Boiler controller gateway · BACnet points list
Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode BACnet points list
Updated 28 October 2026
A ProtoNode FPC-N34 reads the boiler control over Modbus RTU and presents it as a BACnet IP or BACnet MS/TP device with 831 objects numbered in one sequence across AI, AV, BI and MI. Besides temperatures, status, counters and lockout history, it carries the priority and network (cascade) settings, a block per cascade member (Shadow 2-8), and bit-level BIs for relay outputs, inputs and lockout causes.
This page lists 831 BACnet objects for the Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode — 111 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Weil-McLain’s own free documentation, linked below.
- Manufacturer
- Weil-McLain
- Model
- Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode
- Equipment
- Boiler controller gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 831 (111 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Evergreen, SlimFit 550-750, SlimFit 1000-2000 Series 2, SVF, ProtoNode FPC-N34, ProtoNode FPC-N35, ProtoNode
BMS integration notes: Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode
Most objects are read-only monitoring. Map boiler status, target and outlet temperatures, modulation rate, gas valve output and sensor warnings. The writable AVs are the priority, network and cascade settings (supply targets, outdoor reset, differentials, rates, times); the supplement does not say which one a BMS should use as a run or setpoint command.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MI 138 | Boiler Status | Boiler status code | Read |
| AI 10 | Active Target Supply Temperature | Supply temperature the boiler is aiming for | Read |
| AI 7 | Boiler Out 1 Temperature | Boiler outlet water temperature | Read |
| AI 307 | Boiler Modulation Rate | Burner modulation rate | Read |
| BI 594 | Relay Output Gas Valve ON | Gas valve energized (burner firing) | Read |
| AI 19 | Outdoor Temp | Outdoor air temperature | Read |
| AI 160 | Sensor Warnings | Sensor warning code | Read |
Network setup
- Device instance, MAC address and baud rate are set on the ProtoNode (see the ProtoNode start-up guide); this supplement does not list them.
- Object IDs are unique across object types (1-831), so AI 7 and AV 7 never both exist.
Watch out for
- No read/write column: AVs are writable settings, all AI/BI/MI are read-only.
- Several names repeat (for example Boiler Status is MI 138 and AI 653, AI 75 Local Return Temp and AI 151 Local Return Temperature); use the object ID, not the name.
- Writable AVs are boiler configuration values; avoid writing them cyclically.
Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Pad00HB | Read | |||
| MI | 2 | Boiler Model | Read | |||
| AI | 3 | U1 Sw Version | Read | |||
| AI | 4 | U2 Sw Version | Read | |||
| AI | 5 | NET Volts Output | Read | |||
| AI | 6 | Relay Output Status | Read | |||
| AImin | 7 | Boiler Out 1 Temperature | Boiler outlet 1 temperature | Read | ||
| AI | 8 | Mod Return Temp | Read | |||
| AI | 9 | MHEOTmp F1 | Read | |||
| AImin | 10 | Active Target Supply Temperature | Active target supply temperature | Read | ||
| AI | 11 | Mod Temp | Read | |||
| AI | 12 | Fire Rate Selection | Read | |||
| BI | 13 | Boiler Status 2 | Read | |||
| AI | 14 | HLOReset | Read | |||
| AI | 15 | Fan Speed | Read | |||
| AI | 16 | Flame Sense Value | Read | |||
| AI | 17 | AvgFlameL | Read | |||
| AI | 18 | Slave Fire Rate Unconverted | Read | |||
| AImin | 19 | Outdoor Temp | Outdoor temperature | Read | ||
| AV | 20 | System Time (Minutes) | Write | |||
| AV | 21 | System Time (Hours) | Write | |||
| AV | 22 | System Date (Day) | Write | |||
| AV | 23 | System Date (Month) | Write | |||
| AV | 24 | System Date (Year) | Write | |||
| AI | 25 | 0-10V Output | Read | |||
| AI | 26 | 0-10V Output | Read | |||
| AI | 27 | 0-10V Input | Read | |||
| AI | 28 | Max Blower RPM | Read | |||
| AI | 29 | Flame Boost | Read | |||
| AV | 30 | Circulator Exercise/Freeze Protection | Write | |||
| AI | 31 | Input 2 Hours RAM MSB | Read | |||
| AI | 32 | Priority 1 Settings | Read | |||
| AV | 33 | Priority 1 Supply Max Target | Write | |||
| AV | 34 | Priority 1 Supply Min Target | Write | |||
| AV | 35 | Priority 1 OD Reset/Volts Max | Write | |||
| AV | 36 | Priority 1 OD Reset/Volts Min | Write | |||
| AV | 37 | Priority 1 Max Boiler Temperature | Write | |||
| AV | 38 | Priority 3 Max Rate Volts | Write | |||
| AI | 39 | OAT Configuration | Read | |||
| AI | 40 | Active Network Priority's Boiler Off Diff | Read | |||
| AV | 41 | Priority 1 System On Diff | Write | |||
| AV | 42 | Priority 1 Max On Time Setting | Write | |||
| AV | 43 | Priority 1 Post Pump Time | Write | |||
| AV | 44 | Priority 1 Boost Time | Write | |||
| AI | 45 | Input 1 Priority | Read | |||
| AV | 46 | Priority 1 Pre Pump Time | Write | |||
| AI | 47 | Min Blower RPM | Read | |||
| AV | 48 | Priority 1 Boiler On Diff | Write | |||
| AV | 49 | Priority 1 Boiler Off Diff | Write | |||
| AV | 50 | Priority 1 Max Rate | Write | |||
| AV | 51 | Priority 1 Min Rate | Write | |||
| AI | 52 | Active Network Priority's Max BLR Temp | Read | |||
| AI | 53 | Active Network Priority's Boiler On Diff | Read | |||
| AI | 54 | Input 2 Hours RAM LSB | Read | |||
| AI | 55 | Priority 2 Setting | Read | |||
| AV | 56 | Priority 2 Supply Max Target | Write | |||
| AV | 57 | Priority 2 Supply Min Target | Write | |||
| AV | 58 | Priority 2 OD Reset/Volts Max | Write | |||
| AV | 59 | Priority 2 OD Reset/Volts Min | Write | |||
| AI | 60 | Active Network Prepump Time | Read | |||
| AI | 61 | Ignition Counter RAM | Read | |||
| AV | 62 | Priority 2 Min On Time Setting | Write | |||
| AV | 63 | Priority 2 Max On Time Setting | Write | |||
| AV | 64 | Priority 2 Post Pump Time | Write | |||
| AV | 65 | Priority 2 Boost Time | Write | |||
| AI | 66 | Boiler Control Type | Read | |||
| AV | 67 | Priority 1 Pre Pump Time | Write | |||
| AV | 68 | Priority 2 System Off Diff | Write | |||
| AI | 69 | Network Minimum On Time | Read | |||
| AV | 70 | Priority 2 Boiler On Diff | Write | |||
| AV | 71 | Priority 2 Boiler Off Diff | Write | |||
| AV | 72 | Priority 2 Max Rate | Write | |||
| AV | 73 | Priority 2 Min Rate | Write | |||
| AI | 74 | Network Return Temp | Read | |||
| AI | 75 | Local Return Temp | Read | |||
| AI | 76 | Active Network Priority Post Pump Time | Read | |||
