Weil-McLain SlimFit 1000-2000 - UPC BACnet translator BACnet points list

Updated 6 November 2026

Short answer

The UPC translator reads the SlimFit's Honeywell SOLA control over Modbus and publishes 144 BACnet objects (BACnet MS/TP or ARC156). They cover active setpoints, demand and burner states, temperatures, fan speed, flame signal, lockout and alert history, lead/lag master and slave status, pump and burner counters, and paired write/status objects for CH, DHW, lead/lag, outdoor reset, frost protection and warm weather shutdown.

This page lists 144 BACnet objects for the Weil-McLain SlimFit 1000-2000 - UPC BACnet translator — 36 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Weil-McLain’s own free documentation, linked below.

Manufacturer
Weil-McLain
Model
SlimFit 1000-2000 - UPC BACnet translator
Equipment
Commercial boiler controller gateway
Equipment type
Boilers & water heaters
BACnet objects
144 (36 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
SlimFit, SlimFit 1000, SlimFit 2000, UPC BACnet, 383-600-304, SOLA
Source document
SlimFit Building Automation System Interface Instructions & Reference Guide - UPC BACnet translator · 550-100-130/1113 · rev. 2013-11
Download CSV 144 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Weil-McLain’s current documentation and the live device before use. Not official Weil-McLain information. Terms of use.

BMS integration notes: Weil-McLain SlimFit 1000-2000 - UPC BACnet translator

Integration in brief

Unlock writes through the Password object, then enable central heat with ch_enbl_1 (BV 1) and write the CH setpoint (AV 37), or run lead/lag with the lead/lag switch and setpoint. Read burner control status, outlet temperature, firing rate, the lockout code and the alert records.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 101pswd_w_1Write the unlock code first; 0 relocksWrite
BV 1ch_enbl_1Central heat enable (1 = enable)Write
AV 37ch_stpt_w_1CH setpoint, 70-190 °FWrite
BV 15ll_op_swt_w_1Lead/lag operation on/offWrite
AV 84ll_stpt_w_1Lead/lag setpoint, 70-190 °FWrite
AV 21brnr_ctl_st_1Burner control status codeRead
AV 100outlet_sens_st_1Outlet water temperatureRead
AV 60firing_rate_st_1Firing rate (target blower speed)Read
AV 90lock_out_cd_st_1Lockout code; 0 = no lockoutRead
AV 8alarm_st_1Most recent alert codeRead

Enable & remote start

Write the unlock code given in the manual to AV 101 Password (W) before changing any point; write 0 to relock (the boiler also relocks after 10 minutes without activity). Then BV 1 ch_enbl_1 enables central heat and AV 37 sets the CH setpoint; BV 15 and AV 84 do the same for lead/lag, and AV 75 picks the lead/lag setpoint source (0 local, 1 Modbus, 2 4-20 mA).

Heartbeat & communication loss

No heartbeat object. Write access drops back to locked after 10 minutes of inactivity, so the BMS has to unlock again before later writes.

Network setup

Watch out for

Weil-McLain SlimFit 1000-2000 - UPC BACnet translator BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

