Viessmann Vitocrossal 200 CI2 (WAGO Automation Gateway) BACnet points list

Updated 28 October 2026

Short answer

Viessmann connects the Vitocrossal 200 CI2 to a BMS through a WAGO Automation Gateway that talks CAN to the boiler and exposes BACnet IP objects. The list covers external demand and operating-program commands for the boiler, DHW and four heating circuits, temperatures, burner modulation and hours, a second burner and O2 values, cascade sequence positions, fault codes and energy and gas statistics. Points must be selected in the gateway before they appear on BACnet.

This page lists 129 BACnet objects for the Viessmann Vitocrossal 200 CI2 (WAGO Automation Gateway) — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Viessmann’s own free documentation, linked below.

Manufacturer
Viessmann
Model
Vitocrossal 200 CI2 (WAGO Automation Gateway)
Equipment
Boiler BACnet IP gateway
Equipment type
Boilers & water heaters
BACnet objects
129 (15 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Vitocrossal 200, Vitocrossal CI2, Viessmann WAGO gateway, WAGO Automation Gateway BACnet/IP, 6178 508
Source document
WAGO Gateway Data Points - Communication to a building management system (Vitocrossal 200 CI2) · 6178 508-05 · rev. 01/2025
Download CSV 129 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Viessmann Vitocrossal 200 CI2 (WAGO Automation Gateway)

Integration in brief

Select the needed points in the gateway's web visualization and save, then set Heartbeat Monitoring. The BMS writes MV 3 for the heating program plus AV 2 (supply temperature) or AV 1 (modulation), and keeps rewriting MV 1 with 3 every 10 s so the boiler accepts them. Read flame, supply temperature, modulation, the fault flag and fault codes, and watch BI 1 for the gateway-to-boiler link.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 3Boiler operating program: TargetHeating program: internal, modulation, supply temp, lockedWrite
AV 2Target supply temperatureBoiler supply temperature setpointWrite
AV 1Burner modulation, target valueBurner modulation command, 0-100 %; single boiler onlyWrite
MV 1External demandWrite 3 (BACnet) every 10 s or BMS setpoints dropWrite
BI 2BurnerFlame status; list prints 0 = On, 1 = OffRead
AI 1Supply temperatureBoiler supply water temperatureRead
AI 7Burner modulationActual burner modulation, %Read
BI 5FaultsAny boiler fault presentRead
AI 14Fault number 1First active fault codeRead
BI 1Connection to the boilerGateway-to-boiler link; 0 = no connectionRead

Enable & remote start

The BMS writes setpoints through the gateway's writable values: MV 3 picks the heating-mode program (internal value, target modulation, target supply temperature, target supply temperature exclusive, locked), AV 2 is the supply temperature target and AV 1 the modulation target. DHW uses MV 2 and AV 3; heating circuits 1-4 use MV 4-7 and AV 4-7. The boiler only accepts these while MV 1 External demand is written from the BMS (see heartbeat).

Heartbeat & communication loss

With Heartbeat Monitoring enabled (the gateway default, set in Project Settings), the BMS must write MV 1 External demand with 3 (BACnet) at least every 10 s. The gateway passes it to the boiler and resets MV 1 to 1; if the writes stop, the boiler goes back to its internal setpoints. With monitoring disabled MV 1 must still be written once, and the boiler keeps the last BMS setpoints after a communication loss.

Network setup

Watch out for

Viessmann Vitocrossal 200 CI2 (WAGO Automation Gateway) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

