- Home
- BACnet points lists
- Viessmann
- Vitogate 300 (BN/MB) with Vitocal heat pumps (Vitotronic 200 WO1C)
Heat pump BACnet gateway · BACnet points list
Viessmann Vitogate 300 (BN/MB) with Vitocal heat pumps (Vitotronic 200 WO1C) BACnet points list
Updated 12 November 2026Unofficial source
The Vitogate 300 is Viessmann's BACnet / Modbus gateway for its heat generators. This data point list covers Vitocal heat pumps with the Vitotronic 200 WO1C control: system and outdoor temperatures, heating circuits 1-3, DHW, ventilation, cooling, energy balance and COP, compressor hours and cycles, heat pump stages, additional heat generator and sensor status. Each row gives the BACnet object (AI, AV, BI, BV, MI, MV) and the matching Modbus register.
This page lists 245 BACnet objects for the Viessmann Vitogate 300 (BN/MB) with Vitocal heat pumps (Vitotronic 200 WO1C) — 74 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Viessmann’s documentation hosted by TapHome, not by Viessmann itself, so treat it as unofficial.
- Manufacturer
- Viessmann
- Model
- Vitogate 300 (BN/MB) with Vitocal heat pumps (Vitotronic 200 WO1C)
- Equipment
- Heat pump BACnet gateway
- Equipment type
- Heat pumps
- BACnet objects
- 245 (74 writable)
- Transport
- —
- Firmware
- Vitogate 300 version 2.1.2.0 or later
- Also known as
- Vitogate 300, Vitogate 300 BN/MB, Vitogate 300 Vitocal, Vitocal BACnet, Vitotronic 200 WO1C, 204D, Viessmann heat pump BACnet gateway
- Source document
- Vitogate 300 Datenpunktliste (Vitocal, Vitotronic 200 Typ WO1C) (unofficial copy, hosted by TapHome)
Reference only, provided as-is: verify against Viessmann’s current documentation and the live device before use. Not official Viessmann information. Terms of use.
BMS integration notes: Viessmann Vitogate 300 (BN/MB) with Vitocal heat pumps (Vitotronic 200 WO1C)
Set each heating circuit's operating mode (MV 4-6) and room setpoints, and the DHW setpoint. Read outdoor, system flow and DHW temperatures, circuit status, compressor state and output, and the energy balance.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 6 | Bedienbetriebsart Heizkreis A1/HK1 | Circuit 1 mode: 0 off, 1 DHW only, 2 heat/cool + DHW | Write |
| AV 10 | (2000) Raumtemperatur Soll Heizkreis A1/HK1 | Circuit 1 room setpoint, °C | Write |
| AV 26 | (6000) Warmwassertemperatur-Sollwert | DHW temperature setpoint, °C | Write |
| AI 69 | Außentemperatur | Outdoor temperature (damped) | Read |
| AI 76 | Anlagenvorlauftemperatur-Istwert | System flow temperature | Read |
| AI 78 | Warmwassertemperatur oben | DHW tank temperature, top | Read |
| MI 40 | Betriebsstatus Heizkreis A1/HK1 | Circuit 1 status: standby, reduced, normal, fixed | Read |
| BI 55 | Verdichter 1 (Schütz) | Compressor 1 contactor | Read |
| AI 141 | Leistung Verdichter | Compressor output, % | Read |
Network setup
- Set the system number and device number in the Vitogate; they offset every object instance (100000 per system, 1000 per device).
Watch out for
- Object names are German; map by instance.
- Objects for heating circuits 2-3, cooling, ventilation, solar or a second stage only return data when that equipment is present.
Viessmann Vitogate 300 (BN/MB) with Vitocal heat pumps (Vitotronic 200 WO1C) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 13 | Mischer ext. Wärmeerzeuger - Solltemperatur | General; ID 0x0603 | °C | Read | |
| AI | 74 | Rücklauftemperatur Sekundär 2 | General; ID 0x01C7 | °C | Read | |
| AImin | 76 | Anlagenvorlauftemperatur-Istwert | System; ID 0x01CA | °C | Read | |
| BI | 5 | Ansteuerung ext. Wärmeerzeuger | System; ID 0x048B | Read | 0: AUS, 1: EIN | |
| AImin | 69 | Außentemperatur | System; ID 0x01C1 | °C | Read | |
| AI | 77 | Heizwasser-Pufferspeichertemperatur | System; ID 0x01CB | °C | Read | |
| MI | 39 | Mischer ext. Wärmeerzeuger - Befehl | System; ID 0x0603 | Read | -1: ZU, 0: Regelbetrieb, 1: AUF | |
| BI | 1 | Mischer ext. Wärmeerzeuger - Status | System; ID 0x0603 | Read | 0: Vorhanden, 1: Nicht vorhanden | |
| BI | 47 | 3-Wege-Ventil Heizen/WW2 vorhanden | System equipment; ID 0x0495 | Read | 0: Vorhanden, 1: Nicht vorhanden | |
| BI | 46 | Relais Primärquelle 2 | System equipment; ID 0x0483 | Read | 0: Vorhanden, 1: Nicht vorhanden | |
| AImin | 141 | Leistung Verdichter | Outdoor unit; ID 0xB423 | % | Read | |
| AI | 73 | Rücklauftemperatur Sekundär 1 | Outdoor unit; ID 0x01C6 | °C | Read | |
| AI | 16 | Active cooling | System operating hours; ID 0x058C | hours | Read | |
| AI | 24 | Heizkreispumpe Heizkreis A1/HK1 | System operating hours; ID 0x058D | hours | Read | |
| AI | 25 | Heizkreispumpe Heizkreis M2/HK2 | System operating hours; ID 0x058E | hours | Read | |
| AI | 26 | Heizkreispumpe Heizkreis M3/HK3 | System operating hours; ID 0x058F | hours | Read | |
| AI | 38 | Speicherladepumpe | System operating hours; ID 0x0596 | hours | Read | |
| AI | 18 | EEV1 Verdichter | Heat pump operating hours; ID 0x05A8 | hours | Read | |
| AI | 19 | EEV2 Verdichter | Heat pump operating hours; ID 0x05A9 | hours | Read | |
| BI | 60 | Schalter EVU-Sperre E-Heizstab | Heat pump inputs; ID 0x03C4 | Read | 0: S_AUS, 1: S_EIN | |
