Pressurisation pump / degassing station controller · BACnet points list
Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module BACnet points list
Updated 12 November 2026
Reflex pressurisation, make-up and vacuum degassing units use the Control Touch controller. With the plug-in Anybus BACnet MS/TP module it publishes system pressure, vessel level, valve positions, run hours, make-up volume, output and input states, operating mode and a long list of fault and warning flags as Binary and Analog Values. The BMS can switch pumps or compressors and valves on and off and set the minimum operating pressure p0.
This page lists 105 BACnet objects for the Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Reflex’s own free documentation, linked below.
- Manufacturer
- Reflex
- Model
- Control Touch with Anybus CompactCom M30 BACnet MS/TP module
- Equipment
- Pressurisation pump / degassing station controller
- Equipment type
- VFDs & pumps
- BACnet objects
- 105 (15 writable)
- Transport
- BACnet MS/TP
- Firmware
- Control Touch software V1.02
- Also known as
- Control Touch, Reflex Control Touch, Anybus CompactCom M30 BACnet MS/TP, Variomat, Variomat Giga, Reflexomat, Servitec, Servimat, CT-MK200, Reflex Winkelmann BACnet
Reference only, provided as-is: verify against Reflex’s current documentation and the live device before use. Not official Reflex information. Terms of use.
BMS integration notes: Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module
Set the device number, MAC address and baud in the Control Touch service menu. Read AV 0 system pressure, AV 1 level, the mode BVs and the ER fault and warning flags. Remote commands work only when remote control is enabled in the controller and the unit is in AUTO.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 9 | SET value p0 (mbar) | Minimum operating pressure p0, mbar (if > 0) | Write |
| BV 24 | Mode: AUTO | Unit in AUTO mode | Read |
| AV 0 | AI sys. pressure (mbar) | System pressure, mbar | Read |
| AV 1 | AI water level (%) | Vessel level, % | Read |
| BV 10 | BO pump/compr. 1 | Pump/compressor 1 output on | Read |
| BV 18 | BI FB pump/comp. 1 | Pump/compressor 1 run feedback | Read |
| BV 16 | BO coll. fault | Common fault output | Read |
| BV 28 | ER 01 min. press. | Fault: below minimum pressure | Read |
| BV 29 | ER 02.1 low water | Fault: low water | Read |
Enable & remote start
Remote control from the BACnet master must be enabled in the Control Touch; binary commands are only taken over in AUTO mode.
Network setup
- Settings > Service > Anybus module (shown only when a module is detected).
- Device number (instance) 1-4194302, MAC address 0-127.
- Baud 9600, 19200, 38400 or 76800.
- 5-pin connector: 1 common, 2 Data-, 3 shield, 4 Data+.
Watch out for
- Fit or remove the module only with the controller powered off.
- The network LED flashes red on a BACnet timeout (no new message within the set time).
Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 0 | T-ON pump/compr. 1 | Switch pump/compressor 1 on (1 = on) | Write | ||
| BV | 1 | T-OFF pump/compr. 1 | Switch pump/compressor 1 off (1 = off) | Write | ||
| BV | 2 | T-ON pump/compr. 2 | Switch pump/compressor 2 on (1 = on) | Write | ||
| BV | 3 | T-OFF pump/compr. 2 | Switch pump/compressor 2 off (1 = off) | Write | ||
| BV | 4 | T-ON replen.valve | Open make-up (replenishment) valve | Write | ||
| BV | 5 | T-OFF replen.valve | Close make-up valve | Write | ||
| BV | 6 | T-ON overfl.valve 1 | Open overflow valve / ball valve 1 | Write | ||
| BV | 7 | T-OFF overfl.valve 1 | Close overflow valve / ball valve 1 | Write | ||
| BV | 8 | T-ON overfl.valve 2 | Open overflow valve / ball valve 2 (not Servimat) | Write | ||
| BV | 9 | T-OFF overfl.valve 2 | Close overflow valve / ball valve 2 (not Servimat) | Write | ||
| BV | 95 | T-ON 3-WAY-MV | Servimat: 3-way motor valve on (1 = spray pipe) | Write | ||
| BV | 96 | T-OFF 3-WAY-MV | Servimat: 3-way motor valve off (1 = vessel) | Write | ||
| BV | 97 | T-ON MV-2 | Servimat: open motor valve 2 | Write | ||
| BV | 98 | T-OFF MV-2 | Servimat: close motor valve 2 | Write | ||
| AVmin | 9 | SET value p0 (mbar) | Minimum operating pressure p0 setpoint; used only if > 0 | mbar | Write | |
| BVmin | 10 | BO pump/compr. 1 | Output state, pump/compressor 1 | Read | ||
| BV | 11 | BO pump/compr. 2 | Output state, pump/compressor 2 | Read | ||
| BV | 12 | BO overflow v. 1 | Output state, overflow valve 1 | Read | ||
| BV | 13 | BO overflow v. 2 | Output state, overflow valve 2 | Read | ||
| BV | 14 | BO relplen. valve | Output state, make-up valve | Read | ||
| BV | 15 | BO low water | Output state, minimum level | Read | ||
| BVmin | 16 | BO coll. fault | Output state, common fault | Read | ||
| BV | 17 | BO replen. fault | Output state, make-up fault | Read | ||
| BVmin | 18 | BI FB pump/comp. 1 | Input: pump/compressor 1 feedback | Read | ||
| BV | 19 | BI FB pump/comp. 2 | Input: pump/compressor 2 feedback | Read | ||
| BV | 20 | BI low water | Input: low water | Read | ||
| BV | 21 | BI water meter | Input: water meter | Read | ||
| BV | 22 | Mode: HAND | Operating mode is HAND | Read | ||
| BV | 23 | Mode: STOP | Operating mode is STOP | Read | ||
| BVmin | 24 | Mode: AUTO | Operating mode is AUTOMATIC | Read | ||
| BV | 25 | Mode: 1 pump/compr. | Unit has 1 pump/compressor | Read | ||
| BV | 26 | Mode: 2 pumps/compr. | Unit has 2 pumps/compressors | Read | ||
| BV | 27 | Mode: Levelcontrol | Servitec: 1 = Levelcontrol, 0 = Magcontrol | Read | ||
| BVmin | 28 | ER 01 min. press. | Fault: below minimum pressure | Read | ||
| BVmin | 29 | ER 02.1 low water | Fault: low water 1 | Read | ||
| BV | 30 | ER 02.2 low water | Fault: low water 2 (Servitec, Servimat) | Read | ||
| BV | 31 | ER 03 high water | Warning: maximum level exceeded | Read | ||
| BV | 32 | ER 04.1 pu./co. 1 | Fault: pump/compressor 1 | Read | ||
| BV | 33 | ER 04.2 pu./co. 2 | Fault: pump/compressor 2 | Read | ||
| BV | 34 | ER 05 run time p/c | Warning: pump/compressor run time exceeded | Read | ||
| BV | 35 | ER 06 replen. time | Warning: make-up time exceeded | Read | ||
| BV | 36 | ER 07 replen. cycles | Warning: make-up cycles exceeded | Read | ||
| BV | 37 | ER 08 press. sensor | Fault: system pressure measurement | Read | ||
