Commercial boiler controller gateway · BACnet points list
Weil-McLain SlimFit 1000-2000 - UPC BACnet translator BACnet points list
Updated 6 November 2026
The UPC translator reads the SlimFit's Honeywell SOLA control over Modbus and publishes 144 BACnet objects (BACnet MS/TP or ARC156). They cover active setpoints, demand and burner states, temperatures, fan speed, flame signal, lockout and alert history, lead/lag master and slave status, pump and burner counters, and paired write/status objects for CH, DHW, lead/lag, outdoor reset, frost protection and warm weather shutdown.
This page lists 144 BACnet objects for the Weil-McLain SlimFit 1000-2000 - UPC BACnet translator — 36 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Weil-McLain’s own free documentation, linked below.
- Manufacturer
- Weil-McLain
- Model
- SlimFit 1000-2000 - UPC BACnet translator
- Equipment
- Commercial boiler controller gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 144 (36 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- SlimFit, SlimFit 1000, SlimFit 2000, UPC BACnet, 383-600-304, SOLA
Reference only, provided as-is: verify against Weil-McLain’s current documentation and the live device before use. Not official Weil-McLain information. Terms of use.
BMS integration notes: Weil-McLain SlimFit 1000-2000 - UPC BACnet translator
Unlock writes through the Password object, then enable central heat with ch_enbl_1 (BV 1) and write the CH setpoint (AV 37), or run lead/lag with the lead/lag switch and setpoint. Read burner control status, outlet temperature, firing rate, the lockout code and the alert records.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 101 | pswd_w_1 | Write the unlock code first; 0 relocks | Write |
| BV 1 | ch_enbl_1 | Central heat enable (1 = enable) | Write |
| AV 37 | ch_stpt_w_1 | CH setpoint, 70-190 °F | Write |
| BV 15 | ll_op_swt_w_1 | Lead/lag operation on/off | Write |
| AV 84 | ll_stpt_w_1 | Lead/lag setpoint, 70-190 °F | Write |
| AV 21 | brnr_ctl_st_1 | Burner control status code | Read |
| AV 100 | outlet_sens_st_1 | Outlet water temperature | Read |
| AV 60 | firing_rate_st_1 | Firing rate (target blower speed) | Read |
| AV 90 | lock_out_cd_st_1 | Lockout code; 0 = no lockout | Read |
| AV 8 | alarm_st_1 | Most recent alert code | Read |
Enable & remote start
Write the unlock code given in the manual to AV 101 Password (W) before changing any point; write 0 to relock (the boiler also relocks after 10 minutes without activity). Then BV 1 ch_enbl_1 enables central heat and AV 37 sets the CH setpoint; BV 15 and AV 84 do the same for lead/lag, and AV 75 picks the lead/lag setpoint source (0 local, 1 Modbus, 2 4-20 mA).
Heartbeat & communication loss
No heartbeat object. Write access drops back to locked after 10 minutes of inactivity, so the BMS has to unlock again before later writes.
Network setup
- The UPC translator (kit 383-600-304) talks to the boiler's SOLA control through the S7999D display Modbus gateway (COM 2, 38400 bps default on the SOLA side).
- BAS side: BACnet MS/TP (9600-76.8 kbps) or BACnet over ARC156 on Port 1a; MAC address from the two rotary switches (default translator address 10), baud and protocol from DIP switches 1-8.
- Set the translator address so it does not clash with the boiler Modbus addresses.
Watch out for
- Most settings come as pairs: a (W) object to write and a Status object to read back.
- Cycle counts and run time are writable (W) as well; do not reset them by accident.
- Lockout, alert and burner state codes are in Tables 3, 5 and 6 of the manual.
