- Home
- BACnet points lists
- Starline
- AC Critical Power Monitor (CPM) for busway
Busway power meter (critical power monitor) · BACnet points list
Starline AC Critical Power Monitor (CPM) for busway BACnet points list
Updated 12 November 2026
The AC CPM meters an infeed and up to six outlets, plus enclosure and node temperatures and breaker status. Its BACnet object list has 405 objects with a write-access level for each: device text fields, infeed voltages, currents, power, energy, demand and min/max values, per-outlet metering, alarm thresholds, hex alarm-status words and breaker status.
This page lists 405 BACnet objects for the Starline AC Critical Power Monitor (CPM) for busway — 254 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Starline’s own free documentation, linked below.
- Manufacturer
- Starline
- Model
- AC Critical Power Monitor (CPM) for busway
- Equipment
- Busway power meter (critical power monitor)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 405 (254 writable)
- Transport
- —
- Firmware
- v4.26, v4.26A, v5.07 (list also valid for v4.21-v4.24 and v5.02-v5.05)
- Also known as
- AC CPM, Starline AC CPM, Starline CPM, Critical Power Monitor, Legrand Starline CPM
- Source document
- AC CPM BACNet Object List · Rev 4 · rev. 2023-03-03
Reference only, provided as-is: verify against Starline’s current documentation and the live device before use. Not official Starline information. Terms of use.
BMS integration notes: Starline AC Critical Power Monitor (CPM) for busway
Read the infeed totals (energy, active power, average current and voltage, power factor) and the per-line currents, plus the infeed and outlet alarm status words. Add per-outlet metering for each plug-in unit you need to bill or monitor.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| LAV 17 | INFEED TOTAL ENERGY | Total infeed energy, kWh | Read |
| LAV 1 | INFEED TOTAL ACTIVE POWER | Total infeed active power, W | Read |
| AI 3 | INFEED LINE CURRENT AVERAGE | Average infeed line current, A | Read |
| AI 9 | INFEED LINE CURRENT | Infeed current, line 1, A | Read |
| AI 10 | INFEED LINE CURRENT | Infeed current, line 2, A | Read |
| AI 11 | INFEED LINE CURRENT | Infeed current, line 3, A | Read |
| AI 1 | LINE TO NEUTRAL VOLTAGE AVERAGE | Average line-to-neutral voltage, V | Read |
| AI 4 | INFEED TOTAL POWER FACTOR | Total power factor | Read |
| PIV 4 | INFEED ALARM STATUS | Infeed alarm status bits | Read |
| PIV 5 | OUTLET ALARM STATUS | Outlet 1-4 alarm status bits | Read |
Watch out for
- Many objects share the same name; map by object type and instance, not by name.
- Alarm thresholds, ratings and resets are writable; Admin-level writes need the admin access level. Don't write them cyclically.
Starline AC Critical Power Monitor (CPM) for busway BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| PIV | 1 | LCD POWER DOWN TIME | LCD power down time | Seconds | Write | |
| PIV | 2 | LCD BACKLIGHT LEVEL | LCD backlight level | Write | ||
| PIV | 3 | LCD SLIDESHOW SPEED | slideshow speed | Write | ||
| CSV | 1 | DEVICE ID | Device ID (Admin level) | Write | ||
| CSV | 2 | DEVICE NAME | Device Name (Admin level) | Write | ||
| CSV | 3 | DEVICE LOCATION | Device Location (Admin level) | Write | ||
| CSV | 4 | VENDOR NAME | Vendor Name | Read | ||
| CSV | 5 | MODEL NUMBER | Model Number ID | Read | ||
| CSV | 6 | SERIAL NUMBER | Meter's Serial Number | Read | ||
| CSV | 7 | PRODUCT SERIAL NUMBER | Meter's Product Serial Number | Read | ||
| CSV | 8 | CATALOG NUMBER/PRODUCT TYPE | Device Type | Read | ||
| CSV | 9 | HARDWARE VERSION | Hardware Part Number and Version | Read | ||
| CSV | 10 | FIRMWARE VERSION (M22276-116 v1.00) | Firmware Part Number and Version | Read | ||
| CSV | 11 | METER VERSION | Meter Version | Read | ||
| CSV | 12 | Wi-Fi VERSION | Wi-Fi Version | Read | ||
| CSV | 13 | CALIBRATION DATE (YYYY-MM-DD) | Calibration Date | Read | ||
| AImin | 1 | LINE TO NEUTRAL VOLTAGE AVERAGE | Line to Neutral Voltage Average | Volts | Read | |
| AI | 2 | LINE TO LINE VOLTAGE AVERAGE | Line to Line Voltage Average | Volts | Read | |
| AImin | 3 | INFEED LINE CURRENT AVERAGE | Infeed Line Current Average | Amps | Read | |
| AV | 1 | INFEED LINE CURRENT RATING | Infeed Line Current Rating (Admin level) | Amps | Write | |
| AV | 2 | INFEED TOTAL LINE CURRENT DEMAND | Infeed Current Demand (uses line current to determine demand) | Amps | Write | |
| AV | 3 | INFEED TOTAL LINE CURRENT PEAK DEMAND | Infeed Current Peak Demand | Amps | Write | |
| AV | 4 | INFEED DEMAND TIME | Infeed Demand Interval | Minutes | Write | |
| LAVmin | 1 | INFEED TOTAL ACTIVE POWER | Infeed Total Active Power | W | Read | |
| LAV | 2 | INFEED PEAK TOTAL ACTIVE POWER | Infeed Peak Total Active Power | W | Write | |
| AV | 5 | INFEED TOTAL ACTIVE POWER DEMAND | Infeed Total Active Power Demand | W | Write | |
| AV | 6 | INFEED PEAK TOTAL ACTIVE POWER DEMAND | Infeed Peak Total Active Power Demand | W | Write | |
| LAV | 3 | INFEED TOTAL REACTIVE POWER | Infeed Total Reactive Power | VAR | Read | |
| AV | 7 | INFEED TOTAL REACTIVE POWER DEMAND | Infeed Total Reactive Power | VAR | Write | |
| AV | 8 | INFEED PEAK TOTAL REACTIVE POWER DEMAND | Infeed Total Reactive Power | VAR | Write | |
| LAV | 4 | INFEED TOTAL APPARENT POWER | Infeed Total Apparent Power | VA | Read | |
| AV | 9 | INFEED TOTAL APPARENT POWER DEMAND | Infeed Total Apparent Power Demand | VA | Write | |
| AV | 10 | INFEED PEAK TOTAL APPARENT POWER DEMAND | Infeed Peak Total Apparent Power Demand | VA | Write | |
| AImin | 4 | INFEED TOTAL POWER FACTOR | Total Power Factor | Read | ||
| PIVmin | 4 | INFEED ALARM STATUS | infeed alarm status (hex bit field) | Read | ||
| AI | 5 | FREQUENCY | Frequency | Hertz | Read | |
| AI | 6 | LINE TO LINE VOLTAGE | Line to Line Voltage L1-L2 | Volts | Read | |
| AI | 7 | LINE TO LINE VOLTAGE | Line to Line Voltage L2-L3 | Volts | Read | |
| AI | 8 | LINE TO LINE VOLTAGE | Line to Line Voltage L3-L1 | Volts | Read | |
| AImin | 9 | INFEED LINE CURRENT | Infeed Line Current Line 1 | Amps | Read | |
| AImin | 10 | INFEED LINE CURRENT | Infeed Line Current Line 2 | Amps | Read | |
| AImin | 11 | INFEED LINE CURRENT | Infeed Line Current Line 3 | Amps | Read | |
| AI | 12 | INFEED LINE CURRENT | Infeed Line Current Calculated Neutral | Amps | Read | |
| AI | 13 | INFEED LINE CURRENT | Infeed Line Current Measured Neutral | Amps | Read | |
| AV | 11 | INFEED LINE CURRENT MINIMUM | Infeed Line Current Minimum Line 1 | Amps | Write | |
| AV | 12 | INFEED LINE CURRENT MINIMUM | Infeed Line Current Minimum Line 2 | Amps | Write | |
| AV | 13 | INFEED LINE CURRENT MINIMUM | Infeed Line Current Minimum Line 3 | Amps | Write | |
| AV | 14 | INFEED LINE CURRENT MINIMUM | Infeed Line Current Maximum Calculated Neutral | Amps | Write | |
| AV | 15 | INFEED LINE CURRENT MINIMUM | Infeed Line Current Maximum Measured Neutral | Amps | Write | |
| AV | 16 | INFEED LINE CURRENT MAXIMUM | Infeed Line Current Maximum Line 1 | Amps | Write | |
| AV | 17 | INFEED LINE CURRENT MAXIMUM | Infeed Line Current Maximum Line 2 | Amps | Write | |