144 of 144 shown
Type
AnalogBinary
Access
Show
Weil-McLain SlimFit 1000-2000 - UPC BACnet translator BACnet Points List
DescriptionStates
AV1remt_ctrl_in_4_20_st_14-20mA Remote Control Input Status; 4-20 mA (0.1 mA precision)Read
AV2active_ch_stpt_st_1Active CH Setpoint; -40°- 266° F Setpoint determined by CH setpoint source°FRead
AV3active_dhw_stpt_st_1Active DHW Setpoint Status; -40°- 266° F Setpoint determined by DHW setpoint source°FRead
AV4active_ll_oppt_st_1Active LL Operating Point Status; -40°- 266° F°FRead
AV5active_ll_stpt_st_1Active LL Setpoint Status; -40°- 266° F Setpoint determined by LL setpoint source°FRead
AV6act_sys_op_st_1Active System Operating Point Status; -40°- 266° F°FRead
AV7act_sys_sp_st_1Active System Setpoint Status; -40°- 266° F only valid for CH and DHW. Not Lead/Lag°FRead
AVmin8alarm_st_1Alarm Record 1 Status; Most Recent Alert. See Table 5.Read
AV9alarm_st_2Alarm Record 2 Status; 2nd Newest AlertRead
AV10alarm_st_3Alarm Record 3 Status; 3rd Newest AlertRead
AV11alarm_st_4Alarm Record 4 Status; 4th Newest AlertRead
AV12alarm_st_5Alarm Record 5 Status; 5th Newest AlertRead
AV13ann_first_out_st_1Annunciator First Out Status; Source for annunciator first out:Read0=None or undetermined, 1=ILK, 2=PII, 11=Annunciator 1, 12=Annunciator 2, 13=Annunciator 3, 14=Annunciator 4, 15=Annunciator 5, 16=Annunciator 6, 17=Annunciator 7, 18=Annunciator 8
AV14aux2_pum_cy_cnt_1Auxiliary 2 Pump Cycle Count; 0-999,999Write
AV15aux2_pum_cy_cnt1_st_1Auxiliary 2 Pump Cycle Count Status; 0-999,999Read
AV16aux_pum_cy_cnt_1Auxiliary Pump Cycle Count; 0-999,999Write
AV17aux_pum_cy_cnt1_st_1Auxiliary Pump Cycle Count Status; 0-999,999Read
AV18blr_pum_cy_cnt1_1Boiler Pump Cycle Count; 0-999,999Write
AV19blr_pum_cy_cnt1_st_1Boiler Pump Cycle Count Status; 0-999,999Read
AV20brnr_ctrl_state_st_1Burner Control State Status; Burner control sequence (I/O) state (see Table 6).Read
AVmin21brnr_ctl_st_1Burner Control StatusRead1=Locked out, 4=Anti-short cycle, 5=Unconfigured safety data, 34=Standby Hold, 35=Standby Delay, 48=Normal Standby, 49=Preparing, 50=Ignition, 51=Firing, 52=Postpurge
AV22brn_cy_cnt_1Burner Cycle Count; 0-999,999Write
AV23brn_cy_cnt1_st_1Burner Cycle Count Status; 0-999,999Read
AV24brn_run_tim_1Burner Run Time; HourshWrite
AV25brn_run_tim1st_1Burner Run Time Status; HourshRead
AV26ch_brn_dem_st_1CH Burner Demand StatusRead0=Off, 1=On
AV27ch_heat_dem_st_1CH Heat Demand StatusRead0=Off, 1=On
AV28ch_odr_low_wtr_w_1CH ODR Low Water Temperature (W); 60°- 199° F°FWrite
AV29ch_odr_low_wtr_st_1CH ODR Low Water Temperature Status; 60°- 199° F°FRead
AV30ch_odr_max_tmp_w_1CH ODR Max Outdoor Temperature (W); 50°- 100° F°FWrite
AV31ch_odr_max_tmp_st_1CH ODR Max Outdoor Temperature Status; 50°- 100° F°FRead
AV32ch_odr_min_temp_w_1CH ODR Min Outdoor Temp (W); -40°- 100° F°FWrite
AV33ch_odr_min_temp_st_1CH ODR Min Outdoor Temp Status; -40°- 100° F°FRead
AV34ch_pum_cy_cnt_1CH Pump Cycle Count; 0-999,999Write
AV35ch_pum_cy_cnt1_st_1CH Pump Cycle Count Status; 0-999,999Read
AV36ch_req_rate_st_1CH Requested Rate Status; Percentage (%)%Read
AVmin37ch_stpt_w_1CH Setpoint (W); 70°- 190° F Default: 180°FWrite
AV39ch_stpt_st_1CH Setpoint Status; 70°- 190° F Default: 180°FRead
AV38ch_sp_src_st_1CH Setpoint Source StatusRead0=Unknown, 1=Normal Setpoint, 2=TOD Setpoint, 3=Outdoor Reset, 4=Remote Control, 7=Outdoor Reset TOD, 8=Reserved, 9=Outdoor Boost
AV40ch_st_1CH StatusRead0=Unknown, 1=Disabled, 2=Normal, 3=Suspended
