Thermostat / fan coil controller · BACnet points list

75F MyStat thermostat (BACnet MS/TP server) BACnet points list

Updated 6 November 2026

Short answer

MyStat can act as a BACnet MS/TP server on its RS-485 port. 75F's mapping sheet lists 117 objects: onboard and sensor-bus temperature, humidity, CO2, pressure and occupancy, relay states, operating and fan status, conditioning mode and fan speed commands, setpoints, deadbands, PI and staging settings, relay/analog output mappings and lock pins.

This page lists 117 BACnet objects for the 75F MyStat thermostat (BACnet MS/TP server) — 82 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from 75F’s own free documentation, linked below.

Manufacturer
75F
Model
MyStat thermostat (BACnet MS/TP server)
Equipment
Thermostat / fan coil controller
Equipment type
VAV boxes & fan coils
BACnet objects
117 (82 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
MyStat, 75F MyStat, BACnet_Mapping_MyStat
Source document
MyStat as a BACnet Server (with BACnet_Mapping_MyStat__.xlsx) · rev. 2026-09-18
Download CSV 117 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against 75F’s current documentation and the live device before use. Not official 75F information. Terms of use.

BMS integration notes: 75F MyStat thermostat (BACnet MS/TP server)

Integration in brief

Set MV 0 Conditioning Mode and MV 1 Fan Speed, write the heating/cooling setpoints AV 0/AV 1 (2 x °F) and BV 11 for occupancy, then read MI 0/MI 2 status and AI 0-2 room values.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 0Conditioning ModeMode: 0 off, 1 auto, 2 heating, 3 coolingWrite
MV 1Fan SpeedFan: 0 off, 1 auto, 2 low, 3 medium, 4 highWrite
BV 11Unoccupied Mode0 occupied, 1 unoccupiedWrite
AV 0Set Temperature HeatingHeating setpoint, value = 2 x °FWrite
AV 1Set Temperature CoolingCooling setpoint, value = 2 x °FWrite
MI 0Operating ModeActual: off, heating, coolingRead
MI 2Active Fan SpeedActual fan speedRead
AI 0Room TemperatureRoom temperature, 0.1 °FRead
AI 1HumidityRoom humidity, 0.1 %Read
AI 2CO2Room CO2, ppmRead

Enable & remote start

MV 0 Conditioning Mode sets off/auto/heating/cooling; BV 11 Unoccupied Mode switches between occupied and unoccupied.

Network setup

Watch out for

75F MyStat thermostat (BACnet MS/TP server) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

