- eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)
Pressure-independent 6-way control valve · BACnet points list
SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) BACnet points list
Updated 12 November 2026
The UVC106BF is a motorised 6-port ball valve with its own flow measurement and controller, used to switch a single coil between heating and cooling circuits. The BF variants have a BACnet MS/TP interface; the handbook lists binary, analog input, analog value, analog output and multistate value objects: flow and temperatures, heating/cooling setpoints (Y1h/Y1c or flow Vsh/Vsc), room temperature control settings, energy, climate status and configuration.
This page lists 62 BACnet objects for the SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) — 44 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from SAUTER’s own free documentation, linked below.
- Manufacturer
- SAUTER
- Model
- eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)
- Equipment
- Pressure-independent 6-way control valve
- Equipment type
- Valves & actuators
- BACnet objects
- 62 (44 writable)
- Transport
- BACnet MS/TP
- Firmware
- Firmware 0.8.3 or higher, application 4.06.09 or higher
- Also known as
- UVC106BF, UVC106, eValveco, eValveco UVC10x, SAUTER UVC106, SAUTER 6-way valve BACnet, dynamx valve, P100017780
Reference only, provided as-is: verify against SAUTER’s current documentation and the live device before use. Not official SAUTER information. Terms of use.
BMS integration notes: SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)
Set Ctrl Sig (BV 0) to digital so the bus owns the setpoint, then write the heating or cooling setpoint Y1h/Y1c (0-10) and read flow, climate status, the warning bitfield and energy. With Ctrl Sig analog the valve follows its 0-10 V Y1 input and Y1h/Y1c are read-only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | Ctrl Sig | Must be digital (1) for bus setpoints | Write |
| AV 0 | Y1h | Heating setpoint, 0-10 | Write |
| AV 1 | Y1c | Cooling setpoint, 0-10 | Write |
| MV 1 | ClimStatus | Climate status: heating, cooling, error, check flow | Read |
| AI 0 | Vam | Measured flow | Read |
| AV 20 | XM | Valve motor position, 0-10 | Read |
| AV 10 | EnerHeat | Heating energy | Read |
| AV 11 | EnerCool | Cooling energy | Read |
| AI 8 | Warning | Warning bits: sensor, negative flow, manual | Read |
| AI 9 | Error | Error code | Read |
Enable & remote start
Ctrl Sig (BV 0) selects the setpoint source: analog (the Y1 0-10 V input) or digital (Y1h/Y1c written over the bus). Changing it resets the control loop.
Sensors & values from the BMS
Room temperature (AV 12 Troom) and setpoint adjustment (AV 13 Tsetadj) are writable for the room control function; external sensors on Text1/Text2 are configured with MV 9/10.
Network setup
- BACnet MS/TP, 9600, 19200 or 38400 baud; the PICS lists both master and slave operation.
- Segmentation is not supported.
Watch out for
- Writing the flow setpoints Vsh/Vsc (AV 2/3) directly is meant for troubleshooting only; the handbook warns cyclic writes shorten the internal memory life. Use Y1h/Y1c.
- Y1h and Y1c are read-only while Ctrl Sig is analog.
- Some objects only exist on certain product types.
SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 0 | Ctrl Sig | Setpoint source: analog input or bus (digital) | Write | 0=Analog mode, 1=Digital mode | |
| BV | 1 | Meas Sig | Measuring signal mode | Write | 0=Analog mode, 1=Digital mode | |
| BV | 3 | Port 1 Active | Port 1 active | Read | 0=Port 1 is inactive, 1=Port 1 is active | |
| BV | 4 | Night Mode | Night mode enable | Write | 0=Night Mode disabled, 1=Night Mode enabled | |
| BV | 6 | DI1 Type | Digital input 1 contact type | Write | 0=Normally Closed, 1=Normally Open | |
| BV | 7 | DI2 Type | Digital input 2 contact type | Write | 0=Normally Closed, 1=Normally Open | |
| BV | 12 | Reboot | Reboot the device | Write | 0=Inactive, 1=Reboot | |
| BV | 13 | DI3 Type | Digital input 3 contact type | Write | 0=Normally Closed, 1=Normally Open | |
| BV | 14 | X1 Mode | X1 output mode | Write | 0=Analog mode, 1=Digital mode | |
| BV | 15 | ObjectValues MB based | Multistate value numbering | Write | 0=Default Multistate Values, 1=Multistate Values MBbased | |