| AV | 18 | INFEED LINE CURRENT MAXIMUM | Infeed Line Current Maximum Line 3 | Amps | Write | |
| AV | 19 | INFEED LINE CURRENT MAXIMUM | Infeed Line Current Maximum Calculated Neutral | Amps | Write | |
| AV | 20 | INFEED LINE CURRENT MAXIMUM | Infeed Line Current Maximum Measured Neutral | Amps | Write | |
| AI | 14 | INFEED LINE CURRENT RATING % of | Infeed Line Current % of Rated Line 1 | Percent | Read | |
| AI | 15 | INFEED LINE CURRENT RATING % of | Infeed Line Current % of Rated Line 2 | Percent | Read | |
| AI | 16 | INFEED LINE CURRENT RATING % of | Infeed Line Current % of Rated Line 3 | Percent | Read | |
| AI | 17 | INFEED LINE CURRENT RATING % of | Infeed Line Current % of Rated Calculated Neutral | Percent | Read | |
| AI | 18 | INFEED LINE CURRENT RATING % of | Infeed Line Current % of Rated Measured Neutral | Percent | Read | |
| AV | 21 | INFEED LINE CURRENT MIN ALARM | Infeed Line Current Minimum Alarm Line 1 | Amps | Write | |
| AV | 22 | INFEED LINE CURRENT MIN ALARM | Infeed Line Current Minimum Alarm Line 2 | Amps | Write | |
| AV | 23 | INFEED LINE CURRENT MIN ALARM | Infeed Line Current Minimum Alarm Line 3 | Amps | Write | |
| AV | 24 | INFEED LINE CURRENT MIN ALARM | Infeed Line Current Minimum Alarm Calculated Neutral | Amps | Write | |
| AV | 25 | INFEED LINE CURRENT MIN ALARM | Infeed Line Current Minimum Alarm Measured Neutral | Amps | Write | |
| AV | 26 | INFEED LINE CURRENT MAX ALARM | Infeed Line Current Maximum Alarm Line 1 | Amps | Write | |
| AV | 27 | INFEED LINE CURRENT MAX ALARM | Infeed Line Current Maximum Alarm Line 2 | Amps | Write | |
| AV | 28 | INFEED LINE CURRENT MAX ALARM | Infeed Line Current Maximum Alarm Line 3 | Amps | Write | |
| AV | 29 | INFEED LINE CURRENT MAX ALARM | Infeed Line Current Maximum Alarm Calculated Neutral | Amps | Write | |
| AV | 30 | INFEED LINE CURRENT MAX ALARM | Infeed Line Current Maximum Alarm Measured Neutral | Amps | Write | |
| AV | 31 | INFEED LINE CURRENT DEMAND | Infeed Line Current Demand Line 1 | Amps | Write | |
| AV | 32 | INFEED LINE CURRENT DEMAND | Infeed Line Current Demand Line 2 | Amps | Write | |
| AV | 33 | INFEED LINE CURRENT DEMAND | Infeed Line Current Demand Line 3 | Amps | Write | |
| AV | 34 | INFEED LINE CURRENT DEMAND | Infeed Line Current Demand Calculated Neutral | Amps | Write | |
| AV | 35 | INFEED LINE CURRENT DEMAND | Infeed Line Current Demand Measured Neutral | Amps | Write | |
| AV | 36 | INFEED LINE CURRENT PEAK DEMAND | Infeed Line Current Peak Demand Line 1 | Amps | Write | |
| AV | 37 | INFEED LINE CURRENT PEAK DEMAND | Infeed Line Current Peak Demand Line 2 | Amps | Write | |
| AV | 38 | INFEED LINE CURRENT PEAK DEMAND | Infeed Line Current Peak Demand Line 3 | Amps | Write | |
| AV | 39 | INFEED LINE CURRENT PEAK DEMAND | Infeed Line Current Peak Demand Calculated Neutral | Amps | Write | |
| AV | 40 | INFEED LINE CURRENT PEAK DEMAND | Infeed Line Current Peak Demand Measured Neutral | Amps | Write | |
| AI | 19 | LINE TO NEUTRAL VOLTAGE | Line to Neutral Voltage L1-LN | Volts | Read | |
| AI | 20 | LINE TO NEUTRAL VOLTAGE | Line to Neutral Voltage L2-N | Volts | Read | |
| AI | 21 | LINE TO NEUTRAL VOLTAGE | Line to Neutral Voltage L3-N | Volts | Read | |
| AV | 41 | LINE TO LINE VOLTAGE MINIMUM | Line to Line Voltage Minimum L1-L2 | Volts | Write | |
| AV | 42 | LINE TO LINE VOLTAGE MINIMUM | Line to Line Voltage Minimum L2-L3 | Volts | Write | |
| AV | 43 | LINE TO LINE VOLTAGE MINIMUM | Line to Line Voltage Minimum L3-L1 | Volts | Write | |
| AV | 44 | LINE TO LINE VOLTAGE MAXIMUM | Line to Line Voltage Maximum L1-L2 | Volts | Write | |
| AV | 45 | LINE TO LINE VOLTAGE MAXIMUM | Line to Line Voltage Maximum L2-L3 | Volts | Write | |
| AV | 46 | LINE TO LINE VOLTAGE MAXIMUM | Line to Line Voltage Maximum L3-L1 | Volts | Write | |
| AV | 47 | LINE TO LINE VOLTAGE MIN ALARM | Line to Line Voltage Minimum Alarm L1-L2 | Volts | Write | |
| AV | 48 | LINE TO LINE VOLTAGE MIN ALARM | Line to Line Voltage Minimum Alarm L2-L3 | Volts | Write | |
| AV | 49 | LINE TO LINE VOLTAGE MIN ALARM | Line to Line Voltage Minimum Alarm L3-L1 | Volts | Write | |
| AV | 50 | LINE TO LINE VOLTAGE MAX ALARM | Line to Line Voltage Maximum Alarm L1-L2 | Volts | Write | |
| AV | 51 | LINE TO LINE VOLTAGE MAX ALARM | Line to Line Voltage Maximum Alarm L2-L3 | Volts | Write | |
| AV | 52 | LINE TO LINE VOLTAGE MAX ALARM | Line to Line Voltage Maximum Alarm L3-L1 | Volts | Write | |
| AI | 22 | INFEED POWER FACTOR | Infeed Power Factor L1 | Read | ||
| AI | 23 | INFEED POWER FACTOR | Infeed Power Factor L2 | Read | ||
| AI | 24 | INFEED POWER FACTOR | Infeed Power Factor L3 | Read | ||
| LAV | 5 | INFEED APPARENT POWER | Infeed Apparent Power L1 | VA | Read | |
| LAV | 6 | INFEED APPARENT POWER | Infeed Apparent Power L2 | VA | Read | |
| LAV | 7 | INFEED APPARENT POWER | Infeed Apparent Power L3 | VA | Read | |
| LAV | 8 | INFEED ACTIVE POWER | Infeed Active Power L1 | W | Read | |
| LAV | 9 | INFEED ACTIVE POWER | Infeed Active Power L2 | W | Read | |
| LAV | 10 | INFEED ACTIVE POWER | Infeed Active Power L3 | W | Read | |
| AV | 53 | INFEED PEAK ACTIVE POWER | Infeed Peak Active Power L1 | W | Write | |
| AV | 54 | INFEED PEAK ACTIVE POWER | Infeed Peak Active Power L2 | W | Write | |
| AV | 55 | INFEED PEAK ACTIVE POWER | Infeed Peak Active Power L3 | W | Write | |
| LAV | 11 | INFEED REACTIVE POWER | Infeed Reactive Power L1 | VAR | Read | |
| LAV | 12 | INFEED REACTIVE POWER | Infeed Reactive Power L2 | VAR | Read | |
| LAV | 13 | INFEED REACTIVE POWER | Infeed Reactive Power L3 | VAR | Read | |
| LAV | 14 | INFEED ENERGY | Infeed Energy L1 | kWh | Read | |
| LAV | 15 | INFEED ENERGY | Infeed Energy L2 | kWh | Read | |
| LAV | 16 | INFEED ENERGY | Infeed Energy L3 | kWh | Read | |
| LAVmin | 17 | INFEED TOTAL ENERGY | Infeed Total Energy | kWh | Read | |
| BV | 1 | RESET ALL ENERGY VALUES | Reset all energy values | Write | ||
| CSV | 15 | OUTLET 2 IDENTIFIER | Outlet 2 ID (Admin level) | Write | ||
| CSV | 16 | OUTLET 3 IDENTIFIER | Outlet 3 ID (Admin level) | Write | ||
| CSV | 17 | OUTLET 4 IDENTIFIER | Outlet 4 ID (Admin level) | Write | ||
| PIVmin | 5 | OUTLET ALARM STATUS | OUTLET 1, 2, 3, and 4 alarm status (hex bit field) | Read | ||
| AI | 25 | OUTLET 1 LINE CURRENT | Outlet 1, Line Current Line 1 | Amps | Read | |
| AI | 26 | OUTLET 1 LINE CURRENT | Outlet 1, Line Current Line 2 | Amps | Read | |
| AI | 27 | OUTLET 1 LINE CURRENT | Outlet 1, Line Current Line 3 | Amps | Read | |
| AI | 28 | OUTLET 1 LINE CURRENT | Outlet 1, Line Current Line N | Amps | Read | |
| AI | 29 | OUTLET 2 LINE CURRENT | Outlet 2, Line Current Line 1 | Amps | Read | |
| AI | 30 | OUTLET 2 LINE CURRENT | Outlet 2, Line Current Line 2 | Amps | Read | |
| AI | 31 | OUTLET 2 LINE CURRENT | Outlet 2, Line Current Line 3 | Amps | Read | |
| AI | 32 | OUTLET 2 LINE CURRENT | Outlet 2, Line Current Line N | Amps | Read | |
| AI | 33 | OUTLET 3 LINE CURRENT | Outlet 3, Line Current Line 1 | Amps | Read | |
| AI | 34 | OUTLET 3 LINE CURRENT | Outlet 3, Line Current Line 2 | Amps | Read | |
| AI | 35 | OUTLET 3 LINE CURRENT | Outlet 3, Line Current Line 3 | Amps | Read | |