| BV | 38 | ER 09 level sensor | Fault: level measurement (Variomat, Variomat Giga, Reflexomat) | Read | ||
| BV | 39 | ER 09 press. sens. 2 | Fault: spray pipe pressure measurement (Servitec) | Read | ||
| BV | 40 | ER 10 max. press. | Warning: maximum pressure exceeded | Read | ||
| BV | 41 | ER 11 max.repl.cont. | Warning: make-up quantity exceeded | Read | ||
| BV | 42 | ER 12 fill time | Warning: fill time exceeded (Servitec) | Read | ||
| BV | 43 | ER 13 fill volume | Warning: fill volume exceeded (Servitec) | Read | ||
| BV | 44 | ER 14 exhaust time | Warning: discharge time exceeded (Servitec) | Read | ||
| BV | 45 | ER 15 replen. valve | Warning: make-up valve leaking | Read | ||
| BV | 46 | ER 16 power fault | Warning: power failure | Read | ||
| BV | 47 | ER 18 parameter | Warning: parameter error | Read | ||
| BV | 48 | ER 19 STOP > 4h | Fault: unit in STOP mode for over 4 hours | Read | ||
| BV | 49 | ER 20 tot.replen.vol. | Warning: total make-up volume exceeded | Read | ||
| BV | 50 | ER 21 maintenance | Maintenance due | Read | ||
| BV | 51 | ER 22 blow out time | Warning: blow-out time exceeded (Servitec) | Read | ||
| BV | 52 | ER 24 soft. cartridge | Warning: softening cartridge needs changing | Read | ||
| BV | 53 | ER 25 data logger | Warning: check data logger | Read | ||
| BV | 54 | ER 26 cond. sensor | Fault: conductivity measurement (Servitec) | Read | ||
| BV | 55 | ER 27 cond. exceeded | Warning: maximum conductivity exceeded (Servitec) | Read | ||
| BV | 56 | ER 29 communication | Warning: network communication | Read | ||
| BV | 57 | ER 30 io-module | Fault: expansion module | Read | ||
| BV | 58 | ER 31 eeprom defect. | Fault: EEPROM defective (operating unit) | Read | ||
| BV | 59 | ER 32 power low | Fault: undervoltage | Read | ||
| BV | 60 | ER 33 eeprom adjust. | Fault: calibration parameters (main board) | Read | ||
| BV | 61 | ER 34 io-board | Fault: main board | Read | ||
| BV | 62 | ER 35 dig.sens.volt. | Fault: digital sensor supply missing | Read | ||
| BV | 63 | ER 36 ana.sens.volt. | Fault: analog sensor supply missing | Read | ||
| BV | 64 | ER 37 volt. mbv 1 | Fault: supply to ball valve 1 missing | Read | ||
| BV | 65 | ER 38 volt. mbv 2 | Fault: supply to ball valve 2 missing | Read | ||
| BV | 66 | ER 39 jumper press. | Fault: pressure jumper set wrong | Read | ||
| BV | 67 | ER 40 jumper level | Fault: level jumper set wrong | Read | ||
| BV | 68 | ER 41 battery | Warning: replace battery (operating unit) | Read | ||
| BV | 69 | ER 42 bus module | Warning: check bus module | Read | ||
| BV | 70 | ER 81 ext. input 1 | Warning: expansion module digital input 1 | Read | ||
| BV | 71 | ER 82 ext. input 2 | Warning: expansion module digital input 2 | Read | ||
| BV | 72 | ER 83 ext. input 3 | Warning: expansion module digital input 3 | Read | ||
| BV | 73 | ER 84 ext. input 4 | Warning: expansion module digital input 4 | Read | ||
| BV | 74 | ER 85 ext. input 5 | Warning: expansion module digital input 5 | Read | ||
| BV | 75 | ER 86 ext. input 6 | Warning: expansion module digital input 6 | Read | ||
| BV | 76 | ER 87 ext.output 1 | Warning: expansion module digital output | Read | ||
| BV | 77 | ER 51 mk200-mod. 1 | Fault: MK200 module address 1 (CT-MK200 only) | Read | ||
