- 75F HyperStat smart thermostat / sensor (BACnet MS/TP)
Smart thermostat and room sensor · BACnet points list
75F HyperStat smart thermostat / sensor (BACnet MS/TP) BACnet points list
Updated 12 November 2026Unofficial source
The 75F HyperStat is a room thermostat and multi-sensor that can run standalone on BACnet MS/TP. Analog Inputs give room temperature, humidity, CO2, light, UV, VOC, sound and particulates plus its I/O; Analog Values hold heating and cooling setpoints, limits, deadbands and tuning; Binary and Multi-state objects cover relay enables, occupancy, conditioning mode, fan speed, the equipment profile and I/O mappings.
This page lists 113 BACnet objects for the 75F HyperStat smart thermostat / sensor (BACnet MS/TP) — 89 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of 75F’s documentation hosted by BACnet International catalog, not by 75F itself, so treat it as unofficial.
- Manufacturer
- 75F
- Model
- 75F HyperStat smart thermostat / sensor (BACnet MS/TP)
- Equipment
- Smart thermostat and room sensor
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 113 (89 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- HyperStat, 75F HyperStat, 77X-HS-C2W-X, HyperStat CPU, HyperStat HPU, HyperStat FCU, HyperStat Sense
- Source document
- 75F HyperStat PICS · rev. 2022-11-15 (unofficial copy, hosted by BACnet International catalog)
Reference only, provided as-is: verify against 75F’s current documentation and the live device before use. Not official 75F information. Terms of use.
BMS integration notes: 75F HyperStat smart thermostat / sensor (BACnet MS/TP)
Write the conditioning mode (MV 0), fan speed (MV 1) and heating / cooling setpoints (AV 0, AV 1); read room temperature, humidity and CO2, the active setpoints and the operating, conditioning, fan and occupancy states.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 0 | Desired Conditioning Mode | Conditioning mode: 1 off, 2 auto, 3 heat, 4 cool | Write |
| MV 1 | Desired Fan Speed | Fan speed: 1 off, 2 auto, 3 low, 4 med, 5 high | Write |
| AV 0 | Desired Set Temperature Heating | Heating setpoint | Write |
| AV 1 | Desired Set Temperature Cooling | Cooling setpoint | Write |
| BV 17 | Enable Force Occupied | Force occupied | Write |
| AI 0 | Room Temperature | Room temperature | Write |
| AI 1 | Humidity | Humidity | Read |
| AI 2 | CO2 | CO2 | Read |
| MI 0 | Operating Mode | Operating mode: off, heating, cooling | Write |
| MI 3 | Occupancy Status | Occupancy status | Write |
Network setup
- Device max-master and max-info-frames are writable; the device table shows max-master 127.
Watch out for
- Setpoints are limited by the min/max setpoint objects (AV 2-5).
75F HyperStat smart thermostat / sensor (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | Room Temperature | °F | Write | ||
| AImin | 1 | Humidity | Read | |||
| AImin | 2 | CO2 | Read | |||
| AI | 3 | Illuminance | Read | |||
| AI | 4 | UVI | Read | |||
| AI | 5 | VOC | Read | |||
| AI | 6 | Sound | Read | |||
| AI | 7 | PM2.5 | Read | |||
| AI | 8 | PM10 | Read | |||
| AI | 9 | Analog Input 1 | Read | |||
| AI | 10 | Analog Input 2 | Read | |||
| AI | 11 | Thermistor 1 | Read | |||
| AI | 12 | Thermistor 2 | Read | |||
| AI | 13 | Analog Out 1 | Read | |||
| AI | 14 | Analog Out 2 | Read | |||
| AI | 15 | Analog Out 3 | Read | |||
| AI | 16 | Active Set Temperature Heating | °F | Read | ||
| AI | 17 | Active Set Temperature Cooling | °F | Read | ||