| AI | 77 | Single Boiler: Pri 3 Setting/Master Boiler: Network 1 Pri Setting | Read | |||
| AV | 78 | Priority 3/Net1 Supply Max Target | Write | |||
| AV | 79 | Priority 3/Net1 Supply Min Target | Write | |||
| AV | 80 | Priority 3/Net1 OD Reset/Volts Max | Write | |||
| AV | 81 | Priority 3/Net1 OD Reset/Volts Min | Write | |||
| AI | 82 | Network Max On Time | Read | |||
| AV | 83 | Priority 3/Net1 System On Diff | Write | |||
| AV | 84 | Priority 3 Min On Time Setting | Write | |||
| AV | 85 | Priority 3/Net1 System Off Diff | Write | |||
| AV | 86 | Priority 3/Net1 Post Pump Time | Write | |||
| AV | 87 | Priority 3/Net1 Boost Time | Write | |||
| AV | 88 | Priority 2 Max Boiler Temperature | Write | |||
| AV | 89 | Priority 3/Net1 Pre Pump Time | Write | |||
| AI | 90 | Boiler Status 3 | Read | |||
| AI | 91 | Network Modulation Rate | Modulation rate requested over the network | Read | ||
| AV | 92 | Priority 3/Net1 Boiler On Diff | Write | |||
| AV | 93 | Priority 3/Net1 Boiler Off Diff | Write | |||
| AV | 94 | Priority 3 Max Rate (for single) | Write | |||
| AV | 95 | Priority 3 Min Rate (for single) | Write | |||
| AV | 96 | P3 Max Boiler Temp | Write | |||
| AI | 97 | Network Run Pumps | Read | |||
| AV | 98 | High Limit Temp | Write | |||
| AV | 99 | WWSD Temp | Write | |||
| AV | 100 | P1 More Settings | Write | |||
| AV | 101 | P1 Min Rate Volts | Write | |||
| AV | 102 | P2 More Settings | Write | |||
| AV | 103 | Outdoor Temp Correction | Write | |||
| AV | 104 | P3 More Settings | Write | |||
| AI | 105 | Input 2 Hours LSB | Read | |||
| AV | 106 | P1 System Off Diff | Write | |||
| AI | 107 | Input 2 Hours MSB | Read | |||
| AV | 108 | P2 Min Rate Volts | Write | |||
| AI | 109 | Boiler Model Number | Read | |||
| AV | 110 | P3 Min rate Volts | Write | |||
| AI | 111 | Input 1 Hours MSB | Read | |||
| AI | 112 | Input 1 Hours LSB | Read | |||
| AI | 113 | Input 1 Hours RAM MSB | Read | |||
| AI | 114 | Input 1 Hours RAM LSB | Read | |||
| AV | 115 | P2 System On Diff | Write | |||
| AV | 116 | P1 Response Time | Write | |||
| AV | 117 | P2 Response Time | Write | |||
| AV | 118 | P3 Response Time | Write | |||
| AI | 119 | Network Hours LSB | Read | |||
| AI | 120 | Ignition Speed | Read | |||
| AI | 121 | Input 2 Priority | Read | |||
| AI | 122 | Input 3 Priority | Read | |||
| AI | 123 | Ignition Counts | Read | |||
| AI | 124 | Burner Hours | Read | |||
| AI | 125 | Burner Hours RAM | Read | |||
| AI | 126 | Reset Factory MSB | Read | |||
| AI | 127 | Reset Factory LSB | Read | |||
| AI | 128 | Network Hours MSB | Read | |||
| MI | 129 | Boiler Out 1 | Read | |||
| AI | 130 | Network Hours RAM MSB | Read | |||
| AI | 131 | Network Hours RAM LSB | Read | |||
| MI | 132 | Boiler Out 2 | Read | |||
| AI | 133 | Heat Xchgr 1 | Read | |||
| AI | 134 | Max EE | Read | |||
| AI | 135 | Heat Xchgr 2 | Read | |||
| AI | 136 | Available to run | Read | |||
| MI | 137 | Boiler In Temperature | Read | |||
| MImin | 138 | Boiler Status | Boiler status code | Read | ||
| AI | 139 | bHeatXchgrIn2 | Read | |||
| AI | 140 | Input Status | Read | |||
| MI | 141 | Flue Temperature 1 | Read | |||
| AI | 142 | Local Supply Temp | Read | |||
| MI | 143 | Flue Temperature 2 | Read | |||
| AI | 144 | P1 Max Rate Volts | Read | |||
| AI | 145 | bDHWSensor1 | Read | |||
| MI | 146 | Local Outdoor Temperature | Read | |||
| AI | 147 | bDHWSensor2 | Read | |||
| MI | 148 | Network Outdoor Temperature | Read | |||
| MI | 149 | Network Supply Temperature | Read | |||
| AI | 150 | Local Supply Temperature | Read | |||
| AI | 151 | Local Return Temperature | Read | |||
| AI | 152 | Input 3 Hours MSB | Read | |||
| AI | 153 | Input 3 Hours LSB | Read | |||
| AI | 154 | Bad EEPROM Count | Read | |||
| AI | 155 | Bad Ram Count | Read | |||
| AI | 156 | Default Count | Read | |||
| AI | 157 | Ignition Retries | Read | |||
| AI | 158 | Lockout History 1 Expansion Board Errors | Read | |||
| AI | 159 | Manual Lockout Count | Read | |||
| AImin | 160 | Sensor Warnings | Sensor warning code | Read | ||
| AI | 161 | Auto Lockout Count | Read | |||
| AI | 162 | Lockout History 1 Hard Lockout Errors | Read | |||
| AI | 163 | Lockout History 1 Soft Lockout Errors | Read | |||
| AI | 164 | Lockout History 1 Minutes | Read | |||
| AI | 165 | Lockout History 1 Hours | Read | |||
| AI | 166 | Lockout History 1 Day | Read | |||
| AI | 167 | Lockout History 1 Month | Read | |||
| AI | 168 | Lockout History 1 Year | Read | |||
| AI | 169 | Lockout History 1 Boiler Model | Read | |||
| AI | 170 | Lockout History 1 Input Status | Read | |||
| AI | 171 | Lockout History 1 Relay Output Status | Read | |||
| AI | 172 | Lockout History 1 Flame Signal MSB | Read | |||
| AI | 173 | Lockout History 1 Flame Signal LSB | Read | |||
| AI | 174 | Lockout History 1 Outdoor Temperature | Read | |||
| AI | 175 | Lockout History 1 Flue Temperature 2 | Read | |||
| AI | 176 | Lockout History 1 Boiler Out Temp 2 | Read | |||
| AI | 177 | Lockout History 1 Boiler In Temp 2 | Read | |||
| AI | 178 | bErrSDW | Read | |||
| AI | 179 | Lockout History 1 Flue Temperature 1 | Read | |||
| AI | 180 | Lockout History 1 Boiler Out Temp 1 | Read | |||
| AI | 181 | Lockout History 1 Heat Exchanger Temp 1 | Read | |||
| AI | 182 | Lockout History 1 Supply Temperature | Read | |||
| AI | 183 | Lockout History 1 Return Temperature | Read | |||
| AI | 184 | Lockout History 1 Boiler In Temp 1 | Read | |||
| AI | 185 | Lockout History 1 0-10V Output | Read | |||
| AI | 186 | Lockout History 1 Blower Speed (RPM) | Read | |||
| AI | 187 | Lockout History 2 Hard Lockout Errors | Read | |||
| AI | 188 | Lockout History 2 Soft Lockout Errors | Read | |||
| AI | 189 | Lockout History 2 Minutes | Read | |||
| AI | 190 | Lockout History 2 Hours | Read | |||
| AI | 191 | Lockout History 2 Day | Read | |||
| AI | 192 | Lockout History 2 Month | Read | |||
| AI | 193 | Lockout History 2 Year | Read | |||
| AI | 194 | Lockout History 2 Boiler Model | Read | |||
| AI | 195 | Lockout History 2 Input Status | Read | |||
| AI | 196 | Lockout History 2 Relay Output Status | Read | |||
| AI | 197 | Lockout History 2 Flame Signal MSB | Read | |||
| AI | 198 | Lockout History 2 Flame Signal LSB | Read | |||
| AI | 199 | Lockout History 2 Outdoor Temperature | Read | |||
| AI | 200 | Lockout History 2 Flue Temperature 2 | Read | |||
| AI | 201 | Lockout History 2 Boiler Out Temp 2 | Read | |||
