Commercial boiler controller · BACnet points list
RBI FIII / Fusion / CK boilers with HeatNet V3 control BACnet points list
Updated 28 October 2026
The HeatNet V3 control on RBI FIII, Fusion and CK boilers exposes a fixed BACnet object list. The BMS writes heat demand, the system setpoint (guarded by a countdown failsafe timer), outdoor-reset settings, DHW setpoint, clock and flow/boiler limits as analog and binary values. Read-only analog inputs give plant temperatures, counts and per-boiler run time, cycles, temperatures and modulation, and read-only binary values give interlock, alarm and status flags for each of up to 16 boilers.
This page lists 99 BACnet objects for the RBI FIII / Fusion / CK boilers with HeatNet V3 control — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from RBI’s own free documentation, linked below.
- Manufacturer
- RBI
- Model
- FIII / Fusion / CK boilers with HeatNet V3 control
- Equipment
- Commercial boiler controller
- Equipment type
- Boilers & water heaters
- BACnet objects
- 99 (20 writable)
- Transport
- —
- Firmware
- HeatNet V3; BTUH, system return/flow and boiler-count points need firmware 2.00 or later
- Also known as
- HeatNet V3, HeatNet, Futera III, FIII, Futera Fusion, Fusion, CK Series, Mestek, RBI V3 BACnet Objects
BMS integration notes: RBI FIII / Fusion / CK boilers with HeatNet V3 control
Connect the BMS to the master (boiler 1) HeatNet board. Write BV 1 HeatDemand to call for heat and AV 2 Setpoint for the system setpoint, and keep reloading AV 1 SetpointTimer so the plant does not fall back to its local setpoint. Read header/supply/return temperatures, boilers on, modulation and the per-boiler alarm and failed flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | HeatDemand | Heat demand from the BMS (1 = heat) | Write |
| AV 2 | Setpoint | System setpoint, 40-220 °F | Write |
| AV 1 | SetpointTimer | Failsafe countdown; reload before it reaches 0 | Write |
| AI 144 | OperatingSetpoint | Active setpoint in use | Read |
| AI 3 | HeaderTemp | Header / system temperature, °F | Read |
| AI 1 | BoilersOn | Number of boilers running | Read |
| AI 2 | Modulation | System target modulation, % | Read |
| BV 1005 | Boiler##_Running | Boiler 1 firing (add 32 per boiler number) | Read |
| BV 1002 | Boiler##_Alarm | Boiler 1 alarm (add 32 per boiler number) | Read |
| BV 1003 | Boiler##_Failed | Boiler 1 failed (add 32 per boiler number) | Read |
Enable & remote start
BV 1 HeatDemand puts the boiler (plant) into heating mode when set to 1; 0 removes the demand. The setpoint the BMS writes is AV 2 Setpoint.
Heartbeat & communication loss
AV 1 SetpointTimer (0-65535 s) is a BMS failsafe countdown. The BMS must reload it periodically; if it reaches zero the control assumes the BMS has stopped and reloads its own saved local setpoint. Writing any read/write variable reloads the timer to 60 s if it is below 60 (on firmware below 3.48 only writing the setpoint does this).
Sensors & values from the BMS
AV 16 BMSFlowRateGPM lets the BMS supply the system flow for flow-limited control, and AV 17 BMSLimitBoilers caps how many boilers HeatNet may run. AV 3-7 and BV 2 set up outdoor air reset; there is no writable outdoor temperature.
Network setup
- The object document gives no data link, address or device-instance settings.
- To set the clock, write AV 8-14 (month, day, year, hour, minute, second, weekday) and then write 1 to BV 3 SetClock.
Watch out for
- If SetpointTimer runs out, the plant quietly returns to its local setpoint.
- Per-boiler objects are listed at the boiler 1 instance; offset them by boiler number using the formulas in the notes. Boiler 1 is the master or stand-alone boiler.
- Modulation per boiler (AI 128-143) does not work in AA/High Fire, T1 or T2 modes.
- Several points need firmware 2.00 or later.