| AI | 36 | OUTLET 3 LINE CURRENT | Outlet 3, Line Current Line N | Amps | Read | |
| AI | 37 | OUTLET 4 LINE CURRENT | Outlet 4, Line Current Line 1 | Amps | Read | |
| AI | 38 | OUTLET 4 LINE CURRENT | Outlet 4, Line Current Line 2 | Amps | Read | |
| AI | 39 | OUTLET 4 LINE CURRENT | Outlet 4, Line Current Line 3 | Amps | Read | |
| AI | 40 | OUTLET 4 LINE CURRENT | Outlet 4, Line Current Line N | Amps | Read | |
| AV | 56 | OUTLET 1 LINE CURRENT RATING | Outlet 1 Line Current Rating. One rating for each outlet | Amps | Read | |
| AV | 57 | OUTLET 2 LINE CURRENT RATING | Outlet 2 Line Current Rating. One rating for each outlet | Amps | Read | |
| AV | 58 | OUTLET 3 LINE CURRENT RATING | Outlet 3 Line Current Rating. One rating for each outlet | Amps | Read | |
| AV | 59 | OUTLET 4 LINE CURRENT RATING | Outlet 4 Line Current Rating. One rating for each outlet | Amps | Read | |
| AI | 41 | OUTLET 1 LINE CURRENT RATING % of | Outlet 1 Line Current % of Rated Line 1 | Percent | Read | |
| AI | 42 | OUTLET 1 LINE CURRENT RATING % of | Outlet 1 Line Current % of Rated Line 2 | Percent | Read | |
| AI | 43 | OUTLET 1 LINE CURRENT RATING % of | Outlet 1 Line Current % of Rated Line 3 | Percent | Read | |
| AI | 44 | OUTLET 1 LINE CURRENT RATING % of | Outlet 1 Line Current % of Rated Neutral Conductor | Percent | Read | |
| AI | 45 | OUTLET 2 LINE CURRENT RATING % of | Outlet 2 Line Current % of Rated Line 1 | Percent | Read | |
| AI | 46 | OUTLET 2 LINE CURRENT RATING % of | Outlet 2 Line Current % of Rated Line 2 | Percent | Read | |
| AI | 47 | OUTLET 2 LINE CURRENT RATING % of | Outlet 2 Line Current % of Rated Line 3 | Percent | Read | |
| AI | 48 | OUTLET 2 LINE CURRENT RATING % of | Outlet 2 Line Current % of Rated Neutral Conductor | Percent | Read | |
| AI | 49 | OUTLET 3 LINE CURRENT RATING % of | Outlet 3 Line Current % of Rated Line 1 | Percent | Read | |
| AI | 50 | OUTLET 3 LINE CURRENT RATING % of | Outlet 3 Line Current % of Rated Line 2 | Percent | Read | |
| AI | 51 | OUTLET 3 LINE CURRENT RATING % of | Outlet 3 Line Current % of Rated Line 3 | Percent | Read | |
| AI | 52 | OUTLET 3 LINE CURRENT RATING % of | Outlet 3 Line Current % of Rated Neutral Conductor | Percent | Read | |
| AI | 53 | OUTLET 4 LINE CURRENT RATING % of | Outlet 4 Line Current % of Rated Line 1 | Percent | Read | |
| AI | 54 | OUTLET 4 LINE CURRENT RATING % of | Outlet 4 Line Current % of Rated Line 2 | Percent | Read | |
| AI | 55 | OUTLET 4 LINE CURRENT RATING % of | Outlet 4 Line Current % of Rated Line 3 | Percent | Read | |
| AI | 56 | OUTLET 4 LINE CURRENT RATING % of | Outlet 4 Line Current % of Rated Neutral Conductor | Percent | Read | |
| AV | 60 | OUTLET 1 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 1 | Amps | Write | |
| AV | 61 | OUTLET 1 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 2 | Amps | Write | |
| AV | 62 | OUTLET 1 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 3 | Amps | Write | |
| AV | 63 | OUTLET 1 LINE CURRENT MINIMUM | Outlet Line Current Minimum Neutral Conductor | Amps | Write | |
| AV | 64 | OUTLET 2 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 1 | Amps | Write | |
| AV | 65 | OUTLET 2 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 2 | Amps | Write | |
| AV | 66 | OUTLET 2 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 3 | Amps | Write | |
| AV | 67 | OUTLET 2 LINE CURRENT MINIMUM | Outlet Line Current Minimum Neutral Conductor | Amps | Write | |
| AV | 68 | OUTLET 3 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 1 | Amps | Write | |
| AV | 69 | OUTLET 3 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 2 | Amps | Write | |
| AV | 70 | OUTLET 3 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 3 | Amps | Write | |
| AV | 71 | OUTLET 3 LINE CURRENT MINIMUM | Outlet Line Current Minimum Neutral Conductor | Amps | Write | |
| AV | 72 | OUTLET 4 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 1 | Amps | Write | |
| AV | 73 | OUTLET 4 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 2 | Amps | Write | |
| AV | 74 | OUTLET 4 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 3 | Amps | Write | |
| AV | 75 | OUTLET 4 LINE CURRENT MINIMUM | Outlet Line Current Minimum Neutral Conductor | Amps | Write | |
| AV | 76 | OUTLET 1 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 1 | Amps | Write | |
| AV | 77 | OUTLET 1 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 2 | Amps | Write | |
| AV | 78 | OUTLET 1 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 3 | Amps | Write | |
| AV | 79 | OUTLET 1 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Neutral Conductor | Amps | Write | |
| AV | 80 | OUTLET 2 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 1 | Amps | Write | |
| AV | 81 | OUTLET 2 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 2 | Amps | Write | |
| AV | 82 | OUTLET 2 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 3 | Amps | Write | |
| AV | 83 | OUTLET 2 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Neutral Conductor | Amps | Write | |
| AV | 84 | OUTLET 3 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 1 | Amps | Write | |
| AV | 85 | OUTLET 3 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 2 | Amps | Write | |
| AV | 86 | OUTLET 3 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 3 | Amps | Write | |
| AV | 87 | OUTLET 3 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Neutral Conductor | Amps | Write | |
| AV | 88 | OUTLET 4 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 1 | Amps | Write | |
| AV | 89 | OUTLET 4 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 2 | Amps | Write | |
| AV | 90 | OUTLET 4 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 3 | Amps | Write | |
| AV | 91 | OUTLET 4 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Neutral Conductor | Amps | Write | |
| AV | 92 | OUTLET CURRENT MIN ALARM | Outlet 1 Current Minimum Alarm | Amps | Write | |
| AV | 93 | OUTLET CURRENT MIN ALARM | Outlet 2 Current Minimum Alarm | Amps | Write | |
| AV | 94 | OUTLET CURRENT MIN ALARM | Outlet 3 Current Minimum Alarm | Amps | Write | |
| AV | 95 | OUTLET CURRENT MIN ALARM | Outlet 4 Current Minimum Alarm | Amps | Write | |
| AV | 96 | OUTLET CURRENT MAX ALARM | Outlet 1 Current Maximum Alarm | Amps | Write | |
| AV | 97 | OUTLET CURRENT MAX ALARM | Outlet 2 Current Maximum Alarm | Amps | Write | |
| AV | 98 | OUTLET CURRENT MAX ALARM | Outlet 3 Current Maximum Alarm | Amps | Write | |
| AV | 99 | OUTLET CURRENT MAX ALARM | Outlet 4 Current Maximum Alarm | Amps | Write | |
| AV | 100 | OUTLET 1 DEMAND TIME | Outlet 1 Demand Time | Minutes | Write | |
| AV | 101 | OUTLET 2 DEMAND TIME | Outlet 2 Demand Time | Minutes | Write | |
| AV | 102 | OUTLET 3 DEMAND TIME | Outlet 3 Demand Time | Minutes | Write | |
| AV | 103 | OUTLET 4 DEMAND TIME | Outlet 4 Demand Time | Minutes | Write | |
| LAV | 18 | OUTLET 1 TOTAL ACTIVE POWER | Outlet 1 Total Active Power | W | Read | |
| LAV | 19 | OUTLET 2 TOTAL ACTIVE POWER | Outlet 2 Total Active Power | W | Read | |
| LAV | 20 | OUTLET 3 TOTAL ACTIVE POWER | Outlet 3 Total Active Power | W | Read | |