| BV | 16 | Temp Unit | Temperature unit | Write | 0=°C, 1=°F | |
| BV | 17 | Frost Protection | Frost protection enable | Write | 0=Disabled, 1=Enabled | |
| AImin | 0 | Vam | Measured medium flow | Read | ||
| AI | 1 | Tam1 | Temperature sensor 1 | Read | ||
| AI | 2 | Tam2 | Temperature sensor 2 | Read | ||
| AI | 4 | Text 1 | External temperature input 1 | Read | ||
| AI | 5 | Text 2 | External temperature input 2 | Read | ||
| AI | 6 | Y1 | Setpoint input voltage (analog mode) | Read | ||
| AI | 7 | Y2 | Second analog input voltage | Read | ||
| AImin | 8 | Warning | Warning bitfield | Read | b0=Temperature sensor invalid, b3=Negative flow, b4=Manual mode | |
| AImin | 9 | Error | Error code | Read | ||
| AVmin | 0 | Y1h | Heating setpoint 0-10 (digital mode) | Write | ||
| AVmin | 1 | Y1c | Cooling setpoint 0-10 (digital mode) | Write | ||
| AV | 2 | Vsh | Heating flow setpoint | Write | ||
| AV | 3 | Vsc | Cooling flow setpoint | Write | ||
| AV | 4 | Tset | Room temperature setpoint, 14-35 °C | °C | Write | |
| AV | 5 | Tsetcalc | Calculated room temperature setpoint | °C | Read | |
| AV | 6 | Setp Modif | Setpoint modifier bitfield | Read | b0=window open, b1=away mode, b2=night mode, b3=condensation, b4=frost protection | |
| AV | 7 | Tcoolmin | Minimum cooling temperature, 9-35 °C | °C | Write | |
| AVmin | 10 | EnerHeat | Heating energy (Wh or BTU) | Read | ||
| AVmin | 11 | EnerCool | Cooling energy (Wh or BTU) | Read | ||
| AV | 12 | Troom | Room temperature | °C | Write | |
| AV | 13 | Tsetadj | Room setpoint adjustment | °C | Write | |
| AV | 14 | Test Reg | Test register (test command values only) | Write | ||
| AV | 15 | Command Reg | Internal command register (manufacturer use) | Write | ||
| AV | 16 | Y2 Digital | Y2 value in digital mode | Read | ||
| AV | 17 | Vsmax h | Maximum heating flow | Write | ||
| AV | 18 | Vsmax c | Maximum cooling flow | Write | ||
| AVmin | 20 | XM | Motor position, 0-10 | Read | ||
| AV | 21 | T1 Correction | Sensor 1 correction, -5 to +5 | °C | Write | |
| AV | 22 | T2 Correction | Sensor 2 correction, -5 to +5 | °C | Write | |
| AV | 23 | Temp Dead band | Temperature dead band, 0.2-6 °C | °C | Write | |
| AV | 24 | Temp Db Night | Night dead band, 0.2-20 °C | °C | Write | |
| AV | 25 | Window Open | Window-open temperature limit, 6-35 °C | °C | Write | |
| AV | 26 | Window Open | Window-open temperature limit, 6-40 °C | °C | Write | |
| AV | 27 | Prop band Heating | Heating proportional band, 0.5-6 °C | °C | Write | |
| AV | 28 | Prop band Cooling | Cooling proportional band, 0.5-6 °C | °C | Write | |
| AV | 29 | Integration Time | Integral time, 50-50000 s | seconds | Write | |
| AO | 0 | X1 | Flow feedback / controlled output, 0-10 V | Read | ||
| MV | 0 | SysType | System type | Write | 1=Not used, 2=Not used, 3=Climate 4P, 4=Not used, 5=Not used, 6=Room control climate ceiling, 7=Not used, 8=Not used | |
| MVmin | 1 | ClimStatus | Current climate status | Read | 1=Heating, 2=Cooling, 3=Not defined, 4=Error, 5=Check flow, 6=Flush mode | |
| MV | 2 | End mode | End mode behaviour | Write | 1=Normal behavior, 2=No flow, 3=Flush mode | |
| MV | 3 | 6WayFlush | 6-way flush command | Write | 1=Inactive, 2=Flush cooling, 3=Flush heating | |
| MV | 4 | Control Char | Control characteristic | Write | 1=Linear, 2=Equal percentage | |
| MV | 5 | DI1 Usage | Digital input 1 function | Write | 1=DI1 Not used, 2=Window open, 3=Away mode, 4=Counter, 5=Night mode, 6-8=Not used, 9=Condensation | |
| MV | 6 | DI2 Usage | Digital input 2 function | Write | 1=DI2 Not used, 2=Window open, 3=Away mode, 4=Counter, 5=Night mode, 6-8=Not used, 9=Condensation | |
| MV | 8 | DI3 Usage | Digital input 3 function | Write | 1=DI3 Not used, 2=Window open, 3=Away mode, 4=Counter, 5=Night mode, 6-8=Not used, 9=Condensation | |
| MV | 9 | Text1 Usage | External input 1 sensor type | Write | 1=Pt500, 2=Pt1000, 3=Potentiometer 10k | |
| MV | 10 | Text2 Usage | External input 2 sensor type | Write | 1=Pt500, 2=Pt1000, 3=Potentiometer 10k | |
| MV | 11 | X1 type | X1 output type | Write | 1=Flow, 2=Not used, 3=Controlled | |
| MV | 12 | X1 char | X1 output characteristic | Write | 1=Linear, 2=Equal percentage | |
| MV | 13 | Temp Control Type | Temperature control type | Write | 1=P, 2=PI |
No points match these filters.