| AI | 202 | Lockout History 2 Boiler In Temp 2 | Read | |||
| AI | 203 | bH1ErrSDW | Read | |||
| AI | 204 | Lockout History 2 Flue Temperature 1 | Read | |||
| AI | 205 | Lockout History 2 Boiler Out Temp 1 | Read | |||
| AI | 206 | Lockout History 2 Heat Exchanger Temp 1 | Read | |||
| AI | 207 | Lockout History 2 Supply Temperature | Read | |||
| AI | 208 | Lockout History 2 Return Temperature | Read | |||
| AI | 209 | Lockout History 2 Boiler In Temp 1 | Read | |||
| AI | 210 | Lockout History 2 0-10V Output | Read | |||
| AI | 211 | Lockout History 2 Blower Speed (RPM) | Read | |||
| AI | 212 | Lockout History 3 Hard Lockout Errors | Read | |||
| AI | 213 | Lockout History 3 Soft Lockout Errors | Read | |||
| AI | 214 | Lockout History 3 Minutes | Read | |||
| AI | 215 | Lockout History 3 Hours | Read | |||
| AI | 216 | Lockout History 3 Day | Read | |||
| AI | 217 | Lockout History 3 Month | Read | |||
| AI | 218 | Lockout History 3 Year | Read | |||
| AI | 219 | Lockout History 3 Boiler Model | Read | |||
| AI | 220 | Lockout History 3 Input Status | Read | |||
| AI | 221 | Lockout History 3 Relay Output Status | Read | |||
| AI | 222 | Lockout History 3 Flame Signal MSB | Read | |||
| AI | 223 | Lockout History 3 Flame Signal LSB | Read | |||
| AI | 224 | Lockout History 3 Outdoor Temperature | Read | |||
| AI | 225 | Lockout History 3 Flue Temperature 2 | Read | |||
| AI | 226 | Lockout History 3 Boiler Out Temp 2 | Read | |||
| AI | 227 | Lockout History 3 Boiler In Temp 2 | Read | |||
| AI | 228 | bH1ErrSDW | Read | |||
| AI | 229 | Lockout History 3 Flue Temperature 1 | Read | |||
| AI | 230 | Lockout History 3 Boiler Out Temp 1 | Read | |||
| AI | 231 | Lockout History 3 Heat Exchanger Temp 1 | Read | |||
| AI | 232 | Lockout History 3 Supply Temperature | Read | |||
| AI | 233 | Lockout History 3 Return Temperature | Read | |||
| AI | 234 | Lockout History 3 Boiler In Temp 1 | Read | |||
| AI | 235 | Lockout History 3 0-10V Output | Read | |||
| AI | 236 | Lockout History 3 Blower Speed (RPM) | Read | |||
| AI | 237 | P2 Max Rate Volts | Read | |||
| AI | 238 | Clear Error History | Read | |||
| AI | 239 | Installer Name 1 | Read | |||
| AI | 240 | Installer Name 2 | Read | |||
| AI | 241 | Installer Name 3 | Read | |||
| AI | 242 | Installer Name 4 | Read | |||
| AI | 243 | Installer Name 5 | Read | |||
| AI | 244 | Installer Name 6 | Read | |||
| AI | 245 | Installer Name 7 | Read | |||
| AI | 246 | Installer Name 8 | Read | |||
| AI | 247 | Installer Name 9 | Read | |||
| AI | 248 | Installer Name 10 | Read | |||
| AI | 249 | Installer Name 11 | Read | |||
| AI | 250 | Installer Name 12 | Read | |||
| AI | 251 | Installer Name 13 | Read | |||
| AI | 252 | Installer Name 14 | Read | |||
| AI | 253 | Installer Name 15 | Read | |||
| AI | 254 | bPad88LB | Read | |||
| AI | 255 | Installer Phone 1 | Read | |||
| AI | 256 | Installer Phone 2 | Read | |||
| AI | 257 | Installer Phone 3 | Read | |||
| AI | 258 | Installer Phone 4 | Read | |||
| AI | 259 | Installer Phone 5 | Read | |||
| AI | 260 | Installer Phone 6 | Read | |||
| AI | 261 | Last Maintenance Reminder Month | Read | |||
| AI | 262 | Last Maintenance Reminder Day | Read | |||
| AI | 263 | Last Maintenance Reminder Year | Read | |||
| AV | 264 | Maintenance Reminder Interval | Write | |||
| AI | 265 | Installation Month | Read | |||
| AI | 266 | Installation Day | Read | |||
| AI | 267 | Installation Year | Read | |||
| AI | 268 | Last Maintenance Performed Month | Read | |||
| AI | 269 | Last Maintenance Performed Day | Read | |||
| AI | 270 | Last Maintenance Performed Year | Read | |||
| AI | 271 | Boiler CP Number 1 | Read | |||
| AI | 272 | Boiler CP Number 2 | Read | |||
| AI | 273 | Boiler CP Number 3 | Read | |||
| AI | 274 | Boiler CP Number 4 | Read | |||
| AI | 275 | Boiler CP Number 5 | Read | |||
| AI | 276 | Boiler CP Number 6 | Read | |||
| AI | 277 | Boiler CP Number 7 | Read | |||
| AI | 278 | bInstModelNumber | Read | |||
| AI | 279 | bUTTest2 | Read | |||
| AI | 280 | bUTTest1 | Read | |||
| AI | 281 | bCrntErrFR | Read | |||
| AI | 282 | bH1ErrFR | Read | |||
| AI | 283 | bH2ErrFR | Read | |||
| AI | 284 | bCrntErrExpBrd | Read | |||
| AI | 285 | Lockout History 2 Expansion Board Errors | Read | |||
| AI | 286 | Lockout History 3 Expansion Board Errors | Read | |||
| AI | 287 | Lockout History 1 Boiler Status 2 | Read | |||
| AI | 288 | Lockout History 2 Boiler Status 2 | Read | |||
| AI | 289 | Lockout History 3 Boiler Status 2 | Read | |||
| AI | 290 | Lockout History 1 10 Volt Input | Read | |||
| AI | 291 | Lockout History 2 10 Volt Input | Read | |||
| AI | 292 | Lockout History 3 10 Volt Input | Read | |||
| AI | 293 | bInput3HoursRAM MSB | Read | |||
| AI | 294 | bInput3HoursRAM LSB | Read | |||
| AI | 295 | Ignore Flame Signal Shutdown | Read | |||
| AI | 296 | P1 ODT Setpoint | Read | |||
| AI | 297 | bCommGVCtrlRd | Read | |||
| AI | 298 | Number of Failed Ignitions | Read | |||
| AI | 299 | bExpBrdRev | Read | |||
| AI | 300 | bPad9FLB | Read | |||
| AI | 301 | bCommGVSts1 | Read | |||
| AI | 302 | bCommGVSts2 | Read | |||
| AI | 303 | bCGVOutputs | Read | |||
| AI | 304 | bCommGVCtrl | Read | |||
| AI | 305 | P3 ODT Setpoint | Read | |||
| AI | 306 | P2 ODT Setpoint | Read | |||
| AImin | 307 | Boiler Modulation Rate | Boiler modulation rate | Read | ||
| AI | 308 | Shadow Number | Read | |||
| AV | 309 | Max Time Network | Write | |||
| AV | 310 | Min Time Network | Write | |||
| AV | 311 | Max Rate Network | Write | |||
| AV | 312 | Min Rate Network | Write | |||
| AV | 313 | High Temp Limit | Write | |||
| AI | 314 | Days Passed | Read | |||
| AV | 315 | Base Rate High | Write | |||
| AV | 316 | Base Rate Low | Write | |||
| AI | 317 | Sequence Type | Read | |||
| AV | 318 | Boiler Rotation Method | Write | |||
| AV | 319 | Force Lead Rotate | Write | |||
| AI | 320 | User Mode | Read | |||
| AI | 321 | Net1 P Gain Adjust | Read | |||
| AI | 322 | Net1 I Gain Adjust | Read | |||
| AI | 323 | Net1 Maximum Step Size | Read | |||
| AI | 324 | Net1 Minimum Step Size | Read | |||
| AI | 325 | Net2 P Gain Adjust | Read | |||
| AI | 326 | Net2 I Gain Adjust | Read | |||
| AI | 327 | Net2 Maximum Step Size | Read | |||
| AI | 328 | Net2 Minimum Step Size | Read | |||
| AI | 329 | Modify Equation | Read | |||
| AV | 330 | Net1 Priority System Add Boiler Diff | Write | |||
| AV | 331 | Net1 Priority System Drop Boiler Diff | Write | |||
