Variable frequency drive (HVAC fan and pump) · BACnet points list

Toshiba International Q9 Plus ASD (embedded BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The Q9 Plus has BACnet MS/TP on the terminal board's S4 RJ-45 (RS-485) connector when F829 = 2 (BACnet). The object list covers the terminal inputs and relay outputs, status and command BVs (run/stop, direction, fault reset, preset speeds and command/frequency source overrides), the analog inputs and outputs, and AVs for drive monitors, Virtual Linear Pump values, frequency reference, fault codes and ramp times.

This page lists 64 BACnet objects for the Toshiba International Q9 Plus ASD (embedded BACnet MS/TP) — 17 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Toshiba International’s own free documentation, linked below.

Manufacturer
Toshiba International
Model
Q9 Plus ASD (embedded BACnet MS/TP)
Equipment
Variable frequency drive (HVAC fan and pump)
Equipment type
VFDs & pumps
BACnet objects
64 (17 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
Q9 Plus, Q9+, Q9 Plus ASD, Toshiba Q9 Plus, Q9 Plus adjustable speed drive, TIC Q9 Plus BACnet
Source document
Q9 Plus ASD Installation and Operation Manual, BACnet Setup: BACnet I/O, and Values (Tables 4-8) · rev. 2020-04
Download CSV 64 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Toshiba International’s current documentation and the live device before use. Not official Toshiba International information. Terms of use.

BMS integration notes: Toshiba International Q9 Plus ASD (embedded BACnet MS/TP)

Integration in brief

Set both SW200 switches ON, F802 to a unique station number, F827 = 0 (no parity) and F829 = 2 (BACnet), then reset with F899. Select RS485/BACnet as the command source (F003) and frequency source (F004), or use BV 22/BV 21 to override them. Write BV 10 Run/Stop Cmd and AV 16 Freq Ref, and read BV 0, AV 1, AV 4 and BV 2.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10Run/Stop CmdStart/stop commandCommand
BV 22Cmd OvrdOverrides F003 command sourceCommand
AV 16Freq RefFrequency reference, HzCommand
BV 21Freq OvrdOverrides F004 frequency sourceCommand
BV 14Fault ResetReset a tripped driveCommand
BV 0Run/Stop StatusRunning statusRead
AV 1Output FreqOutput frequency, HzRead
AV 4Output CurrentMotor ampsRead
BV 2Fault StatusAny active drive faultRead
AV 18Last FltActive fault codeRead

Enable & remote start

Run commands follow F003 Command Source (3 = RS485/BACnet) and speed follows F004 Frequency Command Source (6 = RS485/BACnet). BV 22 Cmd Ovrd and BV 21 Freq Ovrd override those selections from the network. BV 4 shows whether the drive is in local control.

Heartbeat & communication loss

F803 Communications Time-Out (0-100 s, default 0 = off) sets how long the RS-485 link may be idle; F804 Time-Out Action (default Trip/Trip) sets whether the drive does nothing, alarms or trips. Both need a power cycle to take effect.

Network setup

Watch out for

Toshiba International Q9 Plus ASD (embedded BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

