 "manufacturer": "Starline",
 "manufacturer_slug": "starline",
 "model": "AC Critical Power Monitor (CPM) for busway",
 "model_slug": "ac-cpm-critical-power-monitor",
 "short_model": "AC CPM",
 "aliases": [
  "AC CPM",
  "Starline AC CPM",
  "Starline CPM",
  "Critical Power Monitor",
  "Legrand Starline CPM"
 ],
 "equipment_type": "Busway power meter (critical power monitor)",
 "applies_to": "Starline (Legrand) AC Critical Power Monitors with firmware v4.21-v4.26, v4.21A-v4.26A or v5.02-v5.07.",
 "summary": "The AC CPM meters an infeed and up to six outlets, plus enclosure and node temperatures and breaker status. Its BACnet object list has 405 objects with a write-access level for each: device text fields, infeed voltages, currents, power, energy, demand and min/max values, per-outlet metering, alarm thresholds, hex alarm-status words and breaker status.",
 "bacnet_transport": [],
 "firmware": "v4.26, v4.26A, v5.07 (list also valid for v4.21-v4.24 and v5.02-v5.05)",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Object names are generic and repeat (e.g. INFEED LINE CURRENT for lines 1-3 and neutral); the description column says which line, outlet or node each object is.",
  "Access comes from the Write Access Level column: User or Admin = writable, '-' = read-only. Admin-level objects are marked in the description.",
  "About 90% of the objects match the M70 CPM list, but it is not a drop-in copy: it has no OUTLET 1 IDENTIFIER (CSV 14), no NUMBER OF BREAKERS, no breaker 5-6 status and no identify/reboot BVs, and the breaker objects are numbered differently (breaker alarm PIV 11, breaker 1-2 status PIV 13-14). Use the M70 list only for M70 meters.",
  "The object list does not state the BACnet transport or network settings.",
  "Source: AC CPM BACNet Object List, revision 4 (3/3/2023), pages 2-10 (405 objects)."
 ],
 "source": {
  "title": "AC CPM BACNet Object List",
  "doc_number": "Rev 4",
  "revision_date": "2023-03-03",
  "url": "https://cdn.starlinepower.com/drupal-media-and-files/files/files/AC-CPM-BACNet-Object-List-v4.26-v5.07.pdf"
 },
 "integration": {
  "summary": "Read the infeed totals (energy, active power, average current and voltage, power factor) and the per-line currents, plus the infeed and outlet alarm status words. Add per-outlet metering for each plug-in unit you need to bill or monitor.",
  "minimum_points": [
   {
    "ref": "LAV 17",
    "name": "INFEED TOTAL ENERGY",
    "why": "Total infeed energy, kWh"
   },
   {
    "ref": "LAV 1",
    "name": "INFEED TOTAL ACTIVE POWER",
    "why": "Total infeed active power, W"
   },
   {
    "ref": "AI 3",
    "name": "INFEED LINE CURRENT AVERAGE",
    "why": "Average infeed line current, A"
   },
   {
    "ref": "AI 9",
    "name": "INFEED LINE CURRENT",
    "why": "Infeed current, line 1, A"
   },
   {
    "ref": "AI 10",
    "name": "INFEED LINE CURRENT",
    "why": "Infeed current, line 2, A"
   },
   {
    "ref": "AI 11",
    "name": "INFEED LINE CURRENT",
    "why": "Infeed current, line 3, A"
   },
   {
    "ref": "AI 1",
    "name": "LINE TO NEUTRAL VOLTAGE AVERAGE",
    "why": "Average line-to-neutral voltage, V"
   },
   {
    "ref": "AI 4",
    "name": "INFEED TOTAL POWER FACTOR",
    "why": "Total power factor"
   },
   {
    "ref": "PIV 4",
    "name": "INFEED ALARM STATUS",
    "why": "Infeed alarm status bits"
   },
   {
    "ref": "PIV 5",
    "name": "OUTLET ALARM STATUS",
    "why": "Outlet 1-4 alarm status bits"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [],
  "gotchas": [
   "Many objects share the same name; map by object type and instance, not by name.",
   "Alarm thresholds, ratings and resets are writable; Admin-level writes need the admin access level. Don't write them cyclically."
  ]
 },
 "points": [
  {
   "type": "PIV",
   "instance": 1,
   "name": "LCD POWER DOWN TIME",
   "description": "LCD power down time",
   "units": "Seconds",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 2,
   "name": "LCD BACKLIGHT LEVEL",
   "description": "LCD backlight level",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 3,
   "name": "LCD SLIDESHOW SPEED",
   "description": "slideshow speed",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 1,
   "name": "DEVICE ID",
   "description": "Device ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 2,
   "name": "DEVICE NAME",
   "description": "Device Name (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 3,
   "name": "DEVICE LOCATION",
   "description": "Device Location (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 4,
   "name": "VENDOR NAME",
   "description": "Vendor Name",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 5,
   "name": "MODEL NUMBER",
   "description": "Model Number ID",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 6,
   "name": "SERIAL NUMBER",
   "description": "Meter's Serial Number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 7,
   "name": "PRODUCT SERIAL NUMBER",
   "description": "Meter's Product Serial Number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 8,
   "name": "CATALOG NUMBER/PRODUCT TYPE",
   "description": "Device Type",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 9,
   "name": "HARDWARE VERSION",
   "description": "Hardware Part Number and Version",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 10,
   "name": "FIRMWARE VERSION (M22276-116 v1.00)",
   "description": "Firmware Part Number and Version",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 11,
   "name": "METER VERSION",
   "description": "Meter Version",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 12,
   "name": "Wi-Fi VERSION",
   "description": "Wi-Fi Version",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 13,
   "name": "CALIBRATION DATE (YYYY-MM-DD)",
   "description": "Calibration Date",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "LINE TO NEUTRAL VOLTAGE AVERAGE",
   "description": "Line to Neutral Voltage Average",
   "units": "Volts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "LINE TO LINE VOLTAGE AVERAGE",
   "description": "Line to Line Voltage Average",
   "units": "Volts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "INFEED LINE CURRENT AVERAGE",
   "description": "Infeed Line Current Average",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "INFEED LINE CURRENT RATING",
   "description": "Infeed Line Current Rating (Admin level)",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "INFEED TOTAL LINE CURRENT DEMAND",
   "description": "Infeed Current Demand (uses line current to determine demand)",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "INFEED TOTAL LINE CURRENT PEAK DEMAND",
   "description": "Infeed Current Peak Demand",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "INFEED DEMAND TIME",
   "description": "Infeed Demand Interval",
   "units": "Minutes",
   "access": "W",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 1,
   "name": "INFEED TOTAL ACTIVE POWER",
   "description": "Infeed Total Active Power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 2,
   "name": "INFEED PEAK TOTAL ACTIVE POWER",
   "description": "Infeed Peak Total Active Power",
   "units": "W",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "INFEED TOTAL ACTIVE POWER DEMAND",
   "description": "Infeed Total Active Power Demand",
   "units": "W",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "INFEED PEAK TOTAL ACTIVE POWER DEMAND",
   "description": "Infeed Peak Total Active Power Demand",
   "units": "W",