Weil-McLain SlimFit 1000-2000 - UPC BACnet translator BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | remt_ctrl_in_4_20_st_1 | 4-20mA Remote Control Input Status; 4-20 mA (0.1 mA precision) | Read | ||
| AV | 2 | active_ch_stpt_st_1 | Active CH Setpoint; -40°- 266° F Setpoint determined by CH setpoint source | °F | Read | |
| AV | 3 | active_dhw_stpt_st_1 | Active DHW Setpoint Status; -40°- 266° F Setpoint determined by DHW setpoint source | °F | Read | |
| AV | 4 | active_ll_oppt_st_1 | Active LL Operating Point Status; -40°- 266° F | °F | Read | |
| AV | 5 | active_ll_stpt_st_1 | Active LL Setpoint Status; -40°- 266° F Setpoint determined by LL setpoint source | °F | Read | |
| AV | 6 | act_sys_op_st_1 | Active System Operating Point Status; -40°- 266° F | °F | Read | |
| AV | 7 | act_sys_sp_st_1 | Active System Setpoint Status; -40°- 266° F only valid for CH and DHW. Not Lead/Lag | °F | Read | |
| AVmin | 8 | alarm_st_1 | Alarm Record 1 Status; Most Recent Alert. See Table 5. | Read | ||
| AV | 9 | alarm_st_2 | Alarm Record 2 Status; 2nd Newest Alert | Read | ||
| AV | 10 | alarm_st_3 | Alarm Record 3 Status; 3rd Newest Alert | Read | ||
| AV | 11 | alarm_st_4 | Alarm Record 4 Status; 4th Newest Alert | Read | ||
| AV | 12 | alarm_st_5 | Alarm Record 5 Status; 5th Newest Alert | Read | ||
| AV | 13 | ann_first_out_st_1 | Annunciator First Out Status; Source for annunciator first out: | Read | 0=None or undetermined, 1=ILK, 2=PII, 11=Annunciator 1, 12=Annunciator 2, 13=Annunciator 3, 14=Annunciator 4, 15=Annunciator 5, 16=Annunciator 6, 17=Annunciator 7, 18=Annunciator 8 | |
| AV | 14 | aux2_pum_cy_cnt_1 | Auxiliary 2 Pump Cycle Count; 0-999,999 | Write | ||
| AV | 15 | aux2_pum_cy_cnt1_st_1 | Auxiliary 2 Pump Cycle Count Status; 0-999,999 | Read | ||
| AV | 16 | aux_pum_cy_cnt_1 | Auxiliary Pump Cycle Count; 0-999,999 | Write | ||
| AV | 17 | aux_pum_cy_cnt1_st_1 | Auxiliary Pump Cycle Count Status; 0-999,999 | Read | ||
| AV | 18 | blr_pum_cy_cnt1_1 | Boiler Pump Cycle Count; 0-999,999 | Write | ||
| AV | 19 | blr_pum_cy_cnt1_st_1 | Boiler Pump Cycle Count Status; 0-999,999 | Read | ||
| AV | 20 | brnr_ctrl_state_st_1 | Burner Control State Status; Burner control sequence (I/O) state (see Table 6). | Read | ||
| AVmin | 21 | brnr_ctl_st_1 | Burner Control Status | Read | 1=Locked out, 4=Anti-short cycle, 5=Unconfigured safety data, 34=Standby Hold, 35=Standby Delay, 48=Normal Standby, 49=Preparing, 50=Ignition, 51=Firing, 52=Postpurge | |
| AV | 22 | brn_cy_cnt_1 | Burner Cycle Count; 0-999,999 | Write | ||
| AV | 23 | brn_cy_cnt1_st_1 | Burner Cycle Count Status; 0-999,999 | Read | ||
| AV | 24 | brn_run_tim_1 | Burner Run Time; Hours | h | Write | |
| AV | 25 | brn_run_tim1st_1 | Burner Run Time Status; Hours | h | Read | |
| AV | 26 | ch_brn_dem_st_1 | CH Burner Demand Status | Read | 0=Off, 1=On | |
| AV | 27 | ch_heat_dem_st_1 | CH Heat Demand Status | Read | 0=Off, 1=On | |
| AV | 28 | ch_odr_low_wtr_w_1 | CH ODR Low Water Temperature (W); 60°- 199° F | °F | Write | |
| AV | 29 | ch_odr_low_wtr_st_1 | CH ODR Low Water Temperature Status; 60°- 199° F | °F | Read | |
| AV | 30 | ch_odr_max_tmp_w_1 | CH ODR Max Outdoor Temperature (W); 50°- 100° F | °F | Write | |
| AV | 31 | ch_odr_max_tmp_st_1 | CH ODR Max Outdoor Temperature Status; 50°- 100° F | °F | Read | |