| AI | 116 | COP Heizbetrieb | Energy balance; ID 0x1690 | Read | ||
| AI | 61 | COP Warmwasserbetrieb | Energy balance; ID 0x1691 | Read | ||
| AI | 120 | Elektroenergie Heizen Verdichter 2 | Energy balance; ID 0x1661 | kWh | Read | |
| AI | 115 | Elektroenergie PV | Energy balance; ID 0x1678 | kWh | Read | |
| AV | 42 | Energiebilanz Faktor | Energy balance; ID 0x163F | Write | ||
| AI | 119 | Heizwärme Heizen Verdichter 2 | Energy balance; ID 0x1641 | kWh | Read | |
| AI | 118 | Jahresarbeitszahl Kühlen | Energy balance; ID 0x1683 | Read | ||
| AI | 117 | Mittlere primäre Eingangstemperatur | Energy balance; ID 0x16B0 | °C | Read | |
| AI | 64 | Mittlere sekundäre Rücklauftemperatur RL1 | Energy balance; ID 0x16B3 | °C | Read | |
| AI | 65 | Mittlere sekundäre Rücklauftemperatur RL2 | Energy balance; ID 0x16B4 | °C | Read | |
| AI | 63 | Mittlere sekundäre Vorlauftemperatur | Energy balance; ID 0x16B2 | °C | Read | |
| MV | 22 | Betriebsart - Heizkessel | Boiler functions; ID 0xA302 | Write | 0: HVAC_AUTO, 1: HVAC_HEAT, 2: HVAC_MRNG_WRMUP, 3: HVAC_COOL, 6: HVAC_OFF, 7: HVAC_TEST, 8: HVAC_EMERG_HEAT, 10: HVAC_FREE_COOL, 12: HVAC_MAX_HEAT, 13: HVAC_ECONOMY, 14: HVAC_DEHUMID, 16: HVAC_EMERG_COOL, 111: HVAC_LOW_FIRE, 112: HVAC_HIGH_FIRE, 113: HVAC_HEAT_DHW, 255: HVAC_NUL | |
| AI | 3 | Effektive Kesselsolltemperatur | Boiler functions; ID 0xA307 | °C | Read | |
| BI | 59 | Kesselleistung - Status | Boiler functions; ID 0xA305 | Read | 0: AUS, 1: EIN | |
| MV | 13 | Kesselsollleistung - Status | Boiler functions; ID 0xA300 | Write | 0: AUS, 1: EIN, 255: AUTO | |
| AV | 44 | Kesselsollleistung - Wert | Boiler functions, range 0..100; ID 0xA300 | % | Write | |
| AV | 5 | Kesselsolltemperatur | Boiler functions, range 0..127; ID 0xA303 | °C | Write | |
| AI | 10 | Kesseltemperatur | Boiler functions; ID 0xA309 | °C | Read | |
| AI | 129 | Modulationsgrad | Boiler functions, range 0..100; ID 0xA305 | % | Read | |
| MV | 19 | Betriebsart - bei externer Vorgabe A1/M1/HK1 | Heating circuit 1 functions; ID 0xA400 | Write | 0: HVAC_AUTO, 1: HVAC_HEAT, 2: HVAC_MRNG_WRMUP, 3: HVAC_COOL, 6: HVAC_OFF, 7: HVAC_TEST, 8: HVAC_EMERG_HEAT, 10: HVAC_FREE_COOL, 12: HVAC_MAX_HEAT, 13: HVAC_ECONOMY, 14: HVAC_DEHUMID, 16: HVAC_EMERG_COOL, 100: HVAC_FLOW_TEMP, 255: HVAC_NUL | |
| AI | 5 | Effektive Raumsolltemperatur A1/M1/HK1 | Heating circuit 1 functions, range 0..35; ID 0xA406 | °C | Read | |
| AV | 39 | Externe Raumsolltemperatur A1/M1/HK1 | Heating circuit 1 functions, range 0..127; ID 0xA401 | °C | Write | |
| AV | 1 | Externe Vorlaufsolltemperatur A1/M1/HK1 | Heating circuit 1 functions, range 0..127; ID 0xA403 | °C | Write | |
| MV | 18 | Betriebsart - bei externer Vorgabe M2/HK2 | Heating circuit 2 functions; ID 0xA440 | Write | 0: HVAC_AUTO, 1: HVAC_HEAT, 2: HVAC_MRNG_WRMUP, 3: HVAC_COOL, 6: HVAC_OFF, 7: HVAC_TEST, 8: HVAC_EMERG_HEAT, 10: HVAC_FREE_COOL, 12: HVAC_MAX_HEAT, 13: HVAC_ECONOMY, 14: HVAC_DEHUMID, 16: HVAC_EMERG_COOL, 100: HVAC_FLOW_TEMP, 255: HVAC_NUL | |
| AI | 6 | Effektive Raumsolltemperatur M2/HK2 | Heating circuit 2 functions, range 0..35; ID 0xA446 | °C | Read | |
| AV | 40 | Externe Raumsolltemperatur M2/HK2 | Heating circuit 2 functions, range 0..127; ID 0xA441 | °C | Write | |
| AV | 2 | Externe Vorlaufsolltemperatur M2/HK2 | Heating circuit 2 functions, range 0..127; ID 0xA443 | °C | Write | |
| MV | 17 | Betriebsart - bei externer Vorgabe M3/HK3 | Heating circuit 3 functions; ID 0xA480 | Write | 0: HVAC_AUTO, 1: HVAC_HEAT, 2: HVAC_MRNG_WRMUP, 3: HVAC_COOL, 6: HVAC_OFF, 7: HVAC_TEST, 8: HVAC_EMERG_HEAT, 10: HVAC_FREE_COOL, 12: HVAC_MAX_HEAT, 13: HVAC_ECONOMY, 14: HVAC_DEHUMID, 16: HVAC_EMERG_COOL, 100: HVAC_FLOW_TEMP, 255: HVAC_NUL | |
| AI | 7 | Effektive Raumsolltemperatur M3/HK3 | Heating circuit 3 functions, range 0..35; ID 0xA486 | °C | Read | |
| AV | 41 | Externe Raumsolltemperatur M3/HK3 | Heating circuit 3 functions, range 0..127; ID 0xA481 | °C | Write | |
| AV | 3 | Externe Vorlaufsolltemperatur M3/HK3 | Heating circuit 3 functions, range 0..127; ID 0xA483 | °C | Write | |
| MV | 20 | Betriebsart - Warmwasser | DHW functions; ID 0xA3C2 | Write | 0: HVAC_AUTO, 1: HVAC_HEAT, 2: HVAC_MRNG_WRMUP, 6: HVAC_OFF, 255: HVAC_NUL | |
| AI | 2 | Effektive Warmwasser-Solltemperatur | DHW functions; ID 0xA3C5 | °C | Read | |
| AV | 38 | Warmwasser-Solltemperatur | DHW functions, range 0..90; ID 0xA3C0 | °C | Write | |
| AVmin | 10 | (2000) Raumtemperatur Soll Heizkreis A1/HK1 | Heating circuit A1/HK1, range 10..30; ID 0x2000 | °C | Write | |
| AV | 11 | (2001) Red. Raumtemperatur Soll Heizkreis A1/HK1 | Heating circuit A1/HK1, range 10..30; ID 0x2001 | °C | Write | |
| AV | 9 | (2006) Niveau Heizkennlinie Heizkreis A1/HK1 | Heating circuit A1/HK1, range -15..40; ID 0x2006 | K | Write | |
| AV | 8 | (2007) Neigung Heizkennlinie Heizkreis A1/HK1 | Heating circuit A1/HK1, range 0..35; ID 0x2007 | Write | ||
| AV | 28 | (2022) Raumtemperatur im Partybetrieb Heizkreis A1/HK1 | Heating circuit A1/HK1, range 10..30; ID 0x2022 | °C | Write | |
| MI | 8 | Bedarf Heizkreis A1/HK1 | Heating circuit A1/HK1; ID 0x1180 | Read | 0: Kein Bedarf, 1: Minimaler Bedarf, 2: Geringer Bedarf, 3: Mittlerer Bedarf, 4: Hoher Bedarf, 5: Maximaler Bedarf | |