   "access": "W",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 3,
   "name": "INFEED TOTAL REACTIVE POWER",
   "description": "Infeed Total Reactive Power",
   "units": "VAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "INFEED TOTAL REACTIVE POWER DEMAND",
   "description": "Infeed Total Reactive Power",
   "units": "VAR",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "INFEED PEAK TOTAL REACTIVE POWER DEMAND",
   "description": "Infeed Total Reactive Power",
   "units": "VAR",
   "access": "W",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 4,
   "name": "INFEED TOTAL APPARENT POWER",
   "description": "Infeed Total Apparent Power",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "INFEED TOTAL APPARENT POWER DEMAND",
   "description": "Infeed Total Apparent Power Demand",
   "units": "VA",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "INFEED PEAK TOTAL APPARENT POWER DEMAND",
   "description": "Infeed Peak Total Apparent Power Demand",
   "units": "VA",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "INFEED TOTAL POWER FACTOR",
   "description": "Total Power Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 4,
   "name": "INFEED ALARM STATUS",
   "description": "infeed alarm status (hex bit field)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "FREQUENCY",
   "description": "Frequency",
   "units": "Hertz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "LINE TO LINE VOLTAGE",
   "description": "Line to Line Voltage L1-L2",
   "units": "Volts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "LINE TO LINE VOLTAGE",
   "description": "Line to Line Voltage L2-L3",
   "units": "Volts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "LINE TO LINE VOLTAGE",
   "description": "Line to Line Voltage L3-L1",
   "units": "Volts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "INFEED LINE CURRENT",
   "description": "Infeed Line Current Line 1",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "INFEED LINE CURRENT",
   "description": "Infeed Line Current Line 2",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "INFEED LINE CURRENT",
   "description": "Infeed Line Current Line 3",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "INFEED LINE CURRENT",
   "description": "Infeed Line Current Calculated Neutral",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "INFEED LINE CURRENT",
   "description": "Infeed Line Current Measured Neutral",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "INFEED LINE CURRENT MINIMUM",
   "description": "Infeed Line Current Minimum Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "INFEED LINE CURRENT MINIMUM",
   "description": "Infeed Line Current Minimum Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "INFEED LINE CURRENT MINIMUM",
   "description": "Infeed Line Current Minimum Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "INFEED LINE CURRENT MINIMUM",
   "description": "Infeed Line Current Maximum Calculated Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "INFEED LINE CURRENT MINIMUM",
   "description": "Infeed Line Current Maximum Measured Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "INFEED LINE CURRENT MAXIMUM",
   "description": "Infeed Line Current Maximum Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "INFEED LINE CURRENT MAXIMUM",
   "description": "Infeed Line Current Maximum Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "INFEED LINE CURRENT MAXIMUM",
   "description": "Infeed Line Current Maximum Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "INFEED LINE CURRENT MAXIMUM",
   "description": "Infeed Line Current Maximum Calculated Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "INFEED LINE CURRENT MAXIMUM",
   "description": "Infeed Line Current Maximum Measured Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "INFEED LINE CURRENT RATING % of",
   "description": "Infeed Line Current % of Rated Line 1",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "INFEED LINE CURRENT RATING % of",
   "description": "Infeed Line Current % of Rated Line 2",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "INFEED LINE CURRENT RATING % of",
   "description": "Infeed Line Current % of Rated Line 3",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "INFEED LINE CURRENT RATING % of",
   "description": "Infeed Line Current % of Rated Calculated Neutral",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "INFEED LINE CURRENT RATING % of",
   "description": "Infeed Line Current % of Rated Measured Neutral",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "INFEED LINE CURRENT MIN ALARM",
   "description": "Infeed Line Current Minimum Alarm Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "INFEED LINE CURRENT MIN ALARM",
   "description": "Infeed Line Current Minimum Alarm Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "INFEED LINE CURRENT MIN ALARM",
   "description": "Infeed Line Current Minimum Alarm Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "INFEED LINE CURRENT MIN ALARM",
   "description": "Infeed Line Current Minimum Alarm Calculated Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "INFEED LINE CURRENT MIN ALARM",
   "description": "Infeed Line Current Minimum Alarm Measured Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "INFEED LINE CURRENT MAX ALARM",
   "description": "Infeed Line Current Maximum Alarm Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "INFEED LINE CURRENT MAX ALARM",
   "description": "Infeed Line Current Maximum Alarm Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "INFEED LINE CURRENT MAX ALARM",
   "description": "Infeed Line Current Maximum Alarm Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "INFEED LINE CURRENT MAX ALARM",
   "description": "Infeed Line Current Maximum Alarm Calculated Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "INFEED LINE CURRENT MAX ALARM",
   "description": "Infeed Line Current Maximum Alarm Measured Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "INFEED LINE CURRENT DEMAND",
   "description": "Infeed Line Current Demand Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "INFEED LINE CURRENT DEMAND",
   "description": "Infeed Line Current Demand Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "INFEED LINE CURRENT DEMAND",
   "description": "Infeed Line Current Demand Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "INFEED LINE CURRENT DEMAND",
   "description": "Infeed Line Current Demand Calculated Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "INFEED LINE CURRENT DEMAND",
   "description": "Infeed Line Current Demand Measured Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "INFEED LINE CURRENT PEAK DEMAND",
   "description": "Infeed Line Current Peak Demand Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "INFEED LINE CURRENT PEAK DEMAND",
   "description": "Infeed Line Current Peak Demand Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "INFEED LINE CURRENT PEAK DEMAND",
   "description": "Infeed Line Current Peak Demand Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "INFEED LINE CURRENT PEAK DEMAND",
   "description": "Infeed Line Current Peak Demand Calculated Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "INFEED LINE CURRENT PEAK DEMAND",
   "description": "Infeed Line Current Peak Demand Measured Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "LINE TO NEUTRAL VOLTAGE",
   "description": "Line to Neutral Voltage L1-LN",
   "units": "Volts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "LINE TO NEUTRAL VOLTAGE",
