Make-up air heater controller · BACnet points list
Cambridge Air Solutions BACnet Controller - MAU BACnet points list
Updated 28 October 2026
Cambridge's BACnet Controller is a BTL-listed, programmable MS/TP controller mounted in the heater that runs the fan and burner and gives a BAS access to its points. The object list is mostly multistate values (statuses, commands, HOA, modes, alarms) and analog values (temperatures, setpoints, delays, runtimes), with four binary values for runtime/cycle-count resets. Operating mode (unit heat, make-up air, make-up air with reset, summer vent, off) is selected with the Normal and Override Mode MVs.
This page lists 77 BACnet objects for the Cambridge Air Solutions BACnet Controller - MAU — 42 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Cambridge Air Solutions’s own free documentation, linked below.
- Manufacturer
- Cambridge Air Solutions
- Model
- BACnet Controller - MAU
- Equipment
- Make-up air heater controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 77 (42 writable)
- Transport
- BACnet MS/TP
- Firmware
- 4.0.3.0012
- Also known as
- Cambridge MAU controller, Cambridge BACnet Controller, Cambridge heater BACnet, MAU Technical Manual 4.0.3.0012
BMS integration notes: Cambridge Air Solutions BACnet Controller - MAU
Enable the unit with MV-3011 Unit Enable Mode, choose the operating mode with MV-50052 Normal Mode (MV-50053 Override Mode for the alternate mode) and command occupancy with MV-3021 Occupancy Override or the controller's own schedule. Adjust the zone and discharge setpoints, read MV-3001 Unit Status, the burner/fan status MVs and the fault MVs, and reset faults with MV-50058. The controller runs stand-alone on its defaults (unit heater mode, 160°F discharge, 65°F zone) if the network is lost, provided a zone sensor is connected.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 3011 | Unit Enable Mode | Shutdown / enable | Write |
| MV 3021 | Occupancy Override | Occupied / unoccupied / standby from the BAS | Write |
| MV 50052 | Normal Mode | Unit heat, make-up air, summer vent or off | Write |
| AV 3037 | Discharge Air Set Point – Makeup Air Mode | Discharge setpoint in make-up air mode | Write |
| AV 3017 | Occupied Zone Heating Set Point | Zone temp the burner heats to when occupied | Write |
| MV 50058 | Reset Unit Fault | Network fault reset | Write |
| MV 3001 | Unit Status | Heating / satisfied / cooling / sensor unreliable | Read |
| AV 3011 | Effective Discharge Air Temperature | Supply air temp leaving the unit, °F | Read |
| MV 3018 | Burner Status | Burner proven on | Read |
| MV 50056 | Burner Fault | Burner alarm | Read |
Enable & remote start
MV-3011 Unit Enable Mode (1=Shutdown, 2=Enable). Fan and burner Hand/Off/Auto overrides are MV-50050 Supply Fan HOA and MV-11 Burner HOA; leave them in Auto (3) for normal control.
Sensors & values from the BMS
Network values can replace the wired sensors: AV-3038 Network Override Outdoor Air Temperature and AV-3045 Network Override Zone Temperature. MV-50064 ZN-T Remote Setpoint Enable selects no remote setpoint, hardware only, network only, or network with hardware backup. The manual gives no timeout for these.
Network setup
- MS/TP only, up to 76.8 kbaud; MAC address 4-127 (default 4), set from the local display (Controller > Network) or a MAP gateway (AV-3003).
- Baud rate defaults to Auto (follows the bus supervisor); the manual suggests 38400 when used with a Smart Building Hub.
- Device Object ID (AV-3004) must be unique; BACnet Encoding Type must match the rest of the network.
- Disconnect from the bus while changing network settings and cycle power afterwards.
- An EOL terminator is needed when the controller is at either end of the MS/TP trunk.
Watch out for
- The heating lockout (AV-3010) stops the burner whenever outdoor temperature is above it, even with a heating call.
- In summer vent mode with SF Bypass = No, the fan will not run if outdoor temperature is above zone temperature.
- Continuous Fan Operation in Occupied (MV-50065) decides whether the fan keeps running when the zone is satisfied in the reset & on/off mode.
- Some faults also need a reset from the local display (Commissioning > Overrides > Unit Reset) or MV-50058.