AV41ch_tod_stpt_w_1CH Time of Day Setpoint (W); 70°- 190° F Default: 160°FWrite
AV42ch_tod_stpt_st_1CH Time of Day Setpoint Status; 70°- 190° F Default: 160°FWrite
AV43cont_cy_cnt1_st_1Controller Cycle Count Status; 0-999,999Read
AV44cont_run_tim1_st_1Controller Run Time Status; HourshRead
AV45demand_src_st_1Demand Source Status; Current demand source:Read0=Unknown, 1=No source demand, 2=CH, 3=DHW, 4=Lead Lag slave, 5=Lead Lag master, 6=CH frost protection, 7=DHW frost protection, 8=No demand due to burner switch (register 199) turned off, 9=DHW storage, 10=Reserved, 11=Warm weather shutdown
AV47dhw_brn_dem_st_1DHW Burner Demand StatusRead0=Off, 1=On
AV48dhw_heat_dem_st_1DHW Heat Demand StatusRead0=Off, 1=On
AV49dhw_pri_cnt_st_1DHW Priority Count StatusRead
AV50dhw_pum_cy_cnt_1DHW Pump Cycle Count; 0-999,999Write
AV51dhw_pum_cy_cnt1_st_1DHW Pump Cycle Count Status; 0-999,999Read
AV52dhw_sens_st_1DHW Sensor Status; 120°- 190° F°FRead
AV53dhw_stpt_w_1DHW Setpoint; 120°- 190° F Default: 190°FWrite
AV55dhw_stpt_st_1DHW Setpoint Status; 120°- 190° F Default: 190°FRead
AV54dhw_sp_src_st_1DHW Setpoint Source StatusRead0=Unknown, 1=Normal Setpoint, 2=TOD Setpoint, 3=DHW Tap Setpoint, 4=DHW Preheat Setpoint
AV46dhw_st_1DHW StatusRead0=Unknown, 1=Disabled, 2=Normal, 3=Suspended
AV56dhw_tod_stpt_w_1DHW Time of Day Setpoint (W); 120°- 190° F Default: 180°FWrite
BV57dhw_tod_stpt_st_1DHW Time of Day Setpoint Status; 120°- 190° F Default: 180°FRead
AV58dhw_req_rate_st_1DWH Requested Rate Status; RPMRPMRead
AV59fan_spd_st_1Fan Speed Status; RPM. Current speed of blower.RPMRead
AVmin60firing_rate_st_1Firing Rate Status; RPM. Target speed of blower.RPMRead
AV61flame_sig_st_1Flame Signal Status; VoltsVRead
AV62inlet_sens_st_1Inlet Sensor Status; -40°- 266° F°FRead
AV63lead_boil_add_st_1Lead Boiler Address StatusRead
AV64ll_act_svc_st_1Lead Lag Active Service Status; 5-14 = ReservedRead0=No Active Service, 1=CH or Steam, 2=DHW, 3=Mix, 4=Frost Protection, 15=Warm Weather Shutdown
AV67ll_ch_4ma_wtr_tmp_w_1Lead Lag CH 4mA Water Temp (W); Temperature corresponding to 4mA signal input: -40°- 266° F°FWrite
AV68ll_ch_4ma_wtr_tmp_st_1Lead Lag CH 4mA Water Temp Status; Temperature corresponding to 4mA signal input: -40°- 266° F°FRead
AV65ll_ch_20ma_wtr_tmp_w_1Lead Lag CH 20mA Water Temp (W); Temperature corresponding to 20mA signal input: -40°- 266° F°FRead
AV66ll_ch_20ma_wtr_tmp_st_1Lead Lag CH 20mA Water Temp Status; Temperature corresponding to 20mA signal input: -40°- 266° F°FRead
AV69ll_odr_low_wtr_tmp_w_1Lead Lag CH ODR Low Water Temperature (W); 60°- 190° F°FWrite
AV70ll_odr_low_wtr_tmp_st_1Lead Lag CH ODR Low Water Temperature Status; 60°- 190° F°FRead
AV71ll_odr_max_tmp_w_1Lead Lag CH ODR Max Outdoor Temperature (W); 50°- 100° F°FWrite
AV72ll_odr_max_tmp_st_1Lead Lag CH ODR Max Outdoor Temperature Status; 50°- 100° F°FRead
AV73ll_odr_min_tmp_w_1Lead Lag CH ODR Min Outdoor Temperature (W); -40°- 100° F°FWrite
AV74ll_odr_min_tmp_st_1Lead Lag CH ODR Min Outdoor Temperature Status; -40°- 100° F°FRead
AV75ll_ch_stpt_src_w_1Lead Lag CH Setpoint Source (W); 2 = 4-20mA SetpointWrite0=Local Setpoint, 1=Modbus Setpoint
AV76ll_ch_spt_src_w_st_1Lead Lag CH Setpoint Source Status; 2 = 4-20mA SetpointRead0=Local Setpoint, 1=Modbus Setpoint
AV77ll_dhw_setp_1Lead Lag DHW Setpoint; 120°- 190° F Default: 190°FWrite
AV78ll_dhw_sp_st_1Lead Lag DHW Setpoint Status; 120°- 190° F Default: 190°FRead
AV79ll_ms_en_st_1Lead Lag Master Enable StatusRead0=Not a Lead/Lag Master, 1=Lead/Lag Master