| AV | 332 | Net1 Priority Mod Delay Time | Write | |||
| AV | 333 | Net1 Priority Stabilization Time | Write | |||
| AV | 334 | Net1 Priority Drop Delay Time | Write | |||
| AI | 335 | Net1 Priority Max Sys Rate | Read | |||
| AI | 336 | Net1 Priority Min Boilers | Read | |||
| AV | 337 | Net1 Priority Max On Time | Write | |||
| AV | 338 | Rotation Frequency | Write | |||
| AI | 339 | Boiler Order 1 | Read | |||
| AI | 340 | Boiler Order 2 | Read | |||
| AI | 341 | Boiler Order 3 | Read | |||
| AI | 342 | Boiler Order 4 | Read | |||
| AI | 343 | Boiler Order 5 | Read | |||
| AI | 344 | Boiler Order 6 | Read | |||
| AI | 345 | Boiler Order 7 | Read | |||
| AI | 346 | Boiler Order 8 | Read | |||
| AV | 347 | Net2 Priority System Type | Write | |||
| AI | 348 | Net2 Priority target Mod Sensor | Read | |||
| AV | 349 | Net2 Priority target Adjust | Write | |||
| AV | 350 | Net2 Priority supply Max | Write | |||
| AV | 351 | Net2 Priority supply Min | Write | |||
| AV | 352 | Net2 Priority Outdoor Reset Max | Write | |||
| AV | 353 | Net2 Priority Outdoor Reset Min | Write | |||
| AV | 354 | Net2 Priority Volts Max | Write | |||
| AV | 355 | Net2 Priority Volts Min | Write | |||
| AV | 356 | Net2 Priority Boost Time | Write | |||
| AV | 357 | Net2 Priority System Off Differential | Write | |||
| AV | 358 | Net2 Priority System On Differential | Write | |||
| AV | 359 | Net2 Priority System Add Boiler Differential | Write | |||
| AV | 360 | Net2 Prioirty System Drop Boiler Diff | Write | |||
| AV | 361 | Net2 Priority Mod Delay Time | Write | |||
| AV | 362 | Net2 Priority Stabilization Time | Write | |||
| AV | 363 | Net2 Priority Drop Delay Time | Write | |||
| AV | 364 | Net2 Priority Max Boiler Temp | Write | |||
| AV | 365 | Net2 Priority Boiler On Diff | Write | |||
| AV | 366 | Net2 Priority Boiler Off Diff | Write | |||
| AI | 367 | Net2 Priority Max On Time | Read | |||
| AV | 368 | Net2 Priority Min On Time | Write | |||
| AI | 369 | Net2 Priority Run Boiler Pump | Read | |||
| AI | 370 | Net2 Prioirity Run Sys Pump Aux Type | Read | |||
| AV | 371 | Net2 Priority Pre Pump Time | Write | |||
| AV | 372 | Net2 Priority Post Pump Time | Write | |||
| AV | 373 | Net2 Priority Max Rate | Write | |||
| AV | 374 | Net2 Priority Min Rate | Write | |||
| AV | 375 | Net2 Priority Max Sys Rate | Write | |||
| AI | 376 | Net2 Priority Min Boilers | Read | |||
| AV | 377 | Net2 Priority Activate Contact Setting | Write | |||
| AV | 378 | Net2 Priority Response Time | Write | |||
| AI | 379 | Custom Type String 1 | Read | |||
| AI | 380 | Custom Type String 2 | Read | |||
| AI | 381 | Custom Type String 3 | Read | |||
| AI | 382 | Custom Type String 4 | Read | |||
| AI | 383 | Custom Type String 5 | Read | |||
| AI | 384 | Custom Type String 6 | Read | |||
| AI | 385 | Custom Type String 7 | Read | |||
| AI | 386 | Custom Type String 8 | Read | |||
| AI | 387 | Custom Type String 9 | Read | |||
| AI | 388 | Custom Type String 10 | Read | |||
| AI | 389 | Custom Type String 11 | Read | |||
| AI | 390 | Custom Type String 12 | Read | |||
| AI | 391 | Custom Type String 13 | Read | |||
| AI | 392 | Master Boiler Commanded Pump Running Bits 1 | Read | |||
| AI | 393 | Master Boiler Commanded Pump Running Bits 2 | Read | |||
| AI | 394 | Master Boiler Commanded Pump Running Bits 3 | Read | |||
| AI | 395 | Master Boiler Commanded Pump Running Bits 4 | Read | |||
| AI | 396 | Master Boiler Commanded Pump Running Bits 5 | Read | |||
| AI | 397 | Master Boiler Commanded Pump Running Bits 6 | Read | |||
| AI | 398 | Master Boiler Commanded Pump Running Bits 7 | Read | |||
| AI | 399 | Master Boiler Commanded Modulation Rates 1 | Read | |||
| AI | 400 | Master Boiler Commanded Modulation Rates 2 | Read | |||
| AI | 401 | Master Boiler Commanded Modulation Rates 3 | Read | |||
| AI | 402 | Master Boiler Commanded Modulation Rates 4 | Read | |||
| AI | 403 | Master Boiler Commanded Modulation Rates 5 | Read | |||
| AI | 404 | Master Boiler Commanded Modulation Rates 6 | Read | |||
| AI | 405 | Master Boiler Commanded Modulation Rates 7 | Read | |||
| AI | 406 | Master Boiler Net1 or Net2 | Read | |||
| AI | 407 | Master Boiler Max Boiler Temp | Read | |||
| AI | 408 | Master Boiler Boiler On Diff | Read | |||
| AI | 409 | Master Boiler Boiler Off Diff | Read | |||
| AI | 410 | Master Boiler Pre Pump Time | Read | |||
| AI | 411 | Master Boiler Post Pump Time | Read | |||
| AI | 412 | Master Boiler Number of Boilers on Network | Read | |||
| MI | 413 | Master Boiler Supply Temp | Read | |||
| MI | 414 | Master Boiler Return Temp | Read | |||
| AI | 415 | Master Boiler Outdoor Temp | Read | |||
| AI | 416 | Master Boiler System Types | Read | |||
| AI | 417 | Shadow 2 Input 1 Priority | Read | |||
| AI | 418 | Shadow 2 Input 1 System Type | Read | |||
| AI | 419 | Shadow 2 Input 2 Priority | Read | |||
| AI | 420 | Shadow 2 Input 2 System Type | Read | |||
| AI | 421 | Shadow 2 Input 3 Priority | Read | |||
| AI | 422 | Shadow 2 Input 3 System Type | Read | |||
| AI | 423 | Shadow 2 Input Status | Read | |||
| MI | 424 | Shadow 2 Boiler Status | Read | |||
| AI | 425 | Shadow 2 Supply Temp (local) | Read | |||
| AI | 426 | Shadow 2 Return Temp (local) | Read | |||
| AI | 427 | Shadow 2 Outdoor Temp (local) | Read | |||
| AI | 428 | Shadow 2 Boiler 1 Out Temp | Read | |||
| AI | 429 | Shadow 2 Relay Output Status | Read | |||
| AI | 430 | Shadow 2 Model Number | Read | |||
| AI | 431 | Shadow 2 Burner Hours | Read | |||
| AI | 432 | Shadow 2 Min Rate | Read | |||
| AI | 433 | Shadow 2 Max Rate | Read | |||
| AI | 434 | Shadow 2 Modulation Rate | Read | |||
| AI | 435 | Shadow 2 Boiler Status 3 and Available Status | Read | |||
| AI | 436 | Shadow 3 Input 1 Priority | Read | |||
| AI | 437 | Shadow 3 Input 1 System Type | Read | |||
| AI | 438 | Shadow 3 Input 2 Priority | Read | |||
| AI | 439 | Shadow 3 Input 2 System Type | Read | |||
| AI | 440 | Shadow 3 Input 3 Priority | Read | |||
| AI | 441 | Shadow 3 Input 3 System Type | Read | |||
| AI | 442 | Shadow 3 Input Status | Read | |||
| MI | 443 | Shadow 3 Boiler Status | Read | |||
| AI | 444 | Shadow 3 Supply Temp (local) | Read | |||
| AI | 445 | Shadow 3 Return Temp (local) | Read | |||
| AI | 446 | Shadow 3 Outdoor Temp (local) | Read | |||
| AI | 447 | Shadow 3 Boiler 1 Out Temp | Read | |||
| AI | 448 | Shadow 3 Relay Output Status | Read | |||
