Natural ventilation and smoke vent window controller · BACnet points list

WindowMaster CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels BACnet points list

Updated 6 November 2026

Short answer

WindowMaster window-actuator control panels for smoke venting and natural ventilation, on BACnet IP or BACnet MS/TP. Objects cover motor groups and lines (position commands, actual positions, close commands and status), smoke zones, up to 10 NV (natural ventilation) controllers with their room values and setpoints, mechanical ventilation and heating links, a weather station and sun controllers. Most objects come in ranges of 2, 8 or 10 instances.

This page lists 97 BACnet objects for the WindowMaster CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels — 47 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WindowMaster’s own free documentation, linked below.

Manufacturer
WindowMaster
Model
CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels
Equipment
Natural ventilation and smoke vent window controller
Equipment type
Other equipment
BACnet objects
97 (47 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
v1
Also known as
WSC 3xx, WCC 3xx, WxC 3xx, CompactSmoke, WindowMaster NV Embedded, WSC 310, WSC 320, WindowMaster BACnet
Source document
WSC 3xx PICS - Protocol Implementation Conformance Statement (PICS WxC 3xx 2.0) · rev. 30 October 2020
Download CSV 97 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against WindowMaster’s current documentation and the live device before use. Not official WindowMaster information. Terms of use.

BMS integration notes: WindowMaster CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels

Integration in brief

Set the device ID, UDP port or MS/TP baud rate and Max_Master on the panel touchscreen. Command window positions per motor group with the AO position objects, read back actual positions and alarms, and feed weather or room values to the NV controllers through the AV objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 11Auto_position_motor_group_1Target window position, motor group 1, %Command
AO 1Max_position_motor_group_1Max allowed opening, motor group 1, %Command
BO 1Close_motor_line_S1_X1Close all windows on line S1 X1Command
AI 1Actual_position_motor_line_S1_X1Actual opening, line S1 X1, %Read
BI 1Closed_motor_line_S1_X1All windows on line S1 X1 closedRead
BI 21Alarm_smoke_zone_1Smoke alarm, zone 1Read
BI 41Error_systemAny system errorRead

Sensors & values from the BMS

Wind speed and direction (AV 41-44) and per-NV-controller room temperature, CO2, humidity and outdoor temperature (AV 46-105) can be written from the BMS.

