 "manufacturer": "RBI",
 "manufacturer_slug": "rbi",
 "model": "FIII / Fusion / CK boilers with HeatNet V3 control",
 "model_slug": "heatnet-v3-fiii-fusion-ck",
 "aliases": [
  "HeatNet V3",
  "HeatNet",
  "Futera III",
  "FIII",
  "Futera Fusion",
  "Fusion",
  "CK Series",
  "Mestek",
  "RBI V3 BACnet Objects"
 ],
 "equipment_type": "Commercial boiler controller",
 "applies_to": "RBI (Mestek) Futera III, Fusion and CK Series boilers with a HeatNet V3 control board, including HeatNet cascades of up to 16 boilers.",
 "summary": "The HeatNet V3 control on RBI FIII, Fusion and CK boilers exposes a fixed BACnet object list. The BMS writes heat demand, the system setpoint (guarded by a countdown failsafe timer), outdoor-reset settings, DHW setpoint, clock and flow/boiler limits as analog and binary values. Read-only analog inputs give plant temperatures, counts and per-boiler run time, cycles, temperatures and modulation, and read-only binary values give interlock, alarm and status flags for each of up to 16 boilers.",
 "bacnet_transport": [],
 "firmware": "HeatNet V3; BTUH, system return/flow and boiler-count points need firmware 2.00 or later",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "The object list does not say which BACnet data link (BACnet IP or BACnet MS/TP) is used and gives no device instance or network settings.",
  "Per-boiler binary values are printed once as Boiler##_<name> with an instance formula; they are listed here at the boiler 1 instance. Boiler n = 1000-series base + (n - 1) x 32, or 2000/3000-series base + (n - 1) x 16. Boiler 1 is the master or stand-alone (BACnet-connected) boiler; members are 2-16.",
  "Per-boiler analog inputs are printed as ranges and listed here for boiler 1 only: Boiler01-16_Runtime AI 48-63, _Cycles AI 64-79, _SupplyTemp AI 80-95, _ReturnTemp AI 96-111, _DHWTemp AI 112-127, _Modulation AI 128-143 (boiler n = boiler 1 instance + n - 1).",
  "No objects are printed at BV 1014, BV 1022 or BV 3004-3008.",
  "The manual describes Boiler##_OutsideSensorNA as 'Header Sensor not available', the same text as HeaderSensorNA; the name suggests the outside sensor.",
  "Temperatures are in °F."
 ],
 "source": {
  "title": "RBI FIII/Fusion/CK Series Boiler - HeatNet V3 BACnet Objects",
  "doc_number": "V1.00",
  "revision_date": null,
  "url": "https://www.literature.mestek.com/dms/RBI%20Water%20Heaters/RBI%20V3%20BACnet%20Objects%20v1.00.pdf"
 },
 "integration": {
  "summary": "Connect the BMS to the master (boiler 1) HeatNet board. Write BV 1 HeatDemand to call for heat and AV 2 Setpoint for the system setpoint, and keep reloading AV 1 SetpointTimer so the plant does not fall back to its local setpoint. Read header/supply/return temperatures, boilers on, modulation and the per-boiler alarm and failed flags.",
  "minimum_points": [
   {
    "ref": "BV 1",
    "name": "HeatDemand",
    "why": "Heat demand from the BMS (1 = heat)"
   },
   {
    "ref": "AV 2",
    "name": "Setpoint",
    "why": "System setpoint, 40-220 °F"
   },
   {
    "ref": "AV 1",
    "name": "SetpointTimer",
    "why": "Failsafe countdown; reload before it reaches 0"
   },
   {
    "ref": "AI 144",
    "name": "OperatingSetpoint",
    "why": "Active setpoint in use"
   },
   {
    "ref": "AI 3",
    "name": "HeaderTemp",
    "why": "Header / system temperature, °F"
   },
   {
    "ref": "AI 1",
    "name": "BoilersOn",
    "why": "Number of boilers running"
   },
   {
    "ref": "AI 2",
    "name": "Modulation",
    "why": "System target modulation, %"
   },
   {
    "ref": "BV 1005",
    "name": "Boiler##_Running",
    "why": "Boiler 1 firing (add 32 per boiler number)"
   },
   {
    "ref": "BV 1002",
    "name": "Boiler##_Alarm",
    "why": "Boiler 1 alarm (add 32 per boiler number)"
   },
   {
    "ref": "BV 1003",
    "name": "Boiler##_Failed",
    "why": "Boiler 1 failed (add 32 per boiler number)"
   }
  ],
  "enable": "BV 1 HeatDemand puts the boiler (plant) into heating mode when set to 1; 0 removes the demand. The setpoint the BMS writes is AV 2 Setpoint.",
  "heartbeat": "AV 1 SetpointTimer (0-65535 s) is a BMS failsafe countdown. The BMS must reload it periodically; if it reaches zero the control assumes the BMS has stopped and reloads its own saved local setpoint. Writing any read/write variable reloads the timer to 60 s if it is below 60 (on firmware below 3.48 only writing the setpoint does this).",
  "remote_sensors": "AV 16 BMSFlowRateGPM lets the BMS supply the system flow for flow-limited control, and AV 17 BMSLimitBoilers caps how many boilers HeatNet may run. AV 3-7 and BV 2 set up outdoor air reset; there is no writable outdoor temperature.",
  "setup": [
   "The object document gives no data link, address or device-instance settings.",
   "To set the clock, write AV 8-14 (month, day, year, hour, minute, second, weekday) and then write 1 to BV 3 SetClock."