AV80ll_ms_sp_src_st_1Lead Lag Master Setpoint Source StatusRead0=Unknown, 1=CH Setpoint, 2=CH TOD Setpoint, 3=Outdoor Reset, 4=Remote Control (4-20mA or Modbus), 7=Outdoor Reset TOD, 8=Reserved, 9=Outdoor Boost
AV81ll_ms_st_1Lead Lag Mater StatusRead0=Unknown, 1=Disabled, 2=Normal, 3=Suspended
AV82ll_mod_bu_sens_w_1Lead Lag Modulation Backup Sensor; Backup Sensor Used for Lead/Lag Modulation:Write0=No Backup Sensor, 1=Outlet Sensor from Lead Boiler, 2=Average Outlet Sensor from All Slave Boilers
AV83ll_mod_bu_sens_st_1Lead Lag Modulation Backup Sensor Status; Backup Sensor Used for Lead/Lag Modulation:Read0=No Backup Sensor, 1=Outlet Sensor from Lead Boiler, 2=Average Outlet Sensor from All Slave Boilers
AVmin84ll_stpt_w_1Lead Lag Setpoint (W); 70°- 190° F Default: 170°FWrite
AV85ll_stpt_st_1Lead Lag Setpoint Status; 70°- 190° F Default: 170°FRead
AV86ll_sl_en_st_1Lead Lag Slave Enable StatusRead0=Lead/Lag Slave Disabled, 1=Lead/Lag Simple Slave Enabled for EnviraCom Master, 2=Lead/Lag Simple Slave Enabled for Sola Modbus Master (BAS), 3=Lead/Lag Full Slave Enabled for Sola Master
AV87ll_sl_st_1Lead Lag Slave Status; Bit map: 7-0=Burner control status (seeRead15=Slave command received, 14=Slave mode has priority over CH & DHW, 13=Slave is modulating, 12=CH frost protection request, 11=DHW frost protection request, 10=Frost protection burner request, 9=Local frost protection request, 8=Reserved (always 0) register 32)
AV88ll_tod_stpt_w_1Lead Lag Time of Day Setpoint (W); 32°- 250° F Default: 160°FWrite
AV89ll_tod_stpt_st_1Lead Lag Time of Day Setpoint Status; 32°- 250° F Default: 160°FRead
AV91lock_out1_st_1Lockout1 Status; Most Recent Lockout. See Table 3.Read
AV92lock_out2_st_1Lockout2 Status; 2nd Newest Lockout. See Table 3.Read
AV93lock_out3_st_1Lockout3 Status; 3rd Newest Lockout. See Table 3.Read
AV94lock_out4_st_1Lockout4 Status; 4th Newest Lockout. See Table 3.Read
AV95lock_out5_st_1Lockout5 Status; 5th Newest Lockout. See Table 3.Read
AVmin90lock_out_cd_st_1Lockout Status; 1-4096 (see Table 3)Read0=No lockout
AV96od_fp_stpt_w_1Outdoor Frost Protection Setpoint (W); -40°-266° F Default: 32°FWrite
AV97od_fp_stpt_st_1Outdoor Frost Protection Setpoint Status; -40°-266° F Default: 32°FRead
AV98otdr_sens_state_st_1Outdoor Sensor State StatusRead0=None, 1=Normal, 2=Open, 3=Shorted, 4=Outside High Range, 7=Outside Low Range, 8=No Reliable
AV99outdoor_tmp_st_1Outdoor Temperature Status; -40°-266° F°FRead
AVmin100outlet_sens_st_1Outlet Sensor Status; -40°-266° F°FRead
AVmin101pswd_w_1Write the unlock code from the manual to allow writes; 0 relocksWrite
AV102pswd_st_1PSWD Status; Register Data Write Access Status:Read0=No register writes allowed, 1=Installer register writes allowed, 2=OEM register writes allowed, 3=All register writes allowed
AV103s5_hdr_sens_st_1S5 (Header) Sensor Status; -40°-266° F°FRead
AV104sl1_fire_rate_st_1Slave 1 Firing Rate Status; Current firing rate (0-100%) of slave 1Read
AV105sl1_state_st_1Slave 1 State StatusRead0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AV106sl2_fire_rate_st_1Slave 2 Firing Rate Status; Current firing rate (0-100%) of slave 1Read
AV107sl2_state_st_1Slave 2 State StatusRead0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AV108sl3_fire_rate_st_1Slave 3 Firing Rate Status; Current firing rate (0-100%) of slave 1Read
AV109sl3_state_st_1Slave 3 State StatusRead0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AV110sl4_fire_rate_st_1Slave 4 Firing Rate Status; Current firing rate (0-100%) of slave 1Read