| LAV | 21 | OUTLET 4 TOTAL ACTIVE POWER | Outlet 4 Total Active Power | W | Read | |
| LAV | 22 | OUTLET 1 PEAK TOTAL ACTIVE POWER | Outlet 1 Peak Total Active Power | W | Write | |
| LAV | 23 | OUTLET 2 PEAK TOTAL ACTIVE POWER | Outlet 2 Peak Total Active Power | W | Write | |
| LAV | 24 | OUTLET 3 PEAK TOTAL ACTIVE POWER | Outlet 3 Peak Total Active Power | W | Write | |
| LAV | 25 | OUTLET 4 PEAK TOTAL ACTIVE POWER | Outlet 4 Peak Total Active Power | W | Write | |
| LAV | 26 | OUTLET 1 TOTAL REACTIVE POWER | Outlet 1 Total Reactive Power | VAR | Read | |
| LAV | 27 | OUTLET 2 TOTAL REACTIVE POWER | Outlet 2 Total Reactive Power | VAR | Read | |
| LAV | 28 | OUTLET 3 TOTAL REACTIVE POWER | Outlet 3 Total Reactive Power | VAR | Read | |
| LAV | 29 | OUTLET 4 TOTAL REACTIVE POWER | Outlet 4 Total Reactive Power | VAR | Read | |
| LAV | 30 | OUTLET 1 TOTAL APPARENT POWER | Outlet 1 Total Apparent Power | VA | Read | |
| LAV | 31 | OUTLET 2 TOTAL APPARENT POWER | Outlet 2 Total Apparent Power | VA | Read | |
| LAV | 32 | OUTLET 3 TOTAL APPARENT POWER | Outlet 3 Total Apparent Power | VA | Read | |
| LAV | 33 | OUTLET 4 TOTAL APPARENT POWER | Outlet 4 Total Apparent Power | VA | Read | |
| AI | 57 | OUTLET 1 TOTAL POWER FACTOR | Outlet 1 Total Power Factor | Read | ||
| AI | 58 | OUTLET 2 TOTAL POWER FACTOR | Outlet 2 Total Power Factor | Read | ||
| AI | 59 | OUTLET 3 TOTAL POWER FACTOR | Outlet 3 Total Power Factor | Read | ||
| AI | 60 | OUTLET 4 TOTAL POWER FACTOR | Outlet 4 Total Power Factor | Read | ||
| LAV | 34 | OUTLET 1 TOTAL ENERGY | Outlet 1 Total Energy | kWh | Read | |
| LAV | 35 | OUTLET 2 TOTAL ENERGY | Outlet 2 Total Energy | kWh | Read | |
| LAV | 36 | OUTLET 3 TOTAL ENERGY | Outlet 3 Total Energy | kWh | Read | |
| LAV | 37 | OUTLET 4 TOTAL ENERGY | Outlet 4 Total Energy | kWh | Read | |
| CSV | 18 | OUTLET 1 LINE IDENTIFIER | Outlet 1 Line 1 ID (Admin level) | Write | ||
| CSV | 19 | OUTLET 1 LINE IDENTIFIER | Outlet 1 Line 2 ID (Admin level) | Write | ||
| CSV | 20 | OUTLET 1 LINE IDENTIFIER | Outlet 1 Line 3 ID (Admin level) | Write | ||
| CSV | 21 | OUTLET 1 LINE IDENTIFIER | Outlet 1 Neutral ID (Admin level) | Write | ||
| CSV | 22 | OUTLET 2 LINE IDENTIFIER | Outlet 2 Line 1 ID (Admin level) | Write | ||
| CSV | 23 | OUTLET 2 LINE IDENTIFIER | Outlet 2 Line 2 ID (Admin level) | Write | ||
| CSV | 24 | OUTLET 2 LINE IDENTIFIER | Outlet 2 Line 3 ID (Admin level) | Write | ||
| CSV | 25 | OUTLET 2 LINE IDENTIFIER | Outlet 2 Neutral ID (Admin level) | Write | ||
| CSV | 26 | OUTLET 3 LINE IDENTIFIER | Outlet 3 Line 1 ID (Admin level) | Write | ||
| CSV | 27 | OUTLET 3 LINE IDENTIFIER | Outlet 3 Line 2 ID (Admin level) | Write | ||
| CSV | 28 | OUTLET 3 LINE IDENTIFIER | Outlet 3 Line 3 ID (Admin level) | Write | ||
| CSV | 29 | OUTLET 3 LINE IDENTIFIER | Outlet 3 Neutral ID (Admin level) | Write | ||
| CSV | 30 | OUTLET 4 LINE IDENTIFIER | Outlet 4 Line 1 ID (Admin level) | Write | ||
| CSV | 31 | OUTLET 4 LINE IDENTIFIER | Outlet 4 Line 2 ID (Admin level) | Write | ||
| CSV | 32 | OUTLET 4 LINE IDENTIFIER | Outlet 4 Line 3 ID (Admin level) | Write | ||
| CSV | 33 | OUTLET 4 LINE IDENTIFIER | Outlet 4 Neutral ID (Admin level) | Write | ||
| AV | 104 | OUTLET 1 LINE CURRENT DEMAND | Outlet 1 Line Current Demand Line 1 | Amps | Write | |
| AV | 105 | OUTLET 1 LINE CURRENT DEMAND | Outlet 1 Line Current Demand Line 2 | Amps | Write | |
| AV | 106 | OUTLET 1 LINE CURRENT DEMAND | Outlet 1 Line Current Demand Line 3 | Amps | Write | |
| AV | 107 | OUTLET 1 LINE CURRENT DEMAND | Outlet 1 Line Current Demand Line Neutral | Amps | Write | |
| AV | 108 | OUTLET 2 LINE CURRENT DEMAND | Outlet 2 Line Current Demand Line 1 | Amps | Write | |
| AV | 109 | OUTLET 2 LINE CURRENT DEMAND | Outlet 2 Line Current Demand Line 2 | Amps | Write | |
| AV | 110 | OUTLET 2 LINE CURRENT DEMAND | Outlet 2 Line Current Demand Line 3 | Amps | Write | |
| AV | 111 | OUTLET 2 LINE CURRENT DEMAND | Outlet 2 Line Current Demand Line Neutral | Amps | Write | |
| AV | 112 | OUTLET 3 LINE CURRENT DEMAND | Outlet 3 Line Current Demand Line 1 | Amps | Write | |
| AV | 113 | OUTLET 3 LINE CURRENT DEMAND | Outlet 3 Line Current Demand Line 2 | Amps | Write | |
| AV | 114 | OUTLET 3 LINE CURRENT DEMAND | Outlet 3 Line Current Demand Line 3 | Amps | Write | |
| AV | 115 | OUTLET 3 LINE CURRENT DEMAND | Outlet 3 Line Current Demand Line Neutral | Amps | Write | |
| AV | 116 | OUTLET 4 LINE CURRENT DEMAND | Outlet 4 Line Current Demand Line 1 | Amps | Write | |
| AV | 117 | OUTLET 4 LINE CURRENT DEMAND | Outlet 4 Line Current Demand Line 2 | Amps | Write | |
| AV | 118 | OUTLET 4 LINE CURRENT DEMAND | Outlet 4 Line Current Demand Line 3 | Amps | Write | |
| AV | 119 | OUTLET 4 LINE CURRENT DEMAND | Outlet 4 Line Current Demand Line Neutral | Amps | Write | |
| AV | 120 | OUTLET 1 LINE CURRENT PEAK DEMAND | Outlet 1 Line Current Peak Demand Line 1 | Amps | Write | |
| AV | 121 | OUTLET 1 LINE CURRENT PEAK DEMAND | Outlet 1 Line Current Peak Demand Line 2 | Amps | Write | |
| AV | 122 | OUTLET 1 LINE CURRENT PEAK DEMAND | Outlet 1 Line Current Peak Demand Line 3 | Amps | Write | |
| AV | 123 | OUTLET 1 LINE CURRENT PEAK DEMAND | Outlet 1 Line Current Peak Demand Neutral Conductor | Amps | Write | |
| AV | 124 | OUTLET 2 LINE CURRENT PEAK DEMAND | Outlet 2 Line Current Peak Demand Line 1 | Amps | Write | |
| AV | 125 | OUTLET 2 LINE CURRENT PEAK DEMAND | Outlet 2 Line Current Peak Demand Line 2 | Amps | Write | |
| AV | 126 | OUTLET 2 LINE CURRENT PEAK DEMAND | Outlet 2 Line Current Peak Demand Line 3 | Amps | Write | |
| AV | 127 | OUTLET 2 LINE CURRENT PEAK DEMAND | Outlet 2 Line Current Peak Demand Neutral Conductor | Amps | Write | |
| AV | 128 | OUTLET 3 LINE CURRENT PEAK DEMAND | Outlet 3 Line Current Peak Demand Line 1 | Amps | Write | |
| AV | 129 | OUTLET 3 LINE CURRENT PEAK DEMAND | Outlet 3 Line Current Peak Demand Line 2 | Amps | Write | |
| AV | 130 | OUTLET 3 LINE CURRENT PEAK DEMAND | Outlet 3 Line Current Peak Demand Line 3 | Amps | Write | |
| AV | 131 | OUTLET 3 LINE CURRENT PEAK DEMAND | Outlet 3 Line Current Peak Demand Neutral Conductor | Amps | Write | |
| AV | 132 | OUTLET 4 LINE CURRENT PEAK DEMAND | Outlet 4 Line Current Peak Demand Line 1 | Amps | Write | |
| AV | 133 | OUTLET 4 LINE CURRENT PEAK DEMAND | Outlet 4 Line Current Peak Demand Line 2 | Amps | Write | |
| AV | 134 | OUTLET 4 LINE CURRENT PEAK DEMAND | Outlet 4 Line Current Peak Demand Line 3 | Amps | Write | |
| AV | 135 | OUTLET 4 LINE CURRENT PEAK DEMAND | Outlet 4 Line Current Peak Demand Neutral Conductor | Amps | Write | |
| AV | 136 | OUTLET 1 TOTAL LINE CURRENT DEMAND | Outlet 1 Total Line Current Demand | Amps | Write | |
| AV | 137 | OUTLET 2 TOTAL LINE CURRENT DEMAND | Outlet 2 Total Line Current Demand | Amps | Write | |
| AV | 138 | OUTLET 3 TOTAL LINE CURRENT DEMAND | Outlet 3 Total Line Current Demand | Amps | Write | |
| AV | 139 | OUTLET 4 TOTAL LINE CURRENT DEMAND | Outlet 4 Total Line Current Demand | Amps | Write | |
| AV | 140 | OUTLET 1 PEAK TOTAL LINE CURRENT DEMAND | Outlet 1 Peak Total Line Current Demand | Amps | Write | |