| AV | 32 | ch_odr_min_temp_w_1 | CH ODR Min Outdoor Temp (W); -40°- 100° F | °F | Write | |
| AV | 33 | ch_odr_min_temp_st_1 | CH ODR Min Outdoor Temp Status; -40°- 100° F | °F | Read | |
| AV | 34 | ch_pum_cy_cnt_1 | CH Pump Cycle Count; 0-999,999 | Write | ||
| AV | 35 | ch_pum_cy_cnt1_st_1 | CH Pump Cycle Count Status; 0-999,999 | Read | ||
| AV | 36 | ch_req_rate_st_1 | CH Requested Rate Status; Percentage (%) | % | Read | |
| AVmin | 37 | ch_stpt_w_1 | CH Setpoint (W); 70°- 190° F Default: 180 | °F | Write | |
| AV | 39 | ch_stpt_st_1 | CH Setpoint Status; 70°- 190° F Default: 180 | °F | Read | |
| AV | 38 | ch_sp_src_st_1 | CH Setpoint Source Status | Read | 0=Unknown, 1=Normal Setpoint, 2=TOD Setpoint, 3=Outdoor Reset, 4=Remote Control, 7=Outdoor Reset TOD, 8=Reserved, 9=Outdoor Boost | |
| AV | 40 | ch_st_1 | CH Status | Read | 0=Unknown, 1=Disabled, 2=Normal, 3=Suspended | |
| AV | 41 | ch_tod_stpt_w_1 | CH Time of Day Setpoint (W); 70°- 190° F Default: 160 | °F | Write | |
| AV | 42 | ch_tod_stpt_st_1 | CH Time of Day Setpoint Status; 70°- 190° F Default: 160 | °F | Write | |
| AV | 43 | cont_cy_cnt1_st_1 | Controller Cycle Count Status; 0-999,999 | Read | ||
| AV | 44 | cont_run_tim1_st_1 | Controller Run Time Status; Hours | h | Read | |
| AV | 45 | demand_src_st_1 | Demand Source Status; Current demand source: | Read | 0=Unknown, 1=No source demand, 2=CH, 3=DHW, 4=Lead Lag slave, 5=Lead Lag master, 6=CH frost protection, 7=DHW frost protection, 8=No demand due to burner switch (register 199) turned off, 9=DHW storage, 10=Reserved, 11=Warm weather shutdown | |
| AV | 47 | dhw_brn_dem_st_1 | DHW Burner Demand Status | Read | 0=Off, 1=On | |
| AV | 48 | dhw_heat_dem_st_1 | DHW Heat Demand Status | Read | 0=Off, 1=On | |
| AV | 49 | dhw_pri_cnt_st_1 | DHW Priority Count Status | Read | ||
| AV | 50 | dhw_pum_cy_cnt_1 | DHW Pump Cycle Count; 0-999,999 | Write | ||
| AV | 51 | dhw_pum_cy_cnt1_st_1 | DHW Pump Cycle Count Status; 0-999,999 | Read | ||
| AV | 52 | dhw_sens_st_1 | DHW Sensor Status; 120°- 190° F | °F | Read | |
| AV | 53 | dhw_stpt_w_1 | DHW Setpoint; 120°- 190° F Default: 190 | °F | Write | |
| AV | 55 | dhw_stpt_st_1 | DHW Setpoint Status; 120°- 190° F Default: 190 | °F | Read | |
| AV | 54 | dhw_sp_src_st_1 | DHW Setpoint Source Status | Read | 0=Unknown, 1=Normal Setpoint, 2=TOD Setpoint, 3=DHW Tap Setpoint, 4=DHW Preheat Setpoint | |
| AV | 46 | dhw_st_1 | DHW Status | Read | 0=Unknown, 1=Disabled, 2=Normal, 3=Suspended | |
| AV | 56 | dhw_tod_stpt_w_1 | DHW Time of Day Setpoint (W); 120°- 190° F Default: 180 | °F | Write | |
| BV | 57 | dhw_tod_stpt_st_1 | DHW Time of Day Setpoint Status; 120°- 190° F Default: 180 | °F | Read | |
| AV | 58 | dhw_req_rate_st_1 | DWH Requested Rate Status; RPM | RPM | Read | |
| AV | 59 | fan_spd_st_1 | Fan Speed Status; RPM. Current speed of blower. | RPM | Read | |
| AVmin | 60 | firing_rate_st_1 | Firing Rate Status; RPM. Target speed of blower. | RPM | Read | |
| AV | 61 | flame_sig_st_1 | Flame Signal Status; Volts | V | Read | |
| AV | 62 | inlet_sens_st_1 | Inlet Sensor Status; -40°- 266° F | °F | Read | |
| AV | 63 | lead_boil_add_st_1 | Lead Boiler Address Status | Read | ||
| AV | 64 | ll_act_svc_st_1 | Lead Lag Active Service Status; 5-14 = Reserved | Read | 0=No Active Service, 1=CH or Steam, 2=DHW, 3=Mix, 4=Frost Protection, 15=Warm Weather Shutdown | |