Network setup

Watch out for

WindowMaster CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

97 of 97 shown
Type
Other
Access
Show
WindowMaster CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels BACnet Points List
DescriptionStates
AOmin1Max_position_motor_group_1Max allowed position, motor group (10 objects, AO 1-10)%Command
AOmin11Auto_position_motor_group_1Target position at auto speed, motor group (10 objects, AO 11-20)%Command
AO21Max_position_motor_line_S1_X1Max allowed position, motor line S1 (2 objects, AO 21-22)%Command
AO23Max_position_motor_line_S2_X1Max allowed position, motor line S2 (8 objects, AO 23-30)%Command
AO31Auto_position_motor_line_S1_X1Target position at auto speed, line S1 (2 objects, AO 31-32)%Command
AO33Auto_position_motor_line_S2_X1Target position at auto speed, line S2 (8 objects, AO 33-40)%Command
AO41Minimum_position_motor_group_1Minimum position, motor group (10 objects, AO 41-50)%Command
AO51Blind_slat_position_motor_line_S1_X1Blind slat angle, motor line S1 (2 objects, AO 51-52)%Command
AO53Blind_slat_position_motor_line_S2_X1Blind slat angle, motor line S2 (8 objects, AO 53-60)%Command
AImin1Actual_position_motor_line_S1_X1Actual position, motor line S1 (2 objects, AI 1-2)%Read
AI3Actual_position_motor_line_S2_X1Actual position, motor line S2 (8 objects, AI 3-10)%Read
AI11Actual_max_position_motor_line_S1_X1Actual max position, motor line S1 (2 objects, AI 11-12)%Read
AI13Actual_max_position_motor_line_S2_X1Actual max position, motor line S2 (8 objects, AI 13-20)%Read
AI21Alarm_wind_direction_smoke_zone_1Alarm wind direction, smoke zone (10 objects, AI 21-30)Read
AI31Building_modeBuilding modeRead
AI32Temperature_in_NV_controller_1Temperature in NV controller (10 objects, AI 32-41)°CRead
AI42CO2_in_NV_controller_1CO2 in NV controller (10 objects, AI 42-51)ppmRead
AI52Relative_humidity_in_NV_controller_1Relative humidity in NV controller (10 objects, AI 52-61)%Read
AI62NV_Actual_ventilation_temperature_setpoint_1Ventilation temperature setpoint in use, NV controller (10 objects, AI 62-71)°CRead
AI72NV_Actual_heating_temperature_setpoint_1Heating temperature setpoint in use, NV controller (10 objects, AI 72-81)°CRead
AI82NV_Ventilation_status_1Ventilation status, NV controller (10 objects, AI 82-91)Read
AI92NV_Comfort_status_1Comfort status, NV controller (10 objects, AI 92-101)Read
AI102Mech_vent_FutureVent_1FutureVent control value (10 objects, AI 102-111)Read
AI112Mech_vent_value_1Mechanical ventilation value (10 objects, AI 112-121)%Read
AI122Mech_vent_ZoneVent_Air_supply_temperature_1ZoneVent air supply temperature (10 objects, AI 122-131)°CRead
AI132Heating_Valve_1Heating valve value (10 objects, AI 132-141)%Read
AI142Weather_temperatureWeather station temperature°CRead
AI143Weather_rain_intensityWeather station rain intensitymm/hRead
AI144Weather_relative_humidityWeather station relative humidity%Read
AI145Weather_humidityWeather station absolute humidityg/m³Read
AI146Weather_dew_pointWeather station dew point°CRead
AI147Weather_status_sensorWeather station sensor statusRead
AI148Weather_wind_statusWeather station wind sensor statusRead
AI149Actual_temperature_setpoint_NV_controller_1Temperature setpoint in use, NV controller (10 objects, AI 149-158)°CRead
AI159Blind_actual_slat_position_motor_line_S1_X1Actual blind slat angle, motor line S1 (2 objects, AI 159-160)%Read
AI161Blind_actual_slat_position_motor_line_S2_X1Actual blind slat angle, motor line S2 (8 objects, AI 161-168)%Read
AI169Status_sun_controller_1Status of sun controller (10 objects, AI 169-178)Read
AV1Hand_position_motor_group_1Target position at hand speed, motor group (10 objects, AV 1-10)%Write
AV11Hand_relative_position_motor_group_1Hand relative position, motor group (10 objects, AV 11-20)%Write
AV21Hand_position_motor_line_S1_X1Target position at hand speed, line S1 (2 objects, AV 21-22)%Write
AV23Hand_position_motor_line_S2_X1Target position at hand speed, line S2 (8 objects, AV 23-30)%Write
AV31Hand_relative_position_motor_line_S1_X1Relative position at hand speed, line S1 (2 objects, AV 31-32)%Write
AV33Hand_relative_position_motor_line_S2_X1Relative position at hand speed, line S2 (8 objects, AV 33-40)%Write
AV41Wind_speedWind speed from the BMS, used for safetym/sWrite
AV42Wind_speed_filteredFiltered wind speed, used for NVm/sWrite
AV43Wind_directionWind direction from the BMS°Write
AV44Wind_direction_filteredFiltered wind direction, used for NV°Write
AV45Building_modeBuilding mode from the BMSWrite
AV46Wind_speed_NV_controller_1Wind speed for NV controller, safety (10 objects, AV 46-55)m/sWrite
AV56Wind_speed_filtered_NV_controller_1Filtered wind speed for NV controller (10 objects, AV 56-65)m/sWrite
AV66Temperature_NV_controller_1Room temperature for NV controller (10 objects, AV 66-75)°CWrite
AV76CO2_NV_controller_1CO2 level for NV controller (10 objects, AV 76-85)ppmWrite
AV86Relative_humidity_NV_controller_1Relative humidity for NV controller (10 objects, AV 86-95)%Write