| AV | 141 | OUTLET 2 PEAK TOTAL LINE CURRENT DEMAND | Outlet 2 Peak Total Line Current Demand | Amps | Write | |
| AV | 142 | OUTLET 3 PEAK TOTAL LINE CURRENT DEMAND | Outlet 3 Peak Total Line Current Demand | Amps | Write | |
| AV | 143 | OUTLET 4 PEAK TOTAL LINE CURRENT DEMAND | Outlet 4 Peak Total Line Current Demand | Amps | Write | |
| CSV | 34 | NODE 1 IDENTIFIER | Node 1 ID (Admin level) | Write | ||
| CSV | 35 | NODE 2 IDENTIFIER | Node 2 ID (Admin level) | Write | ||
| CSV | 36 | NODE 3 IDENTIFIER | Node 3 ID (Admin level) | Write | ||
| CSV | 37 | NODE 4 IDENTIFIER | Node 4 ID (Admin level) | Write | ||
| AI | 61 | ENCLOSURE TEMPERATURE | Enclosure Temperature Value | degrees | Read | |
| AI | 62 | NODE TEMPERATURE | Node 1 Absolute Temperature Value | degrees | Read | |
| AI | 63 | NODE TEMPERATURE | Node 2 Absolute Temperature Value | degrees | Read | |
| AI | 64 | NODE TEMPERATURE | Node 3 Absolute Temperature Value | degrees | Read | |
| AI | 65 | NODE TEMPERATURE | Node 4 Absolute Temperature Value | degrees | Read | |
| AV | 144 | ENCLOSURE TEMPERATURE MAXIMUM | Maximum Enclosure Temperature Value | degrees | Write | |
| AV | 145 | NODE TEMPERATURE MAXIMUM | Maximum Node 1 Temperature Value | degrees | Write | |
| AV | 146 | NODE TEMPERATURE MAXIMUM | Maximum Node 2 Temperature Value | degrees | Write | |
| AV | 147 | NODE TEMPERATURE MAXIMUM | Maximum Node 3 Temperature Value | degrees | Write | |
| AV | 148 | NODE TEMPERATURE MAXIMUM | Maximum Node 4 Temperature Value | degrees | Write | |
| AI | 66 | ENCLOSURE SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLD | Enclosure System Temperature Maximum Alarm Threshold | degrees | Read | |
| AI | 67 | SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLD | Node 1 System Temperature Maximum Alarm Threshold | degrees | Read | |
| AI | 68 | SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLD | Node 2 System Temperature Maximum Alarm Threshold | degrees | Read | |
| AI | 69 | SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLD | Node 3 System Temperature Maximum Alarm Threshold | degrees | Read | |
| AI | 70 | SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLD | Node 4 System Temperature Maximum Alarm Threshold | degrees | Read | |
| AV | 149 | ENCLOSURE USER TEMPERATURE MAXIMUM ALARM THRESHOLD | Enclosure User Temperature Maximum Alarm Threshold (Admin level) | degrees | Write | |
| AV | 150 | USER TEMPERATURE MAXIMUM ALARM THRESHOLD | Node 1 User Temperature Maximum Alarm Threshold (Admin level) | degrees | Write | |
| AV | 151 | USER TEMPERATURE MAXIMUM ALARM THRESHOLD | Node 2 User Temperature Maximum Alarm Threshold (Admin level) | degrees | Write | |
| AV | 152 | USER TEMPERATURE MAXIMUM ALARM THRESHOLD | Node 3 User Temperature Maximum Alarm Threshold (Admin level) | degrees | Write | |
| AV | 153 | USER TEMPERATURE MAXIMUM ALARM THRESHOLD | Node 4 User Temperature Maximum Alarm Threshold (Admin level) | degrees | Write | |
| PIV | 6 | TEMPERATURE ALARM STATUS | Temperature Alarm Status for Feed Temperature Monitoring (hex bit field) | Read | ||
| PIV | 7 | RESET GROUP VALUES | Bit-coded reset of min, max, peak and demand values (Admin level) | Write | ||
| CSV | 38 | OUTLET 5 IDENTIFIER | Outlet 5 ID (Admin level) | Write | ||
| CSV | 39 | OUTLET 6 IDENTIFIER | Outlet 6 ID (Admin level) | Write | ||
| PIV | 8 | OUTLET ALARM STATUS 2 | OUTLET 5 and 6 alarm status (hex bit field) | Read | ||
| AI | 71 | OUTLET 5 LINE CURRENT | Outlet 5, Line Current Line 1 | Amps | Read | |
| AI | 72 | OUTLET 5 LINE CURRENT | Outlet 5, Line Current Line 2 | Amps | Read | |
| AI | 73 | OUTLET 5 LINE CURRENT | Outlet 5, Line Current Line 3 | Amps | Read | |
| AI | 74 | OUTLET 5 LINE CURRENT | Outlet 5, Line Current Line N | Amps | Read | |
| AI | 75 | OUTLET 6 LINE CURRENT | Outlet 6, Line Current Line 1 | Amps | Read | |
| AI | 76 | OUTLET 6 LINE CURRENT | Outlet 6, Line Current Line 2 | Amps | Read | |
| AI | 77 | OUTLET 6 LINE CURRENT | Outlet 6, Line Current Line 3 | Amps | Read | |
| AI | 78 | OUTLET 6 LINE CURRENT | Outlet 6, Line Current Line N | Amps | Read | |
| AV | 154 | OUTLET 5 LINE CURRENT RATING | Outlet 5 Line Current Rating. One rating for each outlet | Amps | Read | |
| AV | 155 | OUTLET 6 LINE CURRENT RATING | Outlet 6 Line Current Rating. One rating for each outlet | Amps | Read | |
| AI | 79 | OUTLET 5 LINE CURRENT RATING % of | Outlet 5 Line Current % of Rated Line 1 | Percent | Read | |
| AI | 80 | OUTLET 5 LINE CURRENT RATING % of | Outlet 5 Line Current % of Rated Line 2 | Percent | Read | |
| AI | 81 | OUTLET 5 LINE CURRENT RATING % of | Outlet 5 Line Current % of Rated Line 3 | Percent | Read | |
| AI | 82 | OUTLET 5 LINE CURRENT RATING % of | Outlet 5 Line Current % of Rated Neutral Conductor | Percent | Read | |
| AI | 83 | OUTLET 6 LINE CURRENT RATING % of | Outlet 6 Line Current % of Rated Line 1 | Percent | Read | |
| AI | 84 | OUTLET 6 LINE CURRENT RATING % of | Outlet 6 Line Current % of Rated Line 2 | Percent | Read | |
| AI | 85 | OUTLET 6 LINE CURRENT RATING % of | Outlet 6 Line Current % of Rated Line 3 | Percent | Read | |
| AI | 86 | OUTLET 6 LINE CURRENT RATING % of | Outlet 6 Line Current % of Rated Neutral Conductor | Percent | Read | |
| AV | 156 | OUTLET 5 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 1 | Amps | Write | |
| AV | 157 | OUTLET 5 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 2 | Amps | Write | |
| AV | 158 | OUTLET 5 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 3 | Amps | Write | |
| AV | 159 | OUTLET 5 LINE CURRENT MINIMUM | Outlet Line Current Minimum Neutral Conductor | Amps | Write | |
| AV | 160 | OUTLET 6 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 1 | Amps | Write | |
| AV | 161 | OUTLET 6 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 2 | Amps | Write | |
| AV | 162 | OUTLET 6 LINE CURRENT MINIMUM | Outlet Line Current Minimum Line 3 | Amps | Write | |
| AV | 163 | OUTLET 6 LINE CURRENT MINIMUM | Outlet Line Current Minimum Neutral Conductor | Amps | Write | |
| AV | 164 | OUTLET 5 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 1 | Amps | Write | |
| AV | 165 | OUTLET 5 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 2 | Amps | Write | |
| AV | 166 | OUTLET 5 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 3 | Amps | Write | |
| AV | 167 | OUTLET 5 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Neutral Conductor | Amps | Write | |
| AV | 168 | OUTLET 6 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 1 | Amps | Write | |
| AV | 169 | OUTLET 6 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 2 | Amps | Write | |
| AV | 170 | OUTLET 6 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Line 3 | Amps | Write | |
| AV | 171 | OUTLET 6 LINE CURRENT MAXIMUM | Outlet Line Current Maximum Neutral Conductor | Amps | Write | |
| AV | 172 | OUTLET CURRENT MIN ALARM | Outlet 5 Current Minimum Alarm | Amps | Write | |
| AV | 173 | OUTLET CURRENT MIN ALARM | Outlet 6 Current Minimum Alarm | Amps | Write | |
| AV | 174 | OUTLET CURRENT MAX ALARM | Outlet 5 Current Maximum Alarm | Amps | Write | |
| AV | 175 | OUTLET CURRENT MAX ALARM | Outlet 6 Current Maximum Alarm | Amps | Write | |