| AV | 67 | ll_ch_4ma_wtr_tmp_w_1 | Lead Lag CH 4mA Water Temp (W); Temperature corresponding to 4mA signal input: -40°- 266° F | °F | Write | |
| AV | 68 | ll_ch_4ma_wtr_tmp_st_1 | Lead Lag CH 4mA Water Temp Status; Temperature corresponding to 4mA signal input: -40°- 266° F | °F | Read | |
| AV | 65 | ll_ch_20ma_wtr_tmp_w_1 | Lead Lag CH 20mA Water Temp (W); Temperature corresponding to 20mA signal input: -40°- 266° F | °F | Read | |
| AV | 66 | ll_ch_20ma_wtr_tmp_st_1 | Lead Lag CH 20mA Water Temp Status; Temperature corresponding to 20mA signal input: -40°- 266° F | °F | Read | |
| AV | 69 | ll_odr_low_wtr_tmp_w_1 | Lead Lag CH ODR Low Water Temperature (W); 60°- 190° F | °F | Write | |
| AV | 70 | ll_odr_low_wtr_tmp_st_1 | Lead Lag CH ODR Low Water Temperature Status; 60°- 190° F | °F | Read | |
| AV | 71 | ll_odr_max_tmp_w_1 | Lead Lag CH ODR Max Outdoor Temperature (W); 50°- 100° F | °F | Write | |
| AV | 72 | ll_odr_max_tmp_st_1 | Lead Lag CH ODR Max Outdoor Temperature Status; 50°- 100° F | °F | Read | |
| AV | 73 | ll_odr_min_tmp_w_1 | Lead Lag CH ODR Min Outdoor Temperature (W); -40°- 100° F | °F | Write | |
| AV | 74 | ll_odr_min_tmp_st_1 | Lead Lag CH ODR Min Outdoor Temperature Status; -40°- 100° F | °F | Read | |
| AV | 75 | ll_ch_stpt_src_w_1 | Lead Lag CH Setpoint Source (W); 2 = 4-20mA Setpoint | Write | 0=Local Setpoint, 1=Modbus Setpoint | |
| AV | 76 | ll_ch_spt_src_w_st_1 | Lead Lag CH Setpoint Source Status; 2 = 4-20mA Setpoint | Read | 0=Local Setpoint, 1=Modbus Setpoint | |
| AV | 77 | ll_dhw_setp_1 | Lead Lag DHW Setpoint; 120°- 190° F Default: 190 | °F | Write | |
| AV | 78 | ll_dhw_sp_st_1 | Lead Lag DHW Setpoint Status; 120°- 190° F Default: 190 | °F | Read | |
| AV | 79 | ll_ms_en_st_1 | Lead Lag Master Enable Status | Read | 0=Not a Lead/Lag Master, 1=Lead/Lag Master | |
| AV | 80 | ll_ms_sp_src_st_1 | Lead Lag Master Setpoint Source Status | Read | 0=Unknown, 1=CH Setpoint, 2=CH TOD Setpoint, 3=Outdoor Reset, 4=Remote Control (4-20mA or Modbus), 7=Outdoor Reset TOD, 8=Reserved, 9=Outdoor Boost | |
| AV | 81 | ll_ms_st_1 | Lead Lag Mater Status | Read | 0=Unknown, 1=Disabled, 2=Normal, 3=Suspended | |
| AV | 82 | ll_mod_bu_sens_w_1 | Lead Lag Modulation Backup Sensor; Backup Sensor Used for Lead/Lag Modulation: | Write | 0=No Backup Sensor, 1=Outlet Sensor from Lead Boiler, 2=Average Outlet Sensor from All Slave Boilers | |
| AV | 83 | ll_mod_bu_sens_st_1 | Lead Lag Modulation Backup Sensor Status; Backup Sensor Used for Lead/Lag Modulation: | Read | 0=No Backup Sensor, 1=Outlet Sensor from Lead Boiler, 2=Average Outlet Sensor from All Slave Boilers | |
| AVmin | 84 | ll_stpt_w_1 | Lead Lag Setpoint (W); 70°- 190° F Default: 170 | °F | Write | |
| AV | 85 | ll_stpt_st_1 | Lead Lag Setpoint Status; 70°- 190° F Default: 170 | °F | Read | |
| AV | 86 | ll_sl_en_st_1 | Lead Lag Slave Enable Status | Read | 0=Lead/Lag Slave Disabled, 1=Lead/Lag Simple Slave Enabled for EnviraCom Master, 2=Lead/Lag Simple Slave Enabled for Sola Modbus Master (BAS), 3=Lead/Lag Full Slave Enabled for Sola Master | |
| AV | 87 | ll_sl_st_1 | Lead Lag Slave Status; Bit map: 7-0=Burner control status (see | Read | 15=Slave command received, 14=Slave mode has priority over CH & DHW, 13=Slave is modulating, 12=CH frost protection request, 11=DHW frost protection request, 10=Frost protection burner request, 9=Local frost protection request, 8=Reserved (always 0) register 32) | |
