VAV box controller (compact, built-in damper drive) · BACnet points list

SAUTER ASV3 VAV Compact Controller (ASV305BF7xxxW) BACnet points list

Updated 6 November 2026

Short answer

The SAUTER ASV3 is a compact VAV controller: damper actuator, differential pressure sensor and airflow/temperature control in one unit, with BACnet MS/TP. Its object list exposes the hardware I/O, airflow and temperature setpoints and limits, PID tuning, room-unit (HMI) display settings, occupancy and cool/heat mode, plus many internal calculation objects.

This page lists 247 BACnet objects for the SAUTER ASV3 VAV Compact Controller (ASV305BF7xxxW) — 79 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from SAUTER’s own free documentation, linked below.

Manufacturer
SAUTER
Model
ASV3 VAV Compact Controller (ASV305BF7xxxW)
Equipment
VAV box controller (compact, built-in damper drive)
Equipment type
VAV boxes & fan coils
BACnet objects
247 (79 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
ASV3, ASV305BF7, ASV305BF7XXXW, SAUTER ASV3, EY-RU305F700xW
Source document
Manual SAUTER ASV3
Download CSV 247 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against SAUTER’s current documentation and the live device before use. Not official SAUTER information. Terms of use.

BMS integration notes: SAUTER ASV3 VAV Compact Controller (ASV305BF7xxxW)

Integration in brief

Command occupancy (BV 1) and cool/heat mode (BV 2), set the cooling and heating setpoints (AV 33, AV 37) or the airflow limits, and read the current airflow, damper position and room temperature. Damper and airflow overrides (BV 5 with AV 6, BV 6 with AV 12) are available for balancing.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1VAV box Occupied/ unoccupiedOccupied/unoccupied: 1 = occupiedWrite
BV 2Cool/Heat mode0 = cooling, 1 = heatingWrite
AV 33Cooling setpointRoom cooling setpointWrite
AV 37Heating set pointRoom heating setpointWrite
AV 4Current VAV airflowMeasured VAV airflowRead
AV 5VAV demand airflowAirflow demandWrite
AV 61Current VAV position feedback (0- 100)Damper position feedback, 0-100 %Read
AV 23HMI Temperature sensorRoom temperature from the HMI room unitRead
BV 10No Airflow in main ductDuct airflow alarm, 1 = no airflowRead

Enable & remote start

Occupancy is BV 1 (VAV box Occupied/unoccupied); Cool/Heat mode is BV 2. Overrides: Override airflow control (BV 5) with Forced airflow control (AV 6), Damper override (BV 6) with AV 12.

Network setup

Watch out for

SAUTER ASV3 VAV Compact Controller (ASV305BF7xxxW) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