| MVmin | 6 | Bedienbetriebsart Heizkreis A1/HK1 | Heating circuit A1/HK1; ID 0xB000 | Write | 0: Abschaltbetrieb, 1: Nur WW, 2: Heizen/Kühlen/WW, 4: Dauernd Reduziert, 5: Dauernd Normal, 6: Normal Abschalt, 7: Nur Kühlen | |
| MI | 7 | Betriebsmodus Heizkreis A1/HK1 | Heating circuit A1/HK1; ID 0x1180 | Read | 0: AUS, 1: Heizen, 2: Kühlen, 3: Auto | |
| MImin | 40 | Betriebsstatus Heizkreis A1/HK1 | Heating circuit A1/HK1; ID 0x1180 | Read | 0: Standby, 1: Reduziert, 2: Normal, 3: Festwert | |
| BI | 9 | Heizkreispumpe Heizkreis A1/HK1 | Heating circuit A1/HK1; ID 0x048D | Read | 0: AUS, 1: EIN | |
| AV | 35 | Neigung Kühlkennlinie Heizkreis A1/HK1 | Heating circuit A1/HK1, range 0..3,5; ID 0x7111 | Write | ||
| AV | 32 | Niveau Kühlkennlinie Heizkreis A1/HK1 | Heating circuit A1/HK1, range -15..40; ID 0x7110 | Write | ||
| BV | 6 | Partybetrieb Heizkreis A1/HK1 | Heating circuit A1/HK1; ID 0xB000 | Write | 0: AUS, 1: EIN | |
| AI | 55 | Raumsolltemperatur Heizkreis A1/HK1 | Heating circuit A1/HK1; ID 0x1180 | °C | Read | |
| AI | 87 | Raumsolltemperatur Heizkreis A1/HK1 von Fernbedienung | Heating circuit A1/HK1; ID 0x01DB | °C | Read | |
| AI | 50 | Raumtemperatur Heizkreis A1/HK1 | Heating circuit A1/HK1; ID 0x01D6 | °C | Read | |
| BV | 9 | Sparbetrieb Heizkreis A1/HK1 | Heating circuit A1/HK1; ID 0xB000 | Write | 0: AUS, 1: EIN | |
| AI | 72 | Vorlauftemperatur Sekundär 1 | Heating circuit A1/HK1; ID 0x01C5 | °C | Read | |
| AI | 145 | Vorlauftemperatur Sekundär 2 | Heating circuit A1/HK1; ID 0x01F0 | °C | Read | |
| AI | 93 | Vorlauftemperatur-Sollwert Heizkreis A1/HK1 | Heating circuit A1/HK1; ID 0x1800 | °C | Read | |
| AV | 14 | (3000) Raumtemperatur Soll Heizkreis M2/HK2 | Heating circuit M2/HK2, range 10..30; ID 0x3000 | °C | Write | |
| AV | 15 | (3001) Red. Raumtemperatur Soll Heizkreis M2/HK2 | Heating circuit M2/HK2, range 10..30; ID 0x3001 | °C | Write | |
| AV | 13 | (3006) Niveau Heizkennlinie Heizkreis M2/HK2 | Heating circuit M2/HK2, range -15..40; ID 0x3006 | K | Write | |
| AV | 12 | (3007) Neigung Heizkennlinie Heizkreis M2/HK2 | Heating circuit M2/HK2, range 0..35; ID 0x3007 | Write | ||
| AV | 29 | (3022) Raumtemperatur im Partybetrieb Heizkreis M2/HK2 | Heating circuit M2/HK2, range 10..30; ID 0x3022 | °C | Write | |
| MI | 10 | Bedarf Heizkreis M2/HK2 | Heating circuit M2/HK2; ID 0x1181 | Read | 0: Kein Bedarf, 1: Minimaler Bedarf, 2: Geringer Bedarf, 3: Mittlerer Bedarf, 4: Hoher Bedarf, 5: Maximaler Bedarf | |
| MV | 4 | Bedienbetriebsart Heizkreis M2/HK2 | Heating circuit M2/HK2; ID 0xB001 | Write | 0: Abschaltbetrieb, 1: Nur WW, 2: Heizen/Kühlen/WW, 4: Dauernd Reduziert, 5: Dauernd Normal, 6: Normal Abschalt, 7: Nur Kühlen | |
| MI | 9 | Betriebsmodus Heizkreis M2/HK2 | Heating circuit M2/HK2; ID 0x1181 | Read | 0: AUS, 1: Heizen, 2: Kühlen, 3: Auto | |
| MI | 41 | Betriebsstatus Heizkreis M2/HK2 | Heating circuit M2/HK2; ID 0x1181 | Read | 0: Standby, 1: Reduziert, 2: Normal, 3: Festwert | |
| BI | 10 | Heizkreispumpe Heizkreis M2/HK2 | Heating circuit M2/HK2; ID 0x048E | Read | 0: AUS, 1: EIN | |
| AV | 36 | Neigung Kühlkennlinie Heizkreis M2/HK2 | Heating circuit M2/HK2, range 0..3,5; ID 0x7111 | Write | ||
| AV | 33 | Niveau Kühlkennlinie Heizkreis M2/HK2 | Heating circuit M2/HK2, range -15..40; ID 0x7110 | Write | ||
| BV | 7 | Partybetrieb Heizkreis M2/HK2 | Heating circuit M2/HK2; ID 0xB001 | Write | 0: AUS, 1: EIN | |
| AI | 56 | Raumsolltemperatur Heizkreis M2/HK2 | Heating circuit M2/HK2; ID 0x1181 | °C | Read | |
| AI | 88 | Raumsolltemperatur Heizkreis M2/HK2 von Fernbedienung | Heating circuit M2/HK2; ID 0x01DC | °C | Read | |
| AI | 51 | Raumtemperatur Heizkreis M2/HK2 | Heating circuit M2/HK2; ID 0x01D7 | °C | Read | |
| BV | 10 | Sparbetrieb Heizkreis M2/HK2 | Heating circuit M2/HK2; ID 0xB001 | Write | 0: AUS, 1: EIN | |
| AI | 85 | Vorlauftemperatur Heizkreis M2/HK2 | Heating circuit M2/HK2; ID 0x01D4 | °C | Read | |
| AI | 94 | Vorlauftemperatur-Sollwert Heizkreis M2/HK2 | Heating circuit M2/HK2; ID 0x1801 | °C | Read | |
| AV | 18 | (4000) Raumtemperatur Soll Heizkreis M3/HK3 | Heating circuit M3/HK3, range 10..30; ID 0x4000 | °C | Write | |
| AV | 19 | (4001) Red. Raumtemperatur Soll Heizkreis M3/HK3 | Heating circuit M3/HK3, range 10..30; ID 0x4001 | °C | Write | |
| AV | 17 | (4006) Niveau Heizkennlinie Heizkreis M3/HK3 | Heating circuit M3/HK3, range -15..40; ID 0x4006 | K | Write | |
| AV | 16 | (4007) Neigung Heizkennlinie Heizkreis M3/HK3 | Heating circuit M3/HK3, range 0..35; ID 0x4007 | Write | ||
| AV | 30 | (4022) Raumtemperatur im Partybetrieb Heizkreis M3/HK3 | Heating circuit M3/HK3, range 10..30; ID 0x4022 | °C | Write | |
| MI | 12 | Bedarf Heizkreis M3/HK3 | Heating circuit M3/HK3; ID 0x1182 | Read | 0: Kein Bedarf, 1: Minimaler Bedarf, 2: Geringer Bedarf, 3: Mittlerer Bedarf, 4: Hoher Bedarf, 5: Maximaler Bedarf | |
| MV | 5 | Bedienbetriebsart Heizkreis M3/HK3 | Heating circuit M3/HK3; ID 0xB002 | Write | 0: Abschaltbetrieb, 1: Nur WW, 2: Heizen/Kühlen/WW, 4: Dauernd Reduziert, 5: Dauernd Normal, 6: Normal Abschalt, 7: Nur Kühlen | |
