Energy recovery ventilator (ERV) · BACnet points list

Tempeff RGSP-K ERV with optional BACnet field device BACnet points list

Updated 12 November 2026

Short answer

The RGSP-K has no native BACnet; an optional Functional Devices BACnet RIB relay module wired to the unit terminal strip gives a BMS four binary outputs (enable, heat recovery / free cooling, fan speed) and four binary inputs (fan / damper status, furnace interlock, two spare dry contacts) over BACnet MS/TP.

This page lists 8 BACnet objects for the Tempeff RGSP-K ERV with optional BACnet field device — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Tempeff’s own free documentation, linked below.

Manufacturer
Tempeff
Model
RGSP-K ERV with optional BACnet field device
Equipment
Energy recovery ventilator (ERV)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
8 (4 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
277XXX (XXX = MS/TP address)
Also known as
RGSP-K, Tempeff RGSP-K, RGSP-K BACnet
Source document
RGSP-K Series Installation Manual · rev. July 2025
Download CSV 8 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Tempeff’s current documentation and the live device before use. Not official Tempeff information. Terms of use.

BMS integration notes: Tempeff RGSP-K ERV with optional BACnet field device

Integration in brief

Enable the unit with BO 1, choose heat recovery or free cooling with BO 2 and high or low fan speed with BO 3; read BI 1 for high speed / damper alarm and BI 2 for the furnace / AHU interlock.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1BINARY_OUTPUT:1Unit enable (on = run)Write
BO 2BINARY_OUTPUT:2On = heat recovery, off = free coolingWrite
BO 3BINARY_OUTPUT:3On = high speed, off = low speedWrite
BI 1BINARY_INPUT:1High speed; 2 s flashing = damper alarmRead
BI 2BINARY_INPUT:2Furnace / AHU interlock statusRead

Enable & remote start

BO 1 enables the unit.

Network setup

Watch out for

Tempeff RGSP-K ERV with optional BACnet field device BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

8 of 8 shown
Type
Access
Show
Tempeff RGSP-K ERV with optional BACnet field device BACnet Points List
DescriptionStates
BOmin1BINARY_OUTPUT:1Unit enableWriteOn = enable
BOmin2BINARY_OUTPUT:2Heat recovery / free cooling selectWriteOn = Heat Recovery, Off = Free Cooling
BOmin3BINARY_OUTPUT:3High / low fan speed selectWriteOn = High Speed, Off = Low Speed
BO4BINARY_OUTPUT:4Not usedWrite
BImin1BINARY_INPUT:1Fans at high speed; flashing = damper alarmReadOn = Fans at High Speed; 2 s on / 2 s off = Damper Alarm
BImin2BINARY_INPUT:2Furnace / AHU interlockRead
BI3BINARY_INPUT:3Spare dry-contact input for other field devicesRead
BI4BINARY_INPUT:4Spare dry-contact input for other field devicesRead
Object ID lookup: Tempeff RGSP-K ERV with optional BACnet field device point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RGSP-K ERV with optional BACnet field device and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Tempeff RGSP-K ERV with optional BACnet field device

How many BACnet points does the Tempeff RGSP-K ERV with optional BACnet field device have?

This list has 8 BACnet objects: 4 binary inputs, 4 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Tempeff RGSP-K ERV with optional BACnet field device BACnet points are writable?

4 of the 8 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Tempeff RGSP-K ERV with optional BACnet field device BACnet documentation?

The source is RGSP-K Series Installation Manual, revision July 2025, published free by Tempeff at https://www.tempeff.com/wp-content/uploads/2022/05/Tempeff-RGSP-K-IOM_July-2025.pdf.

What are the minimum BACnet points to integrate the Tempeff RGSP-K ERV with optional BACnet field device?

Start with BO 1 BINARY_OUTPUT:1 (Unit enable (on = run)); BO 2 BINARY_OUTPUT:2 (On = heat recovery, off = free cooling); BO 3 BINARY_OUTPUT:3 (On = high speed, off = low speed); BI 1 BINARY_INPUT:1 (High speed; 2 s flashing = damper alarm); BI 2 BINARY_INPUT:2 (Furnace / AHU interlock status).

How do I enable BMS control of the Tempeff RGSP-K ERV with optional BACnet field device?

BO 1 enables the unit.

How do I check these points on the real RGSP-K ERV with optional BACnet field device?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: RGSP-K Series Installation Manual · rev. July 2025. Object names, instances and units are reproduced as published; descriptions are our own.