129 of 129 shown
Type
Access
Show
Viessmann Vitocrossal 200 CI2 (WAGO Automation Gateway) BACnet Points List
DescriptionStates
AVmin1Burner modulation, target valueBMS burner modulation target (single boiler only)%Write
AVmin2Target supply temperatureBMS boiler supply temperature target°F/°CWrite
AV3Target DHW temp.BMS domestic hot water temperature target°F/°CWrite
AV4Heating circuit 1: Target temp.Heating circuit 1: BMS supply or room temperature target°F/°CWrite
AV5Heating circuit 2: Target temp.Heating circuit 2: BMS supply or room temperature target°F/°CWrite
AV6Heating circuit 3: Target temp.Heating circuit 3: BMS supply or room temperature target°F/°CWrite
AV7Heating circuit 4: Target temp.Heating circuit 4: BMS supply or room temperature target°F/°CWrite
MVmin1External demandRequesting system / BMS heartbeat; see heartbeat notesWrite0=External demand: No connection, 1=DIO module connection is being established, 2=BACnet connection is being established, 3=KNX connection is being established, 4=Modbus connection is being established, 5=EEBus connection is being established, 6=Plug connection is being established
MV2Domestic hot water operating program: TargetBMS operating program for DHW heatingWrite0=Internal target value, 1=OFF, 2=ON, 3=Target supply temperature, 4=Target boiler modulation
MVmin3Boiler operating program: TargetBMS operating program for heating modeWrite0=Internal target value, 1=Target boiler modulation, 2=Target supply temperature, 3=Target supply temperature exclusive, 4=Locked
MV4Heating circuit 1 targetHeating circuit 1: BMS operating programWrite0=None, 1=Off, 2=Reduced, 3=Normal, 4=Comfort, 5=Target supply temperature, 6=Target room temperature
MV5Heating circuit 2 targetHeating circuit 2: BMS operating programWrite0=None, 1=Off, 2=Reduced, 3=Normal, 4=Comfort, 5=Target supply temperature, 6=Target room temperature
MV6Heating circuit 3 targetHeating circuit 3: BMS operating programWrite0=None, 1=Off, 2=Reduced, 3=Normal, 4=Comfort, 5=Target supply temperature, 6=Target room temperature
MV7Heating circuit 4 targetHeating circuit 4: BMS operating programWrite0=None, 1=Off, 2=Reduced, 3=Normal, 4=Comfort, 5=Target supply temperature, 6=Target room temperature
BV1Acknowledge maintenanceAcknowledge the maintenance messageWrite0=No, 1=Yes
AImin1Supply temperaturePrimary circuit supply temperature after the boiler°F/°CRead
AI2Outside temperatureOutdoor temperature°F/°CRead
AI4Flue gas temperatureFlue gas temperature at the chimney inlet°F/°CRead
AI5Primary circuit pump, target speedPrimary circuit pump target speed%Read
AI6Thermal outputCurrent thermal outputkWRead
AImin7Burner modulationActual burner modulation%Read
AI8Burner hours runBoiler total hours runhRead
AI9Burner runtimeBoiler operating hourshRead
AI10Burner startsBoiler total burner startsRead
AI11DHW temperatureActual DHW tank temperature°F/°CRead
AI12Hot water temperature status: Target domestic hot water temperatureTarget DHW tank temperature°F/°CRead
AI13Maintenance numberMaintenance codeRead
AImin14Fault number 1Fault code 1 (see boiler service instructions)Read
AI15Fault number 2Fault code 2 (see boiler service instructions)Read
AI16Fault number 3Fault code 3 (see boiler service instructions)Read
AI17Fault number 4Fault code 4 (see boiler service instructions)Read
AI18Fault number 5Fault code 5 (see boiler service instructions)Read
AI19Fault number 6Fault code 6 (see boiler service instructions)Read
AI20Fault number 7Fault code 7 (see boiler service instructions)Read
AI21Fault number 8Fault code 8 (see boiler service instructions)Read
AI22Fault number 9Fault code 9 (see boiler service instructions)Read
AI23Fault number 10Fault code 10 (see boiler service instructions)Read
AI24Heating energy consumption: TodayHeating electrical energy use, todaykWhRead
AI25Electrical energy consumption of heating system: The last 7 daysHeating electrical energy use, last 7 dayskWhRead
AI26Electrical energy consumption of heating system: The current monthHeating electrical energy use, current monthkWhRead
AI27Electrical energy consumption of heating system: The last monthHeating electrical energy use, last monthkWhRead
