Smoke vent and natural ventilation window controller · BACnet points list

WindowMaster FlexiSmoke WSC 5xx smoke and natural ventilation panels (WSA 5MC BACnet IP module) BACnet points list

Updated 12 November 2026

Short answer

The WSA 5MC module puts a FlexiSmoke WSC 5xx smoke and natural ventilation panel on BACnet IP. Objects cover up to 13 motor groups and the motor lines on modules S1 and S3-S5: maximum, auto and hand position commands, actual and maximum positions, close commands, closed and error status, plus smoke zone alarms and errors, wind speed and direction, connection values and bit-string status words for groups, lines, smoke zones and the system.

This page lists 56 BACnet objects for the WindowMaster FlexiSmoke WSC 5xx smoke and natural ventilation panels (WSA 5MC BACnet IP module) — 25 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WindowMaster’s own free documentation, linked below.

Manufacturer
WindowMaster
Model
FlexiSmoke WSC 5xx smoke and natural ventilation panels (WSA 5MC BACnet IP module)
Equipment
Smoke vent and natural ventilation window controller
Equipment type
Other equipment
BACnet objects
56 (25 writable)
Transport
BACnet IP
Firmware
v1
Also known as
WSC 5xx, FlexiSmoke, WSA 5MC, WSA 5MC BACnet-IP, WSC 510, WSC 520, WSC 540, WindowMaster FlexiSmoke BACnet
Source document
WSC 5xx PICS - Protocol Implementation Conformance Statement · rev. 29 September 2014
Download CSV 56 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against WindowMaster’s current documentation and the live device before use. Not official WindowMaster information. Terms of use.

BMS integration notes: WindowMaster FlexiSmoke WSC 5xx smoke and natural ventilation panels (WSA 5MC BACnet IP module)

Integration in brief

Command window positions per motor group with the AO position objects, read actual positions and closed status per motor line, and map the smoke zone alarms and the system error. Wind values come from the panel weather inputs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 14Auto_position_motor_group_1Target position, motor group 1, %Command
AO 1Max_position_motor_group_1Max allowed opening, motor group 1, %Command
BO 1Close_motor_line_S3_X1Close all windows on line S3 X1Command
AI 1Actual_position_motor_line_S3_X1Actual opening, line S3 X1, %Read
BI 1Closed_motor_line_S3_X1All windows on line S3 X1 closedRead
BI 27Alarm_smoke_zone_1Smoke alarm, zone 1Read
BI 53Error_systemAny system errorRead

Network setup

WindowMaster FlexiSmoke WSC 5xx smoke and natural ventilation panels (WSA 5MC BACnet IP module) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