   "description": "Line to Neutral Voltage L2-N",
   "units": "Volts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "LINE TO NEUTRAL VOLTAGE",
   "description": "Line to Neutral Voltage L3-N",
   "units": "Volts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "LINE TO LINE VOLTAGE MINIMUM",
   "description": "Line to Line Voltage Minimum L1-L2",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "LINE TO LINE VOLTAGE MINIMUM",
   "description": "Line to Line Voltage Minimum L2-L3",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "LINE TO LINE VOLTAGE MINIMUM",
   "description": "Line to Line Voltage Minimum L3-L1",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "LINE TO LINE VOLTAGE MAXIMUM",
   "description": "Line to Line Voltage Maximum L1-L2",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "LINE TO LINE VOLTAGE MAXIMUM",
   "description": "Line to Line Voltage Maximum L2-L3",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "LINE TO LINE VOLTAGE MAXIMUM",
   "description": "Line to Line Voltage Maximum L3-L1",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "LINE TO LINE VOLTAGE MIN ALARM",
   "description": "Line to Line Voltage Minimum Alarm L1-L2",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "LINE TO LINE VOLTAGE MIN ALARM",
   "description": "Line to Line Voltage Minimum Alarm L2-L3",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "LINE TO LINE VOLTAGE MIN ALARM",
   "description": "Line to Line Voltage Minimum Alarm L3-L1",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "LINE TO LINE VOLTAGE MAX ALARM",
   "description": "Line to Line Voltage Maximum Alarm L1-L2",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "LINE TO LINE VOLTAGE MAX ALARM",
   "description": "Line to Line Voltage Maximum Alarm L2-L3",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "LINE TO LINE VOLTAGE MAX ALARM",
   "description": "Line to Line Voltage Maximum Alarm L3-L1",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "INFEED POWER FACTOR",
   "description": "Infeed Power Factor L1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "INFEED POWER FACTOR",
   "description": "Infeed Power Factor L2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "INFEED POWER FACTOR",
   "description": "Infeed Power Factor L3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 5,
   "name": "INFEED APPARENT POWER",
   "description": "Infeed Apparent Power L1",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 6,
   "name": "INFEED APPARENT POWER",
   "description": "Infeed Apparent Power L2",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 7,
   "name": "INFEED APPARENT POWER",
   "description": "Infeed Apparent Power L3",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 8,
   "name": "INFEED ACTIVE POWER",
   "description": "Infeed Active Power L1",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 9,
   "name": "INFEED ACTIVE POWER",
   "description": "Infeed Active Power L2",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 10,
   "name": "INFEED ACTIVE POWER",
   "description": "Infeed Active Power L3",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "INFEED PEAK ACTIVE POWER",
   "description": "Infeed Peak Active Power L1",
   "units": "W",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "INFEED PEAK ACTIVE POWER",
   "description": "Infeed Peak Active Power L2",
   "units": "W",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "INFEED PEAK ACTIVE POWER",
   "description": "Infeed Peak Active Power L3",
   "units": "W",
   "access": "W",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 11,
   "name": "INFEED REACTIVE POWER",
   "description": "Infeed Reactive Power L1",
   "units": "VAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 12,
   "name": "INFEED REACTIVE POWER",
   "description": "Infeed Reactive Power L2",
   "units": "VAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 13,
   "name": "INFEED REACTIVE POWER",
   "description": "Infeed Reactive Power L3",
   "units": "VAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 14,
   "name": "INFEED ENERGY",
   "description": "Infeed Energy L1",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 15,
   "name": "INFEED ENERGY",
   "description": "Infeed Energy L2",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 16,
   "name": "INFEED ENERGY",
   "description": "Infeed Energy L3",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 17,
   "name": "INFEED TOTAL ENERGY",
   "description": "Infeed Total Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "RESET ALL ENERGY VALUES",
   "description": "Reset all energy values",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 15,
   "name": "OUTLET 2 IDENTIFIER",
   "description": "Outlet 2 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 16,
   "name": "OUTLET 3 IDENTIFIER",
   "description": "Outlet 3 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 17,
   "name": "OUTLET 4 IDENTIFIER",
   "description": "Outlet 4 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 5,
   "name": "OUTLET ALARM STATUS",
   "description": "OUTLET 1, 2, 3, and 4 alarm status (hex bit field)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "OUTLET 1 LINE CURRENT",
   "description": "Outlet 1, Line Current Line 1",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "OUTLET 1 LINE CURRENT",
   "description": "Outlet 1, Line Current Line 2",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "OUTLET 1 LINE CURRENT",
   "description": "Outlet 1, Line Current Line 3",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "OUTLET 1 LINE CURRENT",
   "description": "Outlet 1, Line Current Line N",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "OUTLET 2 LINE CURRENT",
   "description": "Outlet 2, Line Current Line 1",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "OUTLET 2 LINE CURRENT",
   "description": "Outlet 2, Line Current Line 2",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "OUTLET 2 LINE CURRENT",
   "description": "Outlet 2, Line Current Line 3",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "OUTLET 2 LINE CURRENT",
   "description": "Outlet 2, Line Current Line N",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "OUTLET 3 LINE CURRENT",
   "description": "Outlet 3, Line Current Line 1",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "OUTLET 3 LINE CURRENT",
   "description": "Outlet 3, Line Current Line 2",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "OUTLET 3 LINE CURRENT",
   "description": "Outlet 3, Line Current Line 3",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "OUTLET 3 LINE CURRENT",
   "description": "Outlet 3, Line Current Line N",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "OUTLET 4 LINE CURRENT",
   "description": "Outlet 4, Line Current Line 1",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "OUTLET 4 LINE CURRENT",
   "description": "Outlet 4, Line Current Line 2",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "OUTLET 4 LINE CURRENT",
   "description": "Outlet 4, Line Current Line 3",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "OUTLET 4 LINE CURRENT",
   "description": "Outlet 4, Line Current Line N",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "OUTLET 1 LINE CURRENT RATING",
   "description": "Outlet 1 Line Current Rating. One rating for each outlet",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "OUTLET 2 LINE CURRENT RATING",