| AV | 88 | ll_tod_stpt_w_1 | Lead Lag Time of Day Setpoint (W); 32°- 250° F Default: 160 | °F | Write | |
| AV | 89 | ll_tod_stpt_st_1 | Lead Lag Time of Day Setpoint Status; 32°- 250° F Default: 160 | °F | Read | |
| AV | 91 | lock_out1_st_1 | Lockout1 Status; Most Recent Lockout. See Table 3. | Read | ||
| AV | 92 | lock_out2_st_1 | Lockout2 Status; 2nd Newest Lockout. See Table 3. | Read | ||
| AV | 93 | lock_out3_st_1 | Lockout3 Status; 3rd Newest Lockout. See Table 3. | Read | ||
| AV | 94 | lock_out4_st_1 | Lockout4 Status; 4th Newest Lockout. See Table 3. | Read | ||
| AV | 95 | lock_out5_st_1 | Lockout5 Status; 5th Newest Lockout. See Table 3. | Read | ||
| AVmin | 90 | lock_out_cd_st_1 | Lockout Status; 1-4096 (see Table 3) | Read | 0=No lockout | |
| AV | 96 | od_fp_stpt_w_1 | Outdoor Frost Protection Setpoint (W); -40°-266° F Default: 32 | °F | Write | |
| AV | 97 | od_fp_stpt_st_1 | Outdoor Frost Protection Setpoint Status; -40°-266° F Default: 32 | °F | Read | |
| AV | 98 | otdr_sens_state_st_1 | Outdoor Sensor State Status | Read | 0=None, 1=Normal, 2=Open, 3=Shorted, 4=Outside High Range, 7=Outside Low Range, 8=No Reliable | |
| AV | 99 | outdoor_tmp_st_1 | Outdoor Temperature Status; -40°-266° F | °F | Read | |
| AVmin | 100 | outlet_sens_st_1 | Outlet Sensor Status; -40°-266° F | °F | Read | |
| AVmin | 101 | pswd_w_1 | Write the unlock code from the manual to allow writes; 0 relocks | Write | ||
| AV | 102 | pswd_st_1 | PSWD Status; Register Data Write Access Status: | Read | 0=No register writes allowed, 1=Installer register writes allowed, 2=OEM register writes allowed, 3=All register writes allowed | |
| AV | 103 | s5_hdr_sens_st_1 | S5 (Header) Sensor Status; -40°-266° F | °F | Read | |
| AV | 104 | sl1_fire_rate_st_1 | Slave 1 Firing Rate Status; Current firing rate (0-100%) of slave 1 | Read | ||
| AV | 105 | sl1_state_st_1 | Slave 1 State Status | Read | 0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | |
| AV | 106 | sl2_fire_rate_st_1 | Slave 2 Firing Rate Status; Current firing rate (0-100%) of slave 1 | Read | ||
| AV | 107 | sl2_state_st_1 | Slave 2 State Status | Read | 0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | |
| AV | 108 | sl3_fire_rate_st_1 | Slave 3 Firing Rate Status; Current firing rate (0-100%) of slave 1 | Read | ||
| AV | 109 | sl3_state_st_1 | Slave 3 State Status | Read | 0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | |
| AV | 110 | sl4_fire_rate_st_1 | Slave 4 Firing Rate Status; Current firing rate (0-100%) of slave 1 | Read | ||
| AV | 111 | sl4_state_st_1 | Slave 4 State Status | Read | 0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | |
| AV | 112 | sl5_fire_rate_st_1 | Slave 5 Firing Rate Status; Current firing rate (0-100%) of slave 1 | Read | ||
| AV | 113 | sl5_state_st_1 | Slave 5 State Status | Read | 0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | |
| AV | 114 | sl6_fire_rate_st_1 | Slave 6 Firing Rate Status; Current firing rate (0-100%) of slave 1 | Read | ||
| AV | 115 | sl6_state_st_1 | Slave 6 State Status | Read | 0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | |
| AV | 116 | sl7_fire_rate_1 | Slave 7 Firing Rate Status; Current firing rate (0-100%) of slave 1 | Read | ||
| AV | 117 | sl7_state_st_1 | Slave 7 State Status | Read | 0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | |
| AV | 118 | sl8_fire_rate_st_1 | Slave 8 Firing Rate Status; Current firing rate (0-100%) of slave 1 | Read | ||
| AV | 119 | sl8_state_st_1 | Slave 8 State Status | Read | 0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | |
| AV | 120 | stack_sens_st_1 | Stack Sensor Status; -40°-266° F | °F | Read | |
| AV | 121 | sys_pum_cy_cnt_1 | System Pump Cycle Count; 0-999,999 | Write | ||
| AV | 122 | sys_pum_cy_cnt1_st_1 | System Pump Cycle Count Status; 0-999,999 | Read | ||
| AV | 123 | ww_sd_stpt_w_1 | Warm Weather Shutdown Setpoint; -40°-266° F Default: 60 | °F | Write | |
| AV | 124 | ww_sd_stpt_st_1 | Warm Weather Shutdown Setpoint Status; -40°-266° F Default: 60 | °F | Read | |
| BVmin | 1 | ch_enbl_1 | CH Enable (W) | Write | 0=Disable Central Heating, 1=Enable Central Heating | |
| BV | 2 | ch_enable_st_1 | CH Enable Status | Read | 0=Disable Central Heating, 1=Enable Central Heating | |
| BV | 3 | ch_fp_en_w_1 | CH Frost Protection Enable (W) | Write | 0=Disable CH Frost Protection, 1=Enable CH Frost Protection | |
| BV | 4 | ch_frost_en_st_1 | CH Frost Protection Enable Status | Read | 0=Disable CH Frost Protection, 1=Enable CH Frost Protection | |
| BV | 5 | ch_odr_en_w_1 | CH Outdoor Reset Enable (W) | Write | 0=Disable Outdoor Reset, 1=Enable Outdoor Reset | |
| BV | 6 | ch_odr_en_st_1 | CH Outdoor Reset Enable Status | Read | 0=Disable Outdoor Reset, 1=Enable Outdoor Reset | |
| BV | 8 | ch_rem_stat_1 | CH Remote Stat (W) | Write | 0=No Remote Stat Demand, 1=Remote Stat Demand Indicated | |
| BV | 7 | ch_rmt_st_1 | CH Remote Status | Read | 0=No Remote Stat Demand, 1=Remote Stat Demand Indicated | |
| BV | 9 | dhw_en_1 | DHW Enable | Write | 0=DHW Disabled, 1=DHW Enabled | |
| BV | 10 | dhw_en_st_1 | DHW Enable Status | Read | 0=DHW Disabled, 1=DHW Enabled | |
| BV | 11 | dhw_frst_pro_en_1 | DHW Frost Protection Enable | Write | 0=Disable DHW Frost Protection, 1=Enable DHW Frost Protection | |
| BV | 12 | dhw_frost_en_st_1 | DHW Frost Protection Enable Status | Read | 0=Disable DHW Frost Protection, 1=Enable DHW Frost Protection | |
| BVmin | 15 | ll_op_swt_w_1 | Lead Lag Operation Switch (W) | Write | 0=Turn off Lead Lag Operation, 1=Turn on Lead Lag Operation | |
| BV | 16 | ll_op_swt_st_1 | Lead Lag Operation Switch Status | Read | 0=Turn off Lead Lag Operation, 1=Turn on Lead Lag Operation | |
| BV | 13 | htmp_hi_alm_1 | HTemp HI Alarm; Header Sensor High Temperature Alarm Default to 220. | Read | ||
| BV | 14 | htemp_low_alm_1 | HTemp Low Alarm; Header Sensor Low Temperature Alarm Default to -80. | Read | ||
| BV | 17 | ordtemp_hi_alm_1 | ODRTemp Hi Alarm; Outdoor Sensor High Temperature Alarm Default to 220. | Read | ||
| BV | 18 | ordtemp_lo_alm_1 | ORDTemp Low Alarm; Outdoor Sensor Low Temperature Alarm Default to -80. | Read | ||
| BV | 19 | ww_sd_en_w | Warm Weather Shutdown Enable | Write | 0=Disable, 1=Shutdown After Demand has Ended, 2=Shutdown Immediately | |
| BV | 20 | ww_ed_en_st | Warm Weather Shutdown Enable Status | Read | 0=Disable, 1=Shutdown After Demand has Ended, 2=Shutdown Immediately |
No points match these filters.