| MI | 11 | Betriebsmodus Heizkreis M3/HK3 | Heating circuit M3/HK3; ID 0x1182 | Read | 0: AUS, 1: Heizen, 2: Kühlen, 3: Auto | |
| MI | 42 | Betriebsstatus Heizkreis M3/HK3 | Heating circuit M3/HK3; ID 0x1182 | Read | 0: Standby, 1: Reduziert, 2: Normal, 3: Festwert | |
| BI | 11 | Heizkreispumpe Heizkreis M3/HK3 | Heating circuit M3/HK3; ID 0x048F | Read | 0: AUS, 1: EIN | |
| AV | 37 | Neigung Kühlkennlinie Heizkreis M3/HK3 | Heating circuit M3/HK3, range 0..3,5; ID 0x7111 | Write | ||
| AV | 34 | Niveau Kühlkennlinie Heizkreis M3/HK3 | Heating circuit M3/HK3, range -15..40; ID 0x7110 | Write | ||
| BV | 8 | Partybetrieb Heizkreis M3/HK3 | Heating circuit M3/HK3; ID 0xB002 | Write | 0: AUS, 1: EIN | |
| AI | 57 | Raumsolltemperatur Heizkreis M3/HK3 | Heating circuit M3/HK3; ID 0x1182 | °C | Read | |
| AI | 89 | Raumsolltemperatur Heizkreis M3/HK3 von Fernbedienung | Heating circuit M3/HK3; ID 0x01DD | °C | Read | |
| AI | 52 | Raumtemperatur Heizkreis M3/HK3 | Heating circuit M3/HK3; ID 0x01D8 | °C | Read | |
| BV | 11 | Sparbetrieb Heizkreis M3/HK3 | Heating circuit M3/HK3; ID 0xB002 | Write | 0: AUS, 1: EIN | |
| AI | 86 | Vorlauftemperatur Heizkreis M3/HK3 | Heating circuit M3/HK3; ID 0x01D5 | °C | Read | |
| AI | 95 | Vorlauftemperatur-Sollwert Heizkreis M3/HK3 | Heating circuit M3/HK3; ID 0x1802 | °C | Read | |
| MI | 16 | Betriebsmodus Kühlkreis | Cooling circuit; ID 0x1183 | Read | 0: AUS, 1: Heizen, 2: Kühlen, 3: Auto | |
| AI | 54 | Raumtemperatur Kühlkreis | Cooling circuit; ID 0x01DA | °C | Read | |
| AI | 60 | Solltemperatur Kühlkreis | Cooling circuit; ID 0x1183 | °C | Read | |
| AV | 21 | (7110) Niveau Kühlkennlinie Kühlkreis | Cooling, range -15..40; ID 0x7110 | Write | ||
| AV | 20 | (7111) Neigung Kühlkennlinie Kühlkreis | Cooling, range 0..3,5; ID 0x7111 | Write | ||
| MI | 17 | Bedarf Kühlkreis | Cooling; ID 0x1183 | Read | 0: Kein Bedarf, 1: Minimaler Bedarf, 2: Geringer Bedarf, 3: Mittlerer Bedarf, 4: Hoher Bedarf, 5: Maximaler Bedarf | |
| AI | 53 | Vorlauftemperatur Kühlkreis | Cooling, heating circuit A1/HK1; ID 0x01D9 | °C | Read | |
| AI | 139 | Ablufttemperatur | Ventilation; ID 0x0A02 | °C | Read | |
| AI | 133 | Außenlufttemperatur | Ventilation; ID 0x0A00 | °C | Read | |
| MI | 49 | Betriebsprogramm | Ventilation; ID 0x0A7E | Read | 0: Nicht definiert, 1: Notlauf, 2: Frostschutz, 3: Estrichtrocknung, 4: Intensivbetrieb, 5: Ferienprogramm, 1: Sparbetrieb, 7: Lüftungsautomatik, 8: Abschaltbetrieb, 9: Grundbetrieb | |
| MV | 14 | Betriebsprogramm | Ventilation; ID 0xB005 | Write | 0: Abschaltbetrieb, 1: Grundbetrieb, 2: Lüftungsautomatik | |
| MI | 52 | Betriebsstatus | Ventilation; ID 0x11A8 | Read | Grundlüftung, Reduzierte Lüftung, Nennlüftung, Intensivlüftung, Abschaltbetrieb | |
| AI | 136 | CO2 | Ventilation; ID 0x0A07 | % | Read | |
| AI | 131 | Elektrisches Vorheizregister | Ventilation; ID 0x0A0C | % | Read | |
| AI | 130 | Feuchte | Ventilation; ID 0x0A06 | % | Read | |
| AI | 132 | Filterstandzeit Tage | Ventilation, range 1..31; ID 0x0A0E | Tage | Read | |
| AI | 134 | Fortlufttemperatur | Ventilation; ID 0x0A03 | °C | Read | |
| AV | 45 | Grundbetrieb | Ventilation; ID 0xB005 | Write | 0: AUS, 1: EIN | |
| BV | 18 | Intensivbetrieb | Ventilation; ID 0xB005 | Write | 0: AUS, 1: EIN | |
| AV | 46 | Raumtemp. Soll | Ventilation, range 10..30; ID 0x7D08 | °C | Write | |
| AI | 140 | Raumtemperatur-Sollwert T-ABL-Soll | Ventilation; ID 0x0A15 | °C | Read | |
| AI | 135 | Volumenstrom Fortluft | Ventilation; ID 0x0A05 | m³/h | Read | |
| AI | 138 | Volumenstrom Zuluft | Ventilation; ID 0x0A04 | m³/h | Read | |
| AI | 137 | Zulufttemperatur | Ventilation; ID 0x0A01 | °C | Read | |
| AI | 128 | Ausgang Abtauung aktiv | System switching cycles; ID 0xB446 | Read | 0: AUS, 1: Abtauung aktiv | |
| AI | 125 | Drehzahl Ventilator 1 | System switching cycles; ID 0x02C0 | U/min | Read | |
| AI | 126 | Drehzahl Ventilator 2 | System switching cycles; ID 0x02C1 | U/min | Read | |
| AI | 41 | Anzahl Einschalt. Verdichter | Heat pump switching cycles; ID 0x0500 | Read | ||
| AI | 42 | Anzahl Einschalt. Verdichter 2 | Heat pump switching cycles; ID 0x0501 | Read | ||
| MI | 36 | Raumsolltemperatur Heizkreis A1/HK1 | Sensor status; ID 0x01DB | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 37 | Raumsolltemperatur Heizkreis M2/HK2 | Sensor status; ID 0x01DC | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 38 | Raumsolltemperatur Heizkreis M3/HK3 | Sensor status; ID 0x01DD | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 19 | Raumtemperatur Heizkreis A1/HK1 | Sensor status; ID 0x01D6 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 48 | Raumtemperatur Kühlkreis | Sensor status; ID 0x01DA | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 24 | Rücklauftemperatur Primärquelle | Sensor status; ID 0x01C4 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 25 | Rücklauftemperatur Sekundär 1 | Sensor status; ID 0x01C6 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 26 | Rücklauftemperatur Sekundär 2 | Sensor status; ID 0x01C7 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 50 | Status Sensor Sekundär-Vorlauf 2 | Sensor status; ID 0x01F0 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 23 | Vorlauftemperatur Primärquelle | Sensor status; ID 0x01C3 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 47 | Vorlauftemperatur Sekundär 1 | Sensor status; ID 0x01C5 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| BI | 61 | EVU-Sperre | Signal inputs; ID 0x03C3 | Read | 0: AUS, 1: EIN | |