| BV | 78 | ER 52 mk200-mod. 2 | Fault: MK200 module address 2 (CT-MK200 only) | Read | ||
| BV | 79 | ER 53 mk200-mod. 3 | Fault: MK200 module address 3 (CT-MK200 only) | Read | ||
| BV | 80 | ER 54 mk200-mod. 4 | Fault: MK200 module address 4 (CT-MK200 only) | Read | ||
| BV | 81 | ER 55 mk200-mod. 5 | Fault: MK200 module address 5 (CT-MK200 only) | Read | ||
| BV | 82 | ER 56 mk200-mod. 6 | Fault: MK200 module address 6 (CT-MK200 only) | Read | ||
| BV | 83 | ER 57 mk200-mod. 7 | Fault: MK200 module address 7 (CT-MK200 only) | Read | ||
| BV | 84 | ER 58 mk200-mod. 8 | Fault: MK200 module address 8 (CT-MK200 only) | Read | ||
| BV | 85 | BI dig. input 5 | Digital input 5 (CT-MK200 only) | Read | ||
| BV | 86 | BI dig. input 6 | Digital input 6 (CT-MK200 only) | Read | ||
| BV | 87 | BI dig. input 7 | Digital input 7 (CT-MK200 only) | Read | ||
| BV | 88 | ER 43 operating pressure | Working range exceeded (Servitec) | Read | ||
| BV | 89 | ER 44 initialization | Initialisation of Te failed (Servimat) | Read | ||
| BV | 90 | Mode: 2x2-way-mbv | Servitec 2x2-way ball valve version | Read | ||
| AVmin | 0 | AI sys. pressure (mbar) | System pressure | mbar | Read | |
| AVmin | 1 | AI water level (%) | Vessel level (Variomat, Variomat Giga, Reflexomat, Servimat) | % | Read | |
| AV | 2 | AI pressure 2 (mbar) | Fill pipe pressure (Servitec) | mbar | Read | |
| AV | 3 | AI position MBV 1 (%) | Motor ball valve 1 position feedback | % | Read | |
| AV | 4 | AI position MBV 2 (%) | Motor ball valve 2 position feedback | % | Read | |
| AV | 5 | Operating hours 1 (h) | Run hours, pump/compressor 1 | h | Read | |
| AV | 6 | Operating hours 2 (h) | Run hours, pump/compressor 2 | h | Read | |
| AV | 7 | Replen. volume (liter) | Total make-up volume | l | Read | |
| AV | 8 | System type | Unit type | Read | 1=Variomat, 2=Variomat Giga, 3=Reflexomat, 4=Servitec, 11=Servimat |
No points match these filters.
Object ID lookup: Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module point IDs by name
BV0T-ON pump/compr. 1BV1T-OFF pump/compr. 1BV2T-ON pump/compr. 2BV3T-OFF pump/compr. 2BV4T-ON replen.valveBV5T-OFF replen.valveBV6T-ON overfl.valve 1BV7T-OFF overfl.valve 1BV8T-ON overfl.valve 2BV9T-OFF overfl.valve 2BV95T-ON 3-WAY-MVBV96T-OFF 3-WAY-MVBV97T-ON MV-2BV98T-OFF MV-2AV9SET value p0 (mbar)BV10BO pump/compr. 1BV11BO pump/compr. 2BV12BO overflow v. 1BV13BO overflow v. 2BV14BO relplen. valveBV15BO low waterBV16BO coll. faultBV17BO replen. faultBV18BI FB pump/comp. 1BV19BI FB pump/comp. 2BV20BI low waterBV21BI water meterBV22Mode: HANDBV23Mode: STOPBV24Mode: AUTOBV25Mode: 1 pump/compr.BV26Mode: 2 pumps/compr.BV27Mode: LevelcontrolBV28ER 01 min. press.BV29ER 02.1 low waterBV30ER 02.2 low waterBV31ER 03 high waterBV32ER 04.1 pu./co. 1BV33ER 04.2 pu./co. 2BV34ER 05 run time p/cBV35ER 06 replen. timeBV36ER 07 replen. cyclesBV37ER 08 press. sensorBV38ER 09 level sensorBV39ER 09 press. sens. 2BV40ER 10 max. press.BV41ER 11 max.repl.cont.BV42ER 12 fill timeBV43ER 13 fill volumeBV44ER 14 exhaust timeBV45ER 15 replen. valveBV46ER 16 power faultBV47ER 18 parameterBV48ER 19 STOP > 4hBV49ER 20 tot.replen.vol.BV50ER 21 maintenanceBV51ER 22 blow out timeBV52ER 24 soft. cartridgeBV53ER 25 data loggerBV54ER 26 cond. sensorBV55ER 27 cond. exceededBV56ER 29 communicationBV57ER 30 