Pressurisation pump / degassing station controller · BACnet points list

Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module BACnet points list

Updated 12 November 2026

Short answer

Reflex pressurisation, make-up and vacuum degassing units use the Control Touch controller. With the plug-in Anybus BACnet MS/TP module it publishes system pressure, vessel level, valve positions, run hours, make-up volume, output and input states, operating mode and a long list of fault and warning flags as Binary and Analog Values. The BMS can switch pumps or compressors and valves on and off and set the minimum operating pressure p0.

This page lists 105 BACnet objects for the Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Reflex’s own free documentation, linked below.

Manufacturer
Reflex
Model
Control Touch with Anybus CompactCom M30 BACnet MS/TP module
Equipment
Pressurisation pump / degassing station controller
Equipment type
VFDs & pumps
BACnet objects
105 (15 writable)
Transport
BACnet MS/TP
Firmware
Control Touch software V1.02
Also known as
Control Touch, Reflex Control Touch, Anybus CompactCom M30 BACnet MS/TP, Variomat, Variomat Giga, Reflexomat, Servitec, Servimat, CT-MK200, Reflex Winkelmann BACnet
Source document
Beschreibung Anybus-CompactCom M30 für BACnet-MS/TP [Control Touch] · rev. 2020-06-16 (software V1.02)
Download CSV 105 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Reflex’s current documentation and the live device before use. Not official Reflex information. Terms of use.

BMS integration notes: Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module

Integration in brief

Set the device number, MAC address and baud in the Control Touch service menu. Read AV 0 system pressure, AV 1 level, the mode BVs and the ER fault and warning flags. Remote commands work only when remote control is enabled in the controller and the unit is in AUTO.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 9SET value p0 (mbar)Minimum operating pressure p0, mbar (if > 0)Write
BV 24Mode: AUTOUnit in AUTO modeRead
AV 0AI sys. pressure (mbar)System pressure, mbarRead
AV 1AI water level (%)Vessel level, %Read
BV 10BO pump/compr. 1Pump/compressor 1 output onRead
BV 18BI FB pump/comp. 1Pump/compressor 1 run feedbackRead
BV 16BO coll. faultCommon fault outputRead
BV 28ER 01 min. press.Fault: below minimum pressureRead
BV 29ER 02.1 low waterFault: low waterRead

Enable & remote start

Remote control from the BACnet master must be enabled in the Control Touch; binary commands are only taken over in AUTO mode.