| AI | 449 | Shadow 3 Model Number | Read | |||
| AI | 450 | Shadow 3 Burner Hours | Read | |||
| AI | 451 | Shadow 3 Min Rate | Read | |||
| AI | 452 | Shadow 3 Max Rate | Read | |||
| AI | 453 | Shadow 3 Modulation Rate | Read | |||
| AI | 454 | Shadow 3 Boiler Status 3 and Available Status | Read | |||
| AI | 455 | Shadow 4 Input 1 Priority | Read | |||
| AI | 456 | Shadow 4 Input 1 System Type | Read | |||
| AI | 457 | Shadow 4 Input 2 Priority | Read | |||
| AI | 458 | Shadow 4 Input 2 System Type | Read | |||
| AI | 459 | Shadow 4 Input 3 Priority | Read | |||
| AI | 460 | Shadow 4 Input 3 System Type | Read | |||
| AI | 461 | Shadow 4 Input Status | Read | |||
| MI | 462 | Shadow 4 Boiler Status | Read | |||
| AI | 463 | Shadow 4 Supply Temp (local) | Read | |||
| AI | 464 | Shadow 4 Return Temp (local) | Read | |||
| AI | 465 | Shadow 4 Outdoor Temp (local) | Read | |||
| AI | 466 | Shadow 4 Boiler 1 Out Temp | Read | |||
| AI | 467 | Shadow 4 Relay Output Status | Read | |||
| AI | 468 | Shadow 4 Model Number | Read | |||
| AI | 469 | Shadow 4 Burner Hours | Read | |||
| AI | 470 | Shadow 4 Min Rate | Read | |||
| AI | 471 | Shadow 4 Max Rate | Read | |||
| AI | 472 | Shadow 4 Modulation Rate | Read | |||
| AI | 473 | Shadow 4 Boiler Status 3 and Available Status | Read | |||
| AI | 474 | Shadow 5 Input 1 Priority | Read | |||
| AI | 475 | Shadow 5 Input 1 System Type | Read | |||
| AI | 476 | Shadow 5 Input 2 Priority | Read | |||
| AI | 477 | Shadow 5 Input 2 System Type | Read | |||
| AI | 478 | Shadow 5 Input 3 Priority | Read | |||
| AI | 479 | Shadow 5 Input 3 System Type | Read | |||
| AI | 480 | Shadow 5 Input Status | Read | |||
| MI | 481 | Shadow 5 Boiler Status | Read | |||
| AI | 482 | Shadow 5 Supply Temp (local) | Read | |||
| AI | 483 | Shadow 5 Return Temp (local) | Read | |||
| AI | 484 | Shadow 5 Outdoor Temp (local) | Read | |||
| AI | 485 | Shadow 5 Boiler 1 Out Temp | Read | |||
| AI | 486 | Shadow 5 Relay Output Status | Read | |||
| AI | 487 | Shadow 5 Model Number | Read | |||
| AI | 488 | Shadow 5 Burner Hours | Read | |||
| AI | 489 | Shadow 5 Min Rate | Read | |||
| AI | 490 | Shadow 5 Max Rate | Read | |||
| AI | 491 | Shadow 5 Modulation Rate | Read | |||
| AI | 492 | Shadow 5 Boiler Status 3 and Available Status | Read | |||
| AI | 493 | Shadow 6 Input 1 Priority | Read | |||
| AI | 494 | Shadow 6 Input 1 System Type | Read | |||
| AI | 495 | Shadow 6 Input 2 Priority | Read | |||
| AI | 496 | Shadow 6 Input 2 System Type | Read | |||
| AI | 497 | Shadow 6 Input 3 Priority | Read | |||
| AI | 498 | Shadow 6 Input 3 System Type | Read | |||
| AI | 499 | Shadow 6 Input Status | Read | |||
| MI | 500 | Shadow 6 Boiler Status | Read | |||
| AI | 501 | Shadow 6 Supply Temp (local) | Read | |||
| AI | 502 | Shadow 6 Return Temp (local) | Read | |||
| AI | 503 | Shadow 6 Outdoor Temp (local) | Read | |||
| AI | 504 | Shadow 6 Boiler 1 Out Temp | Read | |||
| AI | 505 | Shadow 6 Relay Output Status | Read | |||
| AI | 506 | Shadow 6 Model Number | Read | |||
| AI | 507 | Shadow 6 Burner Hours | Read | |||
| AI | 508 | Shadow 6 Min Rate | Read | |||
| AI | 509 | Shadow 6 Max Rate | Read | |||
| AI | 510 | Shadow 6 Modulation Rate | Read | |||
| AI | 511 | Shadow 6 Boiler Status 3 and Available Status | Read | |||
| AI | 512 | Shadow 7 Input 1 Priority | Read | |||
| AI | 513 | Shadow 7 Input 1 System Type | Read | |||
| AI | 514 | Shadow 7 Input 2 Priority | Read | |||
| AI | 515 | Shadow 7 Input 2 System Type | Read | |||
| AI | 516 | Shadow 7 Input 3 Priority | Read | |||
| AI | 517 | Shadow 7 Input 3 System Type | Read | |||
| AI | 518 | Shadow 7 Input Status | Read | |||
| MI | 519 | Shadow 7 Boiler Status | Read | |||
| AI | 520 | Shadow 7 Supply Temp (local) | Read | |||
| AI | 521 | Shadow 7 Return Temp (local) | Read | |||
| AI | 522 | Shadow 7 Outdoor Temp (local) | Read | |||
| AI | 523 | Shadow 7 Boiler 1 Out Temp | Read | |||
| AI | 524 | Shadow 7 Relay Output Status | Read | |||
| AI | 525 | Shadow 7 Model Number | Read | |||
| AI | 526 | Shadow 7 Burner Hours | Read | |||
| AI | 527 | Shadow 7 Min Rate | Read | |||
| AI | 528 | Shadow 7 Max Rate | Read | |||
| AI | 529 | Shadow 7 Modulation Rate | Read | |||
| AI | 530 | Shadow 7 Boiler Status 3 and Available Status | Read | |||
| AI | 531 | Shadow 8 Input 1 Priority | Read | |||
| AI | 532 | Shadow 8 Input 1 System Type | Read | |||
| AI | 533 | Shadow 8 Input 2 Priority | Read | |||
| AI | 534 | Shadow 8 Input 2 System Type | Read | |||
| AI | 535 | Shadow 8 Input 3 Priority | Read | |||
| AI | 536 | Shadow 8 Input 3 System Type | Read | |||
| AI | 537 | Shadow 8 Input Status | Read | |||
| MI | 538 | Shadow 8 Boiler Status | Read | |||
| AI | 539 | Shadow 8 Supply Temp (local) | Read | |||
| AI | 540 | Shadow 8 Return Temp (local) | Read | |||
| AI | 541 | Shadow 8 Outdoor Temp (local) | Read | |||
| AI | 542 | Shadow 8 Boiler 1 Out Temp | Read | |||
| AI | 543 | Shadow 8 Relay Output Status | Read | |||
| AI | 544 | Shadow 8 Model Number | Read | |||
| AI | 545 | Shadow 8 Burner Hours | Read | |||
| AI | 546 | Shadow 8 Min Rate | Read | |||
| AI | 547 | Shadow 8 Max Rate | Read | |||
| AI | 548 | Shadow 8 Modulation Rate | Read | |||
| AI | 549 | Shadow 8 Boiler Status 3 and Available Status | Read | |||
| AI | 550 | Custom Type String 2 1 | Read | |||
| AI | 551 | Custom Type String 2 2 | Read | |||
| AI | 552 | Custom Type String 2 3 | Read | |||
| AI | 553 | Custom Type String 2 4 | Read | |||
| AI | 554 | Custom Type String 2 5 | Read | |||
| AI | 555 | Custom Type String 2 6 | Read | |||
| AI | 556 | Custom Type String 2 7 | Read | |||
| AI | 557 | Custom Type String 2 8 | Read | |||
| AI | 558 | Custom Type String 2 9 | Read | |||
| AI | 559 | Custom Type String 2 10 | Read | |||
| AI | 560 | Custom Type String 2 11 | Read | |||
| AI | 561 | Custom Type String 2 12 | Read | |||
| AI | 562 | Custom Type String 2 13 | Read | |||
| AI | 563 | Custom Type String 3 1 | Read | |||
| AI | 564 | Custom Type String 3 2 | Read | |||
| AI | 565 | Custom Type String 3 3 | Read | |||
| AI | 566 | Custom Type String 3 4 | Read | |||
| AI | 567 | Custom Type String 3 5 | Read | |||
| AI | 568 | Custom Type String 3 6 | Read | |||
| AI | 569 | Custom Type String 3 7 | Read | |||
| AI | 570 | Custom Type String 3 8 | Read | |||
| AI | 571 | Custom Type String 3 9 | Read | |||
| AI | 572 | Custom Type String 3 10 | Read | |||