AV111sl4_state_st_1Slave 4 State StatusRead0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AV112sl5_fire_rate_st_1Slave 5 Firing Rate Status; Current firing rate (0-100%) of slave 1Read
AV113sl5_state_st_1Slave 5 State StatusRead0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AV114sl6_fire_rate_st_1Slave 6 Firing Rate Status; Current firing rate (0-100%) of slave 1Read
AV115sl6_state_st_1Slave 6 State StatusRead0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AV116sl7_fire_rate_1Slave 7 Firing Rate Status; Current firing rate (0-100%) of slave 1Read
AV117sl7_state_st_1Slave 7 State StatusRead0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AV118sl8_fire_rate_st_1Slave 8 Firing Rate Status; Current firing rate (0-100%) of slave 1Read
AV119sl8_state_st_1Slave 8 State StatusRead0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AV120stack_sens_st_1Stack Sensor Status; -40°-266° F°FRead
AV121sys_pum_cy_cnt_1System Pump Cycle Count; 0-999,999Write
AV122sys_pum_cy_cnt1_st_1System Pump Cycle Count Status; 0-999,999Read
AV123ww_sd_stpt_w_1Warm Weather Shutdown Setpoint; -40°-266° F Default: 60°FWrite
AV124ww_sd_stpt_st_1Warm Weather Shutdown Setpoint Status; -40°-266° F Default: 60°FRead
BVmin1ch_enbl_1CH Enable (W)Write0=Disable Central Heating, 1=Enable Central Heating
BV2ch_enable_st_1CH Enable StatusRead0=Disable Central Heating, 1=Enable Central Heating
BV3ch_fp_en_w_1CH Frost Protection Enable (W)Write0=Disable CH Frost Protection, 1=Enable CH Frost Protection
BV4ch_frost_en_st_1CH Frost Protection Enable StatusRead0=Disable CH Frost Protection, 1=Enable CH Frost Protection
BV5ch_odr_en_w_1CH Outdoor Reset Enable (W)Write0=Disable Outdoor Reset, 1=Enable Outdoor Reset
BV6ch_odr_en_st_1CH Outdoor Reset Enable StatusRead0=Disable Outdoor Reset, 1=Enable Outdoor Reset
BV8ch_rem_stat_1CH Remote Stat (W)Write0=No Remote Stat Demand, 1=Remote Stat Demand Indicated
BV7ch_rmt_st_1CH Remote StatusRead0=No Remote Stat Demand, 1=Remote Stat Demand Indicated
BV9dhw_en_1DHW EnableWrite0=DHW Disabled, 1=DHW Enabled
BV10dhw_en_st_1DHW Enable StatusRead0=DHW Disabled, 1=DHW Enabled
BV11dhw_frst_pro_en_1DHW Frost Protection EnableWrite0=Disable DHW Frost Protection, 1=Enable DHW Frost Protection
BV12dhw_frost_en_st_1DHW Frost Protection Enable StatusRead0=Disable DHW Frost Protection, 1=Enable DHW Frost Protection
BVmin15ll_op_swt_w_1Lead Lag Operation Switch (W)Write0=Turn off Lead Lag Operation, 1=Turn on Lead Lag Operation
BV16ll_op_swt_st_1Lead Lag Operation Switch StatusRead0=Turn off Lead Lag Operation, 1=Turn on Lead Lag Operation
BV13htmp_hi_alm_1HTemp HI Alarm; Header Sensor High Temperature Alarm Default to 220.Read
BV14htemp_low_alm_1HTemp Low Alarm; Header Sensor Low Temperature Alarm Default to -80.Read
BV17ordtemp_hi_alm_1ODRTemp Hi Alarm; Outdoor Sensor High Temperature Alarm Default to 220.Read
BV18ordtemp_lo_alm_1ORDTemp Low Alarm; Outdoor Sensor Low Temperature Alarm Default to -80.Read
BV19ww_sd_en_wWarm Weather Shutdown EnableWrite0=Disable, 1=Shutdown After Demand has Ended, 2=Shutdown Immediately
BV20ww_ed_en_stWarm Weather Shutdown Enable StatusRead0=Disable, 1=Shutdown After Demand has Ended, 2=Shutdown Immediately
Object ID lookup: Weil-McLain SlimFit 1000-2000 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SlimFit 1000-2000 - UPC BACnet translator and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Weil-McLain SlimFit 1000-2000 - UPC BACnet translator