Network setup

Watch out for

Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

105 of 105 shown
Type
AnalogBinary
Access
Show
Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module BACnet Points List
DescriptionStates
BV0T-ON pump/compr. 1Switch pump/compressor 1 on (1 = on)Write
BV1T-OFF pump/compr. 1Switch pump/compressor 1 off (1 = off)Write
BV2T-ON pump/compr. 2Switch pump/compressor 2 on (1 = on)Write
BV3T-OFF pump/compr. 2Switch pump/compressor 2 off (1 = off)Write
BV4T-ON replen.valveOpen make-up (replenishment) valveWrite
BV5T-OFF replen.valveClose make-up valveWrite
BV6T-ON overfl.valve 1Open overflow valve / ball valve 1Write
BV7T-OFF overfl.valve 1Close overflow valve / ball valve 1Write
BV8T-ON overfl.valve 2Open overflow valve / ball valve 2 (not Servimat)Write
BV9T-OFF overfl.valve 2Close overflow valve / ball valve 2 (not Servimat)Write
BV95T-ON 3-WAY-MVServimat: 3-way motor valve on (1 = spray pipe)Write
BV96T-OFF 3-WAY-MVServimat: 3-way motor valve off (1 = vessel)Write
BV97T-ON MV-2Servimat: open motor valve 2Write
BV98T-OFF MV-2Servimat: close motor valve 2Write
AVmin9SET value p0 (mbar)Minimum operating pressure p0 setpoint; used only if > 0mbarWrite
BVmin10BO pump/compr. 1Output state, pump/compressor 1Read
BV11BO pump/compr. 2Output state, pump/compressor 2Read
BV12BO overflow v. 1Output state, overflow valve 1Read
BV13BO overflow v. 2Output state, overflow valve 2Read
BV14BO relplen. valveOutput state, make-up valveRead
BV15BO low waterOutput state, minimum levelRead
BVmin16BO coll. faultOutput state, common faultRead
BV17BO replen. faultOutput state, make-up faultRead
BVmin18BI FB pump/comp. 1Input: pump/compressor 1 feedbackRead
BV19BI FB pump/comp. 2Input: pump/compressor 2 feedbackRead
BV20BI low waterInput: low waterRead
BV21BI water meterInput: water meterRead
BV22Mode: HANDOperating mode is HANDRead
BV23Mode: STOPOperating mode is STOPRead
BVmin24Mode: AUTOOperating mode is AUTOMATICRead
BV25Mode: 1 pump/compr.Unit has 1 pump/compressorRead
BV26Mode: 2 pumps/compr.Unit has 2 pumps/compressorsRead
BV27Mode: LevelcontrolServitec: 1 = Levelcontrol, 0 = MagcontrolRead
BVmin28ER 01 min. press.Fault: below minimum pressureRead
BVmin29ER 02.1 low waterFault: low water 1Read
BV30ER 02.2 low waterFault: low water 2 (Servitec, Servimat)Read
BV31ER 03 high waterWarning: maximum level exceededRead
BV32ER 04.1 pu./co. 1Fault: pump/compressor 1Read
BV33ER 04.2 pu./co. 2Fault: pump/compressor 2Read
BV34ER 05 run time p/cWarning: pump/compressor run time exceededRead
BV35ER 06 replen. timeWarning: make-up time exceededRead
BV36ER 07 replen. cyclesWarning: make-up cycles exceededRead
BV37ER 08 press. sensorFault: system pressure measurementRead
BV38ER 09 level sensorFault: level measurement (Variomat, Variomat Giga, Reflexomat)Read
BV39ER 09 press. sens. 2Fault: spray pipe pressure measurement (Servitec)Read
BV40ER 10 max. press.Warning: maximum pressure exceededRead
BV41ER 11 max.repl.cont.Warning: make-up quantity exceededRead
BV42ER 12 fill timeWarning: fill time exceeded (Servitec)Read
BV43ER 13 fill volumeWarning: fill volume exceeded (Servitec)Read
BV44ER 14 exhaust timeWarning: discharge time exceeded (Servitec)Read
BV45ER 15 replen. valveWarning: make-up valve leakingRead
BV46ER 16 power faultWarning: power failureRead
BV47ER 18 parameterWarning: parameter errorRead
BV48ER 19 STOP > 4hFault: unit in STOP mode for over 4 hoursRead
BV49ER 20 tot.replen.vol.Warning: total make-up volume exceededRead
BV50ER 21 maintenanceMaintenance dueRead
BV51ER 22 blow out timeWarning: blow-out time exceeded (Servitec)Read
BV52ER 24 soft. cartridgeWarning: softening cartridge needs changingRead
BV53ER 25 data loggerWarning: check data loggerRead
BV54ER 26 cond. sensorFault: conductivity measurement (Servitec)Read
BV55ER 27 cond. exceededWarning: maximum conductivity exceeded (Servitec)Read
BV56ER 29 communicationWarning: network communicationRead
BV57ER 30 io-moduleFault: expansion moduleRead
BV58ER 31 eeprom defect.Fault: EEPROM defective (operating unit)Read
BV59ER 32 power lowFault: undervoltageRead
BV60ER 33 eeprom adjust.Fault: calibration parameters (main board)Read
BV61ER 34 io-boardFault: main boardRead
BV62ER 35 dig.sens.volt.Fault: digital sensor supply missingRead
BV63ER 36 ana.sens.volt.Fault: analog sensor supply missingRead
BV64ER 37 volt. mbv 1Fault: supply to ball valve 1 missingRead
BV65ER 38 volt. mbv 2Fault: supply to ball valve 2 missingRead
BV66ER 39 jumper press.Fault: pressure jumper set wrongRead
BV67ER 40 jumper levelFault: level jumper set wrongRead
BV68ER 41 batteryWarning: replace battery (operating unit)Read
BV69ER 42 bus moduleWarning: check bus moduleRead
BV70ER 81 ext. input 1Warning: expansion module digital input 1Read
BV71ER 82 ext. input 2Warning: expansion module digital input 2Read
BV72ER 83 ext. input 3Warning: expansion module digital input 3Read
BV73ER 84 ext. input 4Warning: expansion module digital input 4Read
BV74ER 85 ext. input 5Warning: expansion module digital input 5Read
BV75ER 86 ext. input 6Warning: expansion module digital input 6Read
BV76ER 87 ext.output 1Warning: expansion module digital outputRead
BV77ER 51 mk200-mod. 1Fault: MK200 module address 1 (CT-MK200 only)Read
BV78ER 52 mk200-mod. 2Fault: MK200 module address 2 (CT-MK200 only)Read
BV79ER 53 mk200-mod. 3Fault: MK200 module address 3 (CT-MK200 only)Read
BV80ER 54 mk200-mod. 4Fault: MK200 module address 4 (CT-MK200 only)Read
BV81ER 55 mk200-mod. 5Fault: MK200 module address 5 (CT-MK200 only)Read
BV82ER 56 mk200-mod. 6Fault: MK200 module address 6 (CT-MK200 only)Read
BV83ER 57 mk200-mod. 7Fault: MK200 module address 7 (CT-MK200 only)Read
BV84ER 58 mk200-mod. 8Fault: MK200 module address 8 (CT-MK200 only)Read
BV85BI dig. input 5Digital input 5 (CT-MK200 only)Read
BV86BI dig. input 6Digital input 6 (CT-MK200 only)Read
BV87BI dig. input 7Digital input 7 (CT-MK200 only)Read
BV88ER 43 operating pressureWorking range exceeded (Servitec)Read
BV89ER 44 initializationInitialisation of Te failed (Servimat)Read
BV90Mode: 2x2-way-mbvServitec 2x2-way ball valve versionRead
AVmin0AI sys. pressure (mbar)System pressurembarRead
AVmin1AI water level (%)Vessel level (Variomat, Variomat Giga, Reflexomat, Servimat)%Read
AV2AI pressure 2 (mbar)Fill pipe pressure (Servitec)mbarRead
AV3AI position MBV 1 (%)Motor ball valve 1 position feedback%Read
AV4AI position MBV 2 (%)Motor ball valve 2 position feedback%Read
AV5Operating hours 1 (h)Run hours, pump/compressor 1hRead
AV6Operating hours 2 (h)Run hours, pump/compressor 2hRead
AV7Replen. volume (liter)Total make-up volumelRead
AV8System typeUnit typeRead1=Variomat, 2=Variomat Giga, 3=Reflexomat, 4=Servitec, 11=Servimat
Object ID lookup: Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Control Touch with Anybus CompactCom M30 BACnet MS/TP module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module