117 of 117 shown
Type
Access
Show
75F MyStat thermostat (BACnet MS/TP server) BACnet Points List
DescriptionStates
AImin0Room Temperature0.1 °FRead
AImin1Humidity0.1 %Read
AImin2CO2ppmRead
AI3PressureRange -500 - 500psiRead
AI4Universal Input 5Read
AI5Ext Sensor Bus Temperature 1Read
AI6Ext Sensor Bus Temperature 2Read
AI7Ext Sensor Bus Temperature 3Read
AI8Ext Sensor Bus Temperature 4Read
AI9Ext Sensor Bus Humidity 1Read
AI10Ext Sensor Bus Humidity 2Read
AI11Ext Sensor Bus Humidity 3Read
AI12Ext Sensor Bus Humidity 4Read
AI13Ext Sensor Bus CO2 1Read
AI14Ext Sensor Bus CO2 2Read
AI15Ext Sensor Bus CO2 3Read
AI16Ext Sensor Bus CO2 4Read
AI17Ext Sensor Bus Pressure 1Read
AI18Ext Sensor Bus Pressure 2Read
AI19Ext Sensor Bus Pressure 3Read
AI20Ext Sensor Bus Pressure 4Read
BI0Occupancy StatusRead
BI1Relay 1Read0=Off, 1=On
BI2Relay 2Read0=Off, 1=On
BI3Relay 3Read0=Off, 1=On
BI4Relay 4Read0=Off, 1=On
BI5Occupancy StatusRead
BI6Ext Sensor Bus Occupancy 1Read
BI7Ext Sensor Bus Occupancy 2Read
BI8Ext Sensor Bus Occupancy 3Read
BI9Ext Sensor Bus Occupancy 4Read
BV0Relay 1 EnableWrite0=Disabled, 1=Enabled
BV1Relay 2 EnableWrite0=Disabled, 1=Enabled
BV2Relay 3 EnableWrite0=Disabled, 1=Enabled
BV3Relay 4 EnableWrite0=Disabled, 1=Enabled
BV4Relay 5 EnableWrite0=Disabled, 1=Enabled
BV5Analog Out 1 EnableWrite0=Disabled, 1=Enabled
BV6Analog Out 2 EnableWrite0=Disabled, 1=Enabled
BV7Analog Out 1 Pulse EnableWrite
BV8Analog Out 2 Pulse EnableWrite
BV9Enable Force OccupiedWrite0=Disabled, 1=Enabled
BV10Enable Auto AwayWrite0=Disabled, 1=Enabled
BVmin11Unoccupied ModeWrite0=Occupied, 1=Unoccupied
BV12Show CentigradeWrite0=Disabled, 1=Enabled
BV13Enable Onboard Temp/Humi SensorWrite
BV14Enable Onboard CO2/Occu SensorsWrite
BV15Display Desired TempWrite
BV16Reboot the DeviceWrite
MImin0Operating ModeRead0=OFF, 1=HEATING, 2=COOLING
MI1Active Conditioning ModeRead0=OFF, 1=AUTO, 2=HEATING, 3=COOLING
MImin2Active Fan SpeedRead0=OFF, 1=AUTO, 2=LOW, 3=MEDIUM, 4=HIGH
MI3Occupancy StateRead
AVmin0Set Temperature HeatingRange 120-180 (60.0 - 90.0)0.5 °F (value = 2 x °F)Write
AVmin1Set Temperature CoolingRange 120-180 (60.0 - 90.0)0.5 °F (value = 2 x °F)Write
AV2Max Set Temperature HeatingWrite
AV3Min Set Temperature HeatingWrite
AV4Max Set Temperature CoolingWrite
AV5Min Set Temperature CoolingWrite
AV6Temperature OffsetRange -100 - 100 (-10.0 - 10.0)0.1 °FWrite
AV7Heating DeadbandRange 0-100 (0.0-10.0)0.1 °FWrite
AV8Cooling DeadbandRange 0-100 (0.0-10.0)0.1 °FWrite
AV9Min Humidity SetpointWrite
AV10Max Humidity SetpointWrite
AV11Analog Out 1 Min SettingWrite
AV12Analog Out 2 Min SettingWrite
AV13Analog Out 1 Max SettingWrite
AV14Analog Out 2 Max SettingWrite
AV15Zone CO2 Dampper Opening RateWrite
AV16Zone CO2 ThresholdRange 0-2000ppmWrite
AV17Zone CO2 TargetRange 0-2000ppmWrite
AV18Proportional ConstantRange 0-1000.01Write
AV19Integral ConstantRange 0-1000.01Write
AV20Proportional Temperature RangeRange 0-100 (0.0-10.0)0.1 °FWrite
AV21Integration TimeRange 5-100minWrite
AV22Unoccupied SetbackRange 10-200 (1.0-20.0)0.1 °FWrite
AV23Heating Deadband MultiplierWrite
AV24Relay Activation HysteresisRange 1-50%Write
AV25Analog Fan Speed MultiplierRange 1-100 (0.1-10)0.1Write
AV26Humidity HysteresisRange 1-100%Write
AV27Forced Occupied TimeRange 0-255minWrite
AV28Auto Away TimeRange 0-255minWrite
AV29Auto Away Setback TemperatureWrite
AV30FCU Aux Heating 1 ActivateRange 10-100 (1.0 - 10.0)0.1 °FWrite
AV31FCU Two-Pipe Heating ThresholdRange 70-130°FWrite
AV32FCU Two-Pipe Cooling ThresholdRange 35-70°FWrite
AV33FCU Water Valve Sampling On TimeRange 0-30minWrite
AV34FCU Water Valve Sampling Wait TimeRange 5-255minWrite
AV35FCU Water Valve Sampling During Loop Deadband On TimeRange 0-30minWrite
AV36FCU Water Valve Sampling During Loop Deadband Wait TimeRange 5-255minWrite
AV37Fail-Safe TimeRange 0-65535 where 0 means fail safe will be disableminWrite
AV38Cooling Stage 1 Fan OutputRange 0 - 100 (0.0 - 10.0)0.1 VWrite
AV39Cooling Stage 2 Fan OutputRange 0 - 100 (0.0 - 10.0)0.1 VWrite
AV40Heating Stage 1 Fan OutputRange 0 - 100 (0.0 - 10.0)0.1 VWrite
