Make-up air heater controller · BACnet points list

Cambridge Air Solutions BACnet Controller - MAU BACnet points list

Updated 28 October 2026

Short answer

Cambridge's BACnet Controller is a BTL-listed, programmable MS/TP controller mounted in the heater that runs the fan and burner and gives a BAS access to its points. The object list is mostly multistate values (statuses, commands, HOA, modes, alarms) and analog values (temperatures, setpoints, delays, runtimes), with four binary values for runtime/cycle-count resets. Operating mode (unit heat, make-up air, make-up air with reset, summer vent, off) is selected with the Normal and Override Mode MVs.

This page lists 77 BACnet objects for the Cambridge Air Solutions BACnet Controller - MAU — 42 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Cambridge Air Solutions’s own free documentation, linked below.

Manufacturer
Cambridge Air Solutions
Model
BACnet Controller - MAU
Equipment
Make-up air heater controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
77 (42 writable)
Transport
BACnet MS/TP
Firmware
4.0.3.0012
Also known as
Cambridge MAU controller, Cambridge BACnet Controller, Cambridge heater BACnet, MAU Technical Manual 4.0.3.0012
Source document
Operating Instructions - BACnet Controller - MAU (BACnet Controller MAU Technical Manual) · Version 4.0.3.0012 · rev. 2022-11-30
Download CSV 77 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Cambridge Air Solutions BACnet Controller - MAU

Integration in brief

Enable the unit with MV-3011 Unit Enable Mode, choose the operating mode with MV-50052 Normal Mode (MV-50053 Override Mode for the alternate mode) and command occupancy with MV-3021 Occupancy Override or the controller's own schedule. Adjust the zone and discharge setpoints, read MV-3001 Unit Status, the burner/fan status MVs and the fault MVs, and reset faults with MV-50058. The controller runs stand-alone on its defaults (unit heater mode, 160°F discharge, 65°F zone) if the network is lost, provided a zone sensor is connected.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 3011Unit Enable ModeShutdown / enableWrite
MV 3021Occupancy OverrideOccupied / unoccupied / standby from the BASWrite
MV 50052Normal ModeUnit heat, make-up air, summer vent or offWrite
AV 3037Discharge Air Set Point – Makeup Air ModeDischarge setpoint in make-up air modeWrite
AV 3017Occupied Zone Heating Set PointZone temp the burner heats to when occupiedWrite
MV 50058Reset Unit FaultNetwork fault resetWrite
MV 3001Unit StatusHeating / satisfied / cooling / sensor unreliableRead
AV 3011Effective Discharge Air TemperatureSupply air temp leaving the unit, °FRead
MV 3018Burner StatusBurner proven onRead
MV 50056Burner FaultBurner alarmRead

Enable & remote start

MV-3011 Unit Enable Mode (1=Shutdown, 2=Enable). Fan and burner Hand/Off/Auto overrides are MV-50050 Supply Fan HOA and MV-11 Burner HOA; leave them in Auto (3) for normal control.

Sensors & values from the BMS

Network values can replace the wired sensors: AV-3038 Network Override Outdoor Air Temperature and AV-3045 Network Override Zone Temperature. MV-50064 ZN-T Remote Setpoint Enable selects no remote setpoint, hardware only, network only, or network with hardware backup. The manual gives no timeout for these.

Network setup

Watch out for

Cambridge Air Solutions BACnet Controller - MAU BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