56 of 56 shown
Type
Other
Access
Show
WindowMaster FlexiSmoke WSC 5xx smoke and natural ventilation panels (WSA 5MC BACnet IP module) BACnet Points List
DescriptionStates
AOmin1Max_position_motor_group_1Sets the maximum allowed position for motor group n (13 objects, AO 1-13)%Command
AOmin14Auto_position_motor_group_1Sets the target position with auto speed for motor (13 objects, AO 14-26)%Command
AO27Max_position_motor_line_S3_X1Sets the maximum allowed position for motor line S3 (4 objects, AO 27-30)%Command
AO31Max_position_motor_line_S4_X1Sets the maximum allowed position for motor line S4 (4 objects, AO 31-34)%Command
AO35Max_position_motor_line_S5_X1Sets the maximum allowed position for motor line S5 (4 objects, AO 35-38)%Command
AO39Max_position_motor_line_S1_X1Sets the maximum allowed position for motor line S1%Command
AO40Auto_position_motor_line_S3_X1Set the target position of motor line S3 Xn (4 objects, AO 40-43)%Command
AO44Auto_position_motor_line_S4_X1Set the target position of motor line S4 Xn (4 objects, AO 44-47)%Command
AO48Auto_position_motor_line_S5_X1Set the target position of motor line S5 Xn (4 objects, AO 48-51)%Command
AO52Auto_position_motor_line_S1_X1Set the target position of motor line S1 X1%Command
AImin1Actual_position_motor_line_S3_X1Contains the actual position for line S3 Xn (4 objects, AI 1-4)%Read
AI5Actual_position_motor_line_S4_X1Contains the actual position for line S4 Xn (4 objects, AI 5-8)%Read
AI9Actual_position_motor_line_S5_X1Contains the actual position for line S5 Xn (4 objects, AI 9-12)%Read
AI13Actual_position_motor_line_S1_X1Contains the actual position for line S1 X1%Read
AI14Actual_max_position_motor_line_S3_X1Contains the actual max position for motor line S3 (4 objects, AI 14-17)%Read
AI18Actual_max_position_motor_line_S4_X1Contains the actual max position for motor line S4 (4 objects, AI 18-21)%Read
AI22Actual_max_position_motor_line_S5_X1Contains the actual max position for motor line S5 (4 objects, AI 22-25)%Read
AI26Actual_max_position_motor_line_S1_X1Contains the actual max position for motor line S1%Read
AI27Alarm_wind_direction_smoke_zone_1Contains the actual alarm wind direction for smoke zone (13 objects, AI 27-39)Read
AI40Wind_speedActual wind speedm/sRead
AI41Wind_speed_filteredActual filtered wind speedm/sRead
AI42Wind_directionActual wind direction°Read
AI43Wind_direction_filteredActual filtered wind direction°Read
AV1Hand_position_motor_group_1Set the target position of motor group n (13 objects, AV 1-13)%Write
AV14Hand_relative_position_motor_group_1Set the hand relative position for motor group (13 objects, AV 14-26)%Write
AV27Hand_position_motor_line_S3_X1Set the target position of motor line S3 Xn (4 objects, AV 27-30)%Write
AV31Hand_position_motor_line_S4_X1Set the target position of motor line S4 Xn (4 objects, AV 31-34)%Write
AV35Hand_position_motor_line_S5_X1Set the target position of motor line S5 Xn (4 objects, AV 35-38)%Write
AV39Hand_position_motor_line_S1_X1Set the target position of motor line S1 X1%Write
AV40Hand_relative_position_motor_line_S3_X1Set the relative position of motor line S3 (4 objects, AV 40-43)%Write
AV44Hand_relative_position_motor_line_S4_X1Set the relative position of motor line S4 (4 objects, AV 44-47)%Write
AV48Hand_relative_position_motor_line_S5_X1Set the relative position of motor line S5 (4 objects, AV 48-51)%Write
AV52Hand_relative_position_motor_line_S1_X1Set the relative position of motor line S1 X1%Write
BOmin1Close_motor_line_S3_X1Set that motor line S3 Xn must be closed (4 objects, BO 1-4)Command
BO5Close_motor_line_S4_X1Set that motor line S4 Xn must be closed (4 objects, BO 5-8)Command
BO9Close_motor_line_S5_X1Set that motor line S5 Xn must be closed (4 objects, BO 9-12)Command
BO13Close_motor_line_S1_X1Set that motor line S1 X1 must be closedCommand
BImin1Closed_motor_line_S3_X1Indicates closed not closed status for actuators on motor (4 objects, BI 1-4)Read
BI5Closed_motor_line_S4_X1Indicates closed not closed status for actuators on motor (4 objects, BI 5-8)Read
BI9Closed_motor_line_S5_X1Indicates closed not closed status for actuators on motor (4 objects, BI 9-12)Read
BI13Closed_motor_line_S1_X1Indicates closed not closed status for actuators on motorRead
BI14Error_motor_line_S3_X1Indicates error condition for motor line S3 Xn (4 objects, BI 14-17)Read
BI18Error_motor_line_S4_X1Indicates error condition for motor line S4 Xn (4 objects, BI 18-21)Read
BI22Error_motor_line_S5_X1Indicates error condition for motor line S5 Xn (4 objects, BI 22-25)Read
BI26Error_motor_line_S1_X1Indicates error condition for motor line S1 X1Read
BImin27Alarm_smoke_zone_1Smoke zone n alarm condition (13 objects, BI 27-39)Read
BI40Error_smoke_zone_1Smoke zone n error (13 objects, BI 40-52)Read
BImin53Error_systemSystem error statusRead
BV1Connection_1Object that can be associated to an input or (13 objects, BV 1-13)Write
Other1Status_motor_group_1Indicate status of the motor group n (13 objects, BS 1-13); bit string valueRead
Other14Status_motor_line_S3_X1Indicate status for motor line S3 Xn (4 objects, BS 14-17); bit string valueRead
Other18Status_motor_line_S4_X1Indicate status for motor line S4 Xn (4 objects, BS 18-21); bit string valueRead
Other22Status_motor_line_S5_X1Indicate status for motor line S5 Xn (4 objects, BS 22-25); bit string valueRead
Other26Status_motor_line_S1_X1Indicate status for motor line S1 X1; bit string valueRead
Other27Status_smoke_zone_1Indicate status of smoke zone n (13 objects, BS 27-39); bit string valueRead
Other40Status_systemIndicates the detailed status of the system; bit string valueRead
Object ID lookup: WindowMaster FlexiSmoke WSC 5xx smoke and natural ventilation panels point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FlexiSmoke WSC 5xx smoke and natural ventilation panels (WSA 5MC BACnet IP module) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WindowMaster FlexiSmoke WSC 5xx smoke and natural ventilation panels (WSA 5MC BACnet IP module)

How many BACnet points does the WindowMaster FlexiSmoke WSC 5xx smoke and natural ventilation panels (WSA 5MC BACnet IP module) have?

This list has 56 BACnet objects: 13 analog inputs, 10 analog outputs, 10 analog values, 11 binary inputs, 4 binary outputs, 1 binary value, 7 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WindowMaster FlexiSmoke WSC 5xx smoke and natural ventilation panels (WSA 5MC BACnet IP module) BACnet points are writable?

25 of the 56 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WindowMaster FlexiSmoke WSC 5xx smoke and natural ventilation panels (WSA 5MC BACnet IP module) BACnet documentation?

The source is WSC 5xx PICS - Protocol Implementation Conformance Statement, revision 29 September 2014, published free by WindowMaster at https://www.windowmaster.com/media/Files/Files/pdf/vejledninger/PICS%20WSC%205xx.pdf.

What are the minimum BACnet points to integrate the WindowMaster FlexiSmoke WSC 5xx smoke and natural ventilation panels (WSA 5MC BACnet IP module)?

Start with AO 14 Auto_position_motor_group_1 (Target position, motor group 1, %); AO 1 Max_position_motor_group_1 (Max allowed opening, motor group 1, %); BO 1 Close_motor_line_S3_X1 (Close all windows on line S3 X1); AI 1 Actual_position_motor_line_S3_X1 (Actual opening, line S3 X1, %); BI 1 Closed_motor_line_S3_X1 (All windows on line S3 X1 closed); BI 27 Alarm_smoke_zone_1 (Smoke alarm, zone 1); BI 53 Error_system (Any system error).

How do I check these points on the real FlexiSmoke WSC 5xx smoke and natural ventilation panels (WSA 5MC BACnet IP module)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.