Cambridge Air Solutions BACnet Controller - MAU BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 3032 | Supply Fan Output (optional) | Hardware point AO:2 | % | Read | |
| AV | 3039 | Filter pressure (optional) | Hardware point AI:5 | in. w.c. | Read | |
| MV | 50051 | Filter status (optional) | Hardware point BI:7 | Read | 0=Normal, 1=Alarm | |
| MV | 50055 | Mode Switch (optional) | Hardware point BI:4 | Read | 0=Normal, 1=Override | |
| BV | 0 | Burner Runtime Reset | Write | 0=Off, 1=Reset | ||
| BV | 1 | Burner Cycle Count Reset | Write | 0=Off, 1=Reset | ||
| BV | 2 | Supply Fan Runtime Reset | Write | 0=Off, 1=Reset | ||
| BV | 3 | Supply Fan Cycle Count Reset | Write | 0=Off, 1=Reset | ||
| MV | 11 | Burner HOA | Write | 1=Hand, 2=Off, 3=Auto | ||
| MV | 1577 | Burner Modulation Mode | Write | 1=Auto, 2=Manual | ||
| MVmin | 3001 | Unit Status | Read | 1=Heating, 2=Satisfied, 3=Cooling, 4=Temperature Unreliable | ||
| MV | 3006 | Units | Write | 1=IP, 2=SI | ||
| MV | 3007 | FCB Baud Rate | Write | 1=Auto, 2=1200, 3=9600, 4=19200, 5=38400, 6=76800 | ||
| MV | 3008 | Operating Baud Rate | Baud rate in use (see FCB Baud Rate states) | Read | ||
| MV | 3009 | PID Tuning Reset | Write | 1=Off, 2=Reset | ||
| MV | 3010 | Occupancy Schedule | Occupancy schedule reference | Write | ||
| MVmin | 3011 | Unit Enable Mode | Write | 1=Shutdown, 2=Enable | ||
| MV | 3012 | Effective Occupancy | Read | Occupied / Unoccupied | ||
| MV | 3016 | Supply Fan Status | Hardware point BI:2 | Read | 1=Off, 2=On | |
| MV | 3017 | Unit Reset Fault | Hardware point BI:3 | Read | 1=Normal, 2=Alarm | |
| MVmin | 3018 | Burner Status | Hardware point BI:1 | Read | 1=Off, 2=On | |
| MV | 3019 | Burner Command | Hardware point BO:4 | Read | 1=Off, 2=On | |
| MV | 3020 | Supply Fan Command | Hardware point BO:5 | Read | 1=Off, 2=On | |
| MVmin | 3021 | Occupancy Override | Write | 1=Occupied, 2=UnOccupied, 3=Bypass, 4=Standby, 5=Not Set | ||
| MV | 3022 | Emergency Heat Enabled | Read | 1=Inactive, 2=Active | ||
| MV | 50050 | Supply Fan HOA | Write | 1=Hand, 2=Off, 3=Auto | ||
| MVmin | 50052 | Normal Mode | Write | 1=Unit Heat, 2=Makeup Air, 3=Makeup Air w/Reset, 4=Makeup Air w/Reset & On-Off, 5=Summer Vent, 6=Off | ||
| MV | 50053 | Override Mode | Write | 1=Unit Heat, 2=Makeup Air, 3=Makeup Air w/Reset, 4=Makeup Air w/Reset & On-Off, 5=Summer Vent, 6=Off | ||
| MV | 50054 | Effective Mode | Read | 1=Unit Heat, 2=Makeup Air, 3=Makeup Air w/Reset, 4=Makeup Air w/Reset & On-Off, 5=Summer Vent, 6=Off | ||
| MVmin | 50056 | Burner Fault | Read | 1=Normal, 2=Alarm | ||
| MV | 50057 | Supply Fan Fault | Read | 1=Normal, 2=Alarm | ||
| MVmin | 50058 | Reset Unit Fault | Write | 1=Off, 2=Reset | ||
| MV | 50059 | Zone Temperature Sensor Failure | Read | 1=Normal, 2=Alarm | ||
| MV | 50060 | Supply Air Temperature Sensor Failure | Read | 1=Normal, 2=Alarm | ||
| MV | 50061 | Outdoor Air Temperature Sensor Failure | Read | 1=Normal, 2=Alarm | ||
| MV | 50062 | DAT Low Temperature Alarm | Read | 1=Normal, 2=Lockout | ||
| MV | 50063 | Heater Lockout Alarm | Read | 1=Normal, 2=Lockout | ||
| MV | 50064 | ZN-T Remote Setpoint Enable | Write | 1=No remote Setpoint, 2=Hardware Only, 3=Network Only, 4=Network with Hardware Backup | ||
| MV | 50065 | Continuous Fan Operation in Occupied | Write | 1=No, 2=Yes | ||
| MV | 50066 | SF Bypass | Write | 1=No, 2=Yes | ||
| AV | 130 | Zone Low Limit + Differential | °F | Write | ||
| AV | 756 | Discharge Air Set Point – Unit Heat Mode | °F | Read | ||
| AV | 1382 | Burner Modulation Set Point | % | Read | ||
| AV | 3003 | Device Address | Write | |||
| AV | 3004 | Device Object ID | Write | |||
| AV | 3007 | Zone Low Limit Set Point | °F | Write | ||
| AV | 3008 | Effective Cooling Set Point | °F | Read | ||
| AV | 3009 | Effective Heating Set Point | °F | Read | ||
| AV | 3010 | Heating Lockout Set Point | °F | Write | ||
| AVmin | 3011 | Effective Discharge Air Temperature | Hardware point AI:6 | °F | Read | |
| AV | 3012 | Discharge Air High Set Point | °F | Write | ||
| AV | 3014 | Discharge Air Low Set Point | °F | Write | ||
| AV | 3015 | Occupied Zone Cooling Set Point | °F | Write | ||
| AV | 3016 | Unoccupied Zone Cooling Set Point | °F | Write | ||
| AVmin | 3017 | Occupied Zone Heating Set Point | °F | Write | ||
| AV | 3018 | Unoccupied Zone Heating Set Point | °F | Write | ||
| AV | 3019 | Effective Outdoor Temperature | Hardware point AI:8 | °F | Read | |
