Easy BACnet
  1. Home
  2. BACnet points lists
  3. Starline
  4. AC Critical Power Monitor (CPM) for busway

Busway power meter (critical power monitor) · BACnet points list

Starline AC Critical Power Monitor (CPM) for busway BACnet points list

Updated 12 November 2026

Short answer

The AC CPM meters an infeed and up to six outlets, plus enclosure and node temperatures and breaker status. Its BACnet object list has 405 objects with a write-access level for each: device text fields, infeed voltages, currents, power, energy, demand and min/max values, per-outlet metering, alarm thresholds, hex alarm-status words and breaker status.

This page lists 405 BACnet objects for the Starline AC Critical Power Monitor (CPM) for busway — 254 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Starline’s own free documentation, linked below.

Manufacturer
Starline
Model
AC Critical Power Monitor (CPM) for busway
Equipment
Busway power meter (critical power monitor)
Equipment type
Thermostats, sensors & meters
BACnet objects
405 (254 writable)
Transport
—
Firmware
v4.26, v4.26A, v5.07 (list also valid for v4.21-v4.24 and v5.02-v5.05)
Also known as
AC CPM, Starline AC CPM, Starline CPM, Critical Power Monitor, Legrand Starline CPM
Source document
AC CPM BACNet Object List · Rev 4 · rev. 2023-03-03
Download CSV 405 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Starline’s current documentation and the live device before use. Not official Starline information. Terms of use.

BMS integration notes: Starline AC Critical Power Monitor (CPM) for busway

Integration in brief

Read the infeed totals (energy, active power, average current and voltage, power factor) and the per-line currents, plus the infeed and outlet alarm status words. Add per-outlet metering for each plug-in unit you need to bill or monitor.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
LAV 17INFEED TOTAL ENERGYTotal infeed energy, kWhRead
LAV 1INFEED TOTAL ACTIVE POWERTotal infeed active power, WRead
AI 3INFEED LINE CURRENT AVERAGEAverage infeed line current, ARead
AI 9INFEED LINE CURRENTInfeed current, line 1, ARead
AI 10INFEED LINE CURRENTInfeed current, line 2, ARead
AI 11INFEED LINE CURRENTInfeed current, line 3, ARead
AI 1LINE TO NEUTRAL VOLTAGE AVERAGEAverage line-to-neutral voltage, VRead
AI 4INFEED TOTAL POWER FACTORTotal power factorRead
PIV 4INFEED ALARM STATUSInfeed alarm status bitsRead
PIV 5OUTLET ALARM STATUSOutlet 1-4 alarm status bitsRead

Watch out for

Starline AC Critical Power Monitor (CPM) for busway BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