| AI | 82 | Kollektortemperatur Solar | Solar; ID 0x01D1 | °C | Read | |
| AI | 83 | Rücklauftemperatur Solar | Solar; ID 0x01D2 | °C | Read | |
| AI | 43 | Solarenergie | Solar; ID 0x190A | kWh | Read | |
| BI | 20 | Solarpumpe (int. Solarregelung) | Solar; ID 0x0493 | Read | 0: AUS, 1: EIN | |
| BI | 21 | Solarpumpe (Vitosolic) | Solar; ID 0x04A0 | Read | 0: AUS, 1: EIN | |
| AI | 84 | Speichertemperatur Solar | Solar; ID 0x01D3 | °C | Read | |
| MI | 53 | Sensor-Status Leistung Verdichter | Temperatures; ID 0xB423 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| AI | 127 | Mindestlaufzeit externer Wärmeerzeuger | Timer; ID 0x1386 | Sekunden | Read | |
| AV | 23 | (5030) Leistung Verdichterstufe | Compressor 1, range 1..255; ID 0x5030 | Write | ||
| AV | 24 | (5130) Verdichter2 Leistung Verdichter | Compressor 2, range 1..255; ID 0x5130 | Write | ||
| AV | 50 | Gas Normaltarif | Heat management, range 0..32767; ID 0x7BEB | ct / kWh | Write | |
| BV | 19 | Komfortbetrieb | Heat management; ID 0x7BE0 | Write | 0: AUS, 1: EIN | |
| AV | 52 | Primärenergiefaktor Gas | Heat management; ID 0x7BE5 | Write | ||
| AV | 51 | Primärenergiefaktor Strom | Heat management; ID 0x7BE4 | Write | ||
| MV | 15 | Regelstrategie WE | Heat management; ID 0x7BE1 | Write | Ökonomisch, Ökologisch, Feste Temperatur | |
| AV | 47 | Strom Normaltarif | Heat management, range 0..32767; ID 0x7BE8 | ct / kWh | Write | |
| BI | 2 | 3-Wege-Ventil Heizen/WW1 | Heat pump; ID 0x0494 | Read | 0: Heizen, 1: Warmwasser | |
| BI | 3 | 3-Wege-Ventil Heizen/WW2 | Heat pump; ID 0x0495 | Read | 0: Heizen, 1: Warmwasser | |
| BI | 6 | E-Heizung Stufe 1 | Heat pump; ID 0x0488 | Read | 0: AUS, 1: EIN | |
| AI | 20 | E-Heizung Stufe 1 | Heat pump; ID 0x0588 | hours | Read | |
| BI | 7 | E-Heizung Stufe 2 | Heat pump; ID 0x0489 | Read | 0: AUS, 1: EIN | |
| AI | 21 | E-Heizung Stufe 2 | Heat pump; ID 0x0589 | hours | Read | |
| AI | 90 | Kompressor Frequenz | Heat pump, range 0..255; ID 0x1A54 | Hz | Read | |
| BI | 15 | Primärquelle 2 (Primärpumpe) | Heat pump; ID 0x0483 | Read | 0: AUS, 1: EIN | |
| AI | 146 | PV-Leistung in 0,01kW (Phase 1) | Heat pump; ID 0xB060 | kW | Read | |
| AI | 147 | PV-Leistung in 0,01kW (Phase 2) | Heat pump; ID 0xB061 | kW | Read | |
| AI | 148 | PV-Leistung in 0,01kW (Phase 3) | Heat pump; ID 0xB062 | kW | Read | |
| AI | 71 | Rücklauftemperatur Primärquelle | Heat pump; ID 0x01C4 | °C | Read | |
| BI | 18 | Sekundärpumpe | Heat pump; ID 0x0484 | Read | 0: AUS, 1: EIN | |
| BI | 19 | Sekundärpumpe 2 | Heat pump; ID 0x0485 | Read | 0: AUS, 1: EIN | |
| AI | 70 | Vorlauftemperatur Primärquelle | Heat pump; ID 0x01C3 | °C | Read | |
| BI | 48 | 3-Wege-Ventil Heizen/WW 1 | Heat pump stage 1; ID 0x0414 | Read | 0: AUS, 1: EIN | |
| BI | 52 | Primärquelle 1 (Ventilator oder Primärpumpe) | Heat pump stage 1; ID 0x0402 | Read | 0: AUS, 1: EIN | |
| BI | 50 | Relais EEV1 Verdichter | Heat pump stage 1; ID 0x0428 | Read | 0: AUS, 1: EIN | |
| BI | 54 | Sekundärpumpe 1 | Heat pump stage 1; ID 0x0404 | Read | 0: AUS, 1: EIN | |
| BImin | 55 | Verdichter 1 (Schütz) | Heat pump stage 1; ID 0x0400 | Read | 0: AUS, 1: EIN | |
| BI | 49 | 3-Wege-Ventil Heizen/WW 2 | Heat pump stage 2; ID 0x0415 | Read | 0: AUS, 1: EIN | |
| BI | 53 | Primärquelle 2 (Primärpumpe) | Heat pump stage 2; ID 0x0403 | Read | 0: AUS, 1: EIN | |
| BI | 51 | Relais EEV2 Verdichter | Heat pump stage 2; ID 0x0429 | Read | 0: AUS, 1: EIN | |
| BI | 56 | Verdichter 2 (Schütz) | Heat pump stage 2; ID 0x0401 | Read | 0: AUS, 1: EIN | |
| AVmin | 26 | (6000) Warmwassertemperatur-Sollwert | DHW, range 10..70; ID 0x6000 | °C | Write | |
| AV | 25 | (600C) Warmwassertemperatur-Sollwert 2 | DHW, range 10..70; ID 0x600C | °C | Write | |
| MI | 14 | Bedarf Warmwasser | DHW; ID 0x1185 | Read | 0: Kein Bedarf, 1: Minimaler Bedarf, 2: Geringer Bedarf, 3: Mittlerer Bedarf, 4: Hoher Bedarf, 5: Maximaler Bedarf | |
| MI | 13 | Betriebsmodus Warmwasser | DHW; ID 0x1185 | Read | 0: Abschaltbetrieb, 1: Sparbetrieb, 2: Normalbetrieb, 3: Festwert | |
| BV | 17 | Einmalige Warmwasserbereitung | DHW; ID 0xB020 | Write | 0: AUS, 1: EIN | |
| AI | 59 | Sollleistung Warmwasser | DHW, range 0..100; ID 0x1185 | % | Read | |
| BI | 22 | Speicherladepumpe | DHW; ID 0x0496 | Read | 0: AUS, 1: EIN | |
| AI | 39 | Speichernachheizung | DHW; ID 0x058A | hours | Read | |
| AImin | 78 | Warmwassertemperatur oben | DHW; ID 0x01CD | °C | Read | |
| AI | 79 | Warmwassertemperatur unten | DHW; ID 0x01CE | °C | Read | |
| AI | 58 | Warmwassertemperatur-Sollwert | DHW; ID 0x1185 | °C | Read | |
| BI | 16 | Zirkulationspumpe | DHW; ID 0x0490 | Read | 0: AUS, 1: EIN | |