Object ID lookup: SAUTER eValveco UVC106BF point IDs by name
BV0Ctrl SigBV1Meas SigBV3Port 1 ActiveBV4Night ModeBV6DI1 TypeBV7DI2 TypeBV12RebootBV13DI3 TypeBV14X1 ModeBV15ObjectValues MB basedBV16Temp UnitBV17Frost ProtectionAI0VamAI1Tam1AI2Tam2AI4Text 1AI5Text 2AI6Y1AI7Y2AI8WarningAI9ErrorAV0Y1hAV1Y1cAV2VshAV3VscAV4TsetAV5TsetcalcAV6Setp ModifAV7TcoolminAV10EnerHeatAV11EnerCoolAV12TroomAV13TsetadjAV14Test RegAV15Command RegAV16Y2 DigitalAV17Vsmax hAV18Vsmax cAV20XMAV21T1 CorrectionAV22T2 CorrectionAV23Temp Dead bandAV24Temp Db NightAV25Window OpenAV26Window OpenAV27Prop band HeatingAV28Prop band CoolingAV29Integration TimeAO0X1MV0SysTypeMV1ClimStatusMV2End modeMV36WayFlushMV4Control CharMV5DI1 UsageMV6DI2 UsageMV8DI3 UsageMV9Text1 UsageMV10Text2 UsageMV11X1 typeMV12X1 charMV13Temp Control Type
Integration notes
- Object names are short codes as printed; the descriptions here are from the handbook's variables annex and section 2.
- Many objects are marked as present only on some product types (handbook footnotes); not every object exists in every valve.
- AV 25 and AV 26 are both printed as "Window Open" (ranges 6-35 °C and 6-40 °C); the annex calls the pair Window Open MinTemp and MaxTemp without saying which instance is which.
- Several AVs (Y1h, Y1c, Vsh, Troom, Tsetadj) also have writable Low/High Limit properties that set their range; those are properties, not separate objects.
- Units are not printed per object; temperatures follow Temp Unit (BV 16), energy is Wh or BTU, flow in the unit set on the device.
- Source: handbook chapter 6.4-6.7, Tab. 13, 15, 18, 20 and 22, pages 40-48 (62 objects). The Modbus lists in chapter 5 also cover UVC102/UVC103.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)
How many BACnet points does the SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) have?
This list has 62 BACnet objects: 9 analog inputs, 1 analog output, 27 analog values, 12 binary values, 13 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) BACnet points are writable?
44 of the 62 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) BACnet documentation?
The source is eValveco UVC10x Handbook (P100017780 Version 02 Revision 01), revision 2021-04-01, published free by SAUTER at https://www.sauter-controls.com/wp-content/uploads/ImportPDM/1111937.pdf.
What are the minimum BACnet points to integrate the SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)?
Start with BV 0 Ctrl Sig (Must be digital (1) for bus setpoints); AV 0 Y1h (Heating setpoint, 0-10); AV 1 Y1c (Cooling setpoint, 0-10); MV 1 ClimStatus (Climate status: heating, cooling, error, check flow); AI 0 Vam (Measured flow); AV 20 XM (Valve motor position, 0-10); AV 10 EnerHeat (Heating energy); AV 11 EnerCool (Cooling energy); AI 8 Warning (Warning bits: sensor, negative flow, manual); AI 9 Error (Error code).
How do I enable BMS control of the SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)?
Ctrl Sig (BV 0) selects the setpoint source: analog (the Y1 0-10 V input) or digital (Y1h/Y1c written over the bus). Changing it resets the control loop.
Can the BMS supply sensor values to the SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)?
Room temperature (AV 12 Troom) and setpoint adjustment (AV 13 Tsetadj) are writable for the room control function; external sensors on Text1/Text2 are configured with MV 9/10.
How do I check these points on the real eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More SAUTER BACnet points lists
Source: eValveco UVC10x Handbook · P100017780 Version 02 Revision 01 · rev. 2021-04-01. Object names, instances and units are reproduced as published; descriptions are our own.