405 of 405 shown
Type
Binary
Access
Show
Starline AC Critical Power Monitor (CPM) for busway BACnet Points List
DescriptionStates
PIV1LCD POWER DOWN TIMELCD power down timeSecondsWrite
PIV2LCD BACKLIGHT LEVELLCD backlight levelWrite
PIV3LCD SLIDESHOW SPEEDslideshow speedWrite
CSV1DEVICE IDDevice ID (Admin level)Write
CSV2DEVICE NAMEDevice Name (Admin level)Write
CSV3DEVICE LOCATIONDevice Location (Admin level)Write
CSV4VENDOR NAMEVendor NameRead
CSV5MODEL NUMBERModel Number IDRead
CSV6SERIAL NUMBERMeter's Serial NumberRead
CSV7PRODUCT SERIAL NUMBERMeter's Product Serial NumberRead
CSV8CATALOG NUMBER/PRODUCT TYPEDevice TypeRead
CSV9HARDWARE VERSIONHardware Part Number and VersionRead
CSV10FIRMWARE VERSION (M22276-116 v1.00)Firmware Part Number and VersionRead
CSV11METER VERSIONMeter VersionRead
CSV12Wi-Fi VERSIONWi-Fi VersionRead
CSV13CALIBRATION DATE (YYYY-MM-DD)Calibration DateRead
AImin1LINE TO NEUTRAL VOLTAGE AVERAGELine to Neutral Voltage AverageVoltsRead
AI2LINE TO LINE VOLTAGE AVERAGELine to Line Voltage AverageVoltsRead
AImin3INFEED LINE CURRENT AVERAGEInfeed Line Current AverageAmpsRead
AV1INFEED LINE CURRENT RATINGInfeed Line Current Rating (Admin level)AmpsWrite
AV2INFEED TOTAL LINE CURRENT DEMANDInfeed Current Demand (uses line current to determine demand)AmpsWrite
AV3INFEED TOTAL LINE CURRENT PEAK DEMANDInfeed Current Peak DemandAmpsWrite
AV4INFEED DEMAND TIMEInfeed Demand IntervalMinutesWrite
LAVmin1INFEED TOTAL ACTIVE POWERInfeed Total Active PowerWRead
LAV2INFEED PEAK TOTAL ACTIVE POWERInfeed Peak Total Active PowerWWrite
AV5INFEED TOTAL ACTIVE POWER DEMANDInfeed Total Active Power DemandWWrite
AV6INFEED PEAK TOTAL ACTIVE POWER DEMANDInfeed Peak Total Active Power DemandWWrite
LAV3INFEED TOTAL REACTIVE POWERInfeed Total Reactive PowerVARRead
AV7INFEED TOTAL REACTIVE POWER DEMANDInfeed Total Reactive PowerVARWrite
AV8INFEED PEAK TOTAL REACTIVE POWER DEMANDInfeed Total Reactive PowerVARWrite
LAV4INFEED TOTAL APPARENT POWERInfeed Total Apparent PowerVARead
AV9INFEED TOTAL APPARENT POWER DEMANDInfeed Total Apparent Power DemandVAWrite
AV10INFEED PEAK TOTAL APPARENT POWER DEMANDInfeed Peak Total Apparent Power DemandVAWrite
AImin4INFEED TOTAL POWER FACTORTotal Power FactorRead
PIVmin4INFEED ALARM STATUSinfeed alarm status (hex bit field)Read
AI5FREQUENCYFrequencyHertzRead
AI6LINE TO LINE VOLTAGELine to Line Voltage L1-L2VoltsRead
AI7LINE TO LINE VOLTAGELine to Line Voltage L2-L3VoltsRead
AI8LINE TO LINE VOLTAGELine to Line Voltage L3-L1VoltsRead
AImin9INFEED LINE CURRENTInfeed Line Current Line 1AmpsRead
AImin10INFEED LINE CURRENTInfeed Line Current Line 2AmpsRead
AImin11INFEED LINE CURRENTInfeed Line Current Line 3AmpsRead
AI12INFEED LINE CURRENTInfeed Line Current Calculated NeutralAmpsRead
AI13INFEED LINE CURRENTInfeed Line Current Measured NeutralAmpsRead
AV11INFEED LINE CURRENT MINIMUMInfeed Line Current Minimum Line 1AmpsWrite
AV12INFEED LINE CURRENT MINIMUMInfeed Line Current Minimum Line 2AmpsWrite
AV13INFEED LINE CURRENT MINIMUMInfeed Line Current Minimum Line 3AmpsWrite
AV14INFEED LINE CURRENT MINIMUMInfeed Line Current Maximum Calculated NeutralAmpsWrite
AV15INFEED LINE CURRENT MINIMUMInfeed Line Current Maximum Measured NeutralAmpsWrite
AV16INFEED LINE CURRENT MAXIMUMInfeed Line Current Maximum Line 1AmpsWrite
AV17INFEED LINE CURRENT MAXIMUMInfeed Line Current Maximum Line 2AmpsWrite
AV18INFEED LINE CURRENT MAXIMUMInfeed Line Current Maximum Line 3AmpsWrite
AV19INFEED LINE CURRENT MAXIMUMInfeed Line Current Maximum Calculated NeutralAmpsWrite
AV20INFEED LINE CURRENT MAXIMUMInfeed Line Current Maximum Measured NeutralAmpsWrite
AI14INFEED LINE CURRENT RATING % ofInfeed Line Current % of Rated Line 1PercentRead
AI15INFEED LINE CURRENT RATING % ofInfeed Line Current % of Rated Line 2PercentRead
AI16INFEED LINE CURRENT RATING % ofInfeed Line Current % of Rated Line 3PercentRead
AI17INFEED LINE CURRENT RATING % ofInfeed Line Current % of Rated Calculated NeutralPercentRead
AI18INFEED LINE CURRENT RATING % ofInfeed Line Current % of Rated Measured NeutralPercentRead
AV21INFEED LINE CURRENT MIN ALARMInfeed Line Current Minimum Alarm Line 1AmpsWrite
AV22INFEED LINE CURRENT MIN ALARMInfeed Line Current Minimum Alarm Line 2AmpsWrite
AV23INFEED LINE CURRENT MIN ALARMInfeed Line Current Minimum Alarm Line 3AmpsWrite
AV24INFEED LINE CURRENT MIN ALARMInfeed Line Current Minimum Alarm Calculated NeutralAmpsWrite
AV25INFEED LINE CURRENT MIN ALARMInfeed Line Current Minimum Alarm Measured NeutralAmpsWrite
AV26INFEED LINE CURRENT MAX ALARMInfeed Line Current Maximum Alarm Line 1AmpsWrite
AV27INFEED LINE CURRENT MAX ALARMInfeed Line Current Maximum Alarm Line 2AmpsWrite
AV28INFEED LINE CURRENT MAX ALARMInfeed Line Current Maximum Alarm Line 3AmpsWrite
AV29INFEED LINE CURRENT MAX ALARMInfeed Line Current Maximum Alarm Calculated NeutralAmpsWrite
AV30INFEED LINE CURRENT MAX ALARMInfeed Line Current Maximum Alarm Measured NeutralAmpsWrite
AV31INFEED LINE CURRENT DEMANDInfeed Line Current Demand Line 1AmpsWrite
AV32INFEED LINE CURRENT DEMANDInfeed Line Current Demand Line 2AmpsWrite
AV33INFEED LINE CURRENT DEMANDInfeed Line Current Demand Line 3AmpsWrite
