Set Point | Range 40 to 160, default 75°F | °F | Write | |
| AV | 29542 | Unoccupied Zone Cooling Set Point | Range 40 to 160, default 85°F | °F | Write | |
| AV | 29543 | Freeze Stat Setpoint | Range 40 to 160, default 65°F | °F | Write | |
| AV | 29544 | Netsensor Temp | Range 32 to 104 | °F | Read | |
| AV | 29545 | Netsensor Humidity | Range 0 to 100 | % | Read | |
| AV | 29546 | RH Setpoint | Range 0-100, default 60% | % | Write | |
| AV | 29547 | Inlet Air Cooler | Range 1-2 | Write | ||
| AV | 29548 | Number of Pumps | Range 1-2 | Write | ||
| AV | 29549 | Stage Up Delay | Range 0 to 30 | Minutes | Write | |
| AV | 29552 | OA Heating Lockout Setpoint | Range 0 to 130, default 65°F | °F | Write | |
| AV | 29553 | Discharge Air High Set Point | Range 40 to 160, default 160°F | °F | Write | |
| AV | 29554 | Discharge Air Low Set Point | Range 40 to 160, default 70°F | °F | Write | |
| AVmin | 29555 | Occupied Zone Heating Set Point | Range 60 to 90, default 60°F | °F | Write | |
| AV | 29556 | Unoccupied Zone Heating Set Point | Range 40 to 80, default 55°F | °F | Write | |
| AV | 29557 | Burner Modulation Set Point | % | Read | ||
| AV | 29560 | Burner Fault Delay | Range 0 to 300, default 60 sec | seconds | Write | |
| AV | 29561 | Low Temperature Cutout Setpoint | Range 45 to 55, default 45°F | °F | Write | |
| AV | 29562 | Low Temperature Cutout Delay | Range 0 to 300, default 60 sec | seconds | Write | |
| AV | 29563 | Effective Heating Set Point | °F | Read | ||
| AV | 29564 | Effective Discharge Air Set Point | °F | Read | ||
| AV | 29565 | Burner Runtime | hours | Read | ||
| AV | 29566 | Burner Cycle Count | Counts | Read | ||
| MV | 29573 | Clogged Filter Switch 1 (Optional) | Hardware point BI:3 | Read | 0=Normal, 1=Alarm | |
| MV | 29574 | Clogged Filter Switch 2 (Optional) | Hardware point BI:4 | Read | 0=Normal, 1=Alarm | |
| AVmin | 29504 | Discharge air temperature | Hardware point UI:14, range -50 - 250 | °F | Read | |
| AV | 29550 | Water Conductivity #2 (optional) | Hardware point UI:15, range 0-10,000 | μS/cm | Read | |
| AV | 29506 | Outdoor air temperature | Hardware point UI:16, range -50 - 250 | °F | Read | |
| AV | 29507 | Zone temperature (optional) | Hardware point UI:17, range -50 - 250 | °F | Read | |
| AV | 29508 | Water Conductivity #1 (optional) | Hardware point UI:18, range 0-10,000 | μS/cm | Read | |
| MV | 29564 | Burner command (optional) | Hardware point BO:4 | Read | 0=Off, 1=On | |
| MV | 29516 | Indirect Pump command (optional) | Hardware point BO:6 | Read | 0=Off, 1=On | |
| MV | 29550 | Direct Pump command (optional) | Hardware point BO:8 | Read | 0=Off, 1=On | |
| MV | 29520 | Supply Fan command | Hardware point BO:10 | Read | 0=Off, 1=On | |
| MV | 29521 | Drain Valve #1 command | Hardware point BO:11 | Read | 0=Open, 1=Closed | |
| MV | 29522 | Fill Valve #1 command | Hardware point BO:12 | Read | 0=Closed, 1=Open | |
| MV | 29553 | Drain Valve #2 command (optional) | Hardware point BO:13 | Read | 0=Open, 1=Closed | |
| MV | 29554 | Fill Valve #2 command (optional) | Hardware point BO:14 | Read | 0=Closed, 1=Open | |
| AV | 29551 | Burner Modulation (optional) | Hardware point AO:1, range 0 - 100 | % | Read | |
| AV | 29509 | Supply Fan Output (optional) | Hardware point AO:2, range 0 - 100 | % | Read |
No points match these filters.