| AVmin | 0 | Desired Set Temperature Heating | °F | Write | ||
| AVmin | 1 | Desired Set Temperature Cooling | °F | Write | ||
| AV | 2 | Max Set Temperature Heating | °F | Write | ||
| AV | 3 | Min Set Temperature Heating | °F | Write | ||
| AV | 4 | Max Set Temperature Cooling | °F | Write | ||
| AV | 5 | Min Set Temperature Cooing | °F | Write | ||
| AV | 6 | Temperature Offset | °F | Write | ||
| AV | 7 | Heating Deadband | °F | Write | ||
| AV | 8 | Cooling Deadband | °F | Write | ||
| AV | 9 | Max Humidity Setpoint | %RH | Write | ||
| AV | 10 | Min Humidity Setpoint | %RH | Write | ||
| AV | 11 | Analog Out 1 Min Setting | V | Write | ||
| AV | 12 | Analog Out 1 Max Setting | V | Write | ||
| AV | 13 | Analog Out 2 Min Setting | V | Write | ||
| AV | 14 | Analog Out 2 Max Setting | V | Write | ||
| AV | 15 | Analog Out 3 Min Setting | V | Write | ||
| AV | 16 | Analog Out 3 Max Setting | V | Write | ||
| AV | 17 | CO2 Alert Threshold | ppm | Write | ||
| AV | 18 | VOC Alert Threshold | ppb | Write | ||
| AV | 19 | PM2.5 Alert Threshold | mg/m3 | Write | ||
| AV | 20 | Zone CO2 Damper Opening Rate | % | Write | ||
| AV | 21 | Zone CO2 Threshold | ppm | Write | ||
| AV | 22 | Zone CO2 Target | V | Write | ||
| AV | 23 | Proportional Constant | Write | |||
| AV | 24 | Integral Constant | Write | |||
| AV | 25 | Proportional Temperature Range | Write | |||
| AV | 26 | Integration Time | Write | |||
| AV | 27 | Unoccupied Setback | °F | Write | ||
| AV | 28 | Heating Deadband Multiplier | Write | |||
| AV | 29 | Relay Activation Hysteresis | % | Write | ||
| AV | 30 | Fan Speed Multiplier | Write | |||
| AV | 31 | Humidity Hysteresis | % | Write | ||
| AV | 32 | Forced Occupied Time | min | Write | ||
| AV | 33 | Auto Away Time | min | Write | ||
| AV | 34 | Auto Away Setback Temperature | °F | Write | ||
| AV | 35 | FCU Aux Heating 1 Activate | °F | Write | ||
| AV | 36 | FCU Aux Heating 2 Activate | °F | Write | ||
| AV | 37 | FCU Two Pipe Heating Threshold | °F | Write | ||
| AV | 38 | FCU Two Pipe Cooling Threshold | °F | Write | ||
| AV | 39 | FCU Water Vlv Sampling On Time | min | Write | ||
| AV | 40 | FCU Water Vlv Wait Sampling Time | min | Write | ||
| AV | 41 | FCU Wtr Vlv Sampling During Loop Deadband On | min | Write | ||
| AV | 42 | FCU Wtr Vlv Sampling During Loop Deadband | min | Write | ||
| AV | 43 | Fail-Safe Time | min | Write | ||
| BI | 0 | Occupancy Status | Read | |||
| BI | 1 | Relay 1 | Read | |||
| BI | 2 | Relay 2 | Read | |||
| BI | 3 | Relay 3 | Read | |||
| BI | 4 | Relay 4 | Read | |||
| BI | 5 | Relay 5 | Read | |||
| BI | 6 | Relay 6 | Read | |||
| BV | 0 | Relay 1 Enable | Write | |||
| BV | 1 | Relay 2 Enable | Write | |||
| BV | 2 | Relay 3 Enable | Write | |||
| BV | 3 | Relay 4 Enable | Write | |||
| BV | 4 | Relay 5 Enable | Write | |||
| BV | 5 | Relay 5 Enable | Write | |||
| BV | 6 | Analog In 1 Enable | Write | |||
| BV | 7 | Analog In 2 Enable | Write | |||
| BV | 8 | Analog Out 1 Enable | Write | |||
| BV | 9 | Analog Out 2 Enable | Write | |||
| BV | 10 | Analog Out 3 Enable | Write | |||
| BV | 11 | Analog Out 1 Pulse Enable | Write | |||
| BV | 12 | Analog Out 2 Pulse Enable | Write | |||
| BV | 13 | Analog Out 3 Pulse Enable | Write | |||
| BV | 14 | Thermistor 1 Enable | Write | |||
| BV | 15 | Thermistor 2 Enable | Write | |||
| BV | 16 | Use TH1 As Room Temp Sensor | Write | |||
| BVmin | 17 | Enable Force Occupied | Write | |||