| AV | 3020 | Effective Zone Temperature | Hardware point AI:9 | °F | Read | |
| AV | 3026 | Modulated Burner Control | Hardware point AO:1 | % | Read | |
| AV | 3029 | Application Software Version | Read | |||
| AV | 3030 | Effective Discharge Air Set Point | °F | Read | ||
| AV | 3031 | Supply Fan Speed (optional) | % | Write | ||
| AV | 3033 | Burner Runtime | hours | Read | ||
| AV | 3034 | Burner Cycle Count | Read | |||
| AV | 3035 | Supply Fan Runtime | hours | Read | ||
| AV | 3036 | Supply Fan Cycle Count | Read | |||
| AVmin | 3037 | Discharge Air Set Point – Makeup Air Mode | °F | Write | ||
| AV | 3038 | Network Override Outdoor Air Temperature | °F | Write | ||
| AV | 3040 | Filter Pressure Offset | in. w.c. | Write | ||
| AV | 3041 | Fan Fault Delay | seconds | Write | ||
| AV | 3042 | Burner Fault Delay | seconds | Write | ||
| AV | 3043 | Low Temperature Cutout Setpoint | °F | Write | ||
| AV | 3044 | Low Temperature Cutout Delay | seconds | Write | ||
| AV | 3045 | Network Override Zone Temperature | °F | Write | ||
| AV | 3046 | Zone Differential | °F | Write | ||
| AV | 7018 | AI1 Max Value | in. w.c. | Write | ||
| AV | 7019 | AI1 Output Range High | in. w.c. | Write |
No points match these filters.
Integration notes
- Optional points (mode switch, filter status/pressure, supply fan output and speed) exist only on units with those options.
- Rows from the input/output tables point to the same MV/AV objects as the value tables; hardware terminal numbers are kept in the description.
- The input/output tables show binary states as 0/1 while the MV table shows the same objects as 1/2; both are kept as printed.
- MV-50052/50053/50054 share one mode state list in the source (merged cell).
- Temperatures in °F by default (MV-3006 selects IP/SI); filter pressure in in. w.c.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BACnet Controller - MAU and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Cambridge Air Solutions BACnet Controller - MAU
How many BACnet points does the Cambridge Air Solutions BACnet Controller - MAU have?
This list has 77 BACnet objects: 39 analog values, 4 binary values, 34 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Cambridge Air Solutions BACnet Controller - MAU BACnet points are writable?
42 of the 77 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Cambridge Air Solutions BACnet Controller - MAU BACnet documentation?
The source is Operating Instructions - BACnet Controller - MAU (BACnet Controller MAU Technical Manual) (Version 4.0.3.0012), revision 2022-11-30, published free by Cambridge Air Solutions at https://www.cambridge-eng.com/Portals/0/Operating%20Instructions%20v4_0_3_0012.pdf.
What are the minimum BACnet points to integrate the Cambridge Air Solutions BACnet Controller - MAU?
Start with MV 3011 Unit Enable Mode (Shutdown / enable); MV 3021 Occupancy Override (Occupied / unoccupied / standby from the BAS); MV 50052 Normal Mode (Unit heat, make-up air, summer vent or off); AV 3037 Discharge Air Set Point – Makeup Air Mode (Discharge setpoint in make-up air mode); AV 3017 Occupied Zone Heating Set Point (Zone temp the burner heats to when occupied); MV 50058 Reset Unit Fault (Network fault reset); MV 3001 Unit Status (Heating / satisfied / cooling / sensor unreliable); AV 3011 Effective Discharge Air Temperature (Supply air temp leaving the unit, °F); MV 3018 Burner Status (Burner proven on); MV 50056 Burner Fault (Burner alarm).
How do I enable BMS control of the Cambridge Air Solutions BACnet Controller - MAU?
MV-3011 Unit Enable Mode (1=Shutdown, 2=Enable). Fan and burner Hand/Off/Auto overrides are MV-50050 Supply Fan HOA and MV-11 Burner HOA; leave them in Auto (3) for normal control.
Can the BMS supply sensor values to the Cambridge Air Solutions BACnet Controller - MAU?
Network values can replace the wired sensors: AV-3038 Network Override Outdoor Air Temperature and AV-3045 Network Override Zone Temperature. MV-50064 ZN-T Remote Setpoint Enable selects no remote setpoint, hardware only, network only, or network with hardware backup. The manual gives no timeout for these.
How do I check these points on the real BACnet Controller - MAU?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: Operating Instructions - BACnet Controller - MAU (BACnet Controller MAU Technical Manual) · Version 4.0.3.0012 · rev. 2022-11-30. Object names, instances and units are reproduced as published; descriptions are our own.