RBI FIII / Fusion / CK boilers with HeatNet V3 control BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 1 | SetpointTimer | BMS failsafe timer; reload before it counts to zero; 0 – 65535 seconds | s | Write | |
| AVmin | 2 | Setpoint | System setpoint written by the BMS (see SetpointTimer); 40 - 220 °F (4.5 – 104.4 °C) | °F | Write | |
| AV | 3 | OARSetpoint | Outdoor temperature at which the boiler shuts down; 40 – 100 °F (4.5 – 37.8 °C) | °F | Write | |
| AV | 4 | OARHighWaterTemp | Water setpoint at the high outdoor temperature; 60 – 190 °F (15.6 – 87.8 °C) | °F | Write | |
| AV | 5 | OARHighAirTemp | High outdoor air temperature reset point; 50 – 90 °F (10 – 32.2 °C) | °F | Write | |
| AV | 6 | OARLowWaterTemp | Header/supply setpoint at the low outdoor temperature; 70 – 220 °F (21.1 – 104.4 °C) | °F | Write | |
| AV | 7 | OARLowAirTemp | Low outdoor air temperature reset point; -35 – 40 °F (-37.2 – 4.4 °C) | °F | Write | |
| AV | 8 | SetMonth | Clock set value: month (0 = January); 0 (January) – 11 (December) | months | Write | |
| AV | 9 | SetDay | Clock set value: day; 1 – 31 | days | Write | |
| AV | 10 | SetYear | Clock set value: year (0-99); 0 – 99 | years | Write | |
| AV | 11 | SetHour | Clock set value: hour; 0 – 23 | h | Write | |
| AV | 12 | SetMinute | Clock set value: minute; 0 – 59 | min | Write | |
| AV | 13 | SetSecond | Clock set value: second; 0 – 59 | s | Write | |
| AV | 14 | SetWeekday | Clock set value: weekday (0 = Monday); 0 (Monday) – 6 (Sunday) | Write | ||
| AV | 15 | DHWSetpoint | DHW setpoint; 40 – 200 °F (4.4 – 93.3 °C) | °F | Write | |
| AV | 16 | BMSFlowRateGPM | System flow measured by the BMS (flow-limited control); 0 – 1500 | gpm | Write | |
| AV | 17 | BMSLimitBoilers | Number of boilers HeatNet may run (boilers-limited control); 0 – 16 | Write | ||
| BVmin | 1 | HeatDemand | BMS heat demand: 1 puts the boiler plant into heating | Write | 0=No heat demand, 1=Heat demand | |
| BV | 2 | OAResetEnable | Enable outdoor air reset | Write | 0=Disabled, 1=Enabled | |
| BV | 3 | SetClock | Write 1 to load the Set... values into the clock | Write | 1=Set the clock | |
| BV | 1000 | Boiler##_Disabled | Disabled | Read | 0=enabled, 1=disabled | |
| BV | 1001 | Boiler##_LocalOverride | Local Override (member boilers only) | Read | 0=no override, 1=override | |
| BVmin | 1002 | Boiler##_Alarm | Alarm | Read | 0=ok, 1=alarm | |
| BVmin | 1003 | Boiler##_Failed | Failed | Read | 0=ok, 1=failed | |
| BV | 1004 | Boiler##_MemberError | Member Alarm or Failed | Read | 0=ok, 1=error | |
| BVmin | 1005 | Boiler##_Running | Running/firing | Read | 0=off, 1=running (firing) | |
| BV | 1006 | Boiler##_LocalPumpOn | Local pump is on/running | Read | 0=off, 1=on (running) | |
| BV | 1007 | Boiler##_SystemFlowInterlock | System Flow Interlock | Read | 0=open, 1=closed | |
| BV | 1008 | Boiler##_LwcoInterlock | Low Water Cutoff Interlock | Read | 0=open, 1=closed | |
| BV | 1009 | Boiler##_VfdInterlock | VFD Interlock | Read | 0=open, 1=closed | |