   "description": "Outlet 2 Line Current Rating. One rating for each outlet",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "OUTLET 3 LINE CURRENT RATING",
   "description": "Outlet 3 Line Current Rating. One rating for each outlet",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "OUTLET 4 LINE CURRENT RATING",
   "description": "Outlet 4 Line Current Rating. One rating for each outlet",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "OUTLET 1 LINE CURRENT RATING % of",
   "description": "Outlet 1 Line Current % of Rated Line 1",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "OUTLET 1 LINE CURRENT RATING % of",
   "description": "Outlet 1 Line Current % of Rated Line 2",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "OUTLET 1 LINE CURRENT RATING % of",
   "description": "Outlet 1 Line Current % of Rated Line 3",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "OUTLET 1 LINE CURRENT RATING % of",
   "description": "Outlet 1 Line Current % of Rated Neutral Conductor",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "OUTLET 2 LINE CURRENT RATING % of",
   "description": "Outlet 2 Line Current % of Rated Line 1",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "OUTLET 2 LINE CURRENT RATING % of",
   "description": "Outlet 2 Line Current % of Rated Line 2",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "OUTLET 2 LINE CURRENT RATING % of",
   "description": "Outlet 2 Line Current % of Rated Line 3",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "OUTLET 2 LINE CURRENT RATING % of",
   "description": "Outlet 2 Line Current % of Rated Neutral Conductor",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "OUTLET 3 LINE CURRENT RATING % of",
   "description": "Outlet 3 Line Current % of Rated Line 1",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "OUTLET 3 LINE CURRENT RATING % of",
   "description": "Outlet 3 Line Current % of Rated Line 2",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "OUTLET 3 LINE CURRENT RATING % of",
   "description": "Outlet 3 Line Current % of Rated Line 3",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "OUTLET 3 LINE CURRENT RATING % of",
   "description": "Outlet 3 Line Current % of Rated Neutral Conductor",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "OUTLET 4 LINE CURRENT RATING % of",
   "description": "Outlet 4 Line Current % of Rated Line 1",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "OUTLET 4 LINE CURRENT RATING % of",
   "description": "Outlet 4 Line Current % of Rated Line 2",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "OUTLET 4 LINE CURRENT RATING % of",
   "description": "Outlet 4 Line Current % of Rated Line 3",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "OUTLET 4 LINE CURRENT RATING % of",
   "description": "Outlet 4 Line Current % of Rated Neutral Conductor",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "OUTLET 1 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "OUTLET 1 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "OUTLET 1 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "OUTLET 1 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "OUTLET 2 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "OUTLET 2 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "OUTLET 2 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "OUTLET 2 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "OUTLET 3 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "OUTLET 3 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "OUTLET 3 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "OUTLET 3 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "OUTLET 4 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "OUTLET 4 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "OUTLET 4 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "OUTLET 4 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 76,
   "name": "OUTLET 1 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "OUTLET 1 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "OUTLET 1 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "OUTLET 1 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "OUTLET 2 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "OUTLET 2 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "OUTLET 2 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "OUTLET 2 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "OUTLET 3 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "OUTLET 3 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "OUTLET 3 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "OUTLET 3 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "OUTLET 4 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "OUTLET 4 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "OUTLET 4 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "OUTLET 4 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "OUTLET CURRENT MIN ALARM",
   "description": "Outlet 1 Current Minimum Alarm",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 93,
   "name": "OUTLET CURRENT MIN ALARM",
   "description": "Outlet 2 Current Minimum Alarm",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "OUTLET CURRENT MIN ALARM",
   "description": "Outlet 3 Current Minimum Alarm",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "OUTLET CURRENT MIN ALARM",
   "description": "Outlet 4 Current Minimum Alarm",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "OUTLET CURRENT MAX ALARM",
   "description": "Outlet 1 Current Maximum Alarm",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "OUTLET CURRENT MAX ALARM",
   "description": "Outlet 2 Current Maximum Alarm",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "OUTLET CURRENT MAX ALARM",
   "description": "Outlet 3 Current Maximum Alarm",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 99,
   "name": "OUTLET CURRENT MAX ALARM",
   "description": "Outlet 4 Current Maximum Alarm",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "OUTLET 1 DEMAND TIME",
   "description": "Outlet 1 Demand Time",
   "units": "Minutes",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "OUTLET 2 DEMAND TIME",
   "description": "Outlet 2 Demand Time",
   "units": "Minutes",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "OUTLET 3 DEMAND TIME",
   "description": "Outlet 3 Demand Time",
   "units": "Minutes",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "OUTLET 4 DEMAND TIME",
   "description": "Outlet 4 Demand Time",
   "units": "Minutes",
   "access": "W",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 18,
   "name": "OUTLET 1 TOTAL ACTIVE POWER",
   "description": "Outlet 1 Total Active Power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 19,
   "name": "OUTLET 2 TOTAL ACTIVE POWER",
   "description": "Outlet 2 Total Active Power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 20,
   "name": "OUTLET 3 TOTAL ACTIVE POWER",
   "description": "Outlet 3 Total Active Power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 21,
   "name": "OUTLET 4 TOTAL ACTIVE POWER",
   "description": "Outlet 4 Total Active Power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 22,
   "name": "OUTLET 1 PEAK TOTAL ACTIVE POWER",
   "description": "Outlet 1 Peak Total Active Power",
   "units": "W",
   "access": "W",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 23,
   "name": "OUTLET 2 PEAK TOTAL ACTIVE POWER",
   "description": "Outlet 2 Peak Total Active Power",
   "units": "W",
   "access": "W",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 24,