| AI | 573 | Custom Type String 3 11 | Read | |||
| AI | 574 | Custom Type String 3 12 | Read | |||
| AI | 575 | Custom Type String 3 13 | Read | |||
| AI | 576 | Custom Type String 4 1 | Read | |||
| AI | 577 | Custom Type String 4 2 | Read | |||
| AI | 578 | Custom Type String 4 3 | Read | |||
| AI | 579 | Custom Type String 4 4 | Read | |||
| AI | 580 | Custom Type String 4 5 | Read | |||
| AI | 581 | Custom Type String 4 6 | Read | |||
| AI | 582 | Custom Type String 4 7 | Read | |||
| AI | 583 | Custom Type String 4 8 | Read | |||
| AI | 584 | Custom Type String 4 9 | Read | |||
| AI | 585 | Custom Type String 4 10 | Read | |||
| AI | 586 | Custom Type String 4 11 | Read | |||
| AI | 587 | Custom Type String 4 12 | Read | |||
| AI | 588 | Custom Type String 4 13 | Read | |||
| AV | 589 | Net Priority 1 Add Boiler Delay | Write | |||
| AV | 590 | Net Priority 2 Add Boiler Delay | Write | |||
| AI | 591 | P of the PI | Read | |||
| AI | 592 | I of the PI | Read | |||
| AI | 593 | PI Output t-1 | Read | |||
| BImin | 594 | Relay Output Gas Valve ON | Gas valve relay output on | Read | ||
| BI | 595 | Relay Output Circulator 1 ON | On/off value | Read | ||
| BI | 596 | Relay Output Circulator 2 ON | On/off value | Read | ||
| BI | 597 | Relay Output Circulator 3 ON | On/off value | Read | ||
| BI | 598 | Relay Output Additional Heat Demand ON | On/off value | Read | ||
| BI | 599 | Relay Output Boiler Circulator ON | On/off value | Read | ||
| BI | 600 | Boiler Status 2 Flue Temperature Warning | On/off value | Read | ||
| BI | 601 | Boiler Status 2 Modulation Sensor | On/off value | Read | ||
| BI | 602 | Boiler Status 2 Freeze Protection | On/off value | Read | ||
| BI | 603 | Boiler Status 2 Warm Weather Shutdown | On/off value | Read | ||
| BI | 604 | Exercise Circulator 1 ON | On/off value | Read | ||
| BI | 605 | Exercise Circulator 2 ON | On/off value | Read | ||
| BI | 606 | Exercise Circulator 3 ON | On/off value | Read | ||
| BI | 607 | Exercise Boiler Circulator ON | On/off value | Read | ||
| BI | 608 | Freeze Protect Circulator 1 ON | On/off value | Read | ||
| BI | 609 | Freeze Protect Circulator 2 ON | On/off value | Read | ||
| BI | 610 | Freeze Protect Circulator 3 ON | On/off value | Read | ||
| BI | 611 | Freeze Protect Boiler Circulator ON | On/off value | Read | ||
| AI | 612 | Priority 1 System Type | Read | |||
| AI | 613 | Priority 1 Target Adjustment | Read | |||
| BI | 614 | Priority 1 Run Aux Pump/Output setting | On/off value | Read | ||
| BI | 615 | Priority 1 Run Boiler Pump setting | On/off value | Read | ||
| AI | 616 | Input 1 Priority Boiler | Read | |||
| AI | 617 | Input 1 Aux Pump/Output Type | Read | |||
| BI | 618 | Input 1 Source is set to 0-10V | On/off value | Read | ||
| AI | 619 | Priority 2 System Type | Read | |||
| AI | 620 | Priority 2 Target Adjustment | Read | |||
| BI | 621 | Priority 2 Run Aux Pump/Output setting | On/off value | Read | ||
| BI | 622 | Priority 2 Run Boiler Pump setting | On/off value | Read | ||
| AI | 623 | Priority 3 System Type | Read | |||
| AI | 624 | Priority 3 Target Adjustment | Read | |||
| BI | 625 | Priority 3 Run Aux Pump/Output setting | On/off value | Read | ||
| BI | 626 | Priority 3 Run Boiler Pump setting | On/off value | Read | ||
| BI | 627 | Target was Reduced Flue Temp | On/off value | Read | ||
| BI | 628 | Target was Reduced Boiler In Out | On/off value | Read | ||
| BI | 629 | Modulation was Reduced | On/off value | Read | ||
| BI | 630 | Turn on Additional Heat Contact | On/off value | Read | ||
| BI | 631 | Run Circulator 1 | On/off value | Read | ||
| BI | 632 | Run Circulator 2 | On/off value | Read | ||
| BI | 633 | Run Circulator 3 | On/off value | Read | ||
| BI | 634 | Run Boiler Pump | On/off value | Read | ||
| AI | 635 | P1 activate Contact Setting | Read | |||
| BI | 636 | P1 target ModSensor | On/off value | Read | ||
| BI | 637 | P1 Add Heat Temp Dep | On/off value | Read | ||
| AI | 638 | P1 Add Heat Below SP | Read | |||
| AI | 639 | P2 activate Contact Setting | Read | |||
| BI | 640 | P2 target ModSensor | On/off value | Read | ||
| BI | 641 | P2 Add Heat Temp Dep | On/off value | Read | ||
| AI | 642 | P2 Add Heat Below SP | Read | |||
| AI | 643 | P3 activate Contact Setting | Read | |||
| BI | 644 | P3 target ModSensor | On/off value | Read | ||
| BI | 645 | P3 Add Heat Temp Dep | On/off value | Read | ||
| AI | 646 | P3 Add Heat Below SP | Read | |||
| AI | 647 | Input 2 Priority Boiler | Read | |||
| AI | 648 | Input 2 Aux Pump/Output Type | Read | |||
| BI | 649 | Input 2 Source is set to 0-20V | On/off value | Read | ||
| AI | 650 | Input 3 Priority Boiler | Read | |||
| AI | 651 | Input 3 Aux Pump/Output Type | Read | |||
| BI | 652 | Input 3 Source is set to 0-30V | On/off value | Read | ||
| AI | 653 | Boiler Status | Read | |||
| BI | 654 | Running DHW | On/off value | Read | ||
| BI | 655 | Local Priority 1 Running | On/off value | Read | ||
| BI | 656 | Local Priority 2 Running | On/off value | Read | ||
| BI | 657 | Local Priority 2 Running | On/off value | Read | ||
| BI | 658 | Input 1 active | On/off value | Read | ||
| BI | 659 | Input 2 active | On/off value | Read | ||
| BI | 660 | Input 3 active | On/off value | Read | ||
| BI | 661 | Manual Limit Open | On/off value | Read | ||
| BI | 662 | Auto Limit Open | On/off value | Read | ||
| BI | 663 | Low Water Cutoff Open | On/off value | Read | ||
| BI | 664 | Air P-Switch Open | On/off value | Read | ||
| BI | 665 | Flow Switch Open | On/off value | Read | ||
| BI | 666 | Supply Sensor Error | On/off value | Read | ||
| BI | 667 | Return Sensor Error | On/off value | Read | ||
| BI | 668 | Outdoor Temperature Sensor Error | On/off value | Read | ||
| BI | 669 | Gas Valve Fault 1 | On/off value | Read | ||
| BI | 670 | Gas Valve Fault 2 | On/off value | Read | ||
| BI | 671 | Gas Valve Fault 3 | On/off value | Read | ||
| BI | 672 | Gas Valve Fault 4 | On/off value | Read | ||
| BI | 673 | LKHS1 Hard Flame Fault | On/off value | Read | ||
| BI | 674 | LKHS1 Hard Ignition Fault | On/off value | Read | ||
| BI | 675 | LKHS1 Hard High Temp Limit | On/off value | Read | ||
| BI | 676 | LKHS1 Hard Blower Fault | On/off value | Read | ||
| BI | 677 | LKHS1 Hard Expansion Board Fault Hw Fault | On/off value | Read | ||
| BI | 678 | LKHS1 Hard Air Pressure Switch Fault | On/off value | Read | ||
| BI | 679 | LKHS1 Hard Gas Valve Fault see Sensor Warnings | On/off value | Read | ||