| BV | 1010 | Boiler##_GasProveInterlock | Gas Prove Interlock | Read | 0=open, 1=closed | |
| BV | 1011 | Boiler##_Spare4Interlock | Spare 4 (application defined) Interlock | Read | 0=open, 1=closed | |
| BV | 1012 | Boiler##_OperatorInterlock | Operator Interlock | Read | 0=open, 1=closed | |
| BV | 1013 | Boiler##_LocalFlowInterlock | Local Flow Interlock | Read | 0=open, 1=closed | |
| BV | 1015 | Boiler##_MainValve | Main Valve | Read | 0=closed, 1=open | |
| BV | 1016 | Boiler##_PilotValve | Pilot Valve | Read | 0=closed, 1=open | |
| BV | 1017 | Boiler##_BlowerOn | Blower is on/running | Read | 0=off, 1=on (running) | |
| BV | 1018 | Boiler##_IgnitionAlarm | Ignition Circuit Alarm | Read | 0=ok, 1=alarm | |
| BV | 1019 | Boiler##_IRIAlarm | IRI Alarm | Read | 0=ok, 1=alarm | |
| BV | 1020 | Boiler##_HighLimit | High Limit | Read | 0=ok, 1=tripped | |
| BV | 1021 | Boiler##_AirProveSwitch | Air Prove Switch | Read | 0=proven, 1=not proven | |
| BV | 1023 | Boiler##_SoftwareOperator | Software Operator Tripped | Read | 0=not tripped, 1=tripped | |
| BV | 1024 | Boiler##_HeaderSensorNA | Header Sensor not available (detected) | Read | 0=detected, 1=not available | |
| BV | 1025 | Boiler##_SupplySensorNA | Supply/Outlet Sensor not available (detected) | Read | 0=detected, 1=not available | |
| BV | 1026 | Boiler##_ReturnSensorNA | Return/Inlet Sensor not available (detected) | Read | 0=detected, 1=not available | |
| BV | 1027 | Boiler##_OutsideSensorNA | Outside sensor not available (manual text says Header) | Read | 0=detected, 1=not available | |
| BV | 1028 | Boiler##_SystemPumpOn | System Pump is on/running | Read | 0=off, 1=on (running) | |
| BV | 1029 | Boiler##_DamperProve1 | Combustion Air Damper Prove (J10B). (revision 1.x controls only) | Read | 0=not proven, 1=proven | |
| BV | 1030 | Boiler##_Master | This is the Master Boiler | Read | 0=member, 1=master | |
| BV | 1031 | Boiler##_Detected | Detected (present) | Read | 0=not detected, 1=detected | |
| BV | 2000 | Boiler##_AAHighFire | AA/High Fire Input | Read | 0=open, 1=closed | |
| BV | 2001 | Boiler##_HeatDemand | Heat Demand (Local Override) Input | Read | 0=open, 1=closed | |
| BV | 2002 | Boiler##_4to20Remote | 4 to 20ma Remote Input | Read | 0=open, 1=closed | |
| BV | 2003 | Boiler##_OAROverride | Outside Air Reset Override Input | Read | 0=open, 1=closed | |
| BV | 2004 | Boiler##_T1 | T1 Input | Read | 0=open, 1=closed | |
| BV | 2005 | Boiler##_T2 | T2 Input | Read | 0=open, 1=closed | |
| BV | 2006 | Boiler##_T3 | T3 Input | Read | 0=open, 1=closed | |
| BV | 2007 | Boiler##_T4 | T4 Input | Read | 0=open, 1=closed | |
| BV | 3000 | Boiler##_DHWEnabled | DHW enabled status (menus) | Read | 0=disabled, 1=enabled | |
| BV | 3001 | Boiler##_DamperProve2 | Damper Prove (J12B) | Read | 0=open, 1=closed (proven) | |
| BV | 3002 | Boiler##_ServiceFault | Call service fault | Read | 0=ok, 1=fault | |
| BV | 3003 | Boiler##_BlowerFault | Air Switch Blower fault | Read | 0=ok, 1=fault | |