| AV | 176 | OUTLET 5 DEMAND TIME | Outlet 5 Demand Time | Minutes | Write | |
| AV | 177 | OUTLET 6 DEMAND TIME | Outlet 6 Demand Time | Minutes | Write | |
| LAV | 38 | OUTLET 5 TOTAL ACTIVE POWER | Outlet 5 Total Active Power | W | Read | |
| LAV | 39 | OUTLET 6 TOTAL ACTIVE POWER | Outlet 6 Total Active Power | W | Read | |
| LAV | 40 | OUTLET 5 PEAK TOTAL ACTIVE POWER | Outlet 5 Peak Total Active Power | W | Write | |
| LAV | 41 | OUTLET 6 PEAK TOTAL ACTIVE POWER | Outlet 6 Peak Total Active Power | W | Write | |
| LAV | 42 | OUTLET 5 TOTAL REACTIVE POWER | Outlet 5 Total Reactive Power | VAR | Read | |
| LAV | 43 | OUTLET 6 TOTAL REACTIVE POWER | Outlet 6 Total Reactive Power | VAR | Read | |
| LAV | 44 | OUTLET 5 TOTAL APPARENT POWER | Outlet 5 Total Apparent Power | VA | Read | |
| LAV | 45 | OUTLET 6 TOTAL APPARENT POWER | Outlet 6 Total Apparent Power | VA | Read | |
| AI | 87 | OUTLET 5 TOTAL POWER FACTOR | Outlet 5 Total Power Factor | Read | ||
| AI | 88 | OUTLET 6 TOTAL POWER FACTOR | Outlet 6 Total Power Factor | Read | ||
| LAV | 46 | OUTLET 5 TOTAL ENERGY | Outlet 5 Total Energy | kWh | Read | |
| LAV | 47 | OUTLET 6 TOTAL ENERGY | Outlet 6 Total Energy | kWh | Read | |
| CSV | 40 | OUTLET 5 LINE IDENTIFIER | Outlet 5 Line 1 ID (Admin level) | Write | ||
| CSV | 41 | OUTLET 5 LINE IDENTIFIER | Outlet 5 Line 2 ID (Admin level) | Write | ||
| CSV | 42 | OUTLET 5 LINE IDENTIFIER | Outlet 5 Line 3 ID (Admin level) | Write | ||
| CSV | 43 | OUTLET 5 LINE IDENTIFIER | Outlet 5 Neutral ID (Admin level) | Write | ||
| CSV | 44 | OUTLET 6 LINE IDENTIFIER | Outlet 6 Line 1 ID (Admin level) | Write | ||
| CSV | 45 | OUTLET 6 LINE IDENTIFIER | Outlet 6 Line 2 ID (Admin level) | Write | ||
| CSV | 46 | OUTLET 6 LINE IDENTIFIER | Outlet 6 Line 3 ID (Admin level) | Write | ||
| CSV | 47 | OUTLET 6 LINE IDENTIFIER | Outlet 6 Neutral ID (Admin level) | Write | ||
| AV | 178 | OUTLET 5 LINE CURRENT DEMAND | Outlet 5 Line Current Demand Line 1 | Amps | Write | |
| AV | 179 | OUTLET 5 LINE CURRENT DEMAND | Outlet 5 Line Current Demand Line 2 | Amps | Write | |
| AV | 180 | OUTLET 5 LINE CURRENT DEMAND | Outlet 5 Line Current Demand Line 3 | Amps | Write | |
| AV | 181 | OUTLET 5 LINE CURRENT DEMAND | Outlet 5 Line Current Demand Line Neutral | Amps | Write | |
| AV | 182 | OUTLET 6 LINE CURRENT DEMAND | Outlet 6 Line Current Demand Line 1 | Amps | Write | |
| AV | 183 | OUTLET 6 LINE CURRENT DEMAND | Outlet 6 Line Current Demand Line 2 | Amps | Write | |
| AV | 184 | OUTLET 6 LINE CURRENT DEMAND | Outlet 6 Line Current Demand Line 3 | Amps | Write | |
| AV | 185 | OUTLET 6 LINE CURRENT DEMAND | Outlet 6 Line Current Demand Line Neutral | Amps | Write | |
| AV | 186 | OUTLET 5 LINE CURRENT PEAK DEMAND | Outlet 5 Line Current Peak Demand Line 1 | Amps | Write | |
| AV | 187 | OUTLET 5 LINE CURRENT PEAK DEMAND | Outlet 5 Line Current Peak Demand Line 2 | Amps | Write | |
| AV | 188 | OUTLET 5 LINE CURRENT PEAK DEMAND | Outlet 5 Line Current Peak Demand Line 3 | Amps | Write | |
| AV | 189 | OUTLET 5 LINE CURRENT PEAK DEMAND | Outlet 5 Line Current Peak Demand Neutral Conductor | Amps | Write | |
| AV | 190 | OUTLET 6 LINE CURRENT PEAK DEMAND | Outlet 6 Line Current Peak Demand Line 1 | Amps | Write | |
| AV | 191 | OUTLET 6 LINE CURRENT PEAK DEMAND | Outlet 6 Line Current Peak Demand Line 2 | Amps | Write | |
| AV | 192 | OUTLET 6 LINE CURRENT PEAK DEMAND | Outlet 6 Line Current Peak Demand Line 3 | Amps | Write | |
| AV | 193 | OUTLET 6 LINE CURRENT PEAK DEMAND | Outlet 6 Line Current Peak Demand Neutral Conductor | Amps | Write | |
| AV | 194 | OUTLET 5 TOTAL LINE CURRENT DEMAND | Outlet 5 Total Line Current Demand | Amps | Write | |
| AV | 195 | OUTLET 6 TOTAL LINE CURRENT DEMAND | Outlet 6 Total Line Current Demand | Amps | Write | |
| AV | 196 | OUTLET 5 PEAK TOTAL LINE CURRENT DEMAND | Outlet 5 Peak Total Line Current Demand | Amps | Write | |
| AV | 197 | OUTLET 6 PEAK TOTAL LINE CURRENT DEMAND | Outlet 6 Peak Total Line Current Demand | Amps | Write | |
| AV | 198 | LINE TO NEUTRAL VOLTAGE MINIMUM | Line to Neutral Voltage Minimum L1-N | Volts | Write | |
| AV | 199 | LINE TO NEUTRAL VOLTAGE MAXIMUM | Line to Neutral Voltage Maximum L1-N | Volts | Write | |
| AV | 200 | LINE TO NEUTRAL VOLTAGE MIN ALARM | Line to Neutral Voltage Minimum Alarm L1-N | Volts | Write | |
| AV | 201 | LINE TO NEUTRAL VOLTAGE MAX ALARM | Line to Neutral Voltage Maximum Alarm L1-N | Volts | Write | |
| AV | 202 | LINE TO NEUTRAL VOLTAGE MINIMUM | Line to Neutral Voltage Minimum L2-N | Volts | Write | |
| AV | 203 | LINE TO NEUTRAL VOLTAGE MAXIMUM | Line to Neutral Voltage Maximum L2-N | Volts | Write | |
| AV | 204 | LINE TO NEUTRAL VOLTAGE MIN ALARM | Line to Neutral Voltage Minimum Alarm L2-N | Volts | Write | |
| AV | 205 | LINE TO NEUTRAL VOLTAGE MAX ALARM | Line to Neutral Voltage Maximum Alarm L2-N | Volts | Write | |
| AV | 206 | LINE TO NEUTRAL VOLTAGE MINIMUM | Line to Neutral Voltage Minimum L3-N | Volts | Write | |
| AV | 207 | LINE TO NEUTRAL VOLTAGE MAXIMUM | Line to Neutral Voltage Maximum L3-N | Volts | Write | |
| AV | 208 | LINE TO NEUTRAL VOLTAGE MIN ALARM | Line to Neutral Voltage Minimum Alarm L3-N | Volts | Write | |
| AV | 209 | LINE TO NEUTRAL VOLTAGE MAX ALARM | Line to Neutral Voltage Maximum Alarm L3-N | Volts | Write | |
| AV | 210 | FREQUENCY MINIMUM | Frequency Minimum | Hertz | Write | |
| AV | 211 | FREQUENCY MAXIMUM | Frequency Maximum | Hertz | Write | |
| AV | 212 | INFEED NEUTRAL CURRENT RATING | Infeed Neutral Current Rating (Admin level) | Amps | Write | |
| PIV | 11 | BREAKER ALARM STATUS | the breaker alarm status (hex bit field) | Read | ||
| PIV | 13 | BREAKER 1 STATUS | Breaker 1 Status | Read | 0=Open/Off, 1=Closed/On | |
| PIV | 14 | BREAKER 2 STATUS | Breaker 2 Status | Read | 0=Open/Off, 1=Closed/On |
No points match these filters.
Object ID lookup: Starline AC CPM point IDs by name
PIV1LCD POWER DOWN TIMEPIV2LCD BACKLIGHT LEVELPIV3LCD SLIDESHOW SPEEDCSV1DEVICE IDCSV2DEVICE NAMECSV3DEVICE LOCATIONCSV4VENDOR NAMECSV5MODEL NUMBERCSV6SERIAL NUMBERCSV7PRODUCT SERIAL NUMBERCSV8CATALOG NUMBER/PRODUCT TYPECSV9HARDWARE VERSIONCSV10FIRMWARE VERSION (M22276-116 v1.00)CSV11METER VERSIONCSV12Wi-Fi VERSIONCSV13CALIBRATION DATE (YYYY-MM-DD)AI1LINE TO NEUTRAL VOLTAGE AVERAGEAI2LINE TO LINE VOLTAGE AVERAGEAI3INFEED LINE CURRENT AVERAGEAV1INFEED LINE CURRENT RATINGAV2INFEED TOTAL LINE CURRENT DEMANDAV3INFEED TOTAL LINE CURRENT PEAK DEMANDAV4INFEED DEMAND TIMELAV1INFEED TOTAL ACTIVE POWERLAV2INFEED PEAK TOTAL ACTIVE POWERAV5INFEED TOTAL ACTIVE POWER DEMANDAV6INFEED PEAK TOTAL ACTIVE POWER DEMANDLAV3INFEED TOTAL REACTIVE POWERAV7INFEED TOTAL REACTIVE POWER DEMANDAV8INFEED PEAK TOTAL REACTIVE POWER DEMANDLAV4INFEED TOTAL APPARENT POWERAV9INFEED TOTAL APPARENT POWER DEMANDAV10INFEED PEAK TOTAL APPARENT POWER DEMANDAI4INFEED TOTAL POWER FACTORPIV4INFEED ALARM STATUSAI5FREQUENCYAI6LINE TO LINE VOLTAGEAI7LINE TO LINE VOLTAGEAI8LINE TO LINE VOLTAGEAI9INFEED LINE CURRENTAI10INFEED LINE CURRENTAI11INFEED LINE CURRENTAI12INFEED LINE CURRENTAI13INFEED LINE CURRENTAV11INFEED LINE CURRENT MINIMUMAV12INFEED LINE CURRENT