   "name": "OUTLET 3 PEAK TOTAL ACTIVE POWER",
   "description": "Outlet 3 Peak Total Active Power",
   "units": "W",
   "access": "W",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 25,
   "name": "OUTLET 4 PEAK TOTAL ACTIVE POWER",
   "description": "Outlet 4 Peak Total Active Power",
   "units": "W",
   "access": "W",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 26,
   "name": "OUTLET 1 TOTAL REACTIVE POWER",
   "description": "Outlet 1 Total Reactive Power",
   "units": "VAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 27,
   "name": "OUTLET 2 TOTAL REACTIVE POWER",
   "description": "Outlet 2 Total Reactive Power",
   "units": "VAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 28,
   "name": "OUTLET 3 TOTAL REACTIVE POWER",
   "description": "Outlet 3 Total Reactive Power",
   "units": "VAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 29,
   "name": "OUTLET 4 TOTAL REACTIVE POWER",
   "description": "Outlet 4 Total Reactive Power",
   "units": "VAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 30,
   "name": "OUTLET 1 TOTAL APPARENT POWER",
   "description": "Outlet 1 Total Apparent Power",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 31,
   "name": "OUTLET 2 TOTAL APPARENT POWER",
   "description": "Outlet 2 Total Apparent Power",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 32,
   "name": "OUTLET 3 TOTAL APPARENT POWER",
   "description": "Outlet 3 Total Apparent Power",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 33,
   "name": "OUTLET 4 TOTAL APPARENT POWER",
   "description": "Outlet 4 Total Apparent Power",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 57,
   "name": "OUTLET 1 TOTAL POWER FACTOR",
   "description": "Outlet 1 Total Power Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "OUTLET 2 TOTAL POWER FACTOR",
   "description": "Outlet 2 Total Power Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 59,
   "name": "OUTLET 3 TOTAL POWER FACTOR",
   "description": "Outlet 3 Total Power Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 60,
   "name": "OUTLET 4 TOTAL POWER FACTOR",
   "description": "Outlet 4 Total Power Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 34,
   "name": "OUTLET 1 TOTAL ENERGY",
   "description": "Outlet 1 Total Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 35,
   "name": "OUTLET 2 TOTAL ENERGY",
   "description": "Outlet 2 Total Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 36,
   "name": "OUTLET 3 TOTAL ENERGY",
   "description": "Outlet 3 Total Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 37,
   "name": "OUTLET 4 TOTAL ENERGY",
   "description": "Outlet 4 Total Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 18,
   "name": "OUTLET 1 LINE IDENTIFIER",
   "description": "Outlet 1 Line 1 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 19,
   "name": "OUTLET 1 LINE IDENTIFIER",
   "description": "Outlet 1 Line 2 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 20,
   "name": "OUTLET 1 LINE IDENTIFIER",
   "description": "Outlet 1 Line 3 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 21,
   "name": "OUTLET 1 LINE IDENTIFIER",
   "description": "Outlet 1 Neutral ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 22,
   "name": "OUTLET 2 LINE IDENTIFIER",
   "description": "Outlet 2 Line 1 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 23,
   "name": "OUTLET 2 LINE IDENTIFIER",
   "description": "Outlet 2 Line 2 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 24,
   "name": "OUTLET 2 LINE IDENTIFIER",
   "description": "Outlet 2 Line 3 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 25,
   "name": "OUTLET 2 LINE IDENTIFIER",
   "description": "Outlet 2 Neutral ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 26,
   "name": "OUTLET 3 LINE IDENTIFIER",
   "description": "Outlet 3 Line 1 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 27,
   "name": "OUTLET 3 LINE IDENTIFIER",
   "description": "Outlet 3 Line 2 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 28,
   "name": "OUTLET 3 LINE IDENTIFIER",
   "description": "Outlet 3 Line 3 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 29,
   "name": "OUTLET 3 LINE IDENTIFIER",
   "description": "Outlet 3 Neutral ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 30,
   "name": "OUTLET 4 LINE IDENTIFIER",
   "description": "Outlet 4 Line 1 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 31,
   "name": "OUTLET 4 LINE IDENTIFIER",
   "description": "Outlet 4 Line 2 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 32,
   "name": "OUTLET 4 LINE IDENTIFIER",
   "description": "Outlet 4 Line 3 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 33,
   "name": "OUTLET 4 LINE IDENTIFIER",
   "description": "Outlet 4 Neutral ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "OUTLET 1 LINE CURRENT DEMAND",
   "description": "Outlet 1 Line Current Demand Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "OUTLET 1 LINE CURRENT DEMAND",
   "description": "Outlet 1 Line Current Demand Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "OUTLET 1 LINE CURRENT DEMAND",
   "description": "Outlet 1 Line Current Demand Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "OUTLET 1 LINE CURRENT DEMAND",
   "description": "Outlet 1 Line Current Demand Line Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "OUTLET 2 LINE CURRENT DEMAND",
   "description": "Outlet 2 Line Current Demand Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "OUTLET 2 LINE CURRENT DEMAND",
   "description": "Outlet 2 Line Current Demand Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "OUTLET 2 LINE CURRENT DEMAND",
   "description": "Outlet 2 Line Current Demand Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "OUTLET 2 LINE CURRENT DEMAND",
   "description": "Outlet 2 Line Current Demand Line Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "OUTLET 3 LINE CURRENT DEMAND",
   "description": "Outlet 3 Line Current Demand Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "OUTLET 3 LINE CURRENT DEMAND",
   "description": "Outlet 3 Line Current Demand Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "OUTLET 3 LINE CURRENT DEMAND",
   "description": "Outlet 3 Line Current Demand Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "OUTLET 3 LINE CURRENT DEMAND",
   "description": "Outlet 3 Line Current Demand Line Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "OUTLET 4 LINE CURRENT DEMAND",
   "description": "Outlet 4 Line Current Demand Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "OUTLET 4 LINE CURRENT DEMAND",
   "description": "Outlet 4 Line Current Demand Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "OUTLET 4 LINE CURRENT DEMAND",
   "description": "Outlet 4 Line Current Demand Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "OUTLET 4 LINE CURRENT DEMAND",
   "description": "Outlet 4 Line Current Demand Line Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "OUTLET 1 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 1 Line Current Peak Demand Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "OUTLET 1 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 1 Line Current Peak Demand Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "OUTLET 1 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 1 Line Current Peak Demand Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "OUTLET 1 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 1 Line Current Peak Demand Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "OUTLET 2 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 2 Line Current Peak Demand Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "OUTLET 2 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 2 Line Current Peak Demand Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 126,