| BV | 3009 | Boiler##_DHWSensorNA | DHW Sensor is not available (detected) | Read | 0=detected, 1=not available | |
| BV | 3010 | Boiler##_DHWBoiler | DHW Boiler | Read | 0=no, 1=yes | |
| BV | 3011 | Boiler##_OpLimitClamp | Input limited (clamped) by high supply temperature | Read | 0=not clamped, 1=clamped | |
| BV | 3012 | Boiler01_BoilersFlowLimited | Boilers limited by the BMS flow rate value | Read | 0=not limited, 1=limited | |
| BV | 3013 | Boiler01_BoilersBMSLimited | Boilers limited by the BMS limit-boilers value | Read | 0=not limited, 1=limited | |
| BV | 3014 | Boiler##_StackSensorNA | Stack Sensor is not available (detected) (firmware 2.00+) | Read | 0=detected, 1=not available | |
| BV | 3015 | Boiler##_SysReturnSensorNA | System Return Sensor is not available (detected) (firmware 2.00+) | Read | 0=detected, 1=not available | |
| AImin | 1 | BoilersOn | Boilers currently running | Read | ||
| AImin | 2 | Modulation | System target modulation level | % | Read | |
| AImin | 3 | HeaderTemp | Header / system temperature | °F | Read | |
| AI | 4 | SupplyTemp | Supply temperature | °F | Read | |
| AI | 5 | ReturnTemp | Return temperature | °F | Read | |
| AI | 6 | OutsideTemp | Outside air temperature | °F | Read | |
| AI | 7 | Spare1 | Raw A/D value, spare input 1 | Read | ||
| AI | 8 | Spare2 | Raw A/D value, spare input 2 | Read | ||
| AI | 9 | Month | Clock month (0 = January) | months | Read | |
| AI | 10 | Day | Clock day | days | Read | |
| AI | 11 | Year | Clock year (0-99) | years | Read | |
| AI | 12 | Hour | Clock hour | h | Read | |
| AI | 13 | Minute | Clock minute | min | Read | |
| AI | 14 | Second | Clock second | s | Read | |
| AI | 15 | Weekday | Clock weekday (0 = Monday) | Read | ||
| AI | 16 | DHWTemp | DHW temperature | °F | Read | |
| AI | 48 | Boiler01_Runtime | Boiler 1 run time with the current control board | min | Read | |
| AI | 64 | Boiler01_Cycles | Boiler 1 cycles with the current control board | Read | ||
| AI | 80 | Boiler01_SupplyTemp | Boiler 1 supply (outlet) temperature | °F | Read | |
| AI | 96 | Boiler01_ReturnTemp | Boiler 1 return (inlet) temperature | °F | Read | |
| AI | 112 | Boiler01_DHWTemp | Boiler 1 DHW sensor temperature | °F | Read | |
| AI | 128 | Boiler01_Modulation | Boiler 1 modulation (not in AA/High Fire, T1 or T2 modes) | % | Read | |
| AImin | 144 | OperatingSetpoint | Active setpoint: normal, DHW, outdoor reset or 4-20 mA | °F | Read | |
| AI | 145 | AvailableBoilers | Boilers available | Read | ||
| AI | 146 | BTUH | Estimated plant output (firmware 2.00+) | BTU/h | Read | |
| AI | 147 | SystemReturnTemp | System return temperature, if fitted (firmware 2.00+) | °F | Read | |
| AI | 148 | SystemFlow | System flow: meter reading or BMSFlowRateGPM (firmware 2.00+) | gpm | Read | |
| AI | 149 | HeatingBoilersOn | Boilers running for heating (firmware 2.00+) | Read | ||
| AI | 150 | DHWBoilersOn | Boilers running for DHW (firmware 2.00+) | Read | ||
| AI | 151 | ManualBoilersOn | Boilers running on local override, T1, T2, AA (firmware 2.00+) | Read |
No points match these filters.