MINIMUMAV13INFEED LINE CURRENT MINIMUMAV14INFEED LINE CURRENT MINIMUMAV15INFEED LINE CURRENT MINIMUMAV16INFEED LINE CURRENT MAXIMUMAV17INFEED LINE CURRENT MAXIMUMAV18INFEED LINE CURRENT MAXIMUMAV19INFEED LINE CURRENT MAXIMUMAV20INFEED LINE CURRENT MAXIMUMAI14INFEED LINE CURRENT RATING % ofAI15INFEED LINE CURRENT RATING % ofAI16INFEED LINE CURRENT RATING % ofAI17INFEED LINE CURRENT RATING % ofAI18INFEED LINE CURRENT RATING % ofAV21INFEED LINE CURRENT MIN ALARMAV22INFEED LINE CURRENT MIN ALARMAV23INFEED LINE CURRENT MIN ALARMAV24INFEED LINE CURRENT MIN ALARMAV25INFEED LINE CURRENT MIN ALARMAV26INFEED LINE CURRENT MAX ALARMAV27INFEED LINE CURRENT MAX ALARMAV28INFEED LINE CURRENT MAX ALARMAV29INFEED LINE CURRENT MAX ALARMAV30INFEED LINE CURRENT MAX ALARMAV31INFEED LINE CURRENT DEMANDAV32INFEED LINE CURRENT DEMANDAV33INFEED LINE CURRENT DEMANDAV34INFEED LINE CURRENT DEMANDAV35INFEED LINE CURRENT DEMANDAV36INFEED LINE CURRENT PEAK DEMANDAV37INFEED LINE CURRENT PEAK DEMANDAV38INFEED LINE CURRENT PEAK DEMANDAV39INFEED LINE CURRENT PEAK DEMANDAV40INFEED LINE CURRENT PEAK DEMANDAI19LINE TO NEUTRAL VOLTAGEAI20LINE TO NEUTRAL VOLTAGEAI21LINE TO NEUTRAL VOLTAGEAV41LINE TO LINE VOLTAGE MINIMUMAV42LINE TO LINE VOLTAGE MINIMUMAV43LINE TO LINE VOLTAGE MINIMUMAV44LINE TO LINE VOLTAGE MAXIMUMAV45LINE TO LINE VOLTAGE MAXIMUMAV46LINE TO LINE VOLTAGE MAXIMUMAV47LINE TO LINE VOLTAGE MIN ALARMAV48LINE TO LINE VOLTAGE MIN ALARMAV49LINE TO LINE VOLTAGE MIN ALARMAV50LINE TO LINE VOLTAGE MAX ALARMAV51LINE TO LINE VOLTAGE MAX ALARMAV52LINE TO LINE VOLTAGE MAX ALARMAI22INFEED POWER FACTORAI23INFEED POWER FACTORAI24INFEED POWER FACTORLAV5INFEED APPARENT POWERLAV6INFEED APPARENT POWERLAV7INFEED APPARENT POWERLAV8INFEED ACTIVE POWERLAV9INFEED ACTIVE POWERLAV10INFEED ACTIVE POWERAV53INFEED PEAK ACTIVE POWERAV54INFEED PEAK ACTIVE POWERAV55INFEED PEAK ACTIVE POWERLAV11INFEED REACTIVE POWERLAV12INFEED REACTIVE POWERLAV13INFEED REACTIVE POWERLAV14INFEED ENERGYLAV15INFEED ENERGYLAV16INFEED ENERGYLAV17INFEED TOTAL ENERGYBV1RESET ALL ENERGY VALUESCSV15OUTLET 2 IDENTIFIERCSV16OUTLET 3 IDENTIFIERCSV17OUTLET 4 IDENTIFIERPIV5OUTLET ALARM STATUSAI25OUTLET 1 LINE CURRENTAI26OUTLET 1 LINE CURRENTAI27OUTLET 1 LINE CURRENTAI28OUTLET 1 LINE CURRENTAI29OUTLET 2 LINE CURRENTAI30OUTLET 2 LINE CURRENTAI31OUTLET 2 LINE CURRENTAI32OUTLET 2 LINE CURRENTAI33OUTLET 3 LINE CURRENTAI34OUTLET 3 LINE CURRENTAI35OUTLET 3 LINE CURRENTAI36OUTLET 3 LINE CURRENTAI37OUTLET 4 LINE CURRENTAI38OUTLET 4 LINE CURRENTAI39OUTLET 4 LINE CURRENTAI40OUTLET 4 LINE CURRENTAV56OUTLET 1 LINE CURRENT RATINGAV57OUTLET 2 LINE CURRENT RATINGAV58OUTLET 3 LINE CURRENT RATINGAV59OUTLET 4 LINE CURRENT RATINGAI41OUTLET 1 LINE CURRENT RATING % ofAI42OUTLET 1 LINE CURRENT RATING % ofAI43OUTLET 1 LINE CURRENT RATING % ofAI44OUTLET 1 LINE CURRENT RATING % ofAI45OUTLET 2 LINE CURRENT RATING % ofAI46OUTLET 2 LINE CURRENT RATING % ofAI47OUTLET 2 LINE CURRENT RATING % ofAI48OUTLET 2 LINE CURRENT RATING % ofAI49OUTLET 3 LINE CURRENT RATING % ofAI50OUTLET 3 LINE CURRENT RATING % ofAI51OUTLET 3 LINE CURRENT RATING % ofAI52OUTLET 3 LINE CURRENT RATING % ofAI53OUTLET 4 LINE CURRENT RATING % ofAI54OUTLET 4 LINE CURRENT RATING % ofAI55OUTLET 4 LINE CURRENT RATING % ofAI56OUTLET 4 LINE CURRENT RATING % ofAV60OUTLET 1 LINE CURRENT MINIMUMAV61OUTLET 1 LINE CURRENT MINIMUMAV62OUTLET 1 LINE CURRENT MINIMUMAV63OUTLET 1 LINE CURRENT MINIMUMAV64OUTLET 2 LINE CURRENT MINIMUMAV65OUTLET 2 LINE CURRENT MINIMUMAV66OUTLET 2 LINE CURRENT MINIMUMAV67OUTLET 2 LINE CURRENT MINIMUMAV68OUTLET 3 LINE CURRENT MINIMUMAV69OUTLET 3 LINE CURRENT MINIMUMAV70OUTLET 3 LINE CURRENT MINIMUMAV71OUTLET 3 LINE CURRENT MINIMUMAV72OUTLET 4 LINE CURRENT MINIMUMAV73OUTLET 4 LINE CURRENT MINIMUMAV74OUTLET 4 LINE CURRENT MINIMUMAV75OUTLET 4 LINE CURRENT MINIMUMAV76OUTLET 1 LINE CURRENT MAXIMUMAV77OUTLET 1 LINE CURRENT MAXIMUMAV78OUTLET 1 LINE CURRENT MAXIMUMAV79OUTLET 1 LINE CURRENT MAXIMUMAV80OUTLET 2 LINE CURRENT MAXIMUMAV81OUTLET 2 LINE CURRENT MAXIMUMAV82OUTLET 2 LINE CURRENT MAXIMUMAV83OUTLET 2 LINE CURRENT MAXIMUMAV84OUTLET 3 LINE CURRENT MAXIMUMAV85OUTLET 3 LINE CURRENT MAXIMUMAV86OUTLET 3 LINE CURRENT MAXIMUMAV87OUTLET 3 LINE CURRENT MAXIMUMAV88OUTLET 4 LINE CURRENT MAXIMUMAV89OUTLET 4 LINE CURRENT MAXIMUMAV90OUTLET 4 LINE CURRENT MAXIMUMAV91OUTLET 4 LINE CURRENT MAXIMUMAV92OUTLET CURRENT MIN ALARMAV93OUTLET CURRENT MIN ALARMAV94OUTLET CURRENT MIN ALARMAV95OUTLET CURRENT MIN ALARMAV96OUTLET CURRENT MAX ALARMAV97OUTLET CURRENT MAX ALARMAV98OUTLET CURRENT MAX ALARMAV99OUTLET CURRENT MAX ALARMAV100OUTLET 1 DEMAND TIMEAV101OUTLET 2 DEMAND TIMEAV102OUTLET 3 DEMAND TIMEAV103OUTLET 4 DEMAND TIMELAV18OUTLET 1 TOTAL ACTIVE POWERLAV19OUTLET 2 TOTAL ACTIVE POWERLAV20OUTLET 3 TOTAL ACTIVE POWERLAV21OUTLET 4 TOTAL ACTIVE POWERLAV22OUTLET 1 PEAK TOTAL ACTIVE POWERLAV23OUTLET 2 PEAK TOTAL ACTIVE POWERLAV24OUTLET 3 PEAK TOTAL ACTIVE POWERLAV25OUTLET 4 PEAK TOTAL ACTIVE POWERLAV26OUTLET 1 TOTAL REACTIVE POWERLAV27OUTLET 2 TOTAL REACTIVE POWERLAV28OUTLET 3 TOTAL REACTIVE POWERLAV29OUTLET 4 TOTAL REACTIVE POWERLAV30OUTLET 1 TOTAL APPARENT POWERLAV31OUTLET 2 TOTAL APPARENT POWERLAV32OUTLET 3 TOTAL APPARENT POWERLAV33OUTLET 4 TOTAL APPARENT POWERAI57OUTLET 1 TOTAL POWER FACTORAI58OUTLET 2 TOTAL POWER FACTORAI59OUTLET 3 TOTAL POWER FACTORAI60OUTLET 4 TOTAL POWER FACTORLAV34OUTLET 1 TOTAL ENERGYLAV35OUTLET 2 TOTAL ENERGYLAV36OUTLET 3 TOTAL ENERGYLAV37OUTLET 4 TOTAL ENERGYCSV18OUTLET 1 LINE IDENTIFIERCSV19OUTLET 1 LINE IDENTIFIERCSV20OUTLET 1 LINE IDENTIFIERCSV21OUTLET 1 LINE IDENTIFIERCSV22OUTLET 2 LINE IDENTIFIERCSV23OUTLET 2 LINE IDENTIFIERCSV24OUTLET 2 LINE IDENTIFIERCSV25OUTLET 2 LINE IDENTIFIERCSV26OUTLET 3 LINE IDENTIFIERCSV27OUTLET 3 LINE IDENTIFIERCSV28OUTLET 3 LINE IDENTIFIERCSV29OUTLET 3 LINE IDENTIFIERCSV30OUTLET 4 LINE IDENTIFIERCSV31OUTLET 4 LINE IDENTIFIERCSV32OUTLET 4 LINE IDENTIFIERCSV33OUTLET 4 LINE IDENTIFIERAV104OUTLET 1 LINE CURRENT DEMANDAV105OUTLET 1 LINE CURRENT DEMANDAV106OUTLET 1 LINE CURRENT DEMANDAV107OUTLET 1 LINE CURRENT DEMANDAV108OUTLET 2 LINE CURRENT DEMANDAV109OUTLET 2 LINE CURRENT DEMANDAV110OUTLET 2 LINE CURRENT DEMANDAV111OUTLET 2 LINE CURRENT DEMANDAV112OUTLET 3 LINE CURRENT DEMANDAV113OUTLET 3 LINE CURRENT DEMANDAV114OUTLET 3 LINE CURRENT DEMANDAV115OUTLET 3 LINE CURRENT DEMANDAV116OUTLET 4 LINE CURRENT DEMANDAV117OUTLET 4 LINE CURRENT DEMANDAV118OUTLET 4 LINE CURRENT DEMANDAV119OUTLET 4 LINE CURRENT DEMANDAV120OUTLET 1 LINE CURRENT PEAK DEMANDAV121OUTLET 1 LINE CURRENT PEAK DEMANDAV122OUTLET 1 LINE CURRENT PEAK DEMANDAV123OUTLET 1 LINE CURRENT PEAK DEMANDAV124OUTLET 2 LINE CURRENT PEAK DEMANDAV125OUTLET 2 LINE CURRENT PEAK DEMANDAV126OUTLET 2 LINE CURRENT PEAK DEMANDAV127OUTLET 2 LINE CURRENT PEAK DEMANDAV128OUTLET 3 LINE CURRENT PEAK DEMANDAV129OUTLET 3 LINE CURRENT PEAK DEMANDAV130OUTLET 3 LINE CURRENT PEAK DEMANDAV131OUTLET 3 LINE CURRENT PEAK DEMANDAV132OUTLET 4 LINE CURRENT PEAK DEMANDAV133OUTLET 4 LINE CURRENT PEAK DEMANDAV134OUTLET 4 LINE CURRENT PEAK DEMANDAV135OUTLET 4 LINE CURRENT PEAK DEMANDAV136OUTLET 1 TOTAL LINE CURRENT DEMANDAV137OUTLET 2 TOTAL LINE CURRENT DEMANDAV138OUTLET 3 TOTAL LINE CURRENT DEMANDAV139OUTLET 4 TOTAL LINE CURRENT