How many BACnet points does the Weil-McLain SlimFit 1000-2000 - UPC BACnet translator have?

This list has 144 BACnet objects: 123 analog values, 21 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Weil-McLain SlimFit 1000-2000 - UPC BACnet translator BACnet points are writable?

36 of the 144 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Weil-McLain SlimFit 1000-2000 - UPC BACnet translator BACnet documentation?

The source is SlimFit Building Automation System Interface Instructions & Reference Guide - UPC BACnet translator (550-100-130/1113), revision 2013-11, published free by Weil-McLain at https://www.weil-mclain.com/wp-content/uploads/slimfit-1000-2000-bacnet-interface-manual_1.pdf.

What are the minimum BACnet points to integrate the Weil-McLain SlimFit 1000-2000 - UPC BACnet translator?

Start with AV 101 pswd_w_1 (Write the unlock code first; 0 relocks); BV 1 ch_enbl_1 (Central heat enable (1 = enable)); AV 37 ch_stpt_w_1 (CH setpoint, 70-190 °F); BV 15 ll_op_swt_w_1 (Lead/lag operation on/off); AV 84 ll_stpt_w_1 (Lead/lag setpoint, 70-190 °F); AV 21 brnr_ctl_st_1 (Burner control status code); AV 100 outlet_sens_st_1 (Outlet water temperature); AV 60 firing_rate_st_1 (Firing rate (target blower speed)); AV 90 lock_out_cd_st_1 (Lockout code; 0 = no lockout); AV 8 alarm_st_1 (Most recent alert code).

How do I enable BMS control of the Weil-McLain SlimFit 1000-2000 - UPC BACnet translator?

Write the unlock code given in the manual to AV 101 Password (W) before changing any point; write 0 to relock (the boiler also relocks after 10 minutes without activity). Then BV 1 ch_enbl_1 enables central heat and AV 37 sets the CH setpoint; BV 15 and AV 84 do the same for lead/lag, and AV 75 picks the lead/lag setpoint source (0 local, 1 Modbus, 2 4-20 mA).

Does the Weil-McLain SlimFit 1000-2000 - UPC BACnet translator need a BACnet heartbeat or have a communication timeout?

No heartbeat object. Write access drops back to locked after 10 minutes of inactivity, so the BMS has to unlock again before later writes.

How do I check these points on the real SlimFit 1000-2000 - UPC BACnet translator?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.