| AI | 4 | Aktiver Anlagen-/Solltemperaturwert | Central control functions; ID 0xA391 | °C | Read | |
| MV | 8 | Anlagen-/Heizkessel-Sollleistung - Status | Central control functions; ID 0xA380 | Write | 0: AUS, 1: EIN, 255: AUTO | |
| AV | 4 | Anlagen-/Heizkessel-Sollleistung - Wert | Central control functions, range 0..100; ID 0xA380 | % | Write | |
| MI | 46 | Anlagen-Istleistung - Status | Central control functions; ID 0xA38F | Read | 0: AUS, 1: EIN | |
| AI | 9 | Anlagen-Istleistung - Wert | Central control functions, range 0..100; ID 0xA38F | % | Read | |
| AI | 11 | Anlagenvorlauf-/Kesseltemperatur Istwert | Central control functions; ID 0xA393 | °C | Read | |
| MV | 21 | Betriebsart - Anlage/Heizkessel | Central control functions; ID 0xA382 | Write | 0: HVAC_AUTO, 1: HVAC_HEAT, 2: HVAC_MRNG_WRMUP, 3: HVAC_COOL, 6: HVAC_OFF, 7: HVAC_TEST, 8: HVAC_EMERG_HEAT, 10: HVAC_FREE_COOL, 12: HVAC_MAX_HEAT, 13: HVAC_ECONOMY, 14: HVAC_DEHUMID, 16: HVAC_EMERG_COOL, 111: HVAC_LOW_FIRE, 112: HVAC_HIGH_FIRE, 255: HVAC_NUL | |
| AV | 6 | Vorlauftemperatur-Sollwert Anlage/Heizkessel | Central control functions; ID 0xA383 | °C | Write | |
| AV | 22 | (7102) Raumtemperatur-Sollwert Kühlkreis | Additional information, range 10..30; ID 0x7102 | °C | Write | |
| MI | 27 | Anlagenvorlauf | Additional information; ID 0x01CA | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| AI | 143 | Ausgang Verdichter KK2 | Additional information; ID 0xB4C3 | Read | ||
| MI | 22 | Außentemperatur | Additional information; ID 0x01C1 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MV | 16 | Bedienbetriebsart Kühlkreis | Additional information; ID 0xB003 | Write | 0: Abschaltbetrieb, 1: Nur WW, 2: Kühlen/WW, 4: Dauernd Reduziert, 5: Dauernd Normal, 6: Normal Abschalt, 7: Nur Kühlen | |
| AI | 40 | Betriebsstunden Verdichter 2 | Additional information; ID 0x0581 | hours | Read | |
| AV | 53 | Faktor Energiepreise | Additional information; ID 0x7BEE | Write | 0: 1/100, 1: 1/10, 2: 1 | |
| MI | 51 | Feuchtesensor - Status | Additional information; ID 0x0A06 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 31 | Kollektortemperatur Solar | Additional information; ID 0x01D1 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| AV | 54 | Korrekturfaktor Energieblianz | Additional information; ID 0x7BEF | Write | keine Anzeige der Energiebilanz, 1: 1 Digit = 0,1kWh, 10: 1 Digit = 1 kWh, 100: 1 Digit = 10 kWh | |
| AI | 142 | Leistung Verdichter KK2 | Additional information; ID 0xB4A3 | % | Read | |
| MI | 28 | Pufferspeichertemperatur | Additional information; ID 0x01CB | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 20 | Raumtemperatur Heizkreis M2/HK2 | Additional information; ID 0x01D7 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 21 | Raumtemperatur Heizkreis M3/HK3 | Additional information; ID 0x01D8 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 44 | Raumtemperatursensor Heizkreis A1/HK1 - Status | Additional information; ID 0x01D6 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 32 | Rücklauftemperatur Solar | Additional information; ID 0x01D2 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| AI | 144 | Sekundär-Rücklauftemperatur (Kältekreis 2) | Additional information; ID 0xB483 | °C | Read | |
| MI | 33 | Speichertemperatur Solar | Additional information; ID 0x01D3 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 45 | Status Sensor Vorlauf Kühlung | Additional information; ID 0x01D9 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| AV | 48 | Strom Hochtarif | Additional information, range 0..32767; ID 0x7BE9 | ct / kWh | Write | |
| AV | 49 | Strom Niedertarif | Additional information, range 0..32767; ID 0x7BEA | ct / kWh | Write | |
| AV | 43 | Strompreis Eigenverbrauch | Additional information, range 0..32767; ID 0x7BED | ct / kWh | Write | |
| MI | 34 | Vorlauftemperatur Heizkreis M2/HK2 | Additional information; ID 0x01D4 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 35 | Vorlauftemperatur Heizkreis M3/HK3 | Additional information; ID 0x01D5 | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 29 | Warmwassertemperatur oben | Additional information; ID 0x01CD | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| MI | 30 | Warmwassertemperatur unten | Additional information; ID 0x01CE | Read | 0: Sensor OK, 1: Sensor Kurzschluss, 2: Sensor Unterbrechung, 3: Sensor Referenzfehler, 4: Sensor Referenz unter Min, 5: Sensor Referenz über Max, 6: Sensor nicht vorhanden, 7: Sensor Check, 8: Sensor Fehler, 9: Sensor Kom. Fehler | |
| AI | 124 | Bivalenztemperatur Wärmepumpe | Additional heat generator; ID 0xB380 | °C | Read | |
| AI | 123 | Gemeinsame Vorlauftemperatur | Additional heat generator; ID 0x01F7 | °C | Read | |
| AI | 121 | Kesseltemperatur Zusatz-Wärmeerzeuger | Additional heat generator; ID 0xB370 | °C | Read | |
| AI | 122 | Kesseltemperatur-Sollwert Zusatz-Wärmeerzeuger | Additional heat generator; ID 0xB371 | °C | Read | |
| BI | 58 | Umschaltventil ext. WE | Additional heat generator; ID 0x04BE | Read | 0: AUS, 1: EIN | |
| BI | 57 | Umschaltventil WP | Additional heat generator; ID 0x04BD | Read | 0: AUS, 1: EIN |
No points match these filters.