247 of 247 shown
Type
Access
Show
SAUTER ASV3 VAV Compact Controller (ASV305BF7xxxW) BACnet Points List
DescriptionStates
AI0TempAi0 for NTC sensor, Digital Input (Dry Contact); Selected models only°CRead
AI1ADCAi1 for 0-10VDC; Selected models onlyVRead
AI2NTCFor Knob thermostat NTC temperature sensor (Internal Use)°CRead
AI3VRFor Knob thermostat VR temperature setpoint (Internal Use)°CRead
AI12Air PressureFor DP sensor (Internal Use)PaRead
AI13Air FlowFor VAV box airflow (Internal Use)L/sRead
AO14AO0Ao0 For 0-10VDC (Heating Valve Output); Selected models only%Write
AO15AO1Ao1 for 0-10VDC; Selected models onlyVWrite
AV0BACnet device instance number0-9999; The value in PC configuration software must be divided by 10.Read
AV1DDC Program Version0-999999999Read
AV2VAV box K factor0-1000Write
AV3VAV box inlet diameter mm100=4” 125=5” 150=6” 200=8” 250=10” 300=12” 350=14” 400=16”mmWrite
AVmin4Current VAV airflow0-9999L/s, CFM, CMHRead
AVmin5VAV demand airflow0-9999L/s, CFM, CMHWrite
AV6Forced airflow control0-9999L/s, CFM, CMHWrite
AV7Cooling maximum airflowAV8-9999L/s, CFM, CMHWrite
AV8Cooling minimum airflow0-AV7L/s, CFM, CMHWrite
AV9Heating maximum airflowAV10-9999L/s, CFM, CMHWrite
AV10Heating minimum airflow0-AV9L/s, CFM, CMHWrite
AV11VAV damper position (0-10)0-10; Modbus HMI value is 10 times of this valueRead
AV12VAV damper override position (0-10)0-10Write
AV13Damper actuator travel time0-999sRead
AV14Heating floating valve travel time0-999sRead
AV15Cooling PID parameter- Kp0-3276°C/°FWrite
AV16Cooling PID parameter- Ki0-3276%/°CWrite
AV17Heating PID parameter- Kp0-3276°C/°FWrite
AV18Heating PID parameter- Ki0-3276%/°CWrite
AV19Dead band for temperature control0-3276°C/°FWrite
AV20HMI Temperature sensor display /Pressure display PA0-100°C or PaRead
AV21HMI Humidity sensor display /ID address0-100; For EY-RU305F7002WH and EY-RU305F7003W%RHRead
AV22PPM/RPM/Time display select0-100; For EY-RU305F7003WRead
AVmin23HMI Temperature sensor0-100°C/°FRead
AV24HMI Humidity sensor0-100; For EY-RU305F7002W and EY-RU305F7003W%RHRead
AV25HMI CO2 sensor0-9999; For EY-RU305F7003WppmRead
AV29Airflow display unit select0=LPS 0.1=CFM 0.2=CMHWrite
AV30Alarm codeNo defineWrite
AV31HMI pushbutton lock level0=No Lock 1=Temp Lock 2=All LockWrite
AV32HMI backlight0-100Write
AVmin33Cooling setpointav34-av35°C/°FWrite
AV34Cooling set point high limitav35-9999°C/°FWrite
AV35Cooling set point low limit0-av34°C/°FWrite
AV36set up/down step0.1/0.2/0.5/1°C/°FRead
AVmin37Heating set pointAV39-38°C/°FWrite
AV38Heating set point high limitAV39-9999°C/°FWrite
AV39Heating set point low limit0-AV39°C/°FWrite
AV40HMI VersionRead
AV41HMI Password0-199; Value is mulitply by 10Read
AV42HMI Temperature sensor offset-10~10(0.1)°C/°FWrite
AV43HMI Humidity sensor offset-30~30(1); For EY-RU305F7002WH and EY-RU305F7003W%RHWrite
AV46CO2 or Termperature set point (for ai1 set point)0-3276Read
AV47CO2 PID parameter- Kp (for ai1)0-3276Read
AV48CO2 PID parameter- Ki (for ai1)0-3276Read
AV49CO2 value(for ai1 or HMI CO2)0-9999Read
AV50ai1 for 0-10 v (CO2 or Temperature sensor) input0-10VRead
AV51ai1 for (Co2 sensor or Temperature) input scale min.0-AV52ppmWrite
AV52ai1 for (Co2 sensor or Temperature) input scale max.AV52-9999ppmWrite
AV57Air flow PID outputInternal useRead
AV58Cooling temp setpoint+DBInternal useRead
AV59heating temp setpoint- DBInternal useRead
AV60Ai0 mode select0=not use, 1=Occupied, Unoccupied2=NTC thermistorRead
AVmin61Current VAV position feedback (0- 100)0-100%Read
AV62Damper min. position selectionInternal usePaRead
AV63Cooling set pointInternal useRead
AV64HMI Temp. display- FahrenheitInternal use°FRead
AV65HMI Temp. setpoint- FahrenheitInternal use°CRead
AV66Internal Calculation for AI0/AI1Internal Calculation for AI0/AI1 10k thermistor or Average TempRead
AV67Ai1 mode select0-7Read
AV68Actual airflowInternal useL/sRead
AV69Heating mode select0-5Read
AV70Cooling PID out0-100Read
AV71Airflow correction valueInternal useRead
AV72AV-72Internal useRead
AV73Cooling maximum airflowInternal useRead
AV74Cooling minimum airflowInternal useRead
AV75AV-75Buffer - Setpoint for airflow PIDRead
AV76AV-76Buffer-Damper Position Calculation stage (1)Read