Object ID lookup: Weil-McLain SlimFit 1000-2000 point IDs by name
AV1remt_ctrl_in_4_20_st_1AV2active_ch_stpt_st_1AV3active_dhw_stpt_st_1AV4active_ll_oppt_st_1AV5active_ll_stpt_st_1AV6act_sys_op_st_1AV7act_sys_sp_st_1AV8alarm_st_1AV9alarm_st_2AV10alarm_st_3AV11alarm_st_4AV12alarm_st_5AV13ann_first_out_st_1AV14aux2_pum_cy_cnt_1AV15aux2_pum_cy_cnt1_st_1AV16aux_pum_cy_cnt_1AV17aux_pum_cy_cnt1_st_1AV18blr_pum_cy_cnt1_1AV19blr_pum_cy_cnt1_st_1AV20brnr_ctrl_state_st_1AV21brnr_ctl_st_1AV22brn_cy_cnt_1AV23brn_cy_cnt1_st_1AV24brn_run_tim_1AV25brn_run_tim1st_1AV26ch_brn_dem_st_1AV27ch_heat_dem_st_1AV28ch_odr_low_wtr_w_1AV29ch_odr_low_wtr_st_1AV30ch_odr_max_tmp_w_1AV31ch_odr_max_tmp_st_1AV32ch_odr_min_temp_w_1AV33ch_odr_min_temp_st_1AV34ch_pum_cy_cnt_1AV35ch_pum_cy_cnt1_st_1AV36ch_req_rate_st_1AV37ch_stpt_w_1AV39ch_stpt_st_1AV38ch_sp_src_st_1AV40ch_st_1AV41ch_tod_stpt_w_1AV42ch_tod_stpt_st_1AV43cont_cy_cnt1_st_1AV44cont_run_tim1_st_1AV45demand_src_st_1AV47dhw_brn_dem_st_1AV48dhw_heat_dem_st_1AV49dhw_pri_cnt_st_1AV50dhw_pum_cy_cnt_1AV51dhw_pum_cy_cnt1_st_1AV52dhw_sens_st_1AV53dhw_stpt_w_1AV55dhw_stpt_st_1AV54dhw_sp_src_st_1AV46dhw_st_1AV56dhw_tod_stpt_w_1BV57dhw_tod_stpt_st_1AV58dhw_req_rate_st_1AV59fan_spd_st_1AV60firing_rate_st_1AV61flame_sig_st_1AV62inlet_sens_st_1AV63lead_boil_add_st_1AV64ll_act_svc_st_1AV67ll_ch_4ma_wtr_tmp_w_1AV68ll_ch_4ma_wtr_tmp_st_1AV65ll_ch_20ma_wtr_tmp_w_1AV66ll_ch_20ma_wtr_tmp_st_1AV69ll_odr_low_wtr_tmp_w_1AV70ll_odr_low_wtr_tmp_st_1AV71ll_odr_max_tmp_w_1AV72ll_odr_max_tmp_st_1AV73ll_odr_min_tmp_w_1AV74ll_odr_min_tmp_st_1AV75ll_ch_stpt_src_w_1AV76ll_ch_spt_src_w_st_1AV77ll_dhw_setp_1AV78ll_dhw_sp_st_1AV79ll_ms_en_st_1AV80ll_ms_sp_src_st_1AV81ll_ms_st_1AV82ll_mod_bu_sens_w_1AV83ll_mod_bu_sens_st_1AV84ll_stpt_w_1AV85ll_stpt_st_1AV86ll_sl_en_st_1AV87ll_sl_st_1AV88ll_tod_stpt_w_1AV89ll_tod_stpt_st_1AV91lock_out1_st_1AV92lock_out2_st_1AV93lock_out3_st_1AV94lock_out4_st_1AV95lock_out5_st_1AV90lock_out_cd_st_1AV96od_fp_stpt_w_1AV97od_fp_stpt_st_1AV98otdr_sens_state_st_1AV99outdoor_tmp_st_1AV100outlet_sens_st_1AV101pswd_w_1AV102pswd_st_1AV103s5_hdr_sens_st_1AV104sl1_fire_rate_st_1AV105sl1_state_st_1AV106sl2_fire_rate_st_1AV107sl2_state_st_1AV108sl3_fire_rate_st_1AV109sl3_state_st_1AV110sl4_fire_rate_st_1AV111sl4_state_st_1AV112sl5_fire_rate_st_1AV113sl5_state_st_1AV114sl6_fire_rate_st_1AV115sl6_state_st_1AV116sl7_fire_rate_1AV117sl7_state_st_1AV118sl8_fire_rate_st_1AV119sl8_state_st_1AV120stack_sens_st_1AV121sys_pum_cy_cnt_1AV122sys_pum_cy_cnt1_st_1AV123ww_sd_stpt_w_1AV124ww_sd_stpt_st_1BV1ch_enbl_1BV2ch_enable_st_1BV3ch_fp_en_w_1BV4ch_frost_en_st_1BV5ch_odr_en_w_1BV6ch_odr_en_st_1BV8ch_rem_stat_1BV7ch_rmt_st_1BV9dhw_en_1BV10dhw_en_st_1BV11dhw_frst_pro_en_1BV12dhw_frost_en_st_1BV15ll_op_swt_w_1BV16ll_op_swt_st_1BV13htmp_hi_alm_1BV14htemp_low_alm_1BV17ordtemp_hi_alm_1BV18ordtemp_lo_alm_1BV19ww_sd_en_wBV20ww_ed_en_st
Integration notes
- Table 2 (Complete Map, pages 15-25) is listed here; Table 1 (pages 11-14) is a recommended subset of it.