DEMANDAV140OUTLET 1 PEAK TOTAL LINE CURRENT DEMANDAV141OUTLET 2 PEAK TOTAL LINE CURRENT DEMANDAV142OUTLET 3 PEAK TOTAL LINE CURRENT DEMANDAV143OUTLET 4 PEAK TOTAL LINE CURRENT DEMANDCSV34NODE 1 IDENTIFIERCSV35NODE 2 IDENTIFIERCSV36NODE 3 IDENTIFIERCSV37NODE 4 IDENTIFIERAI61ENCLOSURE TEMPERATUREAI62NODE TEMPERATUREAI63NODE TEMPERATUREAI64NODE TEMPERATUREAI65NODE TEMPERATUREAV144ENCLOSURE TEMPERATURE MAXIMUMAV145NODE TEMPERATURE MAXIMUMAV146NODE TEMPERATURE MAXIMUMAV147NODE TEMPERATURE MAXIMUMAV148NODE TEMPERATURE MAXIMUMAI66ENCLOSURE SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLDAI67SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLDAI68SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLDAI69SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLDAI70SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLDAV149ENCLOSURE USER TEMPERATURE MAXIMUM ALARM THRESHOLDAV150USER TEMPERATURE MAXIMUM ALARM THRESHOLDAV151USER TEMPERATURE MAXIMUM ALARM THRESHOLDAV152USER TEMPERATURE MAXIMUM ALARM THRESHOLDAV153USER TEMPERATURE MAXIMUM ALARM THRESHOLDPIV6TEMPERATURE ALARM STATUSPIV7RESET GROUP VALUESCSV38OUTLET 5 IDENTIFIERCSV39OUTLET 6 IDENTIFIERPIV8OUTLET ALARM STATUS 2AI71OUTLET 5 LINE CURRENTAI72OUTLET 5 LINE CURRENTAI73OUTLET 5 LINE CURRENTAI74OUTLET 5 LINE CURRENTAI75OUTLET 6 LINE CURRENTAI76OUTLET 6 LINE CURRENTAI77OUTLET 6 LINE CURRENTAI78OUTLET 6 LINE CURRENTAV154OUTLET 5 LINE CURRENT RATINGAV155OUTLET 6 LINE CURRENT RATINGAI79OUTLET 5 LINE CURRENT RATING % ofAI80OUTLET 5 LINE CURRENT RATING % ofAI81OUTLET 5 LINE CURRENT RATING % ofAI82OUTLET 5 LINE CURRENT RATING % ofAI83OUTLET 6 LINE CURRENT RATING % ofAI84OUTLET 6 LINE CURRENT RATING % ofAI85OUTLET 6 LINE CURRENT RATING % ofAI86OUTLET 6 LINE CURRENT RATING % ofAV156OUTLET 5 LINE CURRENT MINIMUMAV157OUTLET 5 LINE CURRENT MINIMUMAV158OUTLET 5 LINE CURRENT MINIMUMAV159OUTLET 5 LINE CURRENT MINIMUMAV160OUTLET 6 LINE CURRENT MINIMUMAV161OUTLET 6 LINE CURRENT MINIMUMAV162OUTLET 6 LINE CURRENT MINIMUMAV163OUTLET 6 LINE CURRENT MINIMUMAV164OUTLET 5 LINE CURRENT MAXIMUMAV165OUTLET 5 LINE CURRENT MAXIMUMAV166OUTLET 5 LINE CURRENT MAXIMUMAV167OUTLET 5 LINE CURRENT MAXIMUMAV168OUTLET 6 LINE CURRENT MAXIMUMAV169OUTLET 6 LINE CURRENT MAXIMUMAV170OUTLET 6 LINE CURRENT MAXIMUMAV171OUTLET 6 LINE CURRENT MAXIMUMAV172OUTLET CURRENT MIN ALARMAV173OUTLET CURRENT MIN ALARMAV174OUTLET CURRENT MAX ALARMAV175OUTLET CURRENT MAX ALARMAV176OUTLET 5 DEMAND TIMEAV177OUTLET 6 DEMAND TIMELAV38OUTLET 5 TOTAL ACTIVE POWERLAV39OUTLET 6 TOTAL ACTIVE POWERLAV40OUTLET 5 PEAK TOTAL ACTIVE POWERLAV41OUTLET 6 PEAK TOTAL ACTIVE POWERLAV42OUTLET 5 TOTAL REACTIVE POWERLAV43OUTLET 6 TOTAL REACTIVE POWERLAV44OUTLET 5 TOTAL APPARENT POWERLAV45OUTLET 6 TOTAL APPARENT POWERAI87OUTLET 5 TOTAL POWER FACTORAI88OUTLET 6 TOTAL POWER FACTORLAV46OUTLET 5 TOTAL ENERGYLAV47OUTLET 6 TOTAL ENERGYCSV40OUTLET 5 LINE IDENTIFIERCSV41OUTLET 5 LINE IDENTIFIERCSV42OUTLET 5 LINE IDENTIFIERCSV43OUTLET 5 LINE IDENTIFIERCSV44OUTLET 6 LINE IDENTIFIERCSV45OUTLET 6 LINE IDENTIFIERCSV46OUTLET 6 LINE IDENTIFIERCSV47OUTLET 6 LINE IDENTIFIERAV178OUTLET 5 LINE CURRENT DEMANDAV179OUTLET 5 LINE CURRENT DEMANDAV180OUTLET 5 LINE CURRENT DEMANDAV181OUTLET 5 LINE CURRENT DEMANDAV182OUTLET 6 LINE CURRENT DEMANDAV183OUTLET 6 LINE CURRENT DEMANDAV184OUTLET 6 LINE CURRENT DEMANDAV185OUTLET 6 LINE CURRENT DEMANDAV186OUTLET 5 LINE CURRENT PEAK DEMANDAV187OUTLET 5 LINE CURRENT PEAK DEMANDAV188OUTLET 5 LINE CURRENT PEAK DEMANDAV189OUTLET 5 LINE CURRENT PEAK DEMANDAV190OUTLET 6 LINE CURRENT PEAK DEMANDAV191OUTLET 6 LINE CURRENT PEAK DEMANDAV192OUTLET 6 LINE CURRENT PEAK DEMANDAV193OUTLET 6 LINE CURRENT PEAK DEMANDAV194OUTLET 5 TOTAL LINE CURRENT DEMANDAV195OUTLET 6 TOTAL LINE CURRENT DEMANDAV196OUTLET 5 PEAK TOTAL LINE CURRENT DEMANDAV197OUTLET 6 PEAK TOTAL LINE CURRENT DEMANDAV198LINE TO NEUTRAL VOLTAGE MINIMUMAV199LINE TO NEUTRAL VOLTAGE MAXIMUMAV200LINE TO NEUTRAL VOLTAGE MIN ALARMAV201LINE TO NEUTRAL VOLTAGE MAX ALARMAV202LINE TO NEUTRAL VOLTAGE MINIMUMAV203LINE TO NEUTRAL VOLTAGE MAXIMUMAV204LINE TO NEUTRAL VOLTAGE MIN ALARMAV205LINE TO NEUTRAL VOLTAGE MAX ALARMAV206LINE TO NEUTRAL VOLTAGE MINIMUMAV207LINE TO NEUTRAL VOLTAGE MAXIMUMAV208LINE TO NEUTRAL VOLTAGE MIN ALARMAV209LINE TO NEUTRAL VOLTAGE MAX ALARMAV210FREQUENCY MINIMUMAV211FREQUENCY MAXIMUMAV212INFEED NEUTRAL CURRENT RATINGPIV11BREAKER ALARM STATUSPIV13BREAKER 1 STATUSPIV14BREAKER 2 STATUS
Integration notes
- Object names are generic and repeat (e.g. INFEED LINE CURRENT for lines 1-3 and neutral); the description column says which line, outlet or node each object is.
- Access comes from the Write Access Level column: User or Admin = writable, '-' = read-only. Admin-level objects are marked in the description.
- About 90% of the objects match the M70 CPM list, but it is not a drop-in copy: it has no OUTLET 1 IDENTIFIER (CSV 14), no NUMBER OF BREAKERS, no breaker 5-6 status and no identify/reboot BVs, and the breaker objects are numbered differently (breaker alarm PIV 11, breaker 1-2 status PIV 13-14). Use the M70 list only for M70 meters.
- The object list does not state the BACnet transport or network settings.
- Source: AC CPM BACNet Object List, revision 4 (3/3/2023), pages 2-10 (405 objects).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AC Critical Power Monitor (CPM) for busway and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Starline AC Critical Power Monitor (CPM) for busway
How many BACnet points does the Starline AC Critical Power Monitor (CPM) for busway have?
This list has 405 BACnet objects: 88 analog inputs, 212 analog values, 1 binary value, 46 characterstring values, 47 large analog values, 11 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Starline AC Critical Power Monitor (CPM) for busway BACnet points are writable?
254 of the 405 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Starline AC Critical Power Monitor (CPM) for busway BACnet documentation?
The source is AC CPM BACNet Object List (Rev 4), revision 2023-03-03, published free by Starline at https://cdn.starlinepower.com/drupal-media-and-files/files/files/AC-CPM-BACNet-Object-List-v4.26-v5.07.pdf.
What are the minimum BACnet points to integrate the Starline AC Critical Power Monitor (CPM) for busway?
Start with LAV 17 INFEED TOTAL ENERGY (Total infeed energy, kWh); LAV 1 INFEED TOTAL ACTIVE POWER (Total infeed active power, W); AI 3 INFEED LINE CURRENT AVERAGE (Average infeed line current, A); AI 9 INFEED LINE CURRENT (Infeed current, line 1, A); AI 10 INFEED LINE CURRENT (Infeed current, line 2, A); AI 11 INFEED LINE CURRENT (Infeed current, line 3, A); AI 1 LINE TO NEUTRAL VOLTAGE AVERAGE (Average line-to-neutral voltage, V); AI 4 INFEED TOTAL POWER FACTOR (Total power factor); PIV 4 INFEED ALARM STATUS (Infeed alarm status bits); PIV 5 OUTLET ALARM STATUS (Outlet 1-4 alarm status bits).
How do I check these points on the real AC Critical Power Monitor (CPM) for busway?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Starline BACnet points lists
Source: AC CPM BACNet Object List · Rev 4 · rev. 2023-03-03. Object names, instances and units are reproduced as published; descriptions are our own.