AV34INFEED LINE CURRENT DEMANDInfeed Line Current Demand Calculated NeutralAmpsWrite
AV35INFEED LINE CURRENT DEMANDInfeed Line Current Demand Measured NeutralAmpsWrite
AV36INFEED LINE CURRENT PEAK DEMANDInfeed Line Current Peak Demand Line 1AmpsWrite
AV37INFEED LINE CURRENT PEAK DEMANDInfeed Line Current Peak Demand Line 2AmpsWrite
AV38INFEED LINE CURRENT PEAK DEMANDInfeed Line Current Peak Demand Line 3AmpsWrite
AV39INFEED LINE CURRENT PEAK DEMANDInfeed Line Current Peak Demand Calculated NeutralAmpsWrite
AV40INFEED LINE CURRENT PEAK DEMANDInfeed Line Current Peak Demand Measured NeutralAmpsWrite
AI19LINE TO NEUTRAL VOLTAGELine to Neutral Voltage L1-LNVoltsRead
AI20LINE TO NEUTRAL VOLTAGELine to Neutral Voltage L2-NVoltsRead
AI21LINE TO NEUTRAL VOLTAGELine to Neutral Voltage L3-NVoltsRead
AV41LINE TO LINE VOLTAGE MINIMUMLine to Line Voltage Minimum L1-L2VoltsWrite
AV42LINE TO LINE VOLTAGE MINIMUMLine to Line Voltage Minimum L2-L3VoltsWrite
AV43LINE TO LINE VOLTAGE MINIMUMLine to Line Voltage Minimum L3-L1VoltsWrite
AV44LINE TO LINE VOLTAGE MAXIMUMLine to Line Voltage Maximum L1-L2VoltsWrite
AV45LINE TO LINE VOLTAGE MAXIMUMLine to Line Voltage Maximum L2-L3VoltsWrite
AV46LINE TO LINE VOLTAGE MAXIMUMLine to Line Voltage Maximum L3-L1VoltsWrite
AV47LINE TO LINE VOLTAGE MIN ALARMLine to Line Voltage Minimum Alarm L1-L2VoltsWrite
AV48LINE TO LINE VOLTAGE MIN ALARMLine to Line Voltage Minimum Alarm L2-L3VoltsWrite
AV49LINE TO LINE VOLTAGE MIN ALARMLine to Line Voltage Minimum Alarm L3-L1VoltsWrite
AV50LINE TO LINE VOLTAGE MAX ALARMLine to Line Voltage Maximum Alarm L1-L2VoltsWrite
AV51LINE TO LINE VOLTAGE MAX ALARMLine to Line Voltage Maximum Alarm L2-L3VoltsWrite
AV52LINE TO LINE VOLTAGE MAX ALARMLine to Line Voltage Maximum Alarm L3-L1VoltsWrite
AI22INFEED POWER FACTORInfeed Power Factor L1Read
AI23INFEED POWER FACTORInfeed Power Factor L2Read
AI24INFEED POWER FACTORInfeed Power Factor L3Read
LAV5INFEED APPARENT POWERInfeed Apparent Power L1VARead
LAV6INFEED APPARENT POWERInfeed Apparent Power L2VARead
LAV7INFEED APPARENT POWERInfeed Apparent Power L3VARead
LAV8INFEED ACTIVE POWERInfeed Active Power L1WRead
LAV9INFEED ACTIVE POWERInfeed Active Power L2WRead
LAV10INFEED ACTIVE POWERInfeed Active Power L3WRead
AV53INFEED PEAK ACTIVE POWERInfeed Peak Active Power L1WWrite
AV54INFEED PEAK ACTIVE POWERInfeed Peak Active Power L2WWrite
AV55INFEED PEAK ACTIVE POWERInfeed Peak Active Power L3WWrite
LAV11INFEED REACTIVE POWERInfeed Reactive Power L1VARRead
LAV12INFEED REACTIVE POWERInfeed Reactive Power L2VARRead
LAV13INFEED REACTIVE POWERInfeed Reactive Power L3VARRead
LAV14INFEED ENERGYInfeed Energy L1kWhRead
LAV15INFEED ENERGYInfeed Energy L2kWhRead
LAV16INFEED ENERGYInfeed Energy L3kWhRead
LAVmin17INFEED TOTAL ENERGYInfeed Total EnergykWhRead
BV1RESET ALL ENERGY VALUESReset all energy valuesWrite
CSV15OUTLET 2 IDENTIFIEROutlet 2 ID (Admin level)Write
CSV16OUTLET 3 IDENTIFIEROutlet 3 ID (Admin level)Write
CSV17OUTLET 4 IDENTIFIEROutlet 4 ID (Admin level)Write
PIVmin5OUTLET ALARM STATUSOUTLET 1, 2, 3, and 4 alarm status (hex bit field)Read
AI25OUTLET 1 LINE CURRENTOutlet 1, Line Current Line 1AmpsRead
AI26OUTLET 1 LINE CURRENTOutlet 1, Line Current Line 2AmpsRead
AI27OUTLET 1 LINE CURRENTOutlet 1, Line Current Line 3AmpsRead
AI28OUTLET 1 LINE CURRENTOutlet 1, Line Current Line NAmpsRead
AI29OUTLET 2 LINE CURRENTOutlet 2, Line Current Line 1AmpsRead
AI30OUTLET 2 LINE CURRENTOutlet 2, Line Current Line 2AmpsRead
AI31OUTLET 2 LINE CURRENTOutlet 2, Line Current Line 3AmpsRead
AI32OUTLET 2 LINE CURRENTOutlet 2, Line Current Line NAmpsRead
AI33OUTLET 3 LINE CURRENTOutlet 3, Line Current Line 1AmpsRead
AI34OUTLET 3 LINE CURRENTOutlet 3, Line Current Line 2AmpsRead
AI35OUTLET 3 LINE CURRENTOutlet 3, Line Current Line 3AmpsRead
AI36OUTLET 3 LINE CURRENTOutlet 3, Line Current Line NAmpsRead
AI37OUTLET 4 LINE CURRENTOutlet 4, Line Current Line 1AmpsRead
AI38OUTLET 4 LINE CURRENTOutlet 4, Line Current Line 2AmpsRead
AI39OUTLET 4 LINE CURRENTOutlet 4, Line Current Line 3AmpsRead
AI40OUTLET 4 LINE CURRENTOutlet 4, Line Current Line NAmpsRead
AV56OUTLET 1 LINE CURRENT RATINGOutlet 1 Line Current Rating. One rating for each outletAmpsRead
AV57OUTLET 2 LINE CURRENT RATINGOutlet 2 Line Current Rating. One rating for each outletAmpsRead
AV58OUTLET 3 LINE CURRENT RATINGOutlet 3 Line Current Rating. One rating for each outletAmpsRead
AV59OUTLET 4 LINE CURRENT RATINGOutlet 4 Line Current Rating. One rating for each outletAmpsRead
AI41OUTLET 1 LINE CURRENT RATING % ofOutlet 1 Line Current % of Rated Line 1PercentRead
AI42OUTLET 1 LINE CURRENT RATING % ofOutlet 1 Line Current % of Rated Line 2PercentRead
AI43OUTLET 1 LINE CURRENT RATING % ofOutlet 1 Line Current % of Rated Line 3PercentRead
AI44OUTLET 1 LINE CURRENT RATING % ofOutlet 1 Line Current % of Rated Neutral ConductorPercentRead
AI45OUTLET 2 LINE CURRENT RATING % ofOutlet 2 Line Current % of Rated Line 1PercentRead
AI46OUTLET 2 LINE CURRENT RATING % ofOutlet 2 Line Current % of Rated Line 2PercentRead
AI47OUTLET 2 LINE CURRENT RATING % ofOutlet 2 Line Current % of Rated Line 3PercentRead