  ],
  "gotchas": [
   "If SetpointTimer runs out, the plant quietly returns to its local setpoint.",
   "Per-boiler objects are listed at the boiler 1 instance; offset them by boiler number using the formulas in the notes. Boiler 1 is the master or stand-alone boiler.",
   "Modulation per boiler (AI 128-143) does not work in AA/High Fire, T1 or T2 modes.",
   "Several points need firmware 2.00 or later."
  ]
 },
 "points": [
  {
   "type": "AV",
   "instance": 1,
   "name": "SetpointTimer",
   "description": "BMS failsafe timer; reload before it counts to zero; 0 – 65535 seconds",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Setpoint",
   "description": "System setpoint written by the BMS (see SetpointTimer); 40 - 220 °F (4.5 – 104.4 °C)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "OARSetpoint",
   "description": "Outdoor temperature at which the boiler shuts down; 40 – 100 °F (4.5 – 37.8 °C)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "OARHighWaterTemp",
   "description": "Water setpoint at the high outdoor temperature; 60 – 190 °F (15.6 – 87.8 °C)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "OARHighAirTemp",
   "description": "High outdoor air temperature reset point; 50 – 90 °F (10 – 32.2 °C)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "OARLowWaterTemp",
   "description": "Header/supply setpoint at the low outdoor temperature; 70 – 220 °F (21.1 – 104.4 °C)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "OARLowAirTemp",
   "description": "Low outdoor air temperature reset point; -35 – 40 °F (-37.2 – 4.4 °C)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "SetMonth",
   "description": "Clock set value: month (0 = January); 0 (January) – 11 (December)",
   "units": "months",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "SetDay",
   "description": "Clock set value: day; 1 – 31",
   "units": "days",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "SetYear",
   "description": "Clock set value: year (0-99); 0 – 99",
   "units": "years",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "SetHour",
   "description": "Clock set value: hour; 0 – 23",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "SetMinute",
   "description": "Clock set value: minute; 0 – 59",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "SetSecond",
   "description": "Clock set value: second; 0 – 59",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "SetWeekday",
   "description": "Clock set value: weekday (0 = Monday); 0 (Monday) – 6 (Sunday)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "DHWSetpoint",
   "description": "DHW setpoint; 40 – 200 °F (4.4 – 93.3 °C)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "BMSFlowRateGPM",
   "description": "System flow measured by the BMS (flow-limited control); 0 – 1500",
   "units": "gpm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "BMSLimitBoilers",
   "description": "Number of boilers HeatNet may run (boilers-limited control); 0 – 16",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "HeatDemand",
   "description": "BMS heat demand: 1 puts the boiler plant into heating",
   "units": "",
   "access": "W",
   "states": "0=No heat demand, 1=Heat demand"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "OAResetEnable",
   "description": "Enable outdoor air reset",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "SetClock",
   "description": "Write 1 to load the Set... values into the clock",
   "units": "",
   "access": "W",
   "states": "1=Set the clock"
  },
  {
   "type": "BV",
   "instance": 1000,
   "name": "Boiler##_Disabled",
   "description": "Disabled",
   "units": "",
   "access": "R",
   "states": "0=enabled, 1=disabled"
  },
  {
   "type": "BV",
   "instance": 1001,
   "name": "Boiler##_LocalOverride",
   "description": "Local Override (member boilers only)",
   "units": "",
   "access": "R",
   "states": "0=no override, 1=override"
  },
  {
   "type": "BV",
   "instance": 1002,
   "name": "Boiler##_Alarm",
   "description": "Alarm",
   "units": "",
   "access": "R",
   "states": "0=ok, 1=alarm"
  },
  {
   "type": "BV",
   "instance": 1003,
   "name": "Boiler##_Failed",
   "description": "Failed",
   "units": "",
   "access": "R",
   "states": "0=ok, 1=failed"
  },
  {
   "type": "BV",
   "instance": 1004,
   "name": "Boiler##_MemberError",
   "description": "Member Alarm or Failed",
   "units": "",
   "access": "R",
   "states": "0=ok, 1=error"
  },
  {
   "type": "BV",
   "instance": 1005,
   "name": "Boiler##_Running",