   "name": "OUTLET 2 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 2 Line Current Peak Demand Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 127,
   "name": "OUTLET 2 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 2 Line Current Peak Demand Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 128,
   "name": "OUTLET 3 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 3 Line Current Peak Demand Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 129,
   "name": "OUTLET 3 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 3 Line Current Peak Demand Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 130,
   "name": "OUTLET 3 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 3 Line Current Peak Demand Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 131,
   "name": "OUTLET 3 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 3 Line Current Peak Demand Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 132,
   "name": "OUTLET 4 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 4 Line Current Peak Demand Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 133,
   "name": "OUTLET 4 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 4 Line Current Peak Demand Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 134,
   "name": "OUTLET 4 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 4 Line Current Peak Demand Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 135,
   "name": "OUTLET 4 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 4 Line Current Peak Demand Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 136,
   "name": "OUTLET 1 TOTAL LINE CURRENT DEMAND",
   "description": "Outlet 1 Total Line Current Demand",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 137,
   "name": "OUTLET 2 TOTAL LINE CURRENT DEMAND",
   "description": "Outlet 2 Total Line Current Demand",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 138,
   "name": "OUTLET 3 TOTAL LINE CURRENT DEMAND",
   "description": "Outlet 3 Total Line Current Demand",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 139,
   "name": "OUTLET 4 TOTAL LINE CURRENT DEMAND",
   "description": "Outlet 4 Total Line Current Demand",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 140,
   "name": "OUTLET 1 PEAK TOTAL LINE CURRENT DEMAND",
   "description": "Outlet 1 Peak Total Line Current Demand",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 141,
   "name": "OUTLET 2 PEAK TOTAL LINE CURRENT DEMAND",
   "description": "Outlet 2 Peak Total Line Current Demand",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 142,
   "name": "OUTLET 3 PEAK TOTAL LINE CURRENT DEMAND",
   "description": "Outlet 3 Peak Total Line Current Demand",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 143,
   "name": "OUTLET 4 PEAK TOTAL LINE CURRENT DEMAND",
   "description": "Outlet 4 Peak Total Line Current Demand",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 34,
   "name": "NODE 1 IDENTIFIER",
   "description": "Node 1 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 35,
   "name": "NODE 2 IDENTIFIER",
   "description": "Node 2 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 36,
   "name": "NODE 3 IDENTIFIER",
   "description": "Node 3 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 37,
   "name": "NODE 4 IDENTIFIER",
   "description": "Node 4 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "ENCLOSURE TEMPERATURE",
   "description": "Enclosure Temperature Value",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 62,
   "name": "NODE TEMPERATURE",
   "description": "Node 1 Absolute Temperature Value",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "NODE TEMPERATURE",
   "description": "Node 2 Absolute Temperature Value",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "NODE TEMPERATURE",
   "description": "Node 3 Absolute Temperature Value",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "NODE TEMPERATURE",
   "description": "Node 4 Absolute Temperature Value",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 144,
   "name": "ENCLOSURE TEMPERATURE MAXIMUM",
   "description": "Maximum Enclosure Temperature Value",
   "units": "degrees",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 145,
   "name": "NODE TEMPERATURE MAXIMUM",
   "description": "Maximum Node 1 Temperature Value",
   "units": "degrees",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 146,
   "name": "NODE TEMPERATURE MAXIMUM",
   "description": "Maximum Node 2 Temperature Value",
   "units": "degrees",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 147,
   "name": "NODE TEMPERATURE MAXIMUM",
   "description": "Maximum Node 3 Temperature Value",
   "units": "degrees",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 148,
   "name": "NODE TEMPERATURE MAXIMUM",
   "description": "Maximum Node 4 Temperature Value",
   "units": "degrees",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "ENCLOSURE SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLD",
   "description": "Enclosure System Temperature Maximum Alarm Threshold",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLD",
   "description": "Node 1 System Temperature Maximum Alarm Threshold",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 68,
   "name": "SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLD",
   "description": "Node 2 System Temperature Maximum Alarm Threshold",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 69,
   "name": "SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLD",
   "description": "Node 3 System Temperature Maximum Alarm Threshold",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 70,
   "name": "SYSTEM TEMPERATURE MAXIMUM ALARM THRESHOLD",
   "description": "Node 4 System Temperature Maximum Alarm Threshold",
   "units": "degrees",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 149,
   "name": "ENCLOSURE USER TEMPERATURE MAXIMUM ALARM THRESHOLD",
   "description": "Enclosure User Temperature Maximum Alarm Threshold (Admin level)",
   "units": "degrees",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 150,
   "name": "USER TEMPERATURE MAXIMUM ALARM THRESHOLD",
   "description": "Node 1 User Temperature Maximum Alarm Threshold (Admin level)",
   "units": "degrees",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 151,
   "name": "USER TEMPERATURE MAXIMUM ALARM THRESHOLD",
   "description": "Node 2 User Temperature Maximum Alarm Threshold (Admin level)",
   "units": "degrees",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 152,
   "name": "USER TEMPERATURE MAXIMUM ALARM THRESHOLD",
   "description": "Node 3 User Temperature Maximum Alarm Threshold (Admin level)",
   "units": "degrees",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 153,
   "name": "USER TEMPERATURE MAXIMUM ALARM THRESHOLD",
   "description": "Node 4 User Temperature Maximum Alarm Threshold (Admin level)",
   "units": "degrees",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 6,
   "name": "TEMPERATURE ALARM STATUS",
   "description": "Temperature Alarm Status for Feed Temperature Monitoring (hex bit field)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 7,
   "name": "RESET GROUP VALUES",