AI48OUTLET 2 LINE CURRENT RATING % ofOutlet 2 Line Current % of Rated Neutral ConductorPercentRead
AI49OUTLET 3 LINE CURRENT RATING % ofOutlet 3 Line Current % of Rated Line 1PercentRead
AI50OUTLET 3 LINE CURRENT RATING % ofOutlet 3 Line Current % of Rated Line 2PercentRead
AI51OUTLET 3 LINE CURRENT RATING % ofOutlet 3 Line Current % of Rated Line 3PercentRead
AI52OUTLET 3 LINE CURRENT RATING % ofOutlet 3 Line Current % of Rated Neutral ConductorPercentRead
AI53OUTLET 4 LINE CURRENT RATING % ofOutlet 4 Line Current % of Rated Line 1PercentRead
AI54OUTLET 4 LINE CURRENT RATING % ofOutlet 4 Line Current % of Rated Line 2PercentRead
AI55OUTLET 4 LINE CURRENT RATING % ofOutlet 4 Line Current % of Rated Line 3PercentRead
AI56OUTLET 4 LINE CURRENT RATING % ofOutlet 4 Line Current % of Rated Neutral ConductorPercentRead
AV60OUTLET 1 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 1AmpsWrite
AV61OUTLET 1 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 2AmpsWrite
AV62OUTLET 1 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 3AmpsWrite
AV63OUTLET 1 LINE CURRENT MINIMUMOutlet Line Current Minimum Neutral ConductorAmpsWrite
AV64OUTLET 2 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 1AmpsWrite
AV65OUTLET 2 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 2AmpsWrite
AV66OUTLET 2 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 3AmpsWrite
AV67OUTLET 2 LINE CURRENT MINIMUMOutlet Line Current Minimum Neutral ConductorAmpsWrite
AV68OUTLET 3 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 1AmpsWrite
AV69OUTLET 3 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 2AmpsWrite
AV70OUTLET 3 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 3AmpsWrite
AV71OUTLET 3 LINE CURRENT MINIMUMOutlet Line Current Minimum Neutral ConductorAmpsWrite
AV72OUTLET 4 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 1AmpsWrite
AV73OUTLET 4 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 2AmpsWrite
AV74OUTLET 4 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 3AmpsWrite
AV75OUTLET 4 LINE CURRENT MINIMUMOutlet Line Current Minimum Neutral ConductorAmpsWrite
AV76OUTLET 1 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 1AmpsWrite
AV77OUTLET 1 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 2AmpsWrite
AV78OUTLET 1 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 3AmpsWrite
AV79OUTLET 1 LINE CURRENT MAXIMUMOutlet Line Current Maximum Neutral ConductorAmpsWrite
AV80OUTLET 2 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 1AmpsWrite
AV81OUTLET 2 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 2AmpsWrite
AV82OUTLET 2 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 3AmpsWrite
AV83OUTLET 2 LINE CURRENT MAXIMUMOutlet Line Current Maximum Neutral ConductorAmpsWrite
AV84OUTLET 3 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 1AmpsWrite
AV85OUTLET 3 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 2AmpsWrite
AV86OUTLET 3 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 3AmpsWrite
AV87OUTLET 3 LINE CURRENT MAXIMUMOutlet Line Current Maximum Neutral ConductorAmpsWrite
AV88OUTLET 4 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 1AmpsWrite
AV89OUTLET 4 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 2AmpsWrite
AV90OUTLET 4 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 3AmpsWrite
AV91OUTLET 4 LINE CURRENT MAXIMUMOutlet Line Current Maximum Neutral ConductorAmpsWrite
AV92OUTLET CURRENT MIN ALARMOutlet 1 Current Minimum AlarmAmpsWrite
AV93OUTLET CURRENT MIN ALARMOutlet 2 Current Minimum AlarmAmpsWrite
AV94OUTLET CURRENT MIN ALARMOutlet 3 Current Minimum AlarmAmpsWrite
AV95OUTLET CURRENT MIN ALARMOutlet 4 Current Minimum AlarmAmpsWrite
AV96OUTLET CURRENT MAX ALARMOutlet 1 Current Maximum AlarmAmpsWrite
AV97OUTLET CURRENT MAX ALARMOutlet 2 Current Maximum AlarmAmpsWrite
AV98OUTLET CURRENT MAX ALARMOutlet 3 Current Maximum AlarmAmpsWrite
AV99OUTLET CURRENT MAX ALARMOutlet 4 Current Maximum AlarmAmpsWrite
AV100OUTLET 1 DEMAND TIMEOutlet 1 Demand TimeMinutesWrite
AV101OUTLET 2 DEMAND TIMEOutlet 2 Demand TimeMinutesWrite
AV102OUTLET 3 DEMAND TIMEOutlet 3 Demand TimeMinutesWrite
AV103OUTLET 4 DEMAND TIMEOutlet 4 Demand TimeMinutesWrite
LAV18OUTLET 1 TOTAL ACTIVE POWEROutlet 1 Total Active PowerWRead
LAV19OUTLET 2 TOTAL ACTIVE POWEROutlet 2 Total Active PowerWRead
LAV20OUTLET 3 TOTAL ACTIVE POWEROutlet 3 Total Active PowerWRead
LAV21OUTLET 4 TOTAL ACTIVE POWEROutlet 4 Total Active PowerWRead
LAV22OUTLET 1 PEAK TOTAL ACTIVE POWEROutlet 1 Peak Total Active PowerWWrite
LAV23OUTLET 2 PEAK TOTAL ACTIVE POWEROutlet 2 Peak Total Active PowerWWrite
LAV24OUTLET 3 PEAK TOTAL ACTIVE POWEROutlet 3 Peak Total Active PowerWWrite
LAV25OUTLET 4 PEAK TOTAL ACTIVE POWEROutlet 4 Peak Total Active PowerWWrite
LAV26OUTLET 1 TOTAL REACTIVE POWEROutlet 1 Total Reactive PowerVARRead
LAV27OUTLET 2 TOTAL REACTIVE POWEROutlet 2 Total Reactive PowerVARRead
LAV28OUTLET 3 TOTAL REACTIVE POWEROutlet 3 Total Reactive PowerVARRead
LAV29OUTLET 4 TOTAL REACTIVE POWEROutlet 4 Total Reactive PowerVARRead
LAV30OUTLET 1 TOTAL APPARENT POWEROutlet 1 Total Apparent PowerVARead
LAV31OUTLET 2 TOTAL APPARENT POWEROutlet 2 Total Apparent PowerVARead