io-moduleBV58ER 31 eeprom defect.BV59ER 32 power lowBV60ER 33 eeprom adjust.BV61ER 34 io-boardBV62ER 35 dig.sens.volt.BV63ER 36 ana.sens.volt.BV64ER 37 volt. mbv 1BV65ER 38 volt. mbv 2BV66ER 39 jumper press.BV67ER 40 jumper levelBV68ER 41 batteryBV69ER 42 bus moduleBV70ER 81 ext. input 1BV71ER 82 ext. input 2BV72ER 83 ext. input 3BV73ER 84 ext. input 4BV74ER 85 ext. input 5BV75ER 86 ext. input 6BV76ER 87 ext.output 1BV77ER 51 mk200-mod. 1BV78ER 52 mk200-mod. 2BV79ER 53 mk200-mod. 3BV80ER 54 mk200-mod. 4BV81ER 55 mk200-mod. 5BV82ER 56 mk200-mod. 6BV83ER 57 mk200-mod. 7BV84ER 58 mk200-mod. 8BV85BI dig. input 5BV86BI dig. input 6BV87BI dig. input 7BV88ER 43 operating pressureBV89ER 44 initializationBV90Mode: 2x2-way-mbvAV0AI sys. pressure (mbar)AV1AI water level (%)AV2AI pressure 2 (mbar)AV3AI position MBV 1 (%)AV4AI position MBV 2 (%)AV5Operating hours 1 (h)AV6Operating hours 2 (h)AV7Replen. volume (liter)AV8System type
Integration notes
- The source is in German; object names are as printed (English abbreviations) and descriptions are translated.
- Many objects apply only to one unit type (Servitec, Servimat or CT-MK200); the unit type is shown in AV 8.
- Commands BV 0-9 and BV 95-98 are separate ON and OFF objects (write 1 to act).
- On Servitec units with 2x2-way ball valves, BV 6-9 and BV 12-13 drive the PV and CD valves instead.
- BV 14 is printed 'BO relplen. valve'.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Control Touch with Anybus CompactCom M30 BACnet MS/TP module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module
How many BACnet points does the Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module have?
This list has 105 BACnet objects: 10 analog values, 95 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module BACnet points are writable?
15 of the 105 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module BACnet documentation?
The source is Beschreibung Anybus-CompactCom M30 für BACnet-MS/TP [Control Touch], revision 2020-06-16 (software V1.02), published free by Reflex at https://xom-web.reflex.de/xom-rest/assets/b30cf8d8-8539-458c-a417-52d703e60664/content?locale=de.
What are the minimum BACnet points to integrate the Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module?
Start with AV 9 SET value p0 (mbar) (Minimum operating pressure p0, mbar (if > 0)); BV 24 Mode: AUTO (Unit in AUTO mode); AV 0 AI sys. pressure (mbar) (System pressure, mbar); AV 1 AI water level (%) (Vessel level, %); BV 10 BO pump/compr. 1 (Pump/compressor 1 output on); BV 18 BI FB pump/comp. 1 (Pump/compressor 1 run feedback); BV 16 BO coll. fault (Common fault output); BV 28 ER 01 min. press. (Fault: below minimum pressure); BV 29 ER 02.1 low water (Fault: low water).
How do I enable BMS control of the Reflex Control Touch with Anybus CompactCom M30 BACnet MS/TP module?
Remote control from the BACnet master must be enabled in the Control Touch; binary commands are only taken over in AUTO mode.
How do I check these points on the real Control Touch with Anybus CompactCom M30 BACnet MS/TP module?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: Beschreibung Anybus-CompactCom M30 für BACnet-MS/TP [Control Touch] · rev. 2020-06-16 (software V1.02). Object names, instances and units are reproduced as published; descriptions are our own.