AV77Airflow PID parameter-KpInternal useWrite
AV78Airflow PID parameter-KiInternal useWrite
AV79AV-79Internal useRead
AV80Damper Override Position0-100%Read
AV83AV-83Buffer-Damper position calculation stage (2)Read
AV84AV-84Buffer-Damper position calculation stage (3)Read
AV85Override air flow controlL/sRead
AV88Heating PID Output0-100%Read
AV89Heating maximum airflowL/sRead
AV90Heating temp. setpointInternal useWrite
AV91Heating min airflowInternal useL/sRead
AV92AV-92Buffer- travel time counter AWrite
AV93AV-93Buffer-cooling demand airflowRead
AV94AV-94Buffer-heating demand airflowRead
AV95AV-95Buffer- Damper travel time AWrite
AV96AV-96Buffer- travel time counter BWrite
AV97AV-97Buffer- Damper travel time BWrite
AV98AV-98Buffer- Mode judgment AWrite
AV99AV-99Buffer- Mode judgment BWrite
AV100AV-100Buffer- Damper travel time CWrite
AV101AV-101°C value of cooling setpoint°CRead
AV102AV-102°F value of cooling setpoint°FRead
AV103AV-103°C value of cooling temp setpoint high limit°CWrite
AV104AV-104°F value of cooling temp setpoint high limit°FWrite
AV105AV-1051 stage heating temp. setpointWrite
AV106AV-106°F value of temp set point low limit°FWrite
AV107AV-107°C value of temp set point low limit°CWrite
AV108AV-1082 stage heating temp. setpointWrite
AV109AV-109Cooling output for airflow PID calculation%Read
AV111AV-111Setpoint Value for Cooling temperature PID°CRead
AV112AV-112Present Value for Cooling Temperature PID°CRead
AV113AV-113Actual airflow - filteredL/sRead
AV115AV-115Counter (0-AV117)Read
AV117AV-117Output sampling 2.2secWrite
AV118Demand VAV PositionVAV position control output, 0-100%Read
AV119AV-119Counter for DP changes, 0-25Write
AV120AV-120Heating floating output, 0-100%Read
AV121VAV Off-min position0-100; BV59 is the mode select for this%Read
AV122AV-122Arithmetic Operation (AV75- AV124)Read
AV123AV-123Arithmetic Operation (AV75+AV124)Read
AV124AV-124Dead band for air flow controlWrite
AV125AV-125Arithmetic Operation Air flow unitL/sRead
AV126AV-126Air flow display for HMIWrite
AV127AV-127Humidity offset for HMI%Write
BI4Over CurrentActuator DC motor over current (Internal Use); For Calculation of running timeWrite
BI5Over CurrentActuator DC motor over current (Internal Use); For Calculation of running timeWrite
BO6Open DamperDamper actuator open control (Internal Use); For Calculation of running timeWrite
BO7Close DamperDamper actuator close control (Internal Use); For Calculation of running timeWrite
BO8DO0DO0 for 24VAC; Selected models onlyWrite
BO9DO1DO1 for 24VAC; Selected models onlyWrite
BV0Master/Slave Mode,Write0=Slave, 1=Master
BVmin1VAV box Occupied/ unoccupiedWrite0=Unoccupied, 1=Occupied
BVmin2Cool/Heat modeWrite0=Cooling, 1=Heating
BV3HMI Temperature display type_ Present value/ Set point valueWrite0=Present value, 1=Set point value
BV4BV-4Read
BV5Override airflow controlWrite0=No, 1=Yes
BV6Damper overrideWrite0=No, 1=Yes
BV7Override VAV airflow zero calibrationWrite0=No, 1=Yes
BV8BV-8Internal useRead
BV9BV-9Internal useRead
BVmin10No Airflow in main ductRead0=Airflow, 1=No Airflow
BV11Need lower temp. air for AHURead0=No, 1=Yes
BV12Alarm for 90% of the airflow achieve for more than 300 Sec – Cooling ModeRead0=No, 1=Yes
BV13Alarm for 90% of the airflow achieve for more than 300 Sec – Heating ModeRead0=No, 1=Yes
BV14BV-14Internal useRead
BV15BV-15Internal useRead
BV16BV-16Internal useRead
BV17BV-17Internal useRead
BV18BV-18Internal useRead
BV19BV-19Internal useRead
BV20Alarm iconWrite0=No, 1=Yes
BV21Lock iconRead0=No, 1=Yes
BV22Valve iconWrite0=No, 1=Yes
BV23Cooling iconRead0=No, 1=Yes
BV24Heating iconRead0=No, 1=Yes
BV25Fan IconWrite0=No, 1=Yes
BV26Sleep IconWrite0=No, 1=Yes
BV27Unoccupied IconRead0=No, 1=Yes
BV28Tool IconWrite0=No, 1=Yes
BV29Sending / Calculating IconRead0=No, 1=Yes
BV30ON/OFF iconRead0=No, 1=Yes
BV31Button pressed (alarm reset)Read0=No, 1=Yes
BV32ON/OFF control statusWrite0=Off, 1=On
BV33ON/OFF is allowedRead0=Allow, 1=Prohibit
BV34HMI Temperature setting is allowedRead0=Allow, 1=Prohibit
BV35BV-35HMI humidity setting is allowed; For EY-RU305F7002WWrite0=Allow, 1=Prohibit
BV36BV-36HMI CO2 setting is allowed; For EY-RU305F7003WWrite0=Allow, 1=Prohibit