Object ID lookup: Viessmann Vitogate 300 Vitocal point IDs by name
AI13Mischer ext. Wärmeerzeuger - SolltemperaturAI74Rücklauftemperatur Sekundär 2AI76Anlagenvorlauftemperatur-IstwertBI5Ansteuerung ext. WärmeerzeugerAI69AußentemperaturAI77Heizwasser-PufferspeichertemperaturMI39Mischer ext. Wärmeerzeuger - BefehlBI1Mischer ext. Wärmeerzeuger - StatusBI473-Wege-Ventil Heizen/WW2 vorhandenBI46Relais Primärquelle 2AI141Leistung VerdichterAI73Rücklauftemperatur Sekundär 1AI16Active coolingAI24Heizkreispumpe Heizkreis A1/HK1AI25Heizkreispumpe Heizkreis M2/HK2AI26Heizkreispumpe Heizkreis M3/HK3AI38SpeicherladepumpeAI18EEV1 VerdichterAI19EEV2 VerdichterBI60Schalter EVU-Sperre E-HeizstabAI116COP HeizbetriebAI61COP WarmwasserbetriebAI120Elektroenergie Heizen Verdichter 2AI115Elektroenergie PVAV42Energiebilanz FaktorAI119Heizwärme Heizen Verdichter 2AI118Jahresarbeitszahl KühlenAI117Mittlere primäre EingangstemperaturAI64Mittlere sekundäre Rücklauftemperatur RL1AI65Mittlere sekundäre Rücklauftemperatur RL2AI63Mittlere sekundäre VorlauftemperaturMV22Betriebsart - HeizkesselAI3Effektive KesselsolltemperaturBI59Kesselleistung - StatusMV13Kesselsollleistung - StatusAV44Kesselsollleistung - WertAV5KesselsolltemperaturAI10KesseltemperaturAI129ModulationsgradMV19Betriebsart - bei externer Vorgabe A1/M1/HK1AI5Effektive Raumsolltemperatur A1/M1/HK1AV39Externe Raumsolltemperatur A1/M1/HK1AV1Externe Vorlaufsolltemperatur A1/M1/HK1MV18Betriebsart - bei externer Vorgabe M2/HK2AI6Effektive Raumsolltemperatur M2/HK2AV40Externe Raumsolltemperatur M2/HK2AV2Externe Vorlaufsolltemperatur M2/HK2MV17Betriebsart - bei externer Vorgabe M3/HK3AI7Effektive Raumsolltemperatur M3/HK3AV41Externe Raumsolltemperatur M3/HK3AV3Externe Vorlaufsolltemperatur M3/HK3MV20Betriebsart - WarmwasserAI2Effektive Warmwasser-SolltemperaturAV38Warmwasser-SolltemperaturAV10(2000) Raumtemperatur Soll Heizkreis A1/HK1AV11(2001) Red. Raumtemperatur Soll Heizkreis A1/HK1AV9(2006) Niveau Heizkennlinie Heizkreis A1/HK1AV8(2007) Neigung Heizkennlinie Heizkreis A1/HK1AV28(2022) Raumtemperatur im Partybetrieb Heizkreis A1/HK1MI8Bedarf Heizkreis A1/HK1MV6Bedienbetriebsart Heizkreis A1/HK1MI7Betriebsmodus Heizkreis A1/HK1MI40Betriebsstatus Heizkreis A1/HK1BI9Heizkreispumpe Heizkreis A1/HK1AV35Neigung Kühlkennlinie Heizkreis A1/HK1AV32Niveau Kühlkennlinie Heizkreis A1/HK1BV6Partybetrieb Heizkreis A1/HK1AI55Raumsolltemperatur Heizkreis A1/HK1AI87Raumsolltemperatur Heizkreis A1/HK1 von FernbedienungAI50Raumtemperatur Heizkreis A1/HK1BV9Sparbetrieb Heizkreis A1/HK1AI72Vorlauftemperatur Sekundär 1AI145Vorlauftemperatur Sekundär 2AI93Vorlauftemperatur-Sollwert Heizkreis A1/HK1AV14(3000) Raumtemperatur Soll Heizkreis M2/HK2AV15(3001) Red. Raumtemperatur Soll Heizkreis M2/HK2AV13(3006) Niveau Heizkennlinie Heizkreis M2/HK2AV12(3007) Neigung Heizkennlinie Heizkreis M2/HK2AV29(3022) Raumtemperatur im Partybetrieb Heizkreis M2/HK2MI10Bedarf Heizkreis M2/HK2MV4Bedienbetriebsart Heizkreis M2/HK2MI9Betriebsmodus Heizkreis M2/HK2MI41Betriebsstatus Heizkreis M2/HK2BI10Heizkreispumpe Heizkreis M2/HK2AV36Neigung Kühlkennlinie Heizkreis M2/HK2AV33Niveau Kühlkennlinie Heizkreis M2/HK2BV7Partybetrieb Heizkreis M2/HK2AI56Raumsolltemperatur Heizkreis M2/HK2AI88Raumsolltemperatur Heizkreis M2/HK2 von FernbedienungAI51Raumtemperatur Heizkreis M2/HK2BV10Sparbetrieb Heizkreis M2/HK2AI85Vorlauftemperatur Heizkreis M2/HK2AI94Vorlauftemperatur-Sollwert Heizkreis M2/HK2AV18(4000) Raumtemperatur Soll Heizkreis M3/HK3AV19(4001) Red. Raumtemperatur Soll Heizkreis M3/HK3AV17(4006) Niveau Heizkennlinie Heizkreis M3/HK3AV16(4007) Neigung Heizkennlinie Heizkreis M3/HK3AV30(4022) Raumtemperatur im Partybetrieb Heizkreis M3/HK3MI12Bedarf Heizkreis M3/HK3MV5Bedienbetriebsart Heizkreis M3/HK3MI11Betriebsmodus Heizkreis M3/HK3MI42Betriebsstatus Heizkreis M3/HK3BI11Heizkreispumpe Heizkreis M3/HK3AV37Neigung Kühlkennlinie Heizkreis M3/HK3AV34Niveau Kühlkennlinie Heizkreis M3/HK3BV8Partybetrieb Heizkreis M3/HK3AI57Raumsolltemperatur Heizkreis M3/HK3AI89Raumsolltemperatur Heizkreis M3/HK3 von FernbedienungAI52Raumtemperatur Heizkreis M3/HK3BV11Sparbetrieb Heizkreis M3/HK3AI86Vorlauftemperatur Heizkreis M3/HK3AI95Vorlauftemperatur-Sollwert Heizkreis M3/HK3MI16Betriebsmodus KühlkreisAI54Raumtemperatur KühlkreisAI60Solltemperatur KühlkreisAV21(7110) Niveau Kühlkennlinie KühlkreisAV20(7111) Neigung Kühlkennlinie KühlkreisMI17Bedarf KühlkreisAI53Vorlauftemperatur KühlkreisAI139AblufttemperaturAI133AußenlufttemperaturMI49BetriebsprogrammMV14BetriebsprogrammMI52BetriebsstatusAI136CO2AI131Elektrisches VorheizregisterAI130FeuchteAI132Filterstandzeit TageAI134FortlufttemperaturAV45GrundbetriebBV18IntensivbetriebAV46Raumtemp. SollAI140Raumtemperatur-Sollwert T-ABL-SollAI135Volumenstrom FortluftAI138Volumenstrom ZuluftAI137ZulufttemperaturAI128Ausgang Abtauung aktivAI125Drehzahl Ventilator 1AI126Drehzahl Ventilator 2AI41Anzahl Einschalt. VerdichterAI42Anzahl Einschalt. Verdichter 2MI36Raumsolltemperatur Heizkreis A1/HK1MI37Raumsolltemperatur Heizkreis M2/HK2MI38Raumsolltemperatur Heizkreis M3/HK3MI19Raumtemperatur Heizkreis A1/HK1MI48Raumtemperatur KühlkreisMI24Rücklauftemperatur PrimärquelleMI25Rücklauftemperatur Sekundär 1MI26Rücklauftemperatur Sekundär 2MI50Status Sensor Sekundär-Vorlauf 2MI23Vorlauftemperatur PrimärquelleMI47Vorlauftemperatur Sekundär 1BI61EVU-SperreAI82Kollektortemperatur SolarAI83Rücklauftemperatur SolarAI43SolarenergieBI20Solarpumpe (int. Solarregelung)BI21Solarpumpe (Vitosolic)AI84Speichertemperatur SolarMI53Sensor-Status Leistung VerdichterAI127Mindestlaufzeit externer WärmeerzeugerAV23(5030) Leistung VerdichterstufeAV24(5130) Verdichter2 Leistung VerdichterAV50Gas NormaltarifBV19KomfortbetriebAV52Primärenergiefaktor GasAV51Primärenergiefaktor StromMV15Regelstrategie WEAV47Strom NormaltarifBI23-Wege-Ventil Heizen/WW1BI33-Wege-Ventil Heizen/WW2BI6E-Heizung Stufe 1AI20E-Heizung Stufe 1BI7E-Heizung Stufe 2AI21E-Heizung Stufe 2AI90Kompressor