LAV32OUTLET 3 TOTAL APPARENT POWEROutlet 3 Total Apparent PowerVARead
LAV33OUTLET 4 TOTAL APPARENT POWEROutlet 4 Total Apparent PowerVARead
AI57OUTLET 1 TOTAL POWER FACTOROutlet 1 Total Power FactorRead
AI58OUTLET 2 TOTAL POWER FACTOROutlet 2 Total Power FactorRead
AI59OUTLET 3 TOTAL POWER FACTOROutlet 3 Total Power FactorRead
AI60OUTLET 4 TOTAL POWER FACTOROutlet 4 Total Power FactorRead
LAV34OUTLET 1 TOTAL ENERGYOutlet 1 Total EnergykWhRead
LAV35OUTLET 2 TOTAL ENERGYOutlet 2 Total EnergykWhRead
LAV36OUTLET 3 TOTAL ENERGYOutlet 3 Total EnergykWhRead
LAV37OUTLET 4 TOTAL ENERGYOutlet 4 Total EnergykWhRead
CSV18OUTLET 1 LINE IDENTIFIEROutlet 1 Line 1 ID (Admin level)Write
CSV19OUTLET 1 LINE IDENTIFIEROutlet 1 Line 2 ID (Admin level)Write
CSV20OUTLET 1 LINE IDENTIFIEROutlet 1 Line 3 ID (Admin level)Write
CSV21OUTLET 1 LINE IDENTIFIEROutlet 1 Neutral ID (Admin level)Write
CSV22OUTLET 2 LINE IDENTIFIEROutlet 2 Line 1 ID (Admin level)Write
CSV23OUTLET 2 LINE IDENTIFIEROutlet 2 Line 2 ID (Admin level)Write
CSV24OUTLET 2 LINE IDENTIFIEROutlet 2 Line 3 ID (Admin level)Write
CSV25OUTLET 2 LINE IDENTIFIEROutlet 2 Neutral ID (Admin level)Write
CSV26OUTLET 3 LINE IDENTIFIEROutlet 3 Line 1 ID (Admin level)Write
CSV27OUTLET 3 LINE IDENTIFIEROutlet 3 Line 2 ID (Admin level)Write
CSV28OUTLET 3 LINE IDENTIFIEROutlet 3 Line 3 ID (Admin level)Write
CSV29OUTLET 3 LINE IDENTIFIEROutlet 3 Neutral ID (Admin level)Write
CSV30OUTLET 4 LINE IDENTIFIEROutlet 4 Line 1 ID (Admin level)Write
CSV31OUTLET 4 LINE IDENTIFIEROutlet 4 Line 2 ID (Admin level)Write
CSV32OUTLET 4 LINE IDENTIFIEROutlet 4 Line 3 ID (Admin level)Write
CSV33OUTLET 4 LINE IDENTIFIEROutlet 4 Neutral ID (Admin level)Write
AV104OUTLET 1 LINE CURRENT DEMANDOutlet 1 Line Current Demand Line 1AmpsWrite
AV105OUTLET 1 LINE CURRENT DEMANDOutlet 1 Line Current Demand Line 2AmpsWrite
AV106OUTLET 1 LINE CURRENT DEMANDOutlet 1 Line Current Demand Line 3AmpsWrite
AV107OUTLET 1 LINE CURRENT DEMANDOutlet 1 Line Current Demand Line NeutralAmpsWrite
AV108OUTLET 2 LINE CURRENT DEMANDOutlet 2 Line Current Demand Line 1AmpsWrite
AV109OUTLET 2 LINE CURRENT DEMANDOutlet 2 Line Current Demand Line 2AmpsWrite
AV110OUTLET 2 LINE CURRENT DEMANDOutlet 2 Line Current Demand Line 3AmpsWrite
AV111OUTLET 2 LINE CURRENT DEMANDOutlet 2 Line Current Demand Line NeutralAmpsWrite
AV112OUTLET 3 LINE CURRENT DEMANDOutlet 3 Line Current Demand Line 1AmpsWrite
AV113OUTLET 3 LINE CURRENT DEMANDOutlet 3 Line Current Demand Line 2AmpsWrite
AV114OUTLET 3 LINE CURRENT DEMANDOutlet 3 Line Current Demand Line 3AmpsWrite
AV115OUTLET 3 LINE CURRENT DEMANDOutlet 3 Line Current Demand Line NeutralAmpsWrite
AV116OUTLET 4 LINE CURRENT DEMANDOutlet 4 Line Current Demand Line 1AmpsWrite
AV117OUTLET 4 LINE CURRENT DEMANDOutlet 4 Line Current Demand Line 2AmpsWrite
AV118OUTLET 4 LINE CURRENT DEMANDOutlet 4 Line Current Demand Line 3AmpsWrite
AV119OUTLET 4 LINE CURRENT DEMANDOutlet 4 Line Current Demand Line NeutralAmpsWrite
AV120OUTLET 1 LINE CURRENT PEAK DEMANDOutlet 1 Line Current Peak Demand Line 1AmpsWrite
AV121OUTLET 1 LINE CURRENT PEAK DEMANDOutlet 1 Line Current Peak Demand Line 2AmpsWrite
AV122OUTLET 1 LINE CURRENT PEAK DEMANDOutlet 1 Line Current Peak Demand Line 3AmpsWrite
AV123OUTLET 1 LINE CURRENT PEAK DEMANDOutlet 1 Line Current Peak Demand Neutral ConductorAmpsWrite
AV124OUTLET 2 LINE CURRENT PEAK DEMANDOutlet 2 Line Current Peak Demand Line 1AmpsWrite
AV125OUTLET 2 LINE CURRENT PEAK DEMANDOutlet 2 Line Current Peak Demand Line 2AmpsWrite
AV126OUTLET 2 LINE CURRENT PEAK DEMANDOutlet 2 Line Current Peak Demand Line 3AmpsWrite
AV127OUTLET 2 LINE CURRENT PEAK DEMANDOutlet 2 Line Current Peak Demand Neutral ConductorAmpsWrite
AV128OUTLET 3 LINE CURRENT PEAK DEMANDOutlet 3 Line Current Peak Demand Line 1AmpsWrite
AV129OUTLET 3 LINE CURRENT PEAK DEMANDOutlet 3 Line Current Peak Demand Line 2AmpsWrite
AV130OUTLET 3 LINE CURRENT PEAK DEMANDOutlet 3 Line Current Peak Demand Line 3AmpsWrite
AV131OUTLET 3 LINE CURRENT PEAK DEMANDOutlet 3 Line Current Peak Demand Neutral ConductorAmpsWrite
AV132OUTLET 4 LINE CURRENT PEAK DEMANDOutlet 4 Line Current Peak Demand Line 1AmpsWrite
AV133OUTLET 4 LINE CURRENT PEAK DEMANDOutlet 4 Line Current Peak Demand Line 2AmpsWrite
AV134OUTLET 4 LINE CURRENT PEAK DEMANDOutlet 4 Line Current Peak Demand Line 3AmpsWrite
AV135OUTLET 4 LINE CURRENT PEAK DEMANDOutlet 4 Line Current Peak Demand Neutral ConductorAmpsWrite
AV136OUTLET 1 TOTAL LINE CURRENT DEMANDOutlet 1 Total Line Current DemandAmpsWrite
AV137OUTLET 2 TOTAL LINE CURRENT DEMANDOutlet 2 Total Line Current DemandAmpsWrite
AV138OUTLET 3 TOTAL LINE CURRENT DEMANDOutlet 3 Total Line Current DemandAmpsWrite
AV139OUTLET 4 TOTAL LINE CURRENT DEMANDOutlet 4 Total Line Current DemandAmpsWrite
AV140OUTLET 1 PEAK TOTAL LINE CURRENT DEMANDOutlet 1 Peak Total Line Current DemandAmpsWrite
AV141OUTLET 2 PEAK TOTAL LINE CURRENT DEMANDOutlet 2 Peak Total Line Current DemandAmpsWrite
AV142OUTLET 3 PEAK TOTAL LINE CURRENT DEMANDOutlet 3 Peak Total Line Current DemandAmpsWrite
AV143OUTLET 4 PEAK TOTAL LINE CURRENT DEMANDOutlet 4 Peak Total Line Current DemandAmpsWrite
CSV34NODE 1 IDENTIFIERNode 1 ID (Admin level)Write