BV37BV-37HMI pressure setting is allowedWrite0=Allow, 1=Prohibit
BV38Deg C/F Unit display selectWrite0=DegC, 1=DegF
BV39Deg/Pa display selectWrite0=Deg, 1=Pa
BV4024hr/12hr time mode selectWrite0=24 hr, 1=12 hr
BV41Humidity displayFor EY-RU305F7002WRead0=No, 1=Yes
BV42ID address displayWrite0=No, 1=Yes
BV43Clock displayWrite0=No, 1=Yes
BV44PPM displayFor EY-RU305F7003WRead0=No, 1=Yes
BV45RPM displayWrite0=No, 1=Yes
BV46BV-46Internal useRead
BV47BV-47Internal useRead
BV48BV-48Internal useRead
BV49CO2 controlRead0=ai1 co2 sensor, 1=HMI co2 sensor
BV50BV-50Internal useRead
BV51VAV/CAV mode selectRead0=VAV, 1=CAV
BV52BV-52Arithmetic Operation-Off delay 160 sec after BV55Read
BV53BV-53Arithmetic Operation- BV104 & !BV52Read
BV54BV-54Arithmetic Operation- AV113 is within AV122~AV123Read
BV55BV-55Arithmetic Operation- On delay 5sec after BO54Read
BV56BV-56Arithmetic Operation- BV62 & BV38Read
BV57BV-57Arithmetic Operation- AV33 changes>.1Read
BV58BV-58Arithmetic Operation- AV34 changes>.1Read
BV59Power off min open/min flow selectRead0=min VAV open position, 1=Vmin
BV60Ai1control mode disable/ enable 0- 10VDCRead0=Disable, 1=Enable
BV61BV-61Arithmetic Operation- AV35 changes>.1Read
BV62BV-62Arithmetic Operation- BV57 or BV58 or BV61Read
BV63BV-63Damper end positionRead0=No, 1=Yes
BV64BV-64Arithmetic Operation- one shot BV63Read
BV66BV-66Arithmetic Operation- one shot BV63Read
BV67BV-67Arithmetic Operation- CounterCountCompletion of BO6 once per 5000 secRead
BV68BV-68Arithmetic Operation- AV98=1Read1=AV98
BV69BV-69Arithmetic Operation- one shot BO6Read
BV70BV-70Arithmetic Operation- BV68 or BV80Read
BV71BV-71Arithmetic Operation- Ondelay 1sec after BO7Read
BV72BV-72Arithmetic Operation- V95>2Read
BV73BV-73Arithmetic Operation- AV99=1Read1=AV99
BV74BV-74Arithmetic Operation- BV73 & BV71Read
BV75BV-75Arithmetic Operation-Off delay 160 sec after InitialRead
BV76BV-76Arithmetic Operation- one shot bv63Read
BV77BV-77Arithmetic Operation- CounterCountCompletion of BO7 once per 5000 secRead
BV78BV-78Arithmetic Operation- AV99 is not equal to 1Read
BV79BV-79Arithmetic Operation- one shot BO7Read
BV80BV-80Arithmetic Operation- BV71 & BV78Read
BV84BV-84Arithmetic Operation- BV101 or BV32Read
BV85BV-85Arithmetic Operation- one shot BV89Read
BV86BV-86Arithmetic Operation- one shot BV27Read
BV87BV-87Arithmetic Operation- BV2 & BV84Read
BV88BV-88Arithmetic Operation-!BV2 & BV84Read
BV89BV-89Arithmetic Operation- BV83+BV81Read
BV90BV-90Internal useRead
BV91BV-91Internal useRead
BV92BV-92Internal useRead
BV93BV-93Internal useRead
BV94BV-94Internal useRead
BV95BV-95Internal useRead
BV96BV-96Internal useRead
BV97BV-97Internal useRead
BV98BV-98Internal useRead
BV99BV-99Internal useRead
BV100BV-100Internal useRead
BV101BV-101Internal useRead
BV102BV-102Internal useRead
BV103BV-103Arithmetic Operation-one shot BV7Read
BV104BV-104Arithmetic Operation- CounterCountCompletion of BV105 once per AV117 secRead
BV105BV-105Arithmetic Operation- Counter Start Initial=1Read1=Counter Start Initial
BV106BV-106Arithmetic Operation-AI12 changes>2Read
BV107BV-107Arithmetic Operation-one shot BV106Read
BV108BV-108Arithmetic Operation- BV107 changes count>25Read
BV109BV-109Arithmetic Operation- AV75 changes>2Read
BV110BV-110Arithmetic Operation- AV68 is w tihin 0~10Read
BV111BV-111Arithmetic Operation- BV103 & BV110Read
BV112BV-112Internal useRead
BV113Stage 1 HeatingInternal useRead0=Not active, 1=Active
BV114Stage 2 HeatingInternal useRead0=Not active, 1=Active
BV115BV-115Internal useRead
BV116BV-116Internal useRead
BV117BV-117Internal useRead
BV118Stage 3 HeatingInternal useRead0=Not active, 1=Active
BV119Stage heating Bo8Read0=Off, 1=On
BV120Stage heating Bo9Read0=Off, 1=On
BV121BV-121Need lower temp. air for AHU (no delay)Read
BV122BV-122Need higher temp. air for AHU (no delay)Read
BV124BV-124Need more air volume for AHU (no delay)Read
BV127BV-127Internal useRead
Object ID lookup: SAUTER ASV3 VAV Compact Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ASV3 VAV Compact Controller (ASV305BF7xxxW) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the SAUTER ASV3 VAV Compact Controller (ASV305BF7xxxW)