Object ID lookup: Cambridge Air Solutions EVAP Controller point IDs by name
BV29501System EnableBV29502Water System FlushBV29512Supply Fan Runtime ResetBV29516Humidity Lockout EnableBV29517Burner Runtime Reset (optional)MV29501Unit StatusMV29505FCB Baud RateMV29506Operating Baud RateMV29507Supply Fan StatusMV29525Control PointsMV29534Supply Fan FaultMV29535Sensor 1 AlarmsMV29536Supply Air Temperature Sensor FailureMV29537Outdoor Air Temperature Sensor FailureMV29538Zone Temperature Sensor FailureMV29539Supply Fan Control ModeMV29540Indirect Pump Control Mode (optional)MV29541Drain Valve 1 Control ModeMV29542Fill Valve 1 Control ModeMV29543Effective OccupancyMV29544Occupied Fan ModeMV29545Unoccupied Fan ModeMV29546Occupied Cooling ModeMV29547Unoccupied Cooling ModeMV29548Occupancy OverrideMV29549Occupancy ScheduleMV29555Sensor 2 AlarmsMV29557Cooling TypeMV29562Direct Pump Control Mode (optional)MV29563Burner StatusMV29565Burner Modulation ModeMV29566Burner Control ModeMV29567Burner Alarm ResetMV29568Heat/Cool ModeMV29569Burner FaultMV29570DAT Low Temperature AlarmMV29571Heater Lockout AlarmMV29572System ModeMV25973Filter AMV25974Filter BAV29501Device AddressAV29502Device Object IDAV29510DAT Sensor OffsetAV29512DeadbandAV29513High Drain ThresholdAV29514Drain Delay TimeAV29515Drying TimeAV29516Valve DelayAV29517Fan Fault DelayAV29518Water Flush SystemAV29519OAT Sensor OffsetAV29520Low OA Lockout SetpointAV29521Pump Down TimeAV29522Fan Start DelayAV29524ZNT Sensor OffsetAV29534Supply Fan Cycle CountAV29535Supply Fan RuntimeAV29536Supply Fan Speed (optional)AV29537Effective Cooling SetpointAV29538OA Econ Lockout SetpointAV29539Unoccupied Discharge Air Flow SetpointAV29540Occupied Discharge Air Flow SetpointAV29541Occupied Zone Cooling Set PointAV29542Unoccupied Zone Cooling Set PointAV29543Freeze Stat SetpointAV29544Netsensor TempAV29545Netsensor HumidityAV29546RH SetpointAV29547Inlet Air CoolerAV29548Number of PumpsAV29549Stage Up DelayAV29552OA Heating Lockout SetpointAV29553Discharge Air High Set PointAV29554Discharge Air Low Set PointAV29555Occupied Zone Heating Set PointAV29556Unoccupied Zone Heating Set PointAV29557Burner Modulation Set PointAV29560Burner Fault DelayAV29561Low Temperature Cutout SetpointAV29562Low Temperature Cutout DelayAV29563Effective Heating Set PointAV29564Effective Discharge Air Set PointAV29565Burner RuntimeAV29566Burner Cycle CountMV29573Clogged Filter Switch 1 (Optional)MV29574Clogged Filter Switch 2 (Optional)AV29504Discharge air temperatureAV29550Water Conductivity #2 (optional)AV29506Outdoor air temperatureAV29507Zone temperature (optional)AV29508Water Conductivity #1 (optional)MV29564Burner command (optional)MV29516Indirect Pump command (optional)MV29550Direct Pump command (optional)MV29520Supply Fan commandMV29521Drain Valve #1 commandMV29522Fill Valve #1 commandMV29553Drain Valve #2 command (optional)MV29554Fill Valve #2 command (optional)AV29551Burner Modulation (optional)AV29509Supply Fan Output (optional)
Integration notes
- Optional points (burner, second pump, second fill/drain valves, filter switches, zone sensor, conductivity, fan speed) only apply to units with those options.