   "description": "Bit-coded reset of min, max, peak and demand values (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 38,
   "name": "OUTLET 5 IDENTIFIER",
   "description": "Outlet 5 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 39,
   "name": "OUTLET 6 IDENTIFIER",
   "description": "Outlet 6 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 8,
   "name": "OUTLET ALARM STATUS 2",
   "description": "OUTLET 5 and 6 alarm status (hex bit field)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 71,
   "name": "OUTLET 5 LINE CURRENT",
   "description": "Outlet 5, Line Current Line 1",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 72,
   "name": "OUTLET 5 LINE CURRENT",
   "description": "Outlet 5, Line Current Line 2",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 73,
   "name": "OUTLET 5 LINE CURRENT",
   "description": "Outlet 5, Line Current Line 3",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 74,
   "name": "OUTLET 5 LINE CURRENT",
   "description": "Outlet 5, Line Current Line N",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 75,
   "name": "OUTLET 6 LINE CURRENT",
   "description": "Outlet 6, Line Current Line 1",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 76,
   "name": "OUTLET 6 LINE CURRENT",
   "description": "Outlet 6, Line Current Line 2",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 77,
   "name": "OUTLET 6 LINE CURRENT",
   "description": "Outlet 6, Line Current Line 3",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 78,
   "name": "OUTLET 6 LINE CURRENT",
   "description": "Outlet 6, Line Current Line N",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 154,
   "name": "OUTLET 5 LINE CURRENT RATING",
   "description": "Outlet 5 Line Current Rating. One rating for each outlet",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 155,
   "name": "OUTLET 6 LINE CURRENT RATING",
   "description": "Outlet 6 Line Current Rating. One rating for each outlet",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 79,
   "name": "OUTLET 5 LINE CURRENT RATING % of",
   "description": "Outlet 5 Line Current % of Rated Line 1",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 80,
   "name": "OUTLET 5 LINE CURRENT RATING % of",
   "description": "Outlet 5 Line Current % of Rated Line 2",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 81,
   "name": "OUTLET 5 LINE CURRENT RATING % of",
   "description": "Outlet 5 Line Current % of Rated Line 3",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 82,
   "name": "OUTLET 5 LINE CURRENT RATING % of",
   "description": "Outlet 5 Line Current % of Rated Neutral Conductor",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 83,
   "name": "OUTLET 6 LINE CURRENT RATING % of",
   "description": "Outlet 6 Line Current % of Rated Line 1",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 84,
   "name": "OUTLET 6 LINE CURRENT RATING % of",
   "description": "Outlet 6 Line Current % of Rated Line 2",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 85,
   "name": "OUTLET 6 LINE CURRENT RATING % of",
   "description": "Outlet 6 Line Current % of Rated Line 3",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 86,
   "name": "OUTLET 6 LINE CURRENT RATING % of",
   "description": "Outlet 6 Line Current % of Rated Neutral Conductor",
   "units": "Percent",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 156,
   "name": "OUTLET 5 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 157,
   "name": "OUTLET 5 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 158,
   "name": "OUTLET 5 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 159,
   "name": "OUTLET 5 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 160,
   "name": "OUTLET 6 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 161,
   "name": "OUTLET 6 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 162,
   "name": "OUTLET 6 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 163,
   "name": "OUTLET 6 LINE CURRENT MINIMUM",
   "description": "Outlet Line Current Minimum Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 164,
   "name": "OUTLET 5 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 165,
   "name": "OUTLET 5 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 166,
   "name": "OUTLET 5 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 167,
   "name": "OUTLET 5 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 168,
   "name": "OUTLET 6 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 169,
   "name": "OUTLET 6 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 170,
   "name": "OUTLET 6 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 171,
   "name": "OUTLET 6 LINE CURRENT MAXIMUM",
   "description": "Outlet Line Current Maximum Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 172,
   "name": "OUTLET CURRENT MIN ALARM",
   "description": "Outlet 5 Current Minimum Alarm",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 173,
   "name": "OUTLET CURRENT MIN ALARM",
   "description": "Outlet 6 Current Minimum Alarm",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 174,
   "name": "OUTLET CURRENT MAX ALARM",
   "description": "Outlet 5 Current Maximum Alarm",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 175,
   "name": "OUTLET CURRENT MAX ALARM",
   "description": "Outlet 6 Current Maximum Alarm",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 176,
   "name": "OUTLET 5 DEMAND TIME",
   "description": "Outlet 5 Demand Time",
   "units": "Minutes",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 177,
   "name": "OUTLET 6 DEMAND TIME",
   "description": "Outlet 6 Demand Time",
   "units": "Minutes",
   "access": "W",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 38,
   "name": "OUTLET 5 TOTAL ACTIVE POWER",
   "description": "Outlet 5 Total Active Power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 39,
   "name": "OUTLET 6 TOTAL ACTIVE POWER",
   "description": "Outlet 6 Total Active Power",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 40,
   "name": "OUTLET 5 PEAK TOTAL ACTIVE POWER",
   "description": "Outlet 5 Peak Total Active Power",
   "units": "W",
   "access": "W",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 41,
   "name": "OUTLET 6 PEAK TOTAL ACTIVE POWER",
   "description": "Outlet 6 Peak Total Active Power",
   "units": "W",
   "access": "W",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 42,
   "name": "OUTLET 5 TOTAL REACTIVE POWER",
   "description": "Outlet 5 Total Reactive Power",
   "units": "VAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 43,
   "name": "OUTLET 6 TOTAL REACTIVE POWER",
   "description": "Outlet 6 Total Reactive Power",
   "units": "VAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 44,
   "name": "OUTLET 5 TOTAL APPARENT POWER",
   "description": "Outlet 5 Total Apparent Power",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 45,
   "name": "OUTLET 6 TOTAL APPARENT POWER",
   "description": "Outlet 6 Total Apparent Power",
   "units": "VA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 87,
   "name": "OUTLET 5 TOTAL POWER FACTOR",
   "description": "Outlet 5 Total Power Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 88,
   "name": "OUTLET 6 TOTAL POWER FACTOR",
   "description": "Outlet 6 Total Power Factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 46,
   "name": "OUTLET 5 TOTAL ENERGY",
   "description": "Outlet 5 Total Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "LAV",
   "instance": 47,
   "name": "OUTLET 6 TOTAL ENERGY",