AI28Electrical energy consumption of heating system: The current yearHeating electrical energy use, current yearkWhRead
AI29Electrical energy consumption of heating system: The last yearHeating electrical energy use, last yearkWhRead
AI30DHW energy consumption: TodayDHW electrical energy use, todaykWhRead
AI31Electrical energy consumption of DHW: The last 7 daysDHW electrical energy use, last 7 dayskWhRead
AI32Electrical energy consumption of DHW heating: The current monthDHW electrical energy use, current monthkWhRead
AI33Electrical energy consumption of the DHW heating: The last monthDHW electrical energy use, last monthkWhRead
AI34Electrical energy consumption of DHW heating: The current yearDHW electrical energy use, current yearkWhRead
AI35Electrical energy consumption of the DHW heating: The last yearDHW electrical energy use, last yearkWhRead
AI36Heating gas consumption: TodayHeating gas use, todaym³Read
AI37Gas consumption of heating system: The last 7 daysHeating gas use, last 7 daysm³Read
AI38Gas consumption of heating system: The current monthHeating gas use, current monthm³Read
AI39Gas consumption of heating system: The last monthHeating gas use, last monthm³Read
AI40Gas consumption of heating system: The current yearHeating gas use, current yearm³Read
AI41Gas consumption of heating system: The last yearHeating gas use, last yearm³Read
AI42DHW gas consumption: TodayDHW gas use, todaym³Read
AI43Gas consumption of DHW: The last 7 daysDHW gas use, last 7 daysm³Read
AI44Gas consumption of DHW: The current monthDHW gas use, current monthm³Read
AI45Gas consumption of DHW: The last monthDHW gas use, last monthm³Read
AI46Gas consumption of DHW: The current yearDHW gas use, current yearm³Read
AI47Gas consumption of DHW: The last yearDHW gas use, last yearm³Read
AI81Heating circuit 1: Target temperatureHeating circuit 1: target supply or room temperature°F/°CRead
AI82Heating circuit 1: Supply temperatureHeating circuit 1: actual supply temperature°F/°CRead
AI83Heating circuit 2: Target temperatureHeating circuit 2: target supply or room temperature°F/°CRead
AI84Heating circuit 2: Supply temperatureHeating circuit 2: actual supply temperature°F/°CRead
AI85Heating circuit 3: Target temperatureHeating circuit 3: target supply or room temperature°F/°CRead
AI86Heating circuit 3: Supply temperatureHeating circuit 3: actual supply temperature°F/°CRead
AI87Heating circuit 4: Target temperatureHeating circuit 4: target supply or room temperature°F/°CRead
AI88Heating circuit 4: Supply temperatureHeating circuit 4: actual supply temperature°F/°CRead
AI89Boiler target modulation valueTarget burner modulation%Read
AI90Heating circuit 1: Room temperatureHeating circuit 1: room temperature sensor°F/°CRead
AI91Heating circuit 2: Room temperatureHeating circuit 2: room temperature sensor°F/°CRead
AI92Heating circuit 3: Room temperatureHeating circuit 3: room temperature sensor°F/°CRead
AI93Heating circuit 4: Room temperatureHeating circuit 4: room temperature sensor°F/°CRead
AI94Low loss header: Supply temperatureLow loss header supply temperature°F/°CRead
AI95Temperature demandTemperature demand on the boiler°F/°CRead
AI96Modulation demandModulation demand on the boiler%Read
AI97Boiler: Boiler 1 sequenceCascade switch-on/off position of boiler 1Read
AI98Boiler: Boiler 2 sequenceCascade switch-on/off position of boiler 2Read
AI99Boiler: Boiler 3 sequenceCascade switch-on/off position of boiler 3Read
AI100Boiler: Boiler 4 sequenceCascade switch-on/off position of boiler 4Read
AI101Boiler: Boiler 5 sequenceCascade switch-on/off position of boiler 5Read
AI102Boiler: Boiler 6 sequenceCascade switch-on/off position of boiler 6Read
AI103Boiler: Boiler 7 sequenceCascade switch-on/off position of boiler 7Read
AI104Boiler: Boiler 8 sequenceCascade switch-on/off position of boiler 8Read
AI105Boiler: Boiler 9 sequenceCascade switch-on/off position of boiler 9Read
AI106Boiler: Boiler 10 sequenceCascade switch-on/off position of boiler 10Read
AI107Boiler: Boiler 11 sequenceCascade switch-on/off position of boiler 11Read
AI108Boiler: Boiler 12 sequenceCascade switch-on/off position of boiler 12Read