77 of 77 shown
Type
AnalogBinaryMulti-state
Access
Show
Cambridge Air Solutions BACnet Controller - MAU BACnet Points List
DescriptionStates
AV3032Supply Fan Output (optional)Hardware point AO:2%Read
AV3039Filter pressure (optional)Hardware point AI:5in. w.c.Read
MV50051Filter status (optional)Hardware point BI:7Read0=Normal, 1=Alarm
MV50055Mode Switch (optional)Hardware point BI:4Read0=Normal, 1=Override
BV0Burner Runtime ResetWrite0=Off, 1=Reset
BV1Burner Cycle Count ResetWrite0=Off, 1=Reset
BV2Supply Fan Runtime ResetWrite0=Off, 1=Reset
BV3Supply Fan Cycle Count ResetWrite0=Off, 1=Reset
MV11Burner HOAWrite1=Hand, 2=Off, 3=Auto
MV1577Burner Modulation ModeWrite1=Auto, 2=Manual
MVmin3001Unit StatusRead1=Heating, 2=Satisfied, 3=Cooling, 4=Temperature Unreliable
MV3006UnitsWrite1=IP, 2=SI
MV3007FCB Baud RateWrite1=Auto, 2=1200, 3=9600, 4=19200, 5=38400, 6=76800
MV3008Operating Baud RateBaud rate in use (see FCB Baud Rate states)Read
MV3009PID Tuning ResetWrite1=Off, 2=Reset
MV3010Occupancy ScheduleOccupancy schedule referenceWrite
MVmin3011Unit Enable ModeWrite1=Shutdown, 2=Enable
MV3012Effective OccupancyReadOccupied / Unoccupied
MV3016Supply Fan StatusHardware point BI:2Read1=Off, 2=On
MV3017Unit Reset FaultHardware point BI:3Read1=Normal, 2=Alarm
MVmin3018Burner StatusHardware point BI:1Read1=Off, 2=On
MV3019Burner CommandHardware point BO:4Read1=Off, 2=On
MV3020Supply Fan CommandHardware point BO:5Read1=Off, 2=On
MVmin3021Occupancy OverrideWrite1=Occupied, 2=UnOccupied, 3=Bypass, 4=Standby, 5=Not Set
MV3022Emergency Heat EnabledRead1=Inactive, 2=Active
MV50050Supply Fan HOAWrite1=Hand, 2=Off, 3=Auto
MVmin50052Normal ModeWrite1=Unit Heat, 2=Makeup Air, 3=Makeup Air w/Reset, 4=Makeup Air w/Reset & On-Off, 5=Summer Vent, 6=Off
MV50053Override ModeWrite1=Unit Heat, 2=Makeup Air, 3=Makeup Air w/Reset, 4=Makeup Air w/Reset & On-Off, 5=Summer Vent, 6=Off
MV50054Effective ModeRead1=Unit Heat, 2=Makeup Air, 3=Makeup Air w/Reset, 4=Makeup Air w/Reset & On-Off, 5=Summer Vent, 6=Off
MVmin50056Burner FaultRead1=Normal, 2=Alarm
MV50057Supply Fan FaultRead1=Normal, 2=Alarm
MVmin50058Reset Unit FaultWrite1=Off, 2=Reset
MV50059Zone Temperature Sensor FailureRead1=Normal, 2=Alarm
MV50060Supply Air Temperature Sensor FailureRead1=Normal, 2=Alarm
MV50061Outdoor Air Temperature Sensor FailureRead1=Normal, 2=Alarm
MV50062DAT Low Temperature AlarmRead1=Normal, 2=Lockout
MV50063Heater Lockout AlarmRead1=Normal, 2=Lockout
MV50064ZN-T Remote Setpoint EnableWrite1=No remote Setpoint, 2=Hardware Only, 3=Network Only, 4=Network with Hardware Backup
MV50065Continuous Fan Operation in OccupiedWrite1=No, 2=Yes
MV50066SF BypassWrite1=No, 2=Yes
AV130Zone Low Limit + Differential°FWrite
AV756Discharge Air Set Point – Unit Heat Mode°FRead
AV1382Burner Modulation Set Point%Read
AV3003Device AddressWrite
AV3004Device Object IDWrite
AV3007Zone Low Limit Set Point°FWrite
AV3008Effective Cooling Set Point°FRead
AV3009Effective Heating Set Point°FRead
AV3010Heating Lockout Set Point°FWrite
AVmin3011Effective Discharge Air TemperatureHardware point AI:6°FRead
AV3012Discharge Air High Set Point°FWrite
AV3014Discharge Air Low Set Point°FWrite
AV3015Occupied Zone Cooling Set Point°FWrite
AV3016Unoccupied Zone Cooling Set Point°FWrite
AVmin3017Occupied Zone Heating Set Point°FWrite
AV3018Unoccupied Zone Heating Set Point°FWrite
AV3019Effective Outdoor TemperatureHardware point AI:8°FRead
AV3020Effective Zone TemperatureHardware point AI:9°FRead
AV3026Modulated Burner ControlHardware point AO:1%Read
AV3029Application Software VersionRead
AV3030Effective Discharge Air Set Point°FRead
AV3031Supply Fan Speed (optional)%Write
AV3033Burner RuntimehoursRead
AV3034Burner Cycle CountRead
AV3035Supply Fan RuntimehoursRead
AV3036Supply Fan Cycle CountRead
AVmin3037Discharge Air Set Point – Makeup Air Mode°FWrite
AV3038Network Override Outdoor Air Temperature°FWrite
AV3040Filter Pressure Offsetin. w.c.Write
AV3041Fan Fault DelaysecondsWrite
AV3042Burner Fault DelaysecondsWrite
AV3043Low Temperature Cutout Setpoint°FWrite
AV3044Low Temperature Cutout DelaysecondsWrite
AV3045Network Override Zone Temperature°FWrite
AV3046Zone Differential°FWrite
AV7018AI1 Max Valuein. w.c.Write
AV7019AI1 Output Range Highin. w.c.Write