   "description": "Outlet 6 Total Energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 40,
   "name": "OUTLET 5 LINE IDENTIFIER",
   "description": "Outlet 5 Line 1 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 41,
   "name": "OUTLET 5 LINE IDENTIFIER",
   "description": "Outlet 5 Line 2 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 42,
   "name": "OUTLET 5 LINE IDENTIFIER",
   "description": "Outlet 5 Line 3 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 43,
   "name": "OUTLET 5 LINE IDENTIFIER",
   "description": "Outlet 5 Neutral ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 44,
   "name": "OUTLET 6 LINE IDENTIFIER",
   "description": "Outlet 6 Line 1 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 45,
   "name": "OUTLET 6 LINE IDENTIFIER",
   "description": "Outlet 6 Line 2 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 46,
   "name": "OUTLET 6 LINE IDENTIFIER",
   "description": "Outlet 6 Line 3 ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 47,
   "name": "OUTLET 6 LINE IDENTIFIER",
   "description": "Outlet 6 Neutral ID (Admin level)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 178,
   "name": "OUTLET 5 LINE CURRENT DEMAND",
   "description": "Outlet 5 Line Current Demand Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 179,
   "name": "OUTLET 5 LINE CURRENT DEMAND",
   "description": "Outlet 5 Line Current Demand Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 180,
   "name": "OUTLET 5 LINE CURRENT DEMAND",
   "description": "Outlet 5 Line Current Demand Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 181,
   "name": "OUTLET 5 LINE CURRENT DEMAND",
   "description": "Outlet 5 Line Current Demand Line Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 182,
   "name": "OUTLET 6 LINE CURRENT DEMAND",
   "description": "Outlet 6 Line Current Demand Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 183,
   "name": "OUTLET 6 LINE CURRENT DEMAND",
   "description": "Outlet 6 Line Current Demand Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 184,
   "name": "OUTLET 6 LINE CURRENT DEMAND",
   "description": "Outlet 6 Line Current Demand Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 185,
   "name": "OUTLET 6 LINE CURRENT DEMAND",
   "description": "Outlet 6 Line Current Demand Line Neutral",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 186,
   "name": "OUTLET 5 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 5 Line Current Peak Demand Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 187,
   "name": "OUTLET 5 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 5 Line Current Peak Demand Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 188,
   "name": "OUTLET 5 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 5 Line Current Peak Demand Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 189,
   "name": "OUTLET 5 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 5 Line Current Peak Demand Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 190,
   "name": "OUTLET 6 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 6 Line Current Peak Demand Line 1",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 191,
   "name": "OUTLET 6 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 6 Line Current Peak Demand Line 2",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 192,
   "name": "OUTLET 6 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 6 Line Current Peak Demand Line 3",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 193,
   "name": "OUTLET 6 LINE CURRENT PEAK DEMAND",
   "description": "Outlet 6 Line Current Peak Demand Neutral Conductor",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 194,
   "name": "OUTLET 5 TOTAL LINE CURRENT DEMAND",
   "description": "Outlet 5 Total Line Current Demand",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 195,
   "name": "OUTLET 6 TOTAL LINE CURRENT DEMAND",
   "description": "Outlet 6 Total Line Current Demand",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 196,
   "name": "OUTLET 5 PEAK TOTAL LINE CURRENT DEMAND",
   "description": "Outlet 5 Peak Total Line Current Demand",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 197,
   "name": "OUTLET 6 PEAK TOTAL LINE CURRENT DEMAND",
   "description": "Outlet 6 Peak Total Line Current Demand",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 198,
   "name": "LINE TO NEUTRAL VOLTAGE MINIMUM",
   "description": "Line to Neutral Voltage Minimum L1-N",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 199,
   "name": "LINE TO NEUTRAL VOLTAGE MAXIMUM",
   "description": "Line to Neutral Voltage Maximum L1-N",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 200,
   "name": "LINE TO NEUTRAL VOLTAGE MIN ALARM",
   "description": "Line to Neutral Voltage Minimum Alarm L1-N",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 201,
   "name": "LINE TO NEUTRAL VOLTAGE MAX ALARM",
   "description": "Line to Neutral Voltage Maximum Alarm L1-N",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 202,
   "name": "LINE TO NEUTRAL VOLTAGE MINIMUM",
   "description": "Line to Neutral Voltage Minimum L2-N",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 203,
   "name": "LINE TO NEUTRAL VOLTAGE MAXIMUM",
   "description": "Line to Neutral Voltage Maximum L2-N",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 204,
   "name": "LINE TO NEUTRAL VOLTAGE MIN ALARM",
   "description": "Line to Neutral Voltage Minimum Alarm L2-N",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 205,
   "name": "LINE TO NEUTRAL VOLTAGE MAX ALARM",
   "description": "Line to Neutral Voltage Maximum Alarm L2-N",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 206,
   "name": "LINE TO NEUTRAL VOLTAGE MINIMUM",
   "description": "Line to Neutral Voltage Minimum L3-N",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 207,
   "name": "LINE TO NEUTRAL VOLTAGE MAXIMUM",
   "description": "Line to Neutral Voltage Maximum L3-N",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 208,
   "name": "LINE TO NEUTRAL VOLTAGE MIN ALARM",
   "description": "Line to Neutral Voltage Minimum Alarm L3-N",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 209,
   "name": "LINE TO NEUTRAL VOLTAGE MAX ALARM",
   "description": "Line to Neutral Voltage Maximum Alarm L3-N",
   "units": "Volts",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 210,
   "name": "FREQUENCY MINIMUM",
   "description": "Frequency Minimum",
   "units": "Hertz",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 211,
   "name": "FREQUENCY MAXIMUM",
   "description": "Frequency Maximum",
   "units": "Hertz",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 212,
   "name": "INFEED NEUTRAL CURRENT RATING",
   "description": "Infeed Neutral Current Rating (Admin level)",
   "units": "Amps",
   "access": "W",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 11,
   "name": "BREAKER ALARM STATUS",
   "description": "the breaker alarm status (hex bit field)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "PIV",
   "instance": 13,
   "name": "BREAKER 1 STATUS",
   "description": "Breaker 1 Status",
   "units": "",
   "access": "R",
   "states": "0=Open/Off, 1=Closed/On"
  },
  {
   "type": "PIV",
   "instance": 14,
   "name": "BREAKER 2 STATUS",
   "description": "Breaker 2 Status",
   "units": "",
   "access": "R",
   "states": "0=Open/Off, 1=Closed/On"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/starline/ac-cpm-critical-power-monitor",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}