AI109Boiler: Boiler 13 sequenceCascade switch-on/off position of boiler 13Read
AI110Boiler: Boiler 14 sequenceCascade switch-on/off position of boiler 14Read
AI111Boiler: Boiler 15 sequenceCascade switch-on/off position of boiler 15Read
AI112Boiler: Boiler 16 sequenceCascade switch-on/off position of boiler 16Read
AI113O2 value of burner 1Burner 1 O2 probe value (diagnostics)%Read
AI114Target O2 value, burner 1Burner 1 target O2 value (diagnostics)%Read
AI115Modulation burner 2Burner 2 actual modulation%Read
AI116Burner runtime, burner 2Burner 2 operating hourshRead
AI117Starts burner 2Burner 2 startsRead
AI118O2 value of burner 2Burner 2 O2 probe value (diagnostics)%Read
AI119Target O2 value, burner 2Burner 2 target O2 value (diagnostics)%Read
BImin1Connection to the boilerCAN link between gateway and boilerRead0=No connection, 1=Connection active
BImin2BurnerBurner flame on/offRead0=On, 1=Off
BI3DHW pumpDHW tank charging pump on/offRead0=OFF, 1=ON
BI4Service messagesMaintenance message presentRead0=No maintenance message present, 1=Maintenance message present
BImin5FaultsFault presentRead0=No fault present, 1=Fault present
BI6Heating circuit pump HC1Heating circuit 1 pump on/offRead0=OFF, 1=ON
BI7Heating circuit pump HC2Heating circuit 2 pump on/offRead0=OFF, 1=ON
BI8Heating circuit pump HC3Heating circuit 3 pump on/offRead0=OFF, 1=ON
BI9Heating circuit pump HC4Heating circuit 4 pump on/offRead0=OFF, 1=ON
BI10Heating zone 1: DemandHeating zone 1 call for heatRead0=Off, 1=On
BI11Heating zone 2: DemandHeating zone 2 call for heatRead0=Off, 1=On
BI12Heating zone 3: DemandHeating zone 3 call for heatRead0=Off, 1=On
BI13Units not available in the cascadeUnit not available in the cascadeRead0=No, 1=Yes
BI14Boiler circuit pumpPrimary / boiler circuit pump on/offRead0=Off, 1=On
BI15Hydraulic flap stateHydraulic flap open/closedRead0=Closed, 1=Open
BI16Flame burner 2Burner 2 flame on/offRead0=Off, 1=ON
MI1External demand: StatusStatus of the external demand connectionRead0=External demand: No connection, 1=DIO module connection is being established, 2=BACnet connection is being established, 3=KNX connection is being established, 4=Modbus connection is being established, 5=EEBus connection is being established, 6=Plug connection is being established
MI2Domestic hot water operating program: ActualDHW heating operating program in useRead0=Internal target value, 1=OFF, 2=ON, 3=Target supply temperature, 4=Target boiler modulation
MI3Boiler operating program: ActualHeating mode operating program in useRead0=Internal target value, 1=Target boiler modulation, 2=Target supply temperature, 3=Target supply temperature exclusive, 4=Locked
MI4Heating circuit 1 actualHeating circuit 1: operating program in useRead0=None, 1=Off, 2=Reduced, 3=Normal, 4=Comfort, 5=Target supply temperature, 6=Target room temperature
MI5Heating circuit 2 actualHeating circuit 2: operating program in useRead0=None, 1=Off, 2=Reduced, 3=Normal, 4=Comfort, 5=Target supply temperature, 6=Target room temperature
MI6Heating circuit 3 actualHeating circuit 3: operating program in useRead0=None, 1=Off, 2=Reduced, 3=Normal, 4=Comfort, 5=Target supply temperature, 6=Target room temperature
MI7Heating circuit 4 actualHeating circuit 4: operating program in useRead0=None, 1=Off, 2=Reduced, 3=Normal, 4=Comfort, 5=Target supply temperature, 6=Target room temperature
MI8Domestic hot water statusDHW heating statusRead0=OFF, 1=DHW only, 2=DHW and heating, 3=Emissions test mode WW, 4=Test mode, 5=External target temperature, 6=External target modulation, 7=Hygiene function, 8=Solar operation, FF=Automatic
MI10Heating zone 1: Heating zone pumpHeating zone 1 pump stateRead0=Off, 1=On, 2=Short circuit/lead break
MI11Heating zone 2: Heating zone pumpHeating zone 2 pump stateRead0=Off, 1=On, 2=Short circuit/lead break
MI12Heating zone 3: Heating zone pumpHeating zone 3 pump stateRead0=Off, 1=On, 2=Short circuit/lead break
MI13Type of demandKind of demand on the boilerRead0=None, 1=Temperature demand, 2=Modulation demand
MI14Thermostat switching stateThermostat switching state (plug 96)Read0=Off, 1=On, 2=Short circuit/lead break