AV41Heating Stage 2 Fan OutputRange 0 - 100 (0.0 - 10.0)0.1 VWrite
AV42Linear Fan Speed Level LowWrite
AV43Linear Fan Speed Level HighWrite
AV44Staged Fan Speed Level LowWrite
AV45Staged Fan Speed Level HighWrite
AV46Analog Out Fan DefaultWrite
AV47Fan Runtime Post ConditioningWrite
AV48Staged Fan Analog Out at RecirculationWrite
AV49Installer Lock PinWrite
AV50User Lock PinWrite
AV51Stage Up TimerWrite
AV52Stage Down TimerWrite
MVmin0Conditioning ModeWrite0=OFF, 1=AUTO, 2=HEATING, 3=COOLING
MVmin1Fan SpeedWrite0=OFF, 1=AUTO, 2=LOW, 3=MEDIUM, 4=HIGH
MV2Temperature ModeWrite0=Single Setpoint, 1=Dual Setpoint Fixed Deadband, 2=Dual Setpoint Variable Deadband
MV3HVAC ProfileWrite
MV4Relay 1 MappingWriteNone, Cooling Stage 1, Cooling Stage 2, Heating Stage 1, Heating Stage 2, Fan Low Speed, Fan High Speed, Fan Enable, Occupied Enable, Humidifier, Dehumidifier, Externally Mapped, DVC Damper, Compressor Stage 1, Compressor Stage 2, Aux Heating, O- Energize in Cooling, B- Energize in Heating, Water Valve, Fan Low Speed - Ventilation, Cooling Water Valve, Heating Water Valve (listed without numbers)
MV5Relay 2 MappingWriteNone, Cooling Stage 1, Cooling Stage 2, Heating Stage 1, Heating Stage 2, Fan Low Speed, Fan High Speed, Fan Enable, Occupied Enable, Humidifier, Dehumidifier, Externally Mapped, DVC Damper, Compressor Stage 1, Compressor Stage 2, Aux Heating, O- Energize in Cooling, B- Energize in Heating, Water Valve, Fan Low Speed - Ventilation, Cooling Water Valve, Heating Water Valve (listed without numbers)
MV6Relay 3 MappingWriteNone, Cooling Stage 1, Cooling Stage 2, Heating Stage 1, Heating Stage 2, Fan Low Speed, Fan High Speed, Fan Enable, Occupied Enable, Humidifier, Dehumidifier, Externally Mapped, DVC Damper, Compressor Stage 1, Compressor Stage 2, Aux Heating, O- Energize in Cooling, B- Energize in Heating, Water Valve, Fan Low Speed - Ventilation, Cooling Water Valve, Heating Water Valve (listed without numbers)
MV7Relay 4 MappingWriteNone, Cooling Stage 1, Cooling Stage 2, Heating Stage 1, Heating Stage 2, Fan Low Speed, Fan High Speed, Fan Enable, Occupied Enable, Humidifier, Dehumidifier, Externally Mapped, DVC Damper, Compressor Stage 1, Compressor Stage 2, Aux Heating, O- Energize in Cooling, B- Energize in Heating, Water Valve, Fan Low Speed - Ventilation, Cooling Water Valve, Heating Water Valve (listed without numbers)
MV8Relay 5 MappingWriteNone, Cooling Stage 1, Cooling Stage 2, Heating Stage 1, Heating Stage 2, Fan Low Speed, Fan High Speed, Fan Enable, Occupied Enable, Humidifier, Dehumidifier, Externally Mapped, DVC Damper, Compressor Stage 1, Compressor Stage 2, Aux Heating, O- Energize in Cooling, B- Energize in Heating, Water Valve, Fan Low Speed - Ventilation, Cooling Water Valve, Heating Water Valve (listed without numbers)
MV9Analog Out 1 MappingWriteCooling, Linear Fan Speed, Heating, Staged Fan Speed, Externally Mapped - Analog, DCV Modulating Damper, Compressor Speed, Fan Speed, Water Modulating Valve, Cooling Modulating Valve, Heating Modulating Valve (listed without numbers)
MV10Analog Out 2 MappingWriteCooling, Linear Fan Speed, Heating, Staged Fan Speed, Externally Mapped - Analog, DCV Modulating Damper, Compressor Speed, Fan Speed, Water Modulating Valve, Cooling Modulating Valve, Heating Modulating Valve (listed without numbers)
MV11Universal In1 MappingWriteDischarge Air Temperature, Generic Alarm N/O, Generic Alarm N/C, Keycard Sensor (AI), Door/Window Sensor N/C - Title24, Door/Window Sensor (AI), Fan Run Status N/O, Fan Run Status N/C, Door/Window Sensor N/O - Title24, Door/Window Sensor N/C, Door/Window Sensor N/O, Keycard Sensor N/O, Keycard Sensor N/C, Chilled Water Supply Temperature, Hot Water Supply Temperature, Current TX (0-10Amps), Current TX (0-20Amps), Current TX (0-50Amps), Voltage Input, Thermistor Input (listed without numbers)
Object ID lookup: 75F MyStat thermostat point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MyStat thermostat (BACnet MS/TP server) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the 75F MyStat thermostat (BACnet MS/TP server)

