Air curtain controller · BACnet points list

Berner AIR BMS package (IntelliSwitch) BACnet points list

Updated 4 November 2026

Short answer

The Berner AIR BMS package makes the IntelliSwitch air curtain control a BACnet application specific controller (B-ASC) on BACnet MS/TP or BACnet IP (wired or wireless). Besides mode, fan speed, time delay and door status it adds a BMS mode in which the BMS calls for fan and heat directly, a heater disable and a heater cool-down delay. Heated models add a setpoint and door temperature in °F and °C.

This page lists 14 BACnet objects for the Berner AIR BMS package (IntelliSwitch) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Berner’s own free documentation, linked below.

Manufacturer
Berner
Model
Berner AIR BMS package (IntelliSwitch)
Equipment
Air curtain controller
Equipment type
Other equipment
BACnet objects
14 (9 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Software 3.00, firmware 1.46
Also known as
Berner AIR BMS, IntelliSwitch, IntelliSwitch g5, Architectural Elite AE08-F, Architectural Elite AE10-F, AE08-F, AE10-F
Source document
Berner AIR BMS BACnet PICS (for Berner air curtains with the Berner AIR BMS package) · rev. 2025-03-26
Download CSV 14 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Berner’s current documentation and the live device before use. Not official Berner information. Terms of use.

BMS integration notes: Berner AIR BMS package (IntelliSwitch)

Integration in brief

Either write MV 1 Mode to Off/On/Auto/Comfort+ and let the curtain run itself, or set Mode to 5 (BMS) and drive it with BV 1 CallForFan and, on heated models, BV 2 CallForHeat. Set PIV 2 FanSpeed and the AV 1 (°F) or AV 2 (°C) setpoint, and read BI 1 DoorStatus and the door temperature.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1ModeMode: 1 off, 2 on, 3 auto, 4 Comfort+, 5 BMSWrite
BV 1CallForFanFan run command in BMS modeWrite
BV 2CallForHeatHeat command in BMS mode (heated models)Write
PIV 2FanSpeedFan speed commandWrite
AV 1TargetTemperatureFahrenheitHeat setpoint, 34-90 °F (heated models)Write
BI 1DoorStatusDoor open (active) or closedRead
AI 1TemperatureFahrenheitDoor temperature, °F (heated models)Read

Enable & remote start

MV 1 Mode = 5 (BMS) hands the fan and heater to BV 1 CallForFan and BV 2 CallForHeat. BV 3 HeaterDisabled turns the heater off completely.

Network setup

Watch out for

Berner AIR BMS package (IntelliSwitch) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

14 of 14 shown
Type
Multi-state
Access
Show
Berner AIR BMS package (IntelliSwitch) BACnet Points List
DescriptionStates
MVmin1ModeAir curtain mode; 2-5 states by modelWrite1=Off, 2=On, 3=Auto, 4=Comfort+, 5=BMS
PIV1DoorOpenCountDoor openings since midnightRead
PIVmin2FanSpeedFan speed, 1 to 1/2/3/10 by modelWrite
PIV3TimeDelayTime delay, 0-300 s, default 30sWrite
BImin1DoorStatusDoor open (active) or closed (inactive)Readinactive=closed, active=open
BVmin1CallForFanRuns the fan when Mode is BMSWriteinactive=OFF, active=ON
Other1SerialNetwork Port object; 'Wired' or 'Wireless' in IP modeRead
AVmin1TargetTemperatureFahrenheitTemperature setpoint, 34-90 °F (heated models)°FWrite
AV2TargetTemperatureCelsiusTemperature setpoint, 1-32 °C (heated models)°CWrite
AImin1TemperatureFahrenheitTemperature at the door (heated models)°FRead
AI2TemperatureCelsiusTemperature at the door (heated models)°CRead
PIV4Cool Down DelayHeater cool-down delay (heated models)sWrite
BV3HeaterDisabledDisables the heater completely (heated models)Writeinactive=OFF, active=ON
BVmin2CallForHeatRuns the heater when Mode is BMS (heated models)Writeinactive=OFF, active=ON
Object ID lookup: Berner AIR BMS package point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Berner AIR BMS package (IntelliSwitch) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Berner AIR BMS package (IntelliSwitch)

How many BACnet points does the Berner AIR BMS package (IntelliSwitch) have?

This list has 14 BACnet objects: 2 analog inputs, 2 analog values, 1 binary input, 3 binary values, 1 multi-state value, 4 positive integer values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Berner AIR BMS package (IntelliSwitch) BACnet points are writable?

9 of the 14 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Berner AIR BMS package (IntelliSwitch) BACnet documentation?

The source is Berner AIR BMS BACnet PICS (for Berner air curtains with the Berner AIR BMS package), revision 2025-03-26, published free by Berner at https://berner.com/wp-content/uploads/2025/07/Berner-AIR-BMS-BACnet-PICS-3.1.0212.pdf.

What are the minimum BACnet points to integrate the Berner AIR BMS package (IntelliSwitch)?

Start with MV 1 Mode (Mode: 1 off, 2 on, 3 auto, 4 Comfort+, 5 BMS); BV 1 CallForFan (Fan run command in BMS mode); BV 2 CallForHeat (Heat command in BMS mode (heated models)); PIV 2 FanSpeed (Fan speed command); AV 1 TargetTemperatureFahrenheit (Heat setpoint, 34-90 °F (heated models)); BI 1 DoorStatus (Door open (active) or closed); AI 1 TemperatureFahrenheit (Door temperature, °F (heated models)).

How do I enable BMS control of the Berner AIR BMS package (IntelliSwitch)?

MV 1 Mode = 5 (BMS) hands the fan and heater to BV 1 CallForFan and BV 2 CallForHeat. BV 3 HeaterDisabled turns the heater off completely.

How do I check these points on the real Berner AIR BMS package (IntelliSwitch)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Berner BACnet points lists

Source: Berner AIR BMS BACnet PICS (for Berner air curtains with the Berner AIR BMS package) · rev. 2025-03-26. Object names, instances and units are reproduced as published; descriptions are our own.