 "manufacturer": "75F",
 "manufacturer_slug": "75f",
 "model": "75F HyperStat smart thermostat / sensor (BACnet MS/TP)",
 "model_slug": "hyperstat",
 "aliases": [
  "HyperStat",
  "75F HyperStat",
  "77X-HS-C2W-X",
  "HyperStat CPU",
  "HyperStat HPU",
  "HyperStat FCU",
  "HyperStat Sense"
 ],
 "equipment_type": "Smart thermostat and room sensor",
 "applies_to": "75F HyperStat room controllers (CPU, HPU, 2- and 4-pipe FCU and Sense profiles) on BACnet MS/TP.",
 "summary": "The 75F HyperStat is a room thermostat and multi-sensor that can run standalone on BACnet MS/TP. Analog Inputs give room temperature, humidity, CO2, light, UV, VOC, sound and particulates plus its I/O; Analog Values hold heating and cooling setpoints, limits, deadbands and tuning; Binary and Multi-state objects cover relay enables, occupancy, conditioning mode, fan speed, the equipment profile and I/O mappings.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Built from the 75F HyperStat PICS (15 Nov 2022); object names come from the per-object property tables and access from the present-value row.",
  "The PICS prints °F as the unit of every Analog Input, including humidity, CO2 and light; only the temperature AIs keep °F here.",
  "BV 4 and BV 5 are both printed as \"Relay 5 Enable\" (BV 4 is probably Relay 5 and BV 5 Relay 6); kept as printed. AV 5 is printed \"Min Set Temperature Cooing\".",
  "Relay mapping objects MV 4-9 print only \"-\" for their state texts; MV 2 state 1 is printed \"SINLGE SETPOINT\".",
  "AI 0 Room Temperature has a writable present value."
 ],
 "source": {
  "title": "75F HyperStat PICS",
  "doc_number": null,
  "revision_date": "2022-11-15",
  "url": "https://www.bacnetinternational.net/catalog/manu/75f/75F HyperStat PICS November 15 2022.pdf",
  "unofficial": true,
  "host": "BACnet International catalog"
 },
 "integration": {
  "summary": "Write the conditioning mode (MV 0), fan speed (MV 1) and heating / cooling setpoints (AV 0, AV 1); read room temperature, humidity and CO2, the active setpoints and the operating, conditioning, fan and occupancy states.",
  "minimum_points": [
   {
    "ref": "MV 0",
    "name": "Desired Conditioning Mode",
    "why": "Conditioning mode: 1 off, 2 auto, 3 heat, 4 cool"
   },
   {
    "ref": "MV 1",
    "name": "Desired Fan Speed",
    "why": "Fan speed: 1 off, 2 auto, 3 low, 4 med, 5 high"
   },
   {
    "ref": "AV 0",
    "name": "Desired Set Temperature Heating",
    "why": "Heating setpoint"
   },
   {
    "ref": "AV 1",
    "name": "Desired Set Temperature Cooling",
    "why": "Cooling setpoint"
   },
   {
    "ref": "BV 17",
    "name": "Enable Force Occupied",
    "why": "Force occupied"
   },
   {
    "ref": "AI 0",
    "name": "Room Temperature",
    "why": "Room temperature"
   },
   {
    "ref": "AI 1",
    "name": "Humidity",
    "why": "Humidity"
   },
   {
    "ref": "AI 2",
    "name": "CO2",
    "why": "CO2"
   },
   {
    "ref": "MI 0",
    "name": "Operating Mode",
    "why": "Operating mode: off, heating, cooling"
   },
   {
    "ref": "MI 3",
    "name": "Occupancy Status",
    "why": "Occupancy status"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "Device max-master and max-info-frames are writable; the device table shows max-master 127."