| BI | 680 | LKHS1 Hard Low Water Cutoff | On/off value | Read | ||
| BI | 681 | LKHS1 Hard Limit Open | On/off value | Read | ||
| BI | 682 | LKHS1 Hard Flow Switch Fault Sys Temp High Fault | On/off value | Read | ||
| BI | 683 | LKHS1 Hard Return Water Temp High | On/off value | Read | ||
| BI | 684 | LKHS1 Hard Return above Supply Temp | On/off value | Read | ||
| BI | 685 | LKHS1 Hard Temp Rise Too Quickly | On/off value | Read | ||
| BI | 686 | LKHS1 Hard Supply 58F above Return | On/off value | Read | ||
| BI | 687 | LKHS1 Hard Temperature Sensor | On/off value | Read | ||
| BI | 688 | LKHS1 Hard Flue Temp Too High | On/off value | Read | ||
| BI | 689 | LKHS1 Soft Flame Fault | On/off value | Read | ||
| BI | 690 | LKHS1 Soft Ignition Fault | On/off value | Read | ||
| BI | 691 | LKHS1 Soft High Temp Limit | On/off value | Read | ||
| BI | 692 | LKHS1 Soft Blower Fault | On/off value | Read | ||
| BI | 693 | LKHS1 Soft Expansion Board Fault Hw Fault | On/off value | Read | ||
| BI | 694 | LKHS1 Soft Air Pressure Switch Fault | On/off value | Read | ||
| BI | 695 | LKHS1 Soft Gas Valve Fault see Sensor Warnings | On/off value | Read | ||
| BI | 696 | LKHS1 Soft Low Water Cutoff | On/off value | Read | ||
| BI | 697 | LKHS1 Soft Limit Open | On/off value | Read | ||
| BI | 698 | LKHS1 Soft Flow Switch Fault Sys Temp High Fault | On/off value | Read | ||
| BI | 699 | LKHS1 Soft Return Water Temp High | On/off value | Read | ||
| BI | 700 | LKHS1 Soft Return above Supply Temp | On/off value | Read | ||
| BI | 701 | LKHS1 Soft Temp Rise Too Quickly | On/off value | Read | ||
| BI | 702 | LKHS1 Soft Supply 58F above Return | On/off value | Read | ||
| BI | 703 | LKHS1 Soft Temperature Sensor | On/off value | Read | ||
| BI | 704 | LKHS1 Soft Flue Temp Too High | On/off value | Read | ||
| BI | 705 | LKHS1 In Input 1 active | On/off value | Read | ||
| BI | 706 | LKHS1 In Input 2 active | On/off value | Read | ||
| BI | 707 | LKHS1 In Input 3 active | On/off value | Read | ||
| BI | 708 | LKHS1 In Manual Limit Open | On/off value | Read | ||
| BI | 709 | LKHS1 In Auto Limit Open | On/off value | Read | ||
| BI | 710 | LKHS1 In Low Water Cutoff Open | On/off value | Read | ||
| BI | 711 | LKHS1 In Air P-Switch Open | On/off value | Read | ||
| BI | 712 | LKHS1 In Flow Switch Open | On/off value | Read | ||
| BI | 713 | LKHS1 RO Gas Valve ON | On/off value | Read | ||
| BI | 714 | LKHS1 RO Circulator 1 ON | On/off value | Read | ||
| BI | 715 | LKHS1 RO Circulator 2 ON | On/off value | Read | ||
| BI | 716 | LKHS1 RO Circulator 3 ON | On/off value | Read | ||
| BI | 717 | LKHS1 RO Additional Heat Demand ON | On/off value | Read | ||
| BI | 718 | LKHS1 RO Boiler Circulator ON | On/off value | Read | ||
| BI | 719 | LKHS2 Hard Limit Open | On/off value | Read | ||
| BI | 720 | LKHS2 Hard Flow Switch Fault | On/off value | Read | ||
| BI | 721 | LKHS2 Hard Return Water Temp High | On/off value | Read | ||
| BI | 722 | LKHS2 Hard Return > Supply Temp | On/off value | Read | ||
| BI | 723 | LKHS2 Hard Temp Rise Too Quickly | On/off value | Read | ||
| BI | 724 | LKHS2 Hard Supply 58F > Return | On/off value | Read | ||
| BI | 725 | LKHS2 Hard Temperature Sensor | On/off value | Read | ||
| BI | 726 | LKHS2 Hard Flue Temp Too High | On/off value | Read | ||
| BI | 727 | LKHS2 Hard Flame Fault | On/off value | Read | ||
| BI | 728 | LKHS2 Hard Ignition Fault | On/off value | Read | ||
| BI | 729 | LKHS2 Hard High Temp Limit | On/off value | Read | ||
| BI | 730 | LKHS2 Hard Blower Fault | On/off value | Read | ||
| BI | 731 | LKHS2 Hard Expansion Board Fault | On/off value | Read | ||
| BI | 732 | LKHS2 Hard Air Pressure Switch Fault | On/off value | Read | ||
| BI | 733 | LKHS2 Hard Gas Valve Fault | On/off value | Read | ||
| BI | 734 | LKHS2 Hard Low Water Cutoff | On/off value | Read | ||
| BI | 735 | LKHS2 Soft Limit Open | On/off value | Read | ||
| BI | 736 | LKHS2 Soft Flow Switch Fault | On/off value | Read | ||
| BI | 737 | LKHS2 Soft Return Water Temp High | On/off value | Read | ||
| BI | 738 | LKHS2 Soft Return > Supply Temp | On/off value | Read | ||
| BI | 739 | LKHS2 Soft Temp Rise Too Quickly | On/off value | Read | ||
| BI | 740 | LKHS2 Soft Supply 58F > Return | On/off value | Read | ||
| BI | 741 | LKHS2 Soft Temperature Sensor | On/off value | Read | ||
| BI | 742 | LKHS2 Soft Flue Temp Too High | On/off value | Read | ||
| BI | 743 | LKHS2 Soft Flame Fault | On/off value | Read | ||
| BI | 744 | LKHS2 Soft Ignition Fault | On/off value | Read | ||
| BI | 745 | LKHS2 Soft High Temp Limit | On/off value | Read | ||
| BI | 746 | LKHS2 Soft Blower Fault | On/off value | Read | ||
| BI | 747 | LKHS2 Soft Expansion Board Fault | On/off value | Read | ||
| BI | 748 | LKHS2 Soft Air Pressure Switch Fault | On/off value | Read | ||
| BI | 749 | LKHS2 Soft Gas Valve Fault | On/off value | Read | ||
| BI | 750 | LKHS2 Soft Low Water Cutoff | On/off value | Read | ||
| BI | 751 | LKHS2 In Input 1 active | On/off value | Read | ||
| BI | 752 | LKHS2 In Input 2 active | On/off value | Read | ||
| BI | 753 | LKHS2 In Input 3 active | On/off value | Read | ||
| BI | 754 | LKHS2 In Manual Limit Open | On/off value | Read | ||
| BI | 755 | LKHS2 In Auto Limit Open | On/off value | Read | ||
| BI | 756 | LKHS2 In Low Water Cutoff Open | On/off value | Read | ||
| BI | 757 | LKHS2 In Air P-Switch Open | On/off value | Read | ||
| BI | 758 | LKHS2 In Flow Switch Open | On/off value | Read | ||
| BI | 759 | LKHS2 RO Gas Valve ON | On/off value | Read | ||
| BI | 760 | LKHS2 RO Circulator 1 ON | On/off value | Read | ||
| BI | 761 | LKHS2 RO Circulator 2 ON | On/off value | Read | ||
| BI | 762 | LKHS2 RO Circulator 3 ON | On/off value | Read | ||
| BI | 763 | LKHS2 RO Additional Heat Demand ON | On/off value | Read | ||
| BI | 764 | LKHS2 RO Boiler Circulator ON | On/off value | Read | ||
| BI | 765 | LKHS3 Hard Limit Open | On/off value | Read | ||
| BI | 766 | LKHS3 Hard Flow Switch Fault | On/off value | Read | ||
| BI | 767 | LKHS3 Hard Return Water Temp High | On/off value | Read | ||
| BI | 768 | LKHS3 Hard Return > Supply Temp | On/off value | Read | ||
| BI | 769 | LKHS3 Hard Temp Rise Too Quickly | On/off value | Read | ||
| BI | 770 | LKHS3 Hard Supply 58F > Return | On/off value | Read | ||
| BI | 771 | LKHS3 Hard Temperature Sensor | On/off value | Read | ||
