Fan coil controller (via BACnet gateway) · BACnet points list

RHOSS Idrowall fan coil via KGTW-BAC BACnet gateway BACnet points list

Updated 12 November 2026

Short answer

KGTW-BAC is a DIN-rail Modbus RTU to BACnet gateway for RHOSS terminal units. With the Idrowall profile each Idrowall fan coil appears as its own BACnet device with 12 objects: water and room temperatures, fan RPM, valve state, setpoint, on/off, panel lock, louver, UV lamp, fan speed and mode. BACnet IP and BACnet MS/TP are both available.

This page lists 12 BACnet objects for the RHOSS Idrowall fan coil via KGTW-BAC BACnet gateway — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from RHOSS’s own free documentation, linked below.

Manufacturer
RHOSS
Model
Idrowall fan coil via KGTW-BAC BACnet gateway
Equipment
Fan coil controller (via BACnet gateway)
Equipment type
VAV boxes & fan coils
BACnet objects
12 (7 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
KGTW-BAC, Idrowall, Idrowall_IP, KWPI, H58029
Source document
KGTW-BAC Bacnet Gateway - Istruzioni per l'uso / Instructions for use · H58029
Download CSV 12 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against RHOSS’s current documentation and the live device before use. Not official RHOSS information. Terms of use.

BMS integration notes: RHOSS Idrowall fan coil via KGTW-BAC BACnet gateway

Integration in brief

Switch each Idrowall with IP_FC01_OnOff (BV 1), set mode (MV 2), fan speed (MV 1) and setpoint (AV 1), and read room temperature, valve state and the bus status. The table has no alarm object.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1IP_FC01_OnOffFan coil on/off (1 = Unit ON)Write
MV 2IP_FC01_ModeMode command (2 = Heating, 8 = Cool)Write
MV 1IP_FC01_FanFan speed command (8 = Auto)Write
AV 1IP_FC01_SetRoom temperature setpointWrite
AI 2IP_FC01_ProbeS2Room temperatureRead
BI 1IP_FC01_ValveWater valve state (1 = Open)Read
BI 2IP_FC01_StatusGateway link to the fan coil (1 = Online)Read

Network setup

Watch out for

RHOSS Idrowall fan coil via KGTW-BAC BACnet gateway BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

12 of 12 shown
Type
Multi-state
Access
Show
RHOSS Idrowall fan coil via KGTW-BAC BACnet gateway BACnet Points List
DescriptionStates
AI1IP_FC01_ProbeS1Probe S1, water temperatureRead
AImin2IP_FC01_ProbeS2Probe S2, room temperatureRead
AI3IP_FC01_RPMFan speed (RPM)Read
BImin1IP_FC01_ValveValveRead0=Closed, 1=Open
AVmin1IP_FC01_SetSetpointWrite
BVmin1IP_FC01_OnOffUnit on/offWrite0=Unit OFF, 1=Unit ON
BV2IP_FC01_LockLocal panel locked/unlockedWrite0=Unlocked, 1=Locked
BV3IP_FC01_LouverLouver statusWrite0=Fixed, 1=Swing
BV4IP_FC01_UVUV lamp / ionizerWrite0=Off, 1=On
MVmin1IP_FC01_FanFan speedWrite1=Minimum speed, 2=Medium speed, 4=Maximum speed, 8=Auto
MVmin2IP_FC01_ModeModeWrite1=Dry, 2=Heating, 4=Fan, 8=Cool, 16=Automatic
BImin2IP_FC01_StatusBus statusRead0=Offline, 1=Online
Object ID lookup: RHOSS Idrowall fan coil via KGTW-BAC point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Idrowall fan coil via KGTW-BAC BACnet gateway and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the RHOSS Idrowall fan coil via KGTW-BAC BACnet gateway

How many BACnet points does the RHOSS Idrowall fan coil via KGTW-BAC BACnet gateway have?

This list has 12 BACnet objects: 3 analog inputs, 1 analog value, 2 binary inputs, 4 binary values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which RHOSS Idrowall fan coil via KGTW-BAC BACnet gateway BACnet points are writable?

7 of the 12 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official RHOSS Idrowall fan coil via KGTW-BAC BACnet gateway BACnet documentation?

The source is KGTW-BAC Bacnet Gateway - Istruzioni per l'uso / Instructions for use (H58029), published free by RHOSS at https://www.rhoss.it/wp-content/uploads/2022/07/H58029-KGTW-BAC-Modbus-RTU-Bacnet-IP-gateway-manual-IT-EN.pdf.

What are the minimum BACnet points to integrate the RHOSS Idrowall fan coil via KGTW-BAC BACnet gateway?

Start with BV 1 IP_FC01_OnOff (Fan coil on/off (1 = Unit ON)); MV 2 IP_FC01_Mode (Mode command (2 = Heating, 8 = Cool)); MV 1 IP_FC01_Fan (Fan speed command (8 = Auto)); AV 1 IP_FC01_Set (Room temperature setpoint); AI 2 IP_FC01_ProbeS2 (Room temperature); BI 1 IP_FC01_Valve (Water valve state (1 = Open)); BI 2 IP_FC01_Status (Gateway link to the fan coil (1 = Online)).

How do I check these points on the real Idrowall fan coil via KGTW-BAC BACnet gateway?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More RHOSS BACnet points lists

Source: KGTW-BAC Bacnet Gateway - Istruzioni per l'uso / Instructions for use · H58029. Object names, instances and units are reproduced as published; descriptions are our own.