  ],
  "gotchas": [
   "Setpoints are limited by the min/max setpoint objects (AV 2-5)."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "Room Temperature",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "Humidity",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "CO2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Illuminance",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "UVI",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "VOC",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Sound",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "PM2.5",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "PM10",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Analog Input 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Analog Input 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Thermistor 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "Thermistor 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Analog Out 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "Analog Out 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Analog Out 3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Active Set Temperature Heating",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Active Set Temperature Cooling",
   "description": "",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "Desired Set Temperature Heating",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Desired Set Temperature Cooling",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Max Set Temperature Heating",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Min Set Temperature Heating",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Max Set Temperature Cooling",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Min Set Temperature Cooing",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Temperature Offset",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Heating Deadband",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Cooling Deadband",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Max Humidity Setpoint",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Min Humidity Setpoint",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Analog Out 1 Min Setting",
   "description": "",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Analog Out 1 Max Setting",
   "description": "",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Analog Out 2 Min Setting",
   "description": "",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Analog Out 2 Max Setting",
   "description": "",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Analog Out 3 Min Setting",
   "description": "",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "Analog Out 3 Max Setting",
   "description": "",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "CO2 Alert Threshold",
   "description": "",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "VOC Alert Threshold",
   "description": "",
   "units": "ppb",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "PM2.5 Alert Threshold",
   "description": "",
   "units": "mg/m3",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "Zone CO2 Damper Opening Rate",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "Zone CO2 Threshold",
   "description": "",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "Zone CO2 Target",
   "description": "",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "Proportional Constant",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "Integral Constant",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Proportional Temperature Range",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "Integration Time",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "Unoccupied Setback",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "Heating Deadband Multiplier",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "Relay Activation Hysteresis",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "Fan Speed Multiplier",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "Humidity Hysteresis",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "Forced Occupied Time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "Auto Away Time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "Auto Away Setback Temperature",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "FCU Aux Heating 1 Activate",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "FCU Aux Heating 2 Activate",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "FCU Two Pipe Heating Threshold",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "FCU Two Pipe Cooling Threshold",
   "description": "",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "FCU Water Vlv Sampling On Time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "FCU Water Vlv Wait Sampling Time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "FCU Wtr Vlv Sampling During Loop Deadband On",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "FCU Wtr Vlv Sampling During Loop Deadband",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "Fail-Safe Time",
   "description": "",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 0,
   "name": "Occupancy Status",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Relay 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Relay 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Relay 3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "Relay 4",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Relay 5",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "Relay 6",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "Relay 1 Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Relay 2 Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "Relay 3 Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "Relay 4 Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "Relay 5 Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "Relay 5 Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "Analog In 1 Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "Analog In 2 Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "Analog Out 1 Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "Analog Out 2 Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "Analog Out 3 Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "Analog Out 1 Pulse Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "Analog Out 2 Pulse Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "Analog Out 3 Pulse Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "Thermistor 1 Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "Thermistor 2 Enable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "Use TH1 As Room Temp Sensor",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "Enable Force Occupied",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "Enable Auto Away",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "Unoccupied Mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "Show Centigrade",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "Display CO2",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "Display PM2.5",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "Display VOC",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "Display Humidity",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 0,
   "name": "Operating Mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=HEATING, 3=COOLING"
  },
  {
   "type": "MI",
   "instance": 1,
   "name": "Active Conditioning Mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=AUTO, 3=HEAT, 4=COOL"
  },
  {
   "type": "MI",
   "instance": 2,
   "name": "Active Fan Speed",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=AUTO, 2=LOW, 3=MEDIUM, 4=HIGH"
  },
  {
   "type": "MI",
   "instance": 3,
   "name": "Occupancy Status",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=INITIALIZING, 2=OCCUPIED, 3=UNOCCUPIED, 4=OCC. AUTO AWAY, 5=UNOCC. FORCE OCC."
  },
  {
   "type": "MV",
   "instance": 0,
   "name": "Desired Conditioning Mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=AUTO, 3=HEAT, 4=COOL"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "Desired Fan Speed",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=AUTO, 3=LOW, 4=MEDIUM, 5=HIGH"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "Temperature Mode",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=SINLGE SETPOINT, 2=DUAL SETPOINT FIX DB, 3=DUAL SETPOINT VAR DB, 4=COOL"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "Profile",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=CPU, 3=HPU, 4=FCU 2 PIPE, 5=FCU 4 PIPE, 7=SENSE"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "Relay 1 Mapping",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "Relay 2 Mapping",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "Relay 3 Mapping",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "Relay 4 Mapping",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "Relay 5 Mapping",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "Relay 6 Mapping",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "Analog In 1 Mapping",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=CURRENT 0-10, 2=CURRENT 0-20, 3=CURRENT 0-50, 4=KEYCARD, 5=DOOR WINDOW"
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "Analog In 2 Mapping",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=CURRENT 0-10, 2=CURRENT 0-20, 3=CURRENT 0-50, 4=KEYCARD, 5=DOOR WINDOW"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "Analog Out 1 Mapping",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=COOLING, 2=FAN SPEED, 3=HEATING, 4=DCV DAMPER"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "Analog Out 2 Mapping",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=COOLING, 2=FAN SPEED, 3=HEATING, 4=DCV DAMPER"
  },
  {
   "type": "MV",
   "instance": 14,
   "name": "Analog Out 3 Mapping",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=COOLING, 2=FAN SPEED, 3=HEATING, 4=DCV DAMPER"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/75f/hyperstat",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}