Pressure-independent 6-way control valve · BACnet points list

SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The UVC106BF is a motorised 6-port ball valve with its own flow measurement and controller, used to switch a single coil between heating and cooling circuits. The BF variants have a BACnet MS/TP interface; the handbook lists binary, analog input, analog value, analog output and multistate value objects: flow and temperatures, heating/cooling setpoints (Y1h/Y1c or flow Vsh/Vsc), room temperature control settings, energy, climate status and configuration.

This page lists 62 BACnet objects for the SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) — 44 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from SAUTER’s own free documentation, linked below.

Manufacturer
SAUTER
Model
eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)
Equipment
Pressure-independent 6-way control valve
Equipment type
Valves & actuators
BACnet objects
62 (44 writable)
Transport
BACnet MS/TP
Firmware
Firmware 0.8.3 or higher, application 4.06.09 or higher
Also known as
UVC106BF, UVC106, eValveco, eValveco UVC10x, SAUTER UVC106, SAUTER 6-way valve BACnet, dynamx valve, P100017780
Source document
eValveco UVC10x Handbook · P100017780 Version 02 Revision 01 · rev. 2021-04-01
Download CSV 62 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against SAUTER’s current documentation and the live device before use. Not official SAUTER information. Terms of use.

BMS integration notes: SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)

Integration in brief

Set Ctrl Sig (BV 0) to digital so the bus owns the setpoint, then write the heating or cooling setpoint Y1h/Y1c (0-10) and read flow, climate status, the warning bitfield and energy. With Ctrl Sig analog the valve follows its 0-10 V Y1 input and Y1h/Y1c are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0Ctrl SigMust be digital (1) for bus setpointsWrite
AV 0Y1hHeating setpoint, 0-10Write
AV 1Y1cCooling setpoint, 0-10Write
MV 1ClimStatusClimate status: heating, cooling, error, check flowRead
AI 0VamMeasured flowRead
AV 20XMValve motor position, 0-10Read
AV 10EnerHeatHeating energyRead
AV 11EnerCoolCooling energyRead
AI 8WarningWarning bits: sensor, negative flow, manualRead
AI 9ErrorError codeRead

Enable & remote start

Ctrl Sig (BV 0) selects the setpoint source: analog (the Y1 0-10 V input) or digital (Y1h/Y1c written over the bus). Changing it resets the control loop.

Sensors & values from the BMS

Room temperature (AV 12 Troom) and setpoint adjustment (AV 13 Tsetadj) are writable for the room control function; external sensors on Text1/Text2 are configured with MV 9/10.