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Vitocrossal 200 CI2 (WAGO Automation Gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Viessmann Vitocrossal 200 CI2 (WAGO Automation Gateway)

How many BACnet points does the Viessmann Vitocrossal 200 CI2 (WAGO Automation Gateway) have?

This list has 129 BACnet objects: 85 analog inputs, 7 analog values, 16 binary inputs, 1 binary value, 13 multi-state inputs, 7 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Viessmann Vitocrossal 200 CI2 (WAGO Automation Gateway) BACnet points are writable?

15 of the 129 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Viessmann Vitocrossal 200 CI2 (WAGO Automation Gateway) BACnet documentation?

The source is WAGO Gateway Data Points - Communication to a building management system (Vitocrossal 200 CI2) (6178 508-05), revision 01/2025, published free by Viessmann at https://www.viessmann-us.com/content/dam/public-brands/ca/pdfs/doc/wago/wago_gateway_vitocrossal_tdm.pdf/_jcr_content/renditions/original./wago_gateway_vitocrossal_tdm.pdf.

What are the minimum BACnet points to integrate the Viessmann Vitocrossal 200 CI2 (WAGO Automation Gateway)?

Start with MV 3 Boiler operating program: Target (Heating program: internal, modulation, supply temp, locked); AV 2 Target supply temperature (Boiler supply temperature setpoint); AV 1 Burner modulation, target value (Burner modulation command, 0-100 %; single boiler only); MV 1 External demand (Write 3 (BACnet) every 10 s or BMS setpoints drop); BI 2 Burner (Flame status; list prints 0 = On, 1 = Off); AI 1 Supply temperature (Boiler supply water temperature); AI 7 Burner modulation (Actual burner modulation, %); BI 5 Faults (Any boiler fault present); AI 14 Fault number 1 (First active fault code); BI 1 Connection to the boiler (Gateway-to-boiler link; 0 = no connection).

How do I enable BMS control of the Viessmann Vitocrossal 200 CI2 (WAGO Automation Gateway)?

The BMS writes setpoints through the gateway's writable values: MV 3 picks the heating-mode program (internal value, target modulation, target supply temperature, target supply temperature exclusive, locked), AV 2 is the supply temperature target and AV 1 the modulation target. DHW uses MV 2 and AV 3; heating circuits 1-4 use MV 4-7 and AV 4-7. The boiler only accepts these while MV 1 External demand is written from the BMS (see heartbeat).

Does the Viessmann Vitocrossal 200 CI2 (WAGO Automation Gateway) need a BACnet heartbeat or have a communication timeout?

With Heartbeat Monitoring enabled (the gateway default, set in Project Settings), the BMS must write MV 1 External demand with 3 (BACnet) at least every 10 s. The gateway passes it to the boiler and resets MV 1 to 1; if the writes stop, the boiler goes back to its internal setpoints. With monitoring disabled MV 1 must still be written once, and the boiler keeps the last BMS setpoints after a communication loss.

How do I check these points on the real Vitocrossal 200 CI2 (WAGO Automation Gateway)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.