How many BACnet points does the Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module have?

This list has 105 BACnet objects: 10 analog values, 95 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module BACnet points are writable?

15 of the 105 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module BACnet documentation?

The source is Beschreibung Anybus-CompactCom M30 für BACnet-MS/TP [Control Touch], revision 2020-06-16 (software V1.02), published free by Reflex at https://xom-web.reflex.de/xom-rest/assets/b30cf8d8-8539-458c-a417-52d703e60664/content?locale=de.

What are the minimum BACnet points to integrate the Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module?

Start with AV 9 SET value p0 (mbar) (Minimum operating pressure p0, mbar (if > 0)); BV 24 Mode: AUTO (Unit in AUTO mode); AV 0 AI sys. pressure (mbar) (System pressure, mbar); AV 1 AI water level (%) (Vessel level, %); BV 10 BO pump/compr. 1 (Pump/compressor 1 output on); BV 18 BI FB pump/comp. 1 (Pump/compressor 1 run feedback); BV 16 BO coll. fault (Common fault output); BV 28 ER 01 min. press. (Fault: below minimum pressure); BV 29 ER 02.1 low water (Fault: low water).

How do I enable BMS control of the Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module?

Remote control from the BACnet master must be enabled in the Control Touch; binary commands are only taken over in AUTO mode.

How do I check these points on the real Control Touch with Anybus CompactCom M30 BACnet MS/TP module?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Beschreibung Anybus-CompactCom M30 für BACnet-MS/TP [Control Touch] · rev. 2020-06-16 (software V1.02). Object names, instances and units are reproduced as published; descriptions are our own.