FrequenzBI15Primärquelle 2 (Primärpumpe)AI146PV-Leistung in 0,01kW (Phase 1)AI147PV-Leistung in 0,01kW (Phase 2)AI148PV-Leistung in 0,01kW (Phase 3)AI71Rücklauftemperatur PrimärquelleBI18SekundärpumpeBI19Sekundärpumpe 2AI70Vorlauftemperatur PrimärquelleBI483-Wege-Ventil Heizen/WW 1BI52Primärquelle 1 (Ventilator oder Primärpumpe)BI50Relais EEV1 VerdichterBI54Sekundärpumpe 1BI55Verdichter 1 (Schütz)BI493-Wege-Ventil Heizen/WW 2BI53Primärquelle 2 (Primärpumpe)BI51Relais EEV2 VerdichterBI56Verdichter 2 (Schütz)AV26(6000) Warmwassertemperatur-SollwertAV25(600C) Warmwassertemperatur-Sollwert 2MI14Bedarf WarmwasserMI13Betriebsmodus WarmwasserBV17Einmalige WarmwasserbereitungAI59Sollleistung WarmwasserBI22SpeicherladepumpeAI39SpeichernachheizungAI78Warmwassertemperatur obenAI79Warmwassertemperatur untenAI58Warmwassertemperatur-SollwertBI16ZirkulationspumpeAI4Aktiver Anlagen-/SolltemperaturwertMV8Anlagen-/Heizkessel-Sollleistung - StatusAV4Anlagen-/Heizkessel-Sollleistung - WertMI46Anlagen-Istleistung - StatusAI9Anlagen-Istleistung - WertAI11Anlagenvorlauf-/Kesseltemperatur IstwertMV21Betriebsart - Anlage/HeizkesselAV6Vorlauftemperatur-Sollwert Anlage/HeizkesselAV22(7102) Raumtemperatur-Sollwert KühlkreisMI27AnlagenvorlaufAI143Ausgang Verdichter KK2MI22AußentemperaturMV16Bedienbetriebsart KühlkreisAI40Betriebsstunden Verdichter 2AV53Faktor EnergiepreiseMI51Feuchtesensor - StatusMI31Kollektortemperatur SolarAV54Korrekturfaktor EnergieblianzAI142Leistung Verdichter KK2MI28PufferspeichertemperaturMI20Raumtemperatur Heizkreis M2/HK2MI21Raumtemperatur Heizkreis M3/HK3MI44Raumtemperatursensor Heizkreis A1/HK1 - StatusMI32Rücklauftemperatur SolarAI144Sekundär-Rücklauftemperatur (Kältekreis 2)MI33Speichertemperatur SolarMI45Status Sensor Vorlauf KühlungAV48Strom HochtarifAV49Strom NiedertarifAV43Strompreis EigenverbrauchMI34Vorlauftemperatur Heizkreis M2/HK2MI35Vorlauftemperatur Heizkreis M3/HK3MI29Warmwassertemperatur obenMI30Warmwassertemperatur untenAI124Bivalenztemperatur WärmepumpeAI123Gemeinsame VorlauftemperaturAI121Kesseltemperatur Zusatz-WärmeerzeugerAI122Kesseltemperatur-Sollwert Zusatz-WärmeerzeugerBI58Umschaltventil ext. WEBI57Umschaltventil WP
Integration notes
- Object names are the German data point names as printed; the description gives the list's group in English and the Viessmann technical ID.
- Instances are printed for system 1, device 1. Actual object ID = 100000 x (system no. - 1) + 1000 x (device no. - 1) + printed BACnet-ID.
- The list has no read/write column. Objects mapped to a Modbus holding register or coil (HO/CO) are shown as writable, those mapped to input registers or status bits (IN/ST) as read-only.
- State texts are as printed (German). Values for unused functions or missing equipment are not available.
- The list does not state the BACnet data link; the Vitogate 300 is a network gateway.
- Source: 'Vitogate 300 Datenpunktliste' for 204D_Vitocal_xxx-S_Vitotronic_200_Typ_WO1C, 31 pages (245 objects).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Vitogate 300 (BN/MB) with Vitocal heat pumps (Vitotronic 200 WO1C) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Viessmann Vitogate 300 (BN/MB) with Vitocal heat pumps (Vitotronic 200 WO1C)
How many BACnet points does the Viessmann Vitogate 300 (BN/MB) with Vitocal heat pumps (Vitotronic 200 WO1C) have?
This list has 245 BACnet objects: 95 analog inputs, 51 analog values, 32 binary inputs, 9 binary values, 44 multi-state inputs, 14 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Viessmann Vitogate 300 (BN/MB) with Vitocal heat pumps (Vitotronic 200 WO1C) BACnet points are writable?
74 of the 245 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Viessmann Vitogate 300 (BN/MB) with Vitocal heat pumps (Vitotronic 200 WO1C) BACnet documentation?
Viessmann does not publish it on its own website. This list comes from Vitogate 300 Datenpunktliste (Vitocal, Vitotronic 200 Typ WO1C), a copy hosted by TapHome at https://taphome.com/compatibility/devices/viessmann-vitogate-300-vitocal/manufacturer/vitogate-300-datenpunktliste-vitocal.pdf. Ask Viessmann or its representative for the current revision.
What are the minimum BACnet points to integrate the Viessmann Vitogate 300 (BN/MB) with Vitocal heat pumps (Vitotronic 200 WO1C)?
Start with MV 6 Bedienbetriebsart Heizkreis A1/HK1 (Circuit 1 mode: 0 off, 1 DHW only, 2 heat/cool + DHW); AV 10 (2000) Raumtemperatur Soll Heizkreis A1/HK1 (Circuit 1 room setpoint, °C); AV 26 (6000) Warmwassertemperatur-Sollwert (DHW temperature setpoint, °C); AI 69 Außentemperatur (Outdoor temperature (damped)); AI 76 Anlagenvorlauftemperatur-Istwert (System flow temperature); AI 78 Warmwassertemperatur oben (DHW tank temperature, top); MI 40 Betriebsstatus Heizkreis A1/HK1 (Circuit 1 status: standby, reduced, normal, fixed); BI 55 Verdichter 1 (Schütz) (Compressor 1 contactor); AI 141 Leistung Verdichter (Compressor output, %).
How do I check these points on the real Vitogate 300 (BN/MB) with Vitocal heat pumps (Vitotronic 200 WO1C)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Viessmann BACnet points lists
- Boiler BACnet IP gateway
Viessmann Vitocrossal 200 CI2 (WAGO Automation Gateway)
Viessmann Vitocrossal 200 CI2 boilers connected to a WAGO Automation Gateway BACnet IP, as a single boiler or in a cascade.
Also known as: Vitocrossal 200, Vitocrossal CI2, Viessmann WAGO gateway, WAGO Automation Gateway BACnet/IP, 6178 508 - Boiler BACnet IP gateway
Viessmann Vitodens 200-W B2HE (WAGO Automation Gateway)
Viessmann Vitodens 200-W B2HE wall-mounted boilers connected to a WAGO Automation Gateway BACnet IP, as a single boiler or in a cascade.
Also known as: Vitodens 200, Vitodens 200-W, Vitodens B2HE, Viessmann WAGO gateway, WAGO Automation Gateway BACnet/IP, 6178 507
Source: Vitogate 300 Datenpunktliste (Vitocal, Vitotronic 200 Typ WO1C). Object names, instances and units are reproduced as published; descriptions are our own.