CSV35NODE 2 IDENTIFIERNode 2 ID (Admin level)Write
CSV36NODE 3 IDENTIFIERNode 3 ID (Admin level)Write
CSV37NODE 4 IDENTIFIERNode 4 ID (Admin level)Write
AI61ENCLOSURE TEMPERATUREEnclosure Temperature ValuedegreesRead
AI62NODE TEMPERATURENode 1 Absolute Temperature ValuedegreesRead
AI63NODE TEMPERATURENode 2 Absolute Temperature ValuedegreesRead
AI64NODE TEMPERATURENode 3 Absolute Temperature ValuedegreesRead
AI65NODE TEMPERATURENode 4 Absolute Temperature ValuedegreesRead
AV144ENCLOSURE TEMPERATURE MAXIMUMMaximum Enclosure Temperature ValuedegreesWrite
AV145NODE TEMPERATURE MAXIMUMMaximum Node 1 Temperature ValuedegreesWrite
AV146NODE TEMPERATURE MAXIMUMMaximum Node 2 Temperature ValuedegreesWrite
AV147NODE TEMPERATURE MAXIMUMMaximum Node 3 Temperature ValuedegreesWrite
AV148NODE TEMPERATURE MAXIMUMMaximum Node 4 Temperature ValuedegreesWrite
AI66ENCLOSURE SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLDEnclosure System Temperature Maximum Alarm ThresholddegreesRead
AI67SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLDNode 1 System Temperature Maximum Alarm ThresholddegreesRead
AI68SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLDNode 2 System Temperature Maximum Alarm ThresholddegreesRead
AI69SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLDNode 3 System Temperature Maximum Alarm ThresholddegreesRead
AI70SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLDNode 4 System Temperature Maximum Alarm ThresholddegreesRead
AV149ENCLOSURE USER TEMPERATURE MAXIMUM ALARM THRESHOLDEnclosure User Temperature Maximum Alarm Threshold (Admin level)degreesWrite
AV150USER TEMPERATURE MAXIMUM ALARM THRESHOLDNode 1 User Temperature Maximum Alarm Threshold (Admin level)degreesWrite
AV151USER TEMPERATURE MAXIMUM ALARM THRESHOLDNode 2 User Temperature Maximum Alarm Threshold (Admin level)degreesWrite
AV152USER TEMPERATURE MAXIMUM ALARM THRESHOLDNode 3 User Temperature Maximum Alarm Threshold (Admin level)degreesWrite
AV153USER TEMPERATURE MAXIMUM ALARM THRESHOLDNode 4 User Temperature Maximum Alarm Threshold (Admin level)degreesWrite
PIV6TEMPERATURE ALARM STATUSTemperature Alarm Status for Feed Temperature Monitoring (hex bit field)Read
PIV7RESET GROUP VALUESBit-coded reset of min, max, peak and demand values (Admin level)Write
CSV38OUTLET 5 IDENTIFIEROutlet 5 ID (Admin level)Write
CSV39OUTLET 6 IDENTIFIEROutlet 6 ID (Admin level)Write
PIV8OUTLET ALARM STATUS 2OUTLET 5 and 6 alarm status (hex bit field)Read
AI71OUTLET 5 LINE CURRENTOutlet 5, Line Current Line 1AmpsRead
AI72OUTLET 5 LINE CURRENTOutlet 5, Line Current Line 2AmpsRead
AI73OUTLET 5 LINE CURRENTOutlet 5, Line Current Line 3AmpsRead
AI74OUTLET 5 LINE CURRENTOutlet 5, Line Current Line NAmpsRead
AI75OUTLET 6 LINE CURRENTOutlet 6, Line Current Line 1AmpsRead
AI76OUTLET 6 LINE CURRENTOutlet 6, Line Current Line 2AmpsRead
AI77OUTLET 6 LINE CURRENTOutlet 6, Line Current Line 3AmpsRead
AI78OUTLET 6 LINE CURRENTOutlet 6, Line Current Line NAmpsRead
AV154OUTLET 5 LINE CURRENT RATINGOutlet 5 Line Current Rating. One rating for each outletAmpsRead
AV155OUTLET 6 LINE CURRENT RATINGOutlet 6 Line Current Rating. One rating for each outletAmpsRead
AI79OUTLET 5 LINE CURRENT RATING % ofOutlet 5 Line Current % of Rated Line 1PercentRead
AI80OUTLET 5 LINE CURRENT RATING % ofOutlet 5 Line Current % of Rated Line 2PercentRead
AI81OUTLET 5 LINE CURRENT RATING % ofOutlet 5 Line Current % of Rated Line 3PercentRead
AI82OUTLET 5 LINE CURRENT RATING % ofOutlet 5 Line Current % of Rated Neutral ConductorPercentRead
AI83OUTLET 6 LINE CURRENT RATING % ofOutlet 6 Line Current % of Rated Line 1PercentRead
AI84OUTLET 6 LINE CURRENT RATING % ofOutlet 6 Line Current % of Rated Line 2PercentRead
AI85OUTLET 6 LINE CURRENT RATING % ofOutlet 6 Line Current % of Rated Line 3PercentRead
AI86OUTLET 6 LINE CURRENT RATING % ofOutlet 6 Line Current % of Rated Neutral ConductorPercentRead
AV156OUTLET 5 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 1AmpsWrite
AV157OUTLET 5 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 2AmpsWrite
AV158OUTLET 5 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 3AmpsWrite
AV159OUTLET 5 LINE CURRENT MINIMUMOutlet Line Current Minimum Neutral ConductorAmpsWrite
AV160OUTLET 6 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 1AmpsWrite
AV161OUTLET 6 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 2AmpsWrite
AV162OUTLET 6 LINE CURRENT MINIMUMOutlet Line Current Minimum Line 3AmpsWrite
AV163OUTLET 6 LINE CURRENT MINIMUMOutlet Line Current Minimum Neutral ConductorAmpsWrite
AV164OUTLET 5 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 1AmpsWrite
AV165OUTLET 5 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 2AmpsWrite
AV166OUTLET 5 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 3AmpsWrite
AV167OUTLET 5 LINE CURRENT MAXIMUMOutlet Line Current Maximum Neutral ConductorAmpsWrite
AV168OUTLET 6 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 1AmpsWrite
AV169OUTLET 6 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 2AmpsWrite
AV170OUTLET 6 LINE CURRENT MAXIMUMOutlet Line Current Maximum Line 3AmpsWrite
AV171OUTLET 6 LINE CURRENT MAXIMUMOutlet Line Current Maximum Neutral ConductorAmpsWrite