| BV | 18 | Enable Auto Away | Write | |||
| BV | 19 | Unoccupied Mode | Write | |||
| BV | 20 | Show Centigrade | Write | |||
| BV | 21 | Display CO2 | Write | |||
| BV | 22 | Display PM2.5 | Write | |||
| BV | 23 | Display VOC | Write | |||
| BV | 24 | Display Humidity | Write | |||
| MImin | 0 | Operating Mode | Write | 1=OFF, 2=HEATING, 3=COOLING | ||
| MI | 1 | Active Conditioning Mode | Write | 1=OFF, 2=AUTO, 3=HEAT, 4=COOL | ||
| MI | 2 | Active Fan Speed | Write | 1=AUTO, 2=LOW, 3=MEDIUM, 4=HIGH | ||
| MImin | 3 | Occupancy Status | Write | 1=INITIALIZING, 2=OCCUPIED, 3=UNOCCUPIED, 4=OCC. AUTO AWAY, 5=UNOCC. FORCE OCC. | ||
| MVmin | 0 | Desired Conditioning Mode | Write | 1=OFF, 2=AUTO, 3=HEAT, 4=COOL | ||
| MVmin | 1 | Desired Fan Speed | Write | 1=OFF, 2=AUTO, 3=LOW, 4=MEDIUM, 5=HIGH | ||
| MV | 2 | Temperature Mode | Write | 1=SINLGE SETPOINT, 2=DUAL SETPOINT FIX DB, 3=DUAL SETPOINT VAR DB, 4=COOL | ||
| MV | 3 | Profile | Write | 1=NONE, 2=CPU, 3=HPU, 4=FCU 2 PIPE, 5=FCU 4 PIPE, 7=SENSE | ||
| MV | 4 | Relay 1 Mapping | Write | |||
| MV | 5 | Relay 2 Mapping | Write | |||
| MV | 6 | Relay 3 Mapping | Write | |||
| MV | 7 | Relay 4 Mapping | Write | |||
| MV | 8 | Relay 5 Mapping | Write | |||
| MV | 9 | Relay 6 Mapping | Write | |||
| MV | 10 | Analog In 1 Mapping | Write | 1=CURRENT 0-10, 2=CURRENT 0-20, 3=CURRENT 0-50, 4=KEYCARD, 5=DOOR WINDOW | ||
| MV | 11 | Analog In 2 Mapping | Write | 1=CURRENT 0-10, 2=CURRENT 0-20, 3=CURRENT 0-50, 4=KEYCARD, 5=DOOR WINDOW | ||
| MV | 12 | Analog Out 1 Mapping | Write | 1=COOLING, 2=FAN SPEED, 3=HEATING, 4=DCV DAMPER | ||
| MV | 13 | Analog Out 2 Mapping | Write | 1=COOLING, 2=FAN SPEED, 3=HEATING, 4=DCV DAMPER | ||
| MV | 14 | Analog Out 3 Mapping | Write | 1=COOLING, 2=FAN SPEED, 3=HEATING, 4=DCV DAMPER |
No points match these filters.
Object ID lookup: 75F HyperStat smart thermostat / sensor point IDs by name
AI0Room TemperatureAI1HumidityAI2CO2AI3IlluminanceAI4UVIAI5VOCAI6SoundAI7PM2.5AI8PM10AI9Analog Input 1AI10Analog Input 2AI11Thermistor 1AI12Thermistor 2AI13Analog Out 1AI14Analog Out 2AI15Analog Out 3AI16Active Set Temperature HeatingAI17Active Set Temperature CoolingAV0Desired Set Temperature HeatingAV1Desired Set Temperature CoolingAV2Max Set Temperature HeatingAV3Min Set Temperature HeatingAV4Max Set Temperature CoolingAV5Min Set Temperature CooingAV6Temperature OffsetAV7Heating DeadbandAV8Cooling DeadbandAV9Max Humidity SetpointAV10Min Humidity SetpointAV11Analog Out 1 Min SettingAV12Analog Out 1 Max SettingAV13Analog Out 2 Min SettingAV14Analog Out 2 Max SettingAV15Analog Out 3 Min SettingAV16Analog Out 3 Max SettingAV17CO2 Alert ThresholdAV18VOC Alert ThresholdAV19PM2.5 Alert ThresholdAV20Zone CO2 Damper Opening RateAV21Zone CO2 ThresholdAV22Zone CO2 TargetAV23Proportional ConstantAV24Integral ConstantAV25Proportional Temperature RangeAV26Integration TimeAV27Unoccupied SetbackAV28Heating Deadband MultiplierAV29Relay Activation HysteresisAV30Fan Speed MultiplierAV31Humidity HysteresisAV32Forced Occupied TimeAV33Auto Away TimeAV34Auto Away Setback TemperatureAV35FCU Aux Heating 1 ActivateAV36FCU Aux Heating 2 ActivateAV37FCU Two Pipe Heating ThresholdAV38FCU Two Pipe Cooling ThresholdAV39FCU Water Vlv Sampling On TimeAV40FCU Water Vlv Wait Sampling TimeAV41FCU Wtr Vlv Sampling During Loop Deadband OnAV42FCU Wtr Vlv Sampling During Loop DeadbandAV43Fail-Safe TimeBI0Occupancy StatusBI1Relay 1BI2Relay 2BI3Relay 3BI4Relay 4BI5Relay 5BI6Relay 6BV0Relay 1 