- BACnet over ARC156 is also supported by the UPC.
- The Type column uses BAV/BBV/BALM/BVV; they are listed by their Object ID (AV or BV). BV 13, 14, 17 and 18 are alarm (BALM) objects.
- Object 57 is printed as BV:57 although its type column says BAV and its neighbours are AVs.
- AV 103 has no read/write mark (listed as read-only); AV 42 and AV 65 are marked opposite to their names.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SlimFit 1000-2000 - UPC BACnet translator and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Weil-McLain SlimFit 1000-2000 - UPC BACnet translator
How many BACnet points does the Weil-McLain SlimFit 1000-2000 - UPC BACnet translator have?
This list has 144 BACnet objects: 123 analog values, 21 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Weil-McLain SlimFit 1000-2000 - UPC BACnet translator BACnet points are writable?
36 of the 144 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Weil-McLain SlimFit 1000-2000 - UPC BACnet translator BACnet documentation?
The source is SlimFit Building Automation System Interface Instructions & Reference Guide - UPC BACnet translator (550-100-130/1113), revision 2013-11, published free by Weil-McLain at https://www.weil-mclain.com/wp-content/uploads/slimfit-1000-2000-bacnet-interface-manual_1.pdf.
What are the minimum BACnet points to integrate the Weil-McLain SlimFit 1000-2000 - UPC BACnet translator?
Start with AV 101 pswd_w_1 (Write the unlock code first; 0 relocks); BV 1 ch_enbl_1 (Central heat enable (1 = enable)); AV 37 ch_stpt_w_1 (CH setpoint, 70-190 °F); BV 15 ll_op_swt_w_1 (Lead/lag operation on/off); AV 84 ll_stpt_w_1 (Lead/lag setpoint, 70-190 °F); AV 21 brnr_ctl_st_1 (Burner control status code); AV 100 outlet_sens_st_1 (Outlet water temperature); AV 60 firing_rate_st_1 (Firing rate (target blower speed)); AV 90 lock_out_cd_st_1 (Lockout code; 0 = no lockout); AV 8 alarm_st_1 (Most recent alert code).
How do I enable BMS control of the Weil-McLain SlimFit 1000-2000 - UPC BACnet translator?
Write the unlock code given in the manual to AV 101 Password (W) before changing any point; write 0 to relock (the boiler also relocks after 10 minutes without activity). Then BV 1 ch_enbl_1 enables central heat and AV 37 sets the CH setpoint; BV 15 and AV 84 do the same for lead/lag, and AV 75 picks the lead/lag setpoint source (0 local, 1 Modbus, 2 4-20 mA).
Does the Weil-McLain SlimFit 1000-2000 - UPC BACnet translator need a BACnet heartbeat or have a communication timeout?
No heartbeat object. Write access drops back to locked after 10 minutes of inactivity, so the BMS has to unlock again before later writes.
How do I check these points on the real SlimFit 1000-2000 - UPC BACnet translator?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Weil-McLain BACnet points lists
- Boiler controller gateway
Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode
Weil-McLain Evergreen, SlimFit 550-750 Series 2 & 3, SlimFit 1000-2000 Series 2 and SVF boilers, read through a ProtoNode FPC-N34 gateway.
Also known as: Evergreen, SlimFit 550-750, SlimFit 1000-2000 Series 2, SVF, ProtoNode FPC-N34, ProtoNode FPC-N35, ProtoNode - Boiler controller gateway
Weil-McLain SlimFit 1000-2000 Series 1 (SOLA) - ProtoNode
Weil-McLain SlimFit 1000-2000 Series 1 boilers with the Honeywell SOLA control, read through a ProtoNode FPC-N34 gateway.
Also known as: SlimFit Series 1, SlimFit SOLA, SOLA, ProtoNode FPC-N34, ProtoNode FPC-N35, ProtoNode
Source: SlimFit Building Automation System Interface Instructions & Reference Guide - UPC BACnet translator · 550-100-130/1113 · rev. 2013-11. Object names, instances and units are reproduced as published; descriptions are our own.