AV172OUTLET CURRENT MIN ALARMOutlet 5 Current Minimum AlarmAmpsWrite
AV173OUTLET CURRENT MIN ALARMOutlet 6 Current Minimum AlarmAmpsWrite
AV174OUTLET CURRENT MAX ALARMOutlet 5 Current Maximum AlarmAmpsWrite
AV175OUTLET CURRENT MAX ALARMOutlet 6 Current Maximum AlarmAmpsWrite
AV176OUTLET 5 DEMAND TIMEOutlet 5 Demand TimeMinutesWrite
AV177OUTLET 6 DEMAND TIMEOutlet 6 Demand TimeMinutesWrite
LAV38OUTLET 5 TOTAL ACTIVE POWEROutlet 5 Total Active PowerWRead
LAV39OUTLET 6 TOTAL ACTIVE POWEROutlet 6 Total Active PowerWRead
LAV40OUTLET 5 PEAK TOTAL ACTIVE POWEROutlet 5 Peak Total Active PowerWWrite
LAV41OUTLET 6 PEAK TOTAL ACTIVE POWEROutlet 6 Peak Total Active PowerWWrite
LAV42OUTLET 5 TOTAL REACTIVE POWEROutlet 5 Total Reactive PowerVARRead
LAV43OUTLET 6 TOTAL REACTIVE POWEROutlet 6 Total Reactive PowerVARRead
LAV44OUTLET 5 TOTAL APPARENT POWEROutlet 5 Total Apparent PowerVARead
LAV45OUTLET 6 TOTAL APPARENT POWEROutlet 6 Total Apparent PowerVARead
AI87OUTLET 5 TOTAL POWER FACTOROutlet 5 Total Power FactorRead
AI88OUTLET 6 TOTAL POWER FACTOROutlet 6 Total Power FactorRead
LAV46OUTLET 5 TOTAL ENERGYOutlet 5 Total EnergykWhRead
LAV47OUTLET 6 TOTAL ENERGYOutlet 6 Total EnergykWhRead
CSV40OUTLET 5 LINE IDENTIFIEROutlet 5 Line 1 ID (Admin level)Write
CSV41OUTLET 5 LINE IDENTIFIEROutlet 5 Line 2 ID (Admin level)Write
CSV42OUTLET 5 LINE IDENTIFIEROutlet 5 Line 3 ID (Admin level)Write
CSV43OUTLET 5 LINE IDENTIFIEROutlet 5 Neutral ID (Admin level)Write
CSV44OUTLET 6 LINE IDENTIFIEROutlet 6 Line 1 ID (Admin level)Write
CSV45OUTLET 6 LINE IDENTIFIEROutlet 6 Line 2 ID (Admin level)Write
CSV46OUTLET 6 LINE IDENTIFIEROutlet 6 Line 3 ID (Admin level)Write
CSV47OUTLET 6 LINE IDENTIFIEROutlet 6 Neutral ID (Admin level)Write
AV178OUTLET 5 LINE CURRENT DEMANDOutlet 5 Line Current Demand Line 1AmpsWrite
AV179OUTLET 5 LINE CURRENT DEMANDOutlet 5 Line Current Demand Line 2AmpsWrite
AV180OUTLET 5 LINE CURRENT DEMANDOutlet 5 Line Current Demand Line 3AmpsWrite
AV181OUTLET 5 LINE CURRENT DEMANDOutlet 5 Line Current Demand Line NeutralAmpsWrite
AV182OUTLET 6 LINE CURRENT DEMANDOutlet 6 Line Current Demand Line 1AmpsWrite
AV183OUTLET 6 LINE CURRENT DEMANDOutlet 6 Line Current Demand Line 2AmpsWrite
AV184OUTLET 6 LINE CURRENT DEMANDOutlet 6 Line Current Demand Line 3AmpsWrite
AV185OUTLET 6 LINE CURRENT DEMANDOutlet 6 Line Current Demand Line NeutralAmpsWrite
AV186OUTLET 5 LINE CURRENT PEAK DEMANDOutlet 5 Line Current Peak Demand Line 1AmpsWrite
AV187OUTLET 5 LINE CURRENT PEAK DEMANDOutlet 5 Line Current Peak Demand Line 2AmpsWrite
AV188OUTLET 5 LINE CURRENT PEAK DEMANDOutlet 5 Line Current Peak Demand Line 3AmpsWrite
AV189OUTLET 5 LINE CURRENT PEAK DEMANDOutlet 5 Line Current Peak Demand Neutral ConductorAmpsWrite
AV190OUTLET 6 LINE CURRENT PEAK DEMANDOutlet 6 Line Current Peak Demand Line 1AmpsWrite
AV191OUTLET 6 LINE CURRENT PEAK DEMANDOutlet 6 Line Current Peak Demand Line 2AmpsWrite
AV192OUTLET 6 LINE CURRENT PEAK DEMANDOutlet 6 Line Current Peak Demand Line 3AmpsWrite
AV193OUTLET 6 LINE CURRENT PEAK DEMANDOutlet 6 Line Current Peak Demand Neutral ConductorAmpsWrite
AV194OUTLET 5 TOTAL LINE CURRENT DEMANDOutlet 5 Total Line Current DemandAmpsWrite
AV195OUTLET 6 TOTAL LINE CURRENT DEMANDOutlet 6 Total Line Current DemandAmpsWrite
AV196OUTLET 5 PEAK TOTAL LINE CURRENT DEMANDOutlet 5 Peak Total Line Current DemandAmpsWrite
AV197OUTLET 6 PEAK TOTAL LINE CURRENT DEMANDOutlet 6 Peak Total Line Current DemandAmpsWrite
AV198LINE TO NEUTRAL VOLTAGE MINIMUMLine to Neutral Voltage Minimum L1-NVoltsWrite
AV199LINE TO NEUTRAL VOLTAGE MAXIMUMLine to Neutral Voltage Maximum L1-NVoltsWrite
AV200LINE TO NEUTRAL VOLTAGE MIN ALARMLine to Neutral Voltage Minimum Alarm L1-NVoltsWrite
AV201LINE TO NEUTRAL VOLTAGE MAX ALARMLine to Neutral Voltage Maximum Alarm L1-NVoltsWrite
AV202LINE TO NEUTRAL VOLTAGE MINIMUMLine to Neutral Voltage Minimum L2-NVoltsWrite
AV203LINE TO NEUTRAL VOLTAGE MAXIMUMLine to Neutral Voltage Maximum L2-NVoltsWrite
AV204LINE TO NEUTRAL VOLTAGE MIN ALARMLine to Neutral Voltage Minimum Alarm L2-NVoltsWrite
AV205LINE TO NEUTRAL VOLTAGE MAX ALARMLine to Neutral Voltage Maximum Alarm L2-NVoltsWrite
AV206LINE TO NEUTRAL VOLTAGE MINIMUMLine to Neutral Voltage Minimum L3-NVoltsWrite
AV207LINE TO NEUTRAL VOLTAGE MAXIMUMLine to Neutral Voltage Maximum L3-NVoltsWrite
AV208LINE TO NEUTRAL VOLTAGE MIN ALARMLine to Neutral Voltage Minimum Alarm L3-NVoltsWrite
AV209LINE TO NEUTRAL VOLTAGE MAX ALARMLine to Neutral Voltage Maximum Alarm L3-NVoltsWrite
AV210FREQUENCY MINIMUMFrequency MinimumHertzWrite
AV211FREQUENCY MAXIMUMFrequency MaximumHertzWrite
AV212INFEED NEUTRAL CURRENT RATINGInfeed Neutral Current Rating (Admin level)AmpsWrite
PIV11BREAKER ALARM STATUSthe breaker alarm status (hex bit field)Read
PIV13BREAKER 1 STATUSBreaker 1 StatusRead0=Open/Off, 1=Closed/On
PIV14BREAKER 2 STATUSBreaker 2 StatusRead0=Open/Off, 1=Closed/On
Object ID lookup: Starline AC CPM point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AC Critical Power Monitor (CPM) for busway and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Starline AC Critical Power Monitor (CPM) for busway

