Fan coil controller (via BACnet gateway) · BACnet points list

RHOSS KCMS fan coil controller via KGTW-BAC BACnet gateway BACnet points list

Updated 12 November 2026

Short answer

KGTW-BAC is a DIN-rail Modbus RTU to BACnet gateway for RHOSS terminal units. With the KCMS_IP or KCMS_MSTP profile each KCMS fan coil shows up as a separate BACnet device with the 20 objects below: temperatures, setpoint, mode and fan speed commands, on/off, economy mode and an alarm code. BACnet IP and BACnet MS/TP are both available.

This page lists 20 BACnet objects for the RHOSS KCMS fan coil controller via KGTW-BAC BACnet gateway — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from RHOSS’s own free documentation, linked below.

Manufacturer
RHOSS
Model
KCMS fan coil controller via KGTW-BAC BACnet gateway
Equipment
Fan coil controller (via BACnet gateway)
Equipment type
VAV boxes & fan coils
BACnet objects
20 (7 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
KGTW-BAC, KCMS, KCMS_IP, KCMS_MSTP, KRS485, H58029
Source document
KGTW-BAC Bacnet Gateway - Istruzioni per l'uso / Instructions for use · H58029
Download CSV 20 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against RHOSS’s current documentation and the live device before use. Not official RHOSS information. Terms of use.

BMS integration notes: RHOSS KCMS fan coil controller via KGTW-BAC BACnet gateway

Integration in brief

Switch each fan coil with IP_FC01_OnOff (BV 1), set mode (MV 1), fan speed (MV 2) and setpoint (AV 1), then read the control probe, the setpoint in use and the alarm code. IP_FC01_Status (BI 6) shows whether the gateway still talks to the fan coil.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1IP_FC01_OnOffFan coil on/off (1 = On)Write
MV 1IP_FC01_ModeMode command (3 = Cooling, 6 = Heating)Write
MV 2IP_FC01_FanFan speed command (1 = Auto)Write
AV 1IP_FC01_SetRoom temperature setpointWrite
AI 4IP_FC01_CtrlProbeControl temperatureRead
AI 5IP_FC01_CtrlSetSetpoint in useRead
MI 1IP_FC01_AllarmsAlarm code (1 = No alarms)Read
BI 6IP_FC01_StatusFan coil online/offline status (1 = On)Read

Network setup

Watch out for

RHOSS KCMS fan coil controller via KGTW-BAC BACnet gateway BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

20 of 20 shown
Type
Access
Show
RHOSS KCMS fan coil controller via KGTW-BAC BACnet gateway BACnet Points List
DescriptionStates
AI1IP_FC01_ProbeB1Probe B1, intake air temperatureRead
AI2IP_FC01_ProbeaBTProbe BT, room air (inside control panel)Read
AI3IP_FC01_ProbeB2Probe B2, water temperatureRead
AImin4IP_FC01_CtrlProbeControl probe valueRead
AImin5IP_FC01_CtrlSetControl setpoint in useRead
AI6IP_FC01_FanSpeedActual fan speedRead
AVmin1IP_FC01_SetSetpointWrite
AV2IP_FC01_IncrSetCoolEconomy setpoint increase in coolingWrite
AV3IP_FC01_DecrSetHeatEconomy setpoint decrease in heatingWrite
MImin1IP_FC01_AllarmsAlarmsRead1=No alarms, 2=Probe ST1 is faulty, 3=Probe ST2 is faulty, 4=Probe ST3 is faulty, 5=Anti-freeze, 6=Overheating, 7=Fan alarm, 8=Remote safety (SIC), 9=General alarm, 10=Faulty EEPROM
MVmin1IP_FC01_ModeModeWrite1=Automatic, 2=Automatic + heater, 3=Cooling, 4=Dry, 5=Fan, 6=Heating, 7=Heating + heater
MVmin2IP_FC01_FanFan speedWrite1=Auto, 2=Minimum, 3=Medium, 4=Maximum
BVmin1IP_FC01_OnOffUnit on/offWrite0=Off, 1=On
BV2IP_FC01_SleepEcoEconomy mode on/offWrite0=Off, 1=On
BI1IP_FC01_CoolEnableCool enable active (water too hot)Read0=Off, 1=On
BI2IP_FC01_HeatEnableHeat enable active (water too cold)Read0=Off, 1=On
BI3IP_FC01_EcoEconomy mode enabledRead0=Off, 1=On
BI4IP_FC01_HeatReqHeating requestRead0=Off, 1=On
BI5IP_FC01_CoolReqCooling requestRead0=Off, 1=On
BImin6IP_FC01_StatusOnline/offline statusRead0=Off, 1=On
Object ID lookup: RHOSS KCMS fan coil controller via KGTW-BAC point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the KCMS fan coil controller via KGTW-BAC BACnet gateway and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the RHOSS KCMS fan coil controller via KGTW-BAC BACnet gateway

How many BACnet points does the RHOSS KCMS fan coil controller via KGTW-BAC BACnet gateway have?

This list has 20 BACnet objects: 6 analog inputs, 3 analog values, 6 binary inputs, 2 binary values, 1 multi-state input, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which RHOSS KCMS fan coil controller via KGTW-BAC BACnet gateway BACnet points are writable?

7 of the 20 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official RHOSS KCMS fan coil controller via KGTW-BAC BACnet gateway BACnet documentation?

The source is KGTW-BAC Bacnet Gateway - Istruzioni per l'uso / Instructions for use (H58029), published free by RHOSS at https://www.rhoss.it/wp-content/uploads/2022/07/H58029-KGTW-BAC-Modbus-RTU-Bacnet-IP-gateway-manual-IT-EN.pdf.

What are the minimum BACnet points to integrate the RHOSS KCMS fan coil controller via KGTW-BAC BACnet gateway?

Start with BV 1 IP_FC01_OnOff (Fan coil on/off (1 = On)); MV 1 IP_FC01_Mode (Mode command (3 = Cooling, 6 = Heating)); MV 2 IP_FC01_Fan (Fan speed command (1 = Auto)); AV 1 IP_FC01_Set (Room temperature setpoint); AI 4 IP_FC01_CtrlProbe (Control temperature); AI 5 IP_FC01_CtrlSet (Setpoint in use); MI 1 IP_FC01_Allarms (Alarm code (1 = No alarms)); BI 6 IP_FC01_Status (Fan coil online/offline status (1 = On)).

How do I check these points on the real KCMS fan coil controller via KGTW-BAC BACnet gateway?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More RHOSS BACnet points lists

Source: KGTW-BAC Bacnet Gateway - Istruzioni per l'uso / Instructions for use · H58029. Object names, instances and units are reproduced as published; descriptions are our own.