- The input table's Burner Status, Supply Fan Status and Low Water Switch #1/#2 rows point to the same MV objects as the multistate table (MV 29563, 29507, 29535 Sensor 1 Alarms, 29555 Sensor 2 Alarms); they are listed once with the hardware point in the description. The I/O tables show these as 0/1 while the MV table uses 1/2.
- The manual prints Drain Valve 2 and Fill Valve 2 Control Mode with the same instances as valve 1 (MV 29541/29542), which looks like a typo; only the valve 1 rows are listed.
- Cooling Type (MV 29557) is printed with placeholder states 1=X, 2=Y, 3=Z; the setup section names the cooling types Direct, Indirect and Direct/Indirect.
- Default setpoints in the points table (unoccupied cooling 85°F, deadband 0°F) differ from the manual's Default Settings list (75°F, 5°F).
- Filter A/B are printed as MV 25973/25974, while the alarm table gives the clogged filter switch alarms as MV 29573/29574; 25973/25974 may be a typo. The alarm table also gives the fan alarm as MV 29543 (Effective Occupancy in the points table), where the points table has Supply Fan Fault at MV 29534. Objects are listed here as the points table prints them.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BACnet Controller - EVAP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Cambridge Air Solutions BACnet Controller - EVAP
How many BACnet points does the Cambridge Air Solutions BACnet Controller - EVAP have?
This list has 101 BACnet objects: 51 analog values, 5 binary values, 45 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Cambridge Air Solutions BACnet Controller - EVAP BACnet points are writable?
57 of the 101 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Cambridge Air Solutions BACnet Controller - EVAP BACnet documentation?
The source is Operating Instructions - BACnet Controller - EVAP (BACnet Controller EVAP Technical Manual) (Version 4.0.2.0003), revision 2023-01-31, published free by Cambridge Air Solutions at https://www.cambridge-eng.com/Portals/0/Operating%20Instructions%204_0_2_0003.pdf.
What are the minimum BACnet points to integrate the Cambridge Air Solutions BACnet Controller - EVAP?
Start with BV 29501 System Enable (Unit enable (1 = enable)); MV 29548 Occupancy Override (Occupied / unoccupied / bypass / standby from the BAS); MV 29546 Occupied Cooling Mode (Occupied cooling: auto / off / on); AV 29541 Occupied Zone Cooling Set Point (Occupied zone cooling setpoint, °F); AV 29555 Occupied Zone Heating Set Point (Occupied zone heating setpoint, °F); MV 29501 Unit Status (Heating / satisfied / cooling / sensor unreliable); MV 29507 Supply Fan Status (Supply fan proven on); AV 29504 Discharge air temperature (Discharge air temperature, °F); MV 29534 Supply Fan Fault (Supply fan alarm); MV 29535 Sensor 1 Alarms (Low water switch 1 alarm (1 = alarm)).
How do I enable BMS control of the Cambridge Air Solutions BACnet Controller - EVAP?
BV 29501 System Enable (0 = disable, 1 = enable). Fan, pump and burner Hand/Off/Auto overrides (MV 29539, 29540, 29562, 29566) and the valve control modes (MV 29541, 29542) should stay in Auto for normal control.
How do I check these points on the real BACnet Controller - EVAP?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Cambridge Air Solutions BACnet points lists
Source: Operating Instructions - BACnet Controller - EVAP (BACnet Controller EVAP Technical Manual) · Version 4.0.2.0003 · rev. 2023-01-31. Object names, instances and units are reproduced as published; descriptions are our own.