Integration notes
- The object list does not say which BACnet data link (BACnet IP or BACnet MS/TP) is used and gives no device instance or network settings.
- Per-boiler binary values are printed once as Boiler##_<name> with an instance formula; they are listed here at the boiler 1 instance. Boiler n = 1000-series base + (n - 1) x 32, or 2000/3000-series base + (n - 1) x 16. Boiler 1 is the master or stand-alone (BACnet-connected) boiler; members are 2-16.
- Per-boiler analog inputs are printed as ranges and listed here for boiler 1 only: Boiler01-16_Runtime AI 48-63, _Cycles AI 64-79, _SupplyTemp AI 80-95, _ReturnTemp AI 96-111, _DHWTemp AI 112-127, _Modulation AI 128-143 (boiler n = boiler 1 instance + n - 1).
- No objects are printed at BV 1014, BV 1022 or BV 3004-3008.
- The manual describes Boiler##_OutsideSensorNA as 'Header Sensor not available', the same text as HeaderSensorNA; the name suggests the outside sensor.
- Temperatures are in °F.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FIII / Fusion / CK boilers with HeatNet V3 control and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the RBI FIII / Fusion / CK boilers with HeatNet V3 control
How many BACnet points does the RBI FIII / Fusion / CK boilers with HeatNet V3 control have?
This list has 99 BACnet objects: 30 analog inputs, 17 analog values, 52 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which RBI FIII / Fusion / CK boilers with HeatNet V3 control BACnet points are writable?
20 of the 99 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official RBI FIII / Fusion / CK boilers with HeatNet V3 control BACnet documentation?
The source is RBI FIII/Fusion/CK Series Boiler - HeatNet V3 BACnet Objects (V1.00), published free by RBI at https://www.literature.mestek.com/dms/RBI%20Water%20Heaters/RBI%20V3%20BACnet%20Objects%20v1.00.pdf.
What are the minimum BACnet points to integrate the RBI FIII / Fusion / CK boilers with HeatNet V3 control?
Start with BV 1 HeatDemand (Heat demand from the BMS (1 = heat)); AV 2 Setpoint (System setpoint, 40-220 °F); AV 1 SetpointTimer (Failsafe countdown; reload before it reaches 0); AI 144 OperatingSetpoint (Active setpoint in use); AI 3 HeaderTemp (Header / system temperature, °F); AI 1 BoilersOn (Number of boilers running); AI 2 Modulation (System target modulation, %); BV 1005 Boiler##_Running (Boiler 1 firing (add 32 per boiler number)); BV 1002 Boiler##_Alarm (Boiler 1 alarm (add 32 per boiler number)); BV 1003 Boiler##_Failed (Boiler 1 failed (add 32 per boiler number)).
How do I enable BMS control of the RBI FIII / Fusion / CK boilers with HeatNet V3 control?
BV 1 HeatDemand puts the boiler (plant) into heating mode when set to 1; 0 removes the demand. The setpoint the BMS writes is AV 2 Setpoint.
Does the RBI FIII / Fusion / CK boilers with HeatNet V3 control need a BACnet heartbeat or have a communication timeout?
AV 1 SetpointTimer (0-65535 s) is a BMS failsafe countdown. The BMS must reload it periodically; if it reaches zero the control assumes the BMS has stopped and reloads its own saved local setpoint. Writing any read/write variable reloads the timer to 60 s if it is below 60 (on firmware below 3.48 only writing the setpoint does this).
Can the BMS supply sensor values to the RBI FIII / Fusion / CK boilers with HeatNet V3 control?
AV 16 BMSFlowRateGPM lets the BMS supply the system flow for flow-limited control, and AV 17 BMSLimitBoilers caps how many boilers HeatNet may run. AV 3-7 and BV 2 set up outdoor air reset; there is no writable outdoor temperature.
How do I check these points on the real FIII / Fusion / CK boilers with HeatNet V3 control?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: RBI FIII/Fusion/CK Series Boiler - HeatNet V3 BACnet Objects · V1.00. Object names, instances and units are reproduced as published; descriptions are our own.