AV96Outdoor_temperature_in_NV_controller_1Outdoor temperature for NV controller (10 objects, AV 96-105)°CWrite
AV106NV_base_temperature_setpoint_NV_controller_1Base temperature setpoint, NV controller (10 objects, AV 106-115)°CWrite
AV116NV_heating_cooling_deadband_NV_controller_1Heating/cooling deadband, NV controller (10 objects, AV 116-125)KWrite
AV126NV_heating_standby_offset_NV_controller_1Heating standby offset, NV controller (10 objects, AV 126-135)KWrite
AV136NV_heating_night_offset_NV_controller_1Heating night offset, NV controller (10 objects, AV 136-145)KWrite
AV146NV_cooling_standby_offset_NV_controller_1Cooling standby offset, NV controller (10 objects, AV 146-155)KWrite
AV156NV_cooling_night_offset_NV_controller_1Cooling night offset, NV controller (10 objects, AV 156-165)KWrite
AV166Mech_vent_temperature_setpoint_offset_1Mechanical ventilation setpoint offset (10 objects, AV 166-175)°CWrite
AV176Hand_timer_motor_line_S1_X1Temporary hand timer, motor line S1 (2 objects, AV 176-177)minWrite
AV178Hand_timer_motor_line_S2_X1Temporary hand timer, motor line S2 (8 objects, AV 178-185)minWrite
AV186Actual_illumination_sun_controller_1Illumination level for sun controller (10 objects, AV 186-195)Write
BOmin1Close_motor_line_S1_X1Close all motors on line S1 (2 objects, BO 1-2)CommandClose / No close
BO3Close_motor_line_S2_X1Close all motors on line S2 (8 objects, BO 3-10)CommandClose / No close
BO11NV_Presence_detection_1Presence event, starts occupancy timer (10 objects, BO 11-20)CommandIdle / Presence detection
BO21NV_Disable_automatic_1Disable automatic NV control (10 objects, BO 21-30)CommandIdle / Disable auto
BO31NV_Force_winter_1Force NV controller to winter mode (10 objects, BO 31-40)CommandIdle / Force winter
BO41NV_Ventilate_1Trigger a pulse ventilation (10 objects, BO 41-50)CommandIdle / Ventilate trigger
BO51NV_Comfort_1Set NV controller to comfort (10 objects, BO 51-60)CommandIdle / Comfort
BO61NV_Night_1Set NV controller to night (10 objects, BO 61-70)CommandIdle / Night
BO71Mech_vent_override_1Override mechanical ventilation output (10 objects, BO 71-80)CommandIdle / Mech. vent. override
BO81Heating_override_1Override heating output (10 objects, BO 81-90)CommandIdle / Heating override
BImin1Closed_motor_line_S1_X1All motors on line S1 closed (2 objects, BI 1-2)ReadClosed / Not closed
BI3Closed_motor_line_S2_X1All motors on line S2 closed (8 objects, BI 3-10)ReadClosed / Not closed
BI11Error_motor_line_S1_X1Error on motor line S1 (2 objects, BI 11-12)ReadError / No error
BI13Error_motor_line_S2_X1Error on motor line S2 (8 objects, BI 13-20)ReadError / No error
BImin21Alarm_smoke_zone_1Smoke zone alarm (10 objects, BI 21-30)ReadAlarm active / No alarm
BI31Error_smoke_zone_1Smoke zone error (10 objects, BI 31-40)ReadError / No error
BImin41Error_systemSystem errorReadSystem error / System ok
BI42Error_nv_controllersOne or more NV controllers in errorReadSystem ok / NV controller error (as printed)
BI43Common_mech_ventFan active in any NV controllerReadMech. vent. inactive / Mech. vent. active (as printed)
BI44Common_heatingHeating active in any NV controllerReadHeating inactive / Heating active (as printed)
BI45NV_Occupancy_1NV controller occupied (10 objects, BI 45-54)ReadUnoccupied / Occupied (as printed)
BI55NV_Winter_1NV controller in winter mode (10 objects, BI 55-64)ReadSummer / Winter (as printed)
BI65NV_Lighting_1Lighting on in NV controller (10 objects, BI 65-74)ReadLighting off / Lighting on (as printed)
BI75NV_Error_status_1NV controller error (10 objects, BI 75-84)ReadOK / Error (as printed)
BI85Mech_vent_1Mechanical ventilation output active (10 objects, BI 85-94)ReadMech. vent. inactive / Mech. vent. active (as printed)
BI95Heating_1Heating output active (10 objects, BI 95-104)ReadHeating inactive / Heating active (as printed)
BI105Weather_rainingRain signal from weather stationReadNo rain / Raining (as printed)
BV1Connection_1Free object linkable to a system input or output (10 objects, BV 1-10)Write
Other1Status_motor_group_1Motor group status bits (BitString Value) (10 objects, BS 1-10)Readbit 0 error, 1 closed, 2 max wind, 3 safety, 4 open, 5 smoke alarm, 6 service, 7 KNX error
Other11Status_motor_line_S1_X1Motor line S1 status bits (BitString Value) (2 objects, BS 11-12)Read28 bits: comm/cable/motor errors, closed, locked, moving, overcurrent, timers, open, service (see PICS)
Other13Status_motor_line_S2_X1Motor line S2 status bits (BitString Value) (8 objects, BS 13-20)Readsame bits as BS 11
Other21Status_smoke_zone_1Smoke zone status bits (BitString Value) (10 objects, BS 21-30)Read19 bits: line A-F alarms and errors, reset, break glass, motor group, master/slave, power, weather (see PICS)
Other31Status_systemSystem status bits (BitString Value)Readbit 0 alarm, 1 system error, 2 mains error, 3 mains warning, 4 accumulator error, 5 weather data error, 6 service due
Object ID lookup: WindowMaster CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WindowMaster CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels

How many BACnet points does the WindowMaster CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels have?

This list has 97 BACnet objects: 28 analog inputs, 9 analog outputs, 27 analog values, 17 binary inputs, 10 binary outputs, 1 binary value, 5 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WindowMaster CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels BACnet points are writable?

47 of the 97 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WindowMaster CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels BACnet documentation?

The source is WSC 3xx PICS - Protocol Implementation Conformance Statement (PICS WxC 3xx 2.0), revision 30 October 2020, published free by WindowMaster at https://www.windowmaster.com/media/svhjddr2/pics-wxc-3xx-2-0.pdf.

What are the minimum BACnet points to integrate the WindowMaster CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels?

Start with AO 11 Auto_position_motor_group_1 (Target window position, motor group 1, %); AO 1 Max_position_motor_group_1 (Max allowed opening, motor group 1, %); BO 1 Close_motor_line_S1_X1 (Close all windows on line S1 X1); AI 1 Actual_position_motor_line_S1_X1 (Actual opening, line S1 X1, %); BI 1 Closed_motor_line_S1_X1 (All windows on line S1 X1 closed); BI 21 Alarm_smoke_zone_1 (Smoke alarm, zone 1); BI 41 Error_system (Any system error).

Can the BMS supply sensor values to the WindowMaster CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels?

Wind speed and direction (AV 41-44) and per-NV-controller room temperature, CO2, humidity and outdoor temperature (AV 46-105) can be written from the BMS.

How do I check these points on the real CompactSmoke WSC 3xx / Comfort WCC 3xx NVE control panels?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: WSC 3xx PICS - Protocol Implementation Conformance Statement (PICS WxC 3xx 2.0) · rev. 30 October 2020. Object names, instances and units are reproduced as published; descriptions are our own.