| BI | 772 | LKHS3 Hard Flue Temp Too High | On/off value | Read | ||
| BI | 773 | LKHS3 Hard Flame Fault | On/off value | Read | ||
| BI | 774 | LKHS3 Hard Ignition Fault | On/off value | Read | ||
| BI | 775 | LKHS3 Hard High Temp Limit | On/off value | Read | ||
| BI | 776 | LKHS3 Hard Blower Fault | On/off value | Read | ||
| BI | 777 | LKHS3 Hard Expansion Board Fault | On/off value | Read | ||
| BI | 778 | LKHS3 Hard Air Pressure Switch Fault | On/off value | Read | ||
| BI | 779 | LKHS3 Hard Gas Valve Fault | On/off value | Read | ||
| BI | 780 | LKHS3 Hard Low Water Cutoff | On/off value | Read | ||
| BI | 781 | LKHS3 Soft Limit Open | On/off value | Read | ||
| BI | 782 | LKHS3 Soft Flow Switch Fault | On/off value | Read | ||
| BI | 783 | LKHS3 Soft Return Water Temp High | On/off value | Read | ||
| BI | 784 | LKHS3 Soft Return > Supply Temp | On/off value | Read | ||
| BI | 785 | LKHS3 Soft Temp Rise Too Quickly | On/off value | Read | ||
| BI | 786 | LKHS3 Soft Supply 58F > Return | On/off value | Read | ||
| BI | 787 | LKHS3 Soft Temperature Sensor | On/off value | Read | ||
| BI | 788 | LKHS3 Soft Flue Temp Too High | On/off value | Read | ||
| BI | 789 | LKHS3 Soft Flame Fault | On/off value | Read | ||
| BI | 790 | LKHS3 Soft Ignition Fault | On/off value | Read | ||
| BI | 791 | LKHS3 Soft High Temp Limit | On/off value | Read | ||
| BI | 792 | LKHS3 Soft Blower Fault | On/off value | Read | ||
| BI | 793 | LKHS3 Soft Expansion Board Fault | On/off value | Read | ||
| BI | 794 | LKHS3 Soft Air Pressure Switch Fault | On/off value | Read | ||
| BI | 795 | LKHS3 Soft Gas Valve Fault | On/off value | Read | ||
| BI | 796 | LKHS3 Soft Low Water Cutoff | On/off value | Read | ||
| BI | 797 | LKHS3 In Input 1 active | On/off value | Read | ||
| BI | 798 | LKHS3 In Input 2 active | On/off value | Read | ||
| BI | 799 | LKHS3 In Input 3 active | On/off value | Read | ||
| BI | 800 | LKHS3 In Manual Limit Open | On/off value | Read | ||
| BI | 801 | LKHS3 In Auto Limit Open | On/off value | Read | ||
| BI | 802 | LKHS3 In Low Water Cutoff Open | On/off value | Read | ||
| BI | 803 | LKHS3 In Air P-Switch Open | On/off value | Read | ||
| BI | 804 | LKHS3 In Flow Switch Open | On/off value | Read | ||
| BI | 805 | LKHS3 RO Gas Valve ON | On/off value | Read | ||
| BI | 806 | LKHS3 RO Circulator 1 ON | On/off value | Read | ||
| BI | 807 | LKHS3 RO Circulator 2 ON | On/off value | Read | ||
| BI | 808 | LKHS3 RO Circulator 3 ON | On/off value | Read | ||
| BI | 809 | LKHS3 RO Additional Heat Demand ON | On/off value | Read | ||
| BI | 810 | LKHS3 RO Boiler Circulator ON | On/off value | Read | ||
| BI | 811 | LKHS1 Flue Temperature Warning | On/off value | Read | ||
| BI | 812 | LKHS1 Modulation Sensor | On/off value | Read | ||
| BI | 813 | LKHS1 Freeze Protection | On/off value | Read | ||
| BI | 814 | LKHS1 Warm Weather Shutdown | On/off value | Read | ||
| BI | 815 | LKHS2 Flue Temperature Warning | On/off value | Read | ||
| BI | 816 | LKHS2 Modulation Sensor | On/off value | Read | ||
| BI | 817 | LKHS2 Freeze Protection | On/off value | Read | ||
| BI | 818 | LKHS2 Warm Weather Shutdown | On/off value | Read | ||
| BI | 819 | LKHS3 Flue Temperature Warning | On/off value | Read | ||
| BI | 820 | LKHS3 Modulation Sensor | On/off value | Read | ||
| BI | 821 | LKHS3 Freeze Protection | On/off value | Read | ||
| BI | 822 | LKHS3 Warm Weather Shutdown | On/off value | Read | ||
| AI | 823 | Shad2 In1 Priority Boiler | Read | |||
| AI | 824 | Shad2 In1 Aux Pump/Output Type | Read | |||
| BI | 825 | Shad2 In1 Source is set to 0-10V | On/off value | Read | ||
| AI | 826 | Shad2 In2 Priority Boiler | Read | |||
| AI | 827 | Shad2 In2 Aux Pump/Output Type | Read | |||
| BI | 828 | Shad2 In2 Source is set to 0-10V | On/off value | Read | ||
| AI | 829 | Shad2 In3 Priority Boiler | Read | |||
| AI | 830 | Shad2 In3 Aux Pump/Output Type | Read | |||
| BI | 831 | Shad2 In3 Source is set to 0-10V | On/off value | Read |
No points match these filters.
Integration notes
- This supplement only lists the objects; device instance, MAC address and baud rate are set on the ProtoNode as described in its start-up guide, which is a separate document.
- The same object list is served over BACnet IP or BACnet MS/TP, depending on how the ProtoNode is set up.
- No units or state texts are given. The LonWorks types in the source show which values are temperatures, percentages or hours.
- The supplement has no read/write column. The 111 AVs map to LonWorks input variables, so they are marked writable; every other object is read-only.
- Object IDs run in one sequence (1-831) across AI, AV, BI and MI; each ID is used by one object type only.
- Shadow 2-8 blocks repeat the status of the other boilers in a cascade.
- SlimFit 1000-2000 Series 1 (SOLA) boilers use a different object list.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode
How many BACnet points does the Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode have?
This list has 831 BACnet objects: 487 analog inputs, 111 analog values, 214 binary inputs, 19 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode BACnet points are writable?
111 of the 831 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode BACnet documentation?
The source is ProtoNode FPC-N34 and ProtoNode FPC-N35 Complete Point List Supplement (Weil-McLain) (T17022), revision Document Revision 7.D, January 2019, published free by Weil-McLain at https://www.weil-mclain.com/wp-content/uploads/ProtoNode-Complete-Point-List-Supplement-JAN19_1.pdf.
What are the minimum BACnet points to integrate the Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode?
Start with MI 138 Boiler Status (Boiler status code); AI 10 Active Target Supply Temperature (Supply temperature the boiler is aiming for); AI 7 Boiler Out 1 Temperature (Boiler outlet water temperature); AI 307 Boiler Modulation Rate (Burner modulation rate); BI 594 Relay Output Gas Valve ON (Gas valve energized (burner firing)); AI 19 Outdoor Temp (Outdoor air temperature); AI 160 Sensor Warnings (Sensor warning code).
How do I check these points on the real Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Weil-McLain BACnet points lists
Source: ProtoNode FPC-N34 and ProtoNode FPC-N35 Complete Point List Supplement (Weil-McLain) · T17022 · rev. Document Revision 7.D, January 2019. Object names, instances and units are reproduced as published; descriptions are our own.