How many BACnet points does the Starline AC Critical Power Monitor (CPM) for busway have?

This list has 405 BACnet objects: 88 analog inputs, 212 analog values, 1 binary value, 46 characterstring values, 47 large analog values, 11 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Starline AC Critical Power Monitor (CPM) for busway BACnet points are writable?

254 of the 405 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Starline AC Critical Power Monitor (CPM) for busway BACnet documentation?

The source is AC CPM BACNet Object List (Rev 4), revision 2023-03-03, published free by Starline at https://cdn.starlinepower.com/drupal-media-and-files/files/files/AC-CPM-BACNet-Object-List-v4.26-v5.07.pdf.

What are the minimum BACnet points to integrate the Starline AC Critical Power Monitor (CPM) for busway?

Start with LAV 17 INFEED TOTAL ENERGY (Total infeed energy, kWh); LAV 1 INFEED TOTAL ACTIVE POWER (Total infeed active power, W); AI 3 INFEED LINE CURRENT AVERAGE (Average infeed line current, A); AI 9 INFEED LINE CURRENT (Infeed current, line 1, A); AI 10 INFEED LINE CURRENT (Infeed current, line 2, A); AI 11 INFEED LINE CURRENT (Infeed current, line 3, A); AI 1 LINE TO NEUTRAL VOLTAGE AVERAGE (Average line-to-neutral voltage, V); AI 4 INFEED TOTAL POWER FACTOR (Total power factor); PIV 4 INFEED ALARM STATUS (Infeed alarm status bits); PIV 5 OUTLET ALARM STATUS (Outlet 1-4 alarm status bits).

How do I check these points on the real AC Critical Power Monitor (CPM) for busway?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Starline BACnet points lists

Source: AC CPM BACNet Object List · Rev 4 · rev. 2023-03-03. Object names, instances and units are reproduced as published; descriptions are our own.