64 of 64 shown
Type
Access
Show
Toshiba International Q9 Plus ASD (embedded BACnet MS/TP) BACnet Points List
DescriptionStates
BI0FL StatusFL fault relay state (Any Fault, NC)ReadOn/Off
BI1OUT 1 StatusOUT 1 relay state (Open Damper Command)ReadOn/Off
BI2OUT 2 StatusOUT 2 relay state (Acc or Dec Complete)ReadOn/Off
BI3R2 StatusR2 relay state (expansion I/O)ReadOn/Off
BI4OUT 5 StatusOUT 5 open collector state (expansion I/O)ReadOn/Off
BI5OUT 6 StatusOUT 6 open collector state (expansion I/O)ReadOn/Off
BI6F StatusF input (Forward Run Command)ReadOn/Off
BI7R StatusR input (Reverse Run Command)ReadOn/Off
BI8ST StatusST input (Standby Command)ReadOn/Off
BI9RES StatusRES input (Fault Reset Command)ReadOn/Off
BI10S1 StatusS1 input (Fire-speed Command)ReadOn/Off
BI11S2 StatusS2 input (Preset Speed Bit 2)ReadOn/Off
BI12S3 StatusS3 input (Damper Closed Feedback)ReadOn/Off
BI13S4 StatusS4 input (Emergency Off, NC)ReadOn/Off
BI14LI5 StatusLI5 input (expansion I/O)ReadOn/Off
BI15LI6 StatusLI6 input (expansion I/O)ReadOn/Off
BI16LI7 StatusLI7 input (expansion I/O)ReadOn/Off
BI17LI8 StatusLI8 input (expansion I/O)ReadOn/Off
BVmin0Run/Stop StatusDrive runningReadRuns/Ready
BV1Fwd/Rev StatusRotation directionReadRev/Fwd
BVmin2Fault StatusDrive faultedReadFaulted/None
BV4Local/Remote StatusDrive under local controlReadLocal/Remote
BV6Maint ReqCumulative run timer expiredReadYes/No
BV7Drive ReadyReady to run (ST and run command)ReadReady/Not Ready
BV8At Set-PointTarget speed reachedReadReached/No
BVmin10Run/Stop CmdStart/stop commandCommandStart/Stop
BV11Fwd/Rev CmdRotation direction commandCommandRev/Fwd
BVmin14Fault ResetFault reset commandCommandReset/No
BV18Preset Spd 1Preset Speed 1 commandCommandSP1/None
BV19Preset Spd 2Preset Speed 2 commandCommandSP2/None
BV20Preset Spd 3Preset Speed 3 commandCommandSP3/None
BVmin21Freq OvrdOverrides the Frequency Mode 1 (F004) selectionCommandEnabled/Off
BVmin22Cmd OvrdOverrides the Command Mode (F003) selectionCommandEnabled/Off
AI0RR LevelRR analog input level% of full scaleRead
AI1V/I LevelV/I analog input level% of full scaleRead
AI2RX LevelRX analog input level% of full scaleRead
AI3AI1 LevelAI1 input level (expansion I/O)% of full scaleRead
AI4AI2 LevelAI2 input level (expansion I/O)% of full scaleRead
AO0FM CommandFM analog output level; needs F005 = Data From Comm% of full scaleWrite
AO1AM CommandAM analog output level; needs F670 = Data From Comm% of full scaleWrite
AO2MON1 CommandMON1 output level (expansion I/O); F672 = Data From Comm% of full scaleWrite
AO3MON2 CommandMON2 output level (expansion I/O); F674 = Data From Comm% of full scaleWrite
AV0Output SpeedOutput speed (output freq / base freq x motor rpm)rpmRead
AVmin1Output FreqOutput frequencyHzRead
AV2DC Bus VoltDC bus voltageVRead
AV3Output VoltOutput voltage to the motorVRead
AVmin4Output CurrentMotor currentARead
AV5Output TorqueMotor torque%Read
AV6Input PowerPower drawn by the drivekWRead
AV7Output PowerPower delivered to the motorkWRead
AV8Total Input PowerCumulative drive input energykWhRead
AV9Total Output PowerCumulative motor output energykWhRead
AV10PID FbckPID feedback valueHzRead
AV11Run TimeTotal operating timehRead
AV12VLP Technology AverageVirtual Linear Pump average operating numberRead
AV13VLP Technology FeedbackVirtual Linear Pump process feedbackRead
AV14VLP Technology Direct RefVirtual Linear Pump direct mode command referenceCommand
AV15VLP Technology Process Hold RefVirtual Linear Pump process hold mode referenceCommand
AVmin16Freq RefFrequency referenceHzCommand
AVmin18Last FltCurrent fault codeRead
AV19Prev Flt 1Most recent fault codeRead
AV20Prev Flt 2Second most recent fault codeRead
AV23Accel Time 1Acceleration Time 1 (F009)sWrite
AV24Decel Time 1Deceleration Time 1 (F010)sWrite
Object ID lookup: Toshiba International Q9 Plus ASD point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Q9 Plus ASD (embedded BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Toshiba International Q9 Plus ASD (embedded BACnet MS/TP)

How many BACnet points does the Toshiba International Q9 Plus ASD (embedded BACnet MS/TP) have?

This list has 64 BACnet objects: 5 analog inputs, 4 analog outputs, 22 analog values, 18 binary inputs, 15 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Toshiba International Q9 Plus ASD (embedded BACnet MS/TP) BACnet points are writable?

17 of the 64 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Toshiba International Q9 Plus ASD (embedded BACnet MS/TP) BACnet documentation?

The source is Q9 Plus ASD Installation and Operation Manual, BACnet Setup: BACnet I/O, and Values (Tables 4-8), revision 2020-04, published free by Toshiba International at https://toshiba.com/tic/wp-content/uploads/Q9_Plus_ASD_Installation_and_Operation_Manual.pdf.

What are the minimum BACnet points to integrate the Toshiba International Q9 Plus ASD (embedded BACnet MS/TP)?

Start with BV 10 Run/Stop Cmd (Start/stop command); BV 22 Cmd Ovrd (Overrides F003 command source); AV 16 Freq Ref (Frequency reference, Hz); BV 21 Freq Ovrd (Overrides F004 frequency source); BV 14 Fault Reset (Reset a tripped drive); BV 0 Run/Stop Status (Running status); AV 1 Output Freq (Output frequency, Hz); AV 4 Output Current (Motor amps); BV 2 Fault Status (Any active drive fault); AV 18 Last Flt (Active fault code).

How do I enable BMS control of the Toshiba International Q9 Plus ASD (embedded BACnet MS/TP)?

Run commands follow F003 Command Source (3 = RS485/BACnet) and speed follows F004 Frequency Command Source (6 = RS485/BACnet). BV 22 Cmd Ovrd and BV 21 Freq Ovrd override those selections from the network. BV 4 shows whether the drive is in local control.

Does the Toshiba International Q9 Plus ASD (embedded BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

F803 Communications Time-Out (0-100 s, default 0 = off) sets how long the RS-485 link may be idle; F804 Time-Out Action (default Trip/Trip) sets whether the drive does nothing, alarms or trips. Both need a power cycle to take effect.

How do I check these points on the real Q9 Plus ASD (embedded BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Q9 Plus ASD Installation and Operation Manual, BACnet Setup: BACnet I/O, and Values (Tables 4-8) · rev. 2020-04. Object names, instances and units are reproduced as published; descriptions are our own.