How many BACnet points does the SAUTER ASV3 VAV Compact Controller (ASV305BF7xxxW) have?

This list has 247 BACnet objects: 6 analog inputs, 2 analog outputs, 112 analog values, 2 binary inputs, 4 binary outputs, 121 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which SAUTER ASV3 VAV Compact Controller (ASV305BF7xxxW) BACnet points are writable?

79 of the 247 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official SAUTER ASV3 VAV Compact Controller (ASV305BF7xxxW) BACnet documentation?

The source is Manual SAUTER ASV3, published free by SAUTER at https://www.sauter-controls.com/wp-content/uploads/2021/08/Manual-SAUTER-ASV3.pdf.

What are the minimum BACnet points to integrate the SAUTER ASV3 VAV Compact Controller (ASV305BF7xxxW)?

Start with BV 1 VAV box Occupied/ unoccupied (Occupied/unoccupied: 1 = occupied); BV 2 Cool/Heat mode (0 = cooling, 1 = heating); AV 33 Cooling setpoint (Room cooling setpoint); AV 37 Heating set point (Room heating setpoint); AV 4 Current VAV airflow (Measured VAV airflow); AV 5 VAV demand airflow (Airflow demand); AV 61 Current VAV position feedback (0- 100) (Damper position feedback, 0-100 %); AV 23 HMI Temperature sensor (Room temperature from the HMI room unit); BV 10 No Airflow in main duct (Duct airflow alarm, 1 = no airflow).

How do I enable BMS control of the SAUTER ASV3 VAV Compact Controller (ASV305BF7xxxW)?

Occupancy is BV 1 (VAV box Occupied/unoccupied); Cool/Heat mode is BV 2. Overrides: Override airflow control (BV 5) with Forced airflow control (AV 6), Damper override (BV 6) with AV 12.

How do I check these points on the real ASV3 VAV Compact Controller (ASV305BF7xxxW)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Manual SAUTER ASV3. Object names, instances and units are reproduced as published; descriptions are our own.