How many BACnet points does the 75F MyStat thermostat (BACnet MS/TP server) have?

This list has 117 BACnet objects: 21 analog inputs, 53 analog values, 10 binary inputs, 17 binary values, 4 multi-state inputs, 12 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which 75F MyStat thermostat (BACnet MS/TP server) BACnet points are writable?

82 of the 117 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official 75F MyStat thermostat (BACnet MS/TP server) BACnet documentation?

The source is MyStat as a BACnet Server (with BACnet_Mapping_MyStat__.xlsx), revision 2026-09-18, published free by 75F at https://support.75f.io/hc/en-us/articles/51942488899347.

What are the minimum BACnet points to integrate the 75F MyStat thermostat (BACnet MS/TP server)?

Start with MV 0 Conditioning Mode (Mode: 0 off, 1 auto, 2 heating, 3 cooling); MV 1 Fan Speed (Fan: 0 off, 1 auto, 2 low, 3 medium, 4 high); BV 11 Unoccupied Mode (0 occupied, 1 unoccupied); AV 0 Set Temperature Heating (Heating setpoint, value = 2 x °F); AV 1 Set Temperature Cooling (Cooling setpoint, value = 2 x °F); MI 0 Operating Mode (Actual: off, heating, cooling); MI 2 Active Fan Speed (Actual fan speed); AI 0 Room Temperature (Room temperature, 0.1 °F); AI 1 Humidity (Room humidity, 0.1 %); AI 2 CO2 (Room CO2, ppm).

How do I enable BMS control of the 75F MyStat thermostat (BACnet MS/TP server)?

MV 0 Conditioning Mode sets off/auto/heating/cooling; BV 11 Unoccupied Mode switches between occupied and unoccupied.

How do I check these points on the real MyStat thermostat (BACnet MS/TP server)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: MyStat as a BACnet Server (with BACnet_Mapping_MyStat__.xlsx) · rev. 2026-09-18. Object names, instances and units are reproduced as published; descriptions are our own.