Network setup

Watch out for

SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

62 of 62 shown
Type
BinaryMulti-state
Access
Show
SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) BACnet Points List
DescriptionStates
BVmin0Ctrl SigSetpoint source: analog input or bus (digital)Write0=Analog mode, 1=Digital mode
BV1Meas SigMeasuring signal modeWrite0=Analog mode, 1=Digital mode
BV3Port 1 ActivePort 1 activeRead0=Port 1 is inactive, 1=Port 1 is active
BV4Night ModeNight mode enableWrite0=Night Mode disabled, 1=Night Mode enabled
BV6DI1 TypeDigital input 1 contact typeWrite0=Normally Closed, 1=Normally Open
BV7DI2 TypeDigital input 2 contact typeWrite0=Normally Closed, 1=Normally Open
BV12RebootReboot the deviceWrite0=Inactive, 1=Reboot
BV13DI3 TypeDigital input 3 contact typeWrite0=Normally Closed, 1=Normally Open
BV14X1 ModeX1 output modeWrite0=Analog mode, 1=Digital mode
BV15ObjectValues MB basedMultistate value numberingWrite0=Default Multistate Values, 1=Multistate Values MBbased
BV16Temp UnitTemperature unitWrite0=°C, 1=°F
BV17Frost ProtectionFrost protection enableWrite0=Disabled, 1=Enabled
AImin0VamMeasured medium flowRead
AI1Tam1Temperature sensor 1Read
AI2Tam2Temperature sensor 2Read
AI4Text 1External temperature input 1Read
AI5Text 2External temperature input 2Read
AI6Y1Setpoint input voltage (analog mode)Read
AI7Y2Second analog input voltageRead
AImin8WarningWarning bitfieldReadb0=Temperature sensor invalid, b3=Negative flow, b4=Manual mode
AImin9ErrorError codeRead
AVmin0Y1hHeating setpoint 0-10 (digital mode)Write
AVmin1Y1cCooling setpoint 0-10 (digital mode)Write
AV2VshHeating flow setpointWrite
AV3VscCooling flow setpointWrite
AV4TsetRoom temperature setpoint, 14-35 °C°CWrite
AV5TsetcalcCalculated room temperature setpoint°CRead
AV6Setp ModifSetpoint modifier bitfieldReadb0=window open, b1=away mode, b2=night mode, b3=condensation, b4=frost protection
AV7TcoolminMinimum cooling temperature, 9-35 °C°CWrite
AVmin10EnerHeatHeating energy (Wh or BTU)Read
AVmin11EnerCoolCooling energy (Wh or BTU)Read
AV12TroomRoom temperature°CWrite
AV13TsetadjRoom setpoint adjustment°CWrite
AV14Test RegTest register (test command values only)Write
AV15Command RegInternal command register (manufacturer use)Write
AV16Y2 DigitalY2 value in digital modeRead
AV17Vsmax hMaximum heating flowWrite
AV18Vsmax cMaximum cooling flowWrite
AVmin20XMMotor position, 0-10Read
AV21T1 CorrectionSensor 1 correction, -5 to +5°CWrite
AV22T2 CorrectionSensor 2 correction, -5 to +5°CWrite
AV23Temp Dead bandTemperature dead band, 0.2-6 °C°CWrite
AV24Temp Db NightNight dead band, 0.2-20 °C°CWrite
AV25Window OpenWindow-open temperature limit, 6-35 °C°CWrite
AV26Window OpenWindow-open temperature limit, 6-40 °C°CWrite
AV27Prop band HeatingHeating proportional band, 0.5-6 °C°CWrite
AV28Prop band CoolingCooling proportional band, 0.5-6 °C°CWrite
AV29Integration TimeIntegral time, 50-50000 ssecondsWrite
AO0X1Flow feedback / controlled output, 0-10 VRead
MV0SysTypeSystem typeWrite1=Not used, 2=Not used, 3=Climate 4P, 4=Not used, 5=Not used, 6=Room control climate ceiling, 7=Not used, 8=Not used
MVmin1ClimStatusCurrent climate statusRead1=Heating, 2=Cooling, 3=Not defined, 4=Error, 5=Check flow, 6=Flush mode
MV2End modeEnd mode behaviourWrite1=Normal behavior, 2=No flow, 3=Flush mode
MV36WayFlush6-way flush commandWrite1=Inactive, 2=Flush cooling, 3=Flush heating
MV4Control CharControl characteristicWrite1=Linear, 2=Equal percentage
MV5DI1 UsageDigital input 1 functionWrite1=DI1 Not used, 2=Window open, 3=Away mode, 4=Counter, 5=Night mode, 6-8=Not used, 9=Condensation
MV6DI2 UsageDigital input 2 functionWrite1=DI2 Not used, 2=Window open, 3=Away mode, 4=Counter, 5=Night mode, 6-8=Not used, 9=Condensation
MV8DI3 UsageDigital input 3 functionWrite1=DI3 Not used, 2=Window open, 3=Away mode, 4=Counter, 5=Night mode, 6-8=Not used, 9=Condensation
MV9Text1 UsageExternal input 1 sensor typeWrite1=Pt500, 2=Pt1000, 3=Potentiometer 10k
MV10Text2 UsageExternal input 2 sensor typeWrite1=Pt500, 2=Pt1000, 3=Potentiometer 10k
MV11X1 typeX1 output typeWrite1=Flow, 2=Not used, 3=Controlled
MV12X1 charX1 output characteristicWrite1=Linear, 2=Equal percentage
MV13Temp Control TypeTemperature control typeWrite1=P, 2=PI
Object ID lookup: SAUTER eValveco UVC106BF point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)

How many BACnet points does the SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) have?

This list has 62 BACnet objects: 9 analog inputs, 1 analog output, 27 analog values, 12 binary values, 13 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) BACnet points are writable?

44 of the 62 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP) BACnet documentation?

The source is eValveco UVC10x Handbook (P100017780 Version 02 Revision 01), revision 2021-04-01, published free by SAUTER at https://www.sauter-controls.com/wp-content/uploads/ImportPDM/1111937.pdf.

What are the minimum BACnet points to integrate the SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)?

Start with BV 0 Ctrl Sig (Must be digital (1) for bus setpoints); AV 0 Y1h (Heating setpoint, 0-10); AV 1 Y1c (Cooling setpoint, 0-10); MV 1 ClimStatus (Climate status: heating, cooling, error, check flow); AI 0 Vam (Measured flow); AV 20 XM (Valve motor position, 0-10); AV 10 EnerHeat (Heating energy); AV 11 EnerCool (Cooling energy); AI 8 Warning (Warning bits: sensor, negative flow, manual); AI 9 Error (Error code).

How do I enable BMS control of the SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)?

Ctrl Sig (BV 0) selects the setpoint source: analog (the Y1 0-10 V input) or digital (Y1h/Y1c written over the bus). Changing it resets the control loop.

Can the BMS supply sensor values to the SAUTER eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)?

Room temperature (AV 12 Troom) and setpoint adjustment (AV 13 Tsetadj) are writable for the room control function; external sensors on Text1/Text2 are configured with MV 9/10.

How do I check these points on the real eValveco UVC106BF electronic pressure-independent 6-port valve (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More SAUTER BACnet points lists

Source: eValveco UVC10x Handbook · P100017780 Version 02 Revision 01 · rev. 2021-04-01. Object names, instances and units are reproduced as published; descriptions are our own.