EnableBV1Relay 2 EnableBV2Relay 3 EnableBV3Relay 4 EnableBV4Relay 5 EnableBV5Relay 5 EnableBV6Analog In 1 EnableBV7Analog In 2 EnableBV8Analog Out 1 EnableBV9Analog Out 2 EnableBV10Analog Out 3 EnableBV11Analog Out 1 Pulse EnableBV12Analog Out 2 Pulse EnableBV13Analog Out 3 Pulse EnableBV14Thermistor 1 EnableBV15Thermistor 2 EnableBV16Use TH1 As Room Temp SensorBV17Enable Force OccupiedBV18Enable Auto AwayBV19Unoccupied ModeBV20Show CentigradeBV21Display CO2BV22Display PM2.5BV23Display VOCBV24Display HumidityMI0Operating ModeMI1Active Conditioning ModeMI2Active Fan SpeedMI3Occupancy StatusMV0Desired Conditioning ModeMV1Desired Fan SpeedMV2Temperature ModeMV3ProfileMV4Relay 1 MappingMV5Relay 2 MappingMV6Relay 3 MappingMV7Relay 4 MappingMV8Relay 5 MappingMV9Relay 6 MappingMV10Analog In 1 MappingMV11Analog In 2 MappingMV12Analog Out 1 MappingMV13Analog Out 2 MappingMV14Analog Out 3 Mapping
Integration notes
- Built from the 75F HyperStat PICS (15 Nov 2022); object names come from the per-object property tables and access from the present-value row.
- The PICS prints °F as the unit of every Analog Input, including humidity, CO2 and light; only the temperature AIs keep °F here.
- BV 4 and BV 5 are both printed as "Relay 5 Enable" (BV 4 is probably Relay 5 and BV 5 Relay 6); kept as printed. AV 5 is printed "Min Set Temperature Cooing".
- Relay mapping objects MV 4-9 print only "-" for their state texts; MV 2 state 1 is printed "SINLGE SETPOINT".
- AI 0 Room Temperature has a writable present value.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 75F HyperStat smart thermostat / sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the 75F HyperStat smart thermostat / sensor (BACnet MS/TP)
How many BACnet points does the 75F HyperStat smart thermostat / sensor (BACnet MS/TP) have?
This list has 113 BACnet objects: 18 analog inputs, 44 analog values, 7 binary inputs, 25 binary values, 4 multi-state inputs, 15 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which 75F HyperStat smart thermostat / sensor (BACnet MS/TP) BACnet points are writable?
89 of the 113 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official 75F HyperStat smart thermostat / sensor (BACnet MS/TP) BACnet documentation?
75F does not publish it on its own website. This list comes from 75F HyperStat PICS, revision 2022-11-15, a copy hosted by BACnet International catalog at https://www.bacnetinternational.net/catalog/manu/75f/75F HyperStat PICS November 15 2022.pdf. Ask 75F or its representative for the current revision.
What are the minimum BACnet points to integrate the 75F HyperStat smart thermostat / sensor (BACnet MS/TP)?
Start with MV 0 Desired Conditioning Mode (Conditioning mode: 1 off, 2 auto, 3 heat, 4 cool); MV 1 Desired Fan Speed (Fan speed: 1 off, 2 auto, 3 low, 4 med, 5 high); AV 0 Desired Set Temperature Heating (Heating setpoint); AV 1 Desired Set Temperature Cooling (Cooling setpoint); BV 17 Enable Force Occupied (Force occupied); AI 0 Room Temperature (Room temperature); AI 1 Humidity (Humidity); AI 2 CO2 (CO2); MI 0 Operating Mode (Operating mode: off, heating, cooling); MI 3 Occupancy Status (Occupancy status).
How do I check these points on the real 75F HyperStat smart thermostat / sensor (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More 75F BACnet points lists
Source: 75F HyperStat PICS · rev. 2022-11-15. Object names, instances and units are reproduced as published; descriptions are our own.