 "manufacturer": "Berner",
 "manufacturer_slug": "berner",
 "model": "Berner AIR BMS package (IntelliSwitch)",
 "model_slug": "air-bms-intelliswitch",
 "aliases": [
  "Berner AIR BMS",
  "IntelliSwitch",
  "IntelliSwitch g5",
  "Architectural Elite AE08-F",
  "Architectural Elite AE10-F",
  "AE08-F",
  "AE10-F"
 ],
 "equipment_type": "Air curtain controller",
 "applies_to": "Berner air curtains fitted with the Berner AIR BMS package on the IntelliSwitch control (software 3.00, firmware 1.46), including the Architectural Elite AE08-F and AE10-F.",
 "summary": "The Berner AIR BMS package makes the IntelliSwitch air curtain control a BACnet application specific controller (B-ASC) on BACnet MS/TP or BACnet IP (wired or wireless). Besides mode, fan speed, time delay and door status it adds a BMS mode in which the BMS calls for fan and heat directly, a heater disable and a heater cool-down delay. Heated models add a setpoint and door temperature in °F and °C.",
 "bacnet_transport": [
  "BACnet MS/TP",
  "BACnet IP"
 ],
 "firmware": "Software 3.00, firmware 1.46",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "From the PICS dated 26 March 2025 (footer Rev. December 2024; file name 3.1.0212); each object's present value is marked RO or RW.",
  "Berner's earlier PICS for the Architectural Elite AE08-F / AE10-F (same software 3.00 / firmware 1.46) lists a subset: no BMS mode state, CallForFan, CallForHeat, HeaterDisabled or Cool Down Delay.",
  "The Network Port object (type 56) is listed as Other 1; it is named Serial in MS/TP mode and Wired or Wireless in IP mode.",
  "The summary table spells PIV 4 as CoolDownDelay; the object block gives the name Cool Down Delay.",
  "AV 1-2, AI 1-2, PIV 4, BV 2 and BV 3 apply to heated models only."
 ],
 "source": {
  "title": "Berner AIR BMS BACnet PICS (for Berner air curtains with the Berner AIR BMS package)",
  "doc_number": null,
  "revision_date": "2025-03-26",
  "url": "https://berner.com/wp-content/uploads/2025/07/Berner-AIR-BMS-BACnet-PICS-3.1.0212.pdf"
 },
 "integration": {
  "summary": "Either write MV 1 Mode to Off/On/Auto/Comfort+ and let the curtain run itself, or set Mode to 5 (BMS) and drive it with BV 1 CallForFan and, on heated models, BV 2 CallForHeat. Set PIV 2 FanSpeed and the AV 1 (°F) or AV 2 (°C) setpoint, and read BI 1 DoorStatus and the door temperature.",
  "minimum_points": [
   {
    "ref": "MV 1",
    "name": "Mode",
    "why": "Mode: 1 off, 2 on, 3 auto, 4 Comfort+, 5 BMS"
   },
   {
    "ref": "BV 1",
    "name": "CallForFan",
    "why": "Fan run command in BMS mode"
   },
   {
    "ref": "BV 2",
    "name": "CallForHeat",
    "why": "Heat command in BMS mode (heated models)"
   },
   {
    "ref": "PIV 2",
    "name": "FanSpeed",
    "why": "Fan speed command"
   },
   {
    "ref": "AV 1",
    "name": "TargetTemperatureFahrenheit",
    "why": "Heat setpoint, 34-90 °F (heated models)"
   },
   {
    "ref": "BI 1",
    "name": "DoorStatus",
    "why": "Door open (active) or closed"
   },
   {
    "ref": "AI 1",
    "name": "TemperatureFahrenheit",
    "why": "Door temperature, °F (heated models)"
   }
  ],
  "enable": "MV 1 Mode = 5 (BMS) hands the fan and heater to BV 1 CallForFan and BV 2 CallForHeat. BV 3 HeaterDisabled turns the heater off completely.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "MS/TP: MAC address 0-127, max master and max info frames are set in the Network Port object (Serial).",
   "IP: wired or wireless is chosen on the touchscreen or the mobile app; UDP port 47808 by default; foreign device registration with a BBMD address and a default lifetime of 30."
  ],
  "gotchas": [
   "MV 1 reports Out_Of_Service = true while the emergency stop is active.",
   "CallForFan and CallForHeat only act when Mode is BMS.",
   "AV 1 (°F) and AV 2 (°C) are both the temperature setpoint; map the one in your BMS units."
  ]
 },
 "points": [
  {
   "type": "MV",
   "instance": 1,
   "name": "Mode",
   "description": "Air curtain mode; 2-5 states by model",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=On, 3=Auto, 4=Comfort+, 5=BMS"
  },
  {
   "type": "PIV",
   "instance": 1,
   "name": "DoorOpenCount",
   "description": "Door openings since midnight",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 2,
   "name": "FanSpeed",
   "description": "Fan speed, 1 to 1/2/3/10 by model",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 3,
   "name": "TimeDelay",
   "description": "Time delay, 0-300 s, default 30",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "DoorStatus",
   "description": "Door open (active) or closed (inactive)",
   "units": "",
   "access": "R",
   "states": "inactive=closed, active=open"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "CallForFan",
   "description": "Runs the fan when Mode is BMS",
   "units": "",
   "access": "W",
   "states": "inactive=OFF, active=ON"
  },
  {
   "type": "Other",
   "instance": 1,
   "name": "Serial",
   "description": "Network Port object; 'Wired' or 'Wireless' in IP mode",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "TargetTemperatureFahrenheit",
   "description": "Temperature setpoint, 34-90 °F (heated models)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "TargetTemperatureCelsius",
   "description": "Temperature setpoint, 1-32 °C (heated models)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "TemperatureFahrenheit",
   "description": "Temperature at the door (heated models)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "TemperatureCelsius",
   "description": "Temperature at the door (heated models)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 4,
   "name": "Cool Down Delay",
   "description": "Heater cool-down delay (heated models)",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "HeaterDisabled",
   "description": "Disables the heater completely (heated models)",
   "units": "",
   "access": "W",
   "states": "inactive=OFF, active=ON"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "CallForHeat",
   "description": "Runs the heater when Mode is BMS (heated models)",
   "units": "",
   "access": "W",
   "states": "inactive=OFF, active=ON"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/berner/air-bms-intelliswitch",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}