Air curtain controller · BACnet points list

Berner AIR air curtain (WCA) BACnet points list

Updated 4 November 2026

Short answer

The Berner AIR WCA interface puts a Berner air curtain on BACnet IP as an application specific controller (B-ASC). It exposes 11 objects: the mode, fan speed and time delay commands, a weekly operating-hours schedule, door status and door-open count, an operating status, and on heated models a temperature setpoint and door temperature in both °F and °C.

This page lists 11 BACnet objects for the Berner AIR air curtain (WCA) — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Berner’s own free documentation, linked below.

Manufacturer
Berner
Model
Berner AIR air curtain (WCA)
Equipment
Air curtain controller
Equipment type
Other equipment
BACnet objects
11 (6 writable)
Transport
BACnet IP
Firmware
Software 2.33, firmware revision 2254
Also known as
Berner WCA, Berner AIR WCA, Berner AIR
Source document
Berner AIR BACnet PICS (Berner WCA) · rev. 2024-03-28
Download CSV 11 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Berner’s current documentation and the live device before use. Not official Berner information. Terms of use.

BMS integration notes: Berner AIR air curtain (WCA)

Integration in brief

Write MV 1 Mode (Off/On/Auto/Comfort+) and PIV 2 FanSpeed, and on heated models the setpoint AV 1 (°F) or AV 2 (°C). The SCH 1 OperatingHours schedule drives BI 2 OperatingStatus. Read BI 1 DoorStatus and the door temperature.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1ModeMode: 1 off, 2 on, 3 auto, 4 Comfort+Write
PIV 2FanSpeedFan speed commandWrite
AV 1TargetTemperatureFahrenheitHeat setpoint, 34-90 °F (heated models)Write
BI 2OperatingStatusOperating per scheduleRead
BI 1DoorStatusDoor open (active) or closedRead
AI 1TemperatureFahrenheitDoor temperature, °F (heated models)Read

Enable & remote start

MV 1 Mode selects Off (1), On (2), Auto (3) or Comfort+ (4); the number of available states depends on the model.

Network setup

Watch out for

Berner AIR air curtain (WCA) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

11 of 11 shown
Type
BinaryMulti-state
Access
Show
Berner AIR air curtain (WCA) BACnet Points List
DescriptionStates
MVmin1ModeAir curtain mode; 2-4 states by modelWrite1=Off, 2=On, 3=Auto, 4=Comfort+
SCH1OperatingHoursWeekly operating schedule, default 24/7Write
PIV1DoorOpenCountDoor openings since midnightRead
PIVmin2FanSpeedFan speed, 1 to 1/2/3/10 by modelWrite
PIV3TimeDelayTime delay for the selected mode, 0-300 ssWrite
BImin1DoorStatusDoor open (active) or closed (inactive)Readinactive=closed, active=open
BImin2OperatingStatusOperating status from the scheduleReadinactive=off, active=on
AVmin1TargetTemperatureFahrenheitTemperature setpoint, 34-90 °F (heated models)°FWrite
AV2TargetTemperatureCelsiusTemperature setpoint, 1-32 °C (heated models)°CWrite
AImin1TemperatureFahrenheitTemperature at the door (heated models)°FRead
AI2TemperatureCelsiusTemperature at the door (heated models)°CRead
Object ID lookup: Berner AIR air curtain point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Berner AIR air curtain (WCA) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Berner AIR air curtain (WCA)

How many BACnet points does the Berner AIR air curtain (WCA) have?

This list has 11 BACnet objects: 2 analog inputs, 2 analog values, 2 binary inputs, 1 schedule, 1 multi-state value, 3 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Berner AIR air curtain (WCA) BACnet points are writable?

6 of the 11 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Berner AIR air curtain (WCA) BACnet documentation?

The source is Berner AIR BACnet PICS (Berner WCA), revision 2024-03-28, published free by Berner at https://berner.com/wp-content/uploads/2025/05/Berner-AIR-BACnet-PICS-WCA.pdf.

What are the minimum BACnet points to integrate the Berner AIR air curtain (WCA)?

Start with MV 1 Mode (Mode: 1 off, 2 on, 3 auto, 4 Comfort+); PIV 2 FanSpeed (Fan speed command); AV 1 TargetTemperatureFahrenheit (Heat setpoint, 34-90 °F (heated models)); BI 2 OperatingStatus (Operating per schedule); BI 1 DoorStatus (Door open (active) or closed); AI 1 TemperatureFahrenheit (Door temperature, °F (heated models)).

How do I enable BMS control of the Berner AIR air curtain (WCA)?

MV 1 Mode selects Off (1), On (2), Auto (3) or Comfort+ (4); the number of available states depends on the model.

How do I check these points on the real Berner AIR air curtain (WCA)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Berner BACnet points lists

Source: Berner AIR BACnet PICS (Berner WCA) · rev. 2024-03-28. Object names, instances and units are reproduced as published; descriptions are our own.