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BACnet Controller - MAU and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cambridge Air Solutions BACnet Controller - MAU

How many BACnet points does the Cambridge Air Solutions BACnet Controller - MAU have?

This list has 77 BACnet objects: 39 analog values, 4 binary values, 34 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cambridge Air Solutions BACnet Controller - MAU BACnet points are writable?

42 of the 77 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Cambridge Air Solutions BACnet Controller - MAU BACnet documentation?

The source is Operating Instructions - BACnet Controller - MAU (BACnet Controller MAU Technical Manual) (Version 4.0.3.0012), revision 2022-11-30, published free by Cambridge Air Solutions at https://www.cambridge-eng.com/Portals/0/Operating%20Instructions%20v4_0_3_0012.pdf.

What are the minimum BACnet points to integrate the Cambridge Air Solutions BACnet Controller - MAU?

Start with MV 3011 Unit Enable Mode (Shutdown / enable); MV 3021 Occupancy Override (Occupied / unoccupied / standby from the BAS); MV 50052 Normal Mode (Unit heat, make-up air, summer vent or off); AV 3037 Discharge Air Set Point – Makeup Air Mode (Discharge setpoint in make-up air mode); AV 3017 Occupied Zone Heating Set Point (Zone temp the burner heats to when occupied); MV 50058 Reset Unit Fault (Network fault reset); MV 3001 Unit Status (Heating / satisfied / cooling / sensor unreliable); AV 3011 Effective Discharge Air Temperature (Supply air temp leaving the unit, °F); MV 3018 Burner Status (Burner proven on); MV 50056 Burner Fault (Burner alarm).

How do I enable BMS control of the Cambridge Air Solutions BACnet Controller - MAU?

MV-3011 Unit Enable Mode (1=Shutdown, 2=Enable). Fan and burner Hand/Off/Auto overrides are MV-50050 Supply Fan HOA and MV-11 Burner HOA; leave them in Auto (3) for normal control.

Can the BMS supply sensor values to the Cambridge Air Solutions BACnet Controller - MAU?

Network values can replace the wired sensors: AV-3038 Network Override Outdoor Air Temperature and AV-3045 Network Override Zone Temperature. MV-50064 ZN-T Remote Setpoint Enable selects no remote setpoint, hardware only, network only, or network with hardware backup. The manual gives no timeout for these.

How do I check these points on the real BACnet Controller - MAU?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Operating Instructions - BACnet Controller - MAU (BACnet Controller MAU Technical Manual) · Version 4.0.3.0012 · rev. 2022-11-30. Object names, instances and units are reproduced as published; descriptions are our own.