   "description": "Running/firing",
   "units": "",
   "access": "R",
   "states": "0=off, 1=running (firing)"
  },
  {
   "type": "BV",
   "instance": 1006,
   "name": "Boiler##_LocalPumpOn",
   "description": "Local pump is on/running",
   "units": "",
   "access": "R",
   "states": "0=off, 1=on (running)"
  },
  {
   "type": "BV",
   "instance": 1007,
   "name": "Boiler##_SystemFlowInterlock",
   "description": "System Flow Interlock",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 1008,
   "name": "Boiler##_LwcoInterlock",
   "description": "Low Water Cutoff Interlock",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 1009,
   "name": "Boiler##_VfdInterlock",
   "description": "VFD Interlock",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 1010,
   "name": "Boiler##_GasProveInterlock",
   "description": "Gas Prove Interlock",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 1011,
   "name": "Boiler##_Spare4Interlock",
   "description": "Spare 4 (application defined) Interlock",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 1012,
   "name": "Boiler##_OperatorInterlock",
   "description": "Operator Interlock",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 1013,
   "name": "Boiler##_LocalFlowInterlock",
   "description": "Local Flow Interlock",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 1015,
   "name": "Boiler##_MainValve",
   "description": "Main Valve",
   "units": "",
   "access": "R",
   "states": "0=closed, 1=open"
  },
  {
   "type": "BV",
   "instance": 1016,
   "name": "Boiler##_PilotValve",
   "description": "Pilot Valve",
   "units": "",
   "access": "R",
   "states": "0=closed, 1=open"
  },
  {
   "type": "BV",
   "instance": 1017,
   "name": "Boiler##_BlowerOn",
   "description": "Blower is on/running",
   "units": "",
   "access": "R",
   "states": "0=off, 1=on (running)"
  },
  {
   "type": "BV",
   "instance": 1018,
   "name": "Boiler##_IgnitionAlarm",
   "description": "Ignition Circuit Alarm",
   "units": "",
   "access": "R",
   "states": "0=ok, 1=alarm"
  },
  {
   "type": "BV",
   "instance": 1019,
   "name": "Boiler##_IRIAlarm",
   "description": "IRI Alarm",
   "units": "",
   "access": "R",
   "states": "0=ok, 1=alarm"
  },
  {
   "type": "BV",
   "instance": 1020,
   "name": "Boiler##_HighLimit",
   "description": "High Limit",
   "units": "",
   "access": "R",
   "states": "0=ok, 1=tripped"
  },
  {
   "type": "BV",
   "instance": 1021,
   "name": "Boiler##_AirProveSwitch",
   "description": "Air Prove Switch",
   "units": "",
   "access": "R",
   "states": "0=proven, 1=not proven"
  },
  {
   "type": "BV",
   "instance": 1023,
   "name": "Boiler##_SoftwareOperator",
   "description": "Software Operator Tripped",
   "units": "",
   "access": "R",
   "states": "0=not tripped, 1=tripped"
  },
  {
   "type": "BV",
   "instance": 1024,
   "name": "Boiler##_HeaderSensorNA",
   "description": "Header Sensor not available (detected)",
   "units": "",
   "access": "R",
   "states": "0=detected, 1=not available"
  },
  {
   "type": "BV",
   "instance": 1025,
   "name": "Boiler##_SupplySensorNA",
   "description": "Supply/Outlet Sensor not available (detected)",
   "units": "",
   "access": "R",
   "states": "0=detected, 1=not available"
  },
  {
   "type": "BV",
   "instance": 1026,
   "name": "Boiler##_ReturnSensorNA",
   "description": "Return/Inlet Sensor not available (detected)",
   "units": "",
   "access": "R",
   "states": "0=detected, 1=not available"
  },
  {
   "type": "BV",
   "instance": 1027,
   "name": "Boiler##_OutsideSensorNA",
   "description": "Outside sensor not available (manual text says Header)",
   "units": "",
   "access": "R",
   "states": "0=detected, 1=not available"
  },
  {
   "type": "BV",
   "instance": 1028,
   "name": "Boiler##_SystemPumpOn",
   "description": "System Pump is on/running",
   "units": "",
   "access": "R",
   "states": "0=off, 1=on (running)"
  },
  {
   "type": "BV",
   "instance": 1029,
   "name": "Boiler##_DamperProve1",
   "description": "Combustion Air Damper Prove (J10B). (revision 1.x controls only)",
   "units": "",
   "access": "R",
   "states": "0=not proven, 1=proven"
  },
  {
   "type": "BV",
   "instance": 1030,
   "name": "Boiler##_Master",
   "description": "This is the Master Boiler",
   "units": "",
   "access": "R",
   "states": "0=member, 1=master"
  },
  {
   "type": "BV",
   "instance": 1031,
   "name": "Boiler##_Detected",
   "description": "Detected (present)",
   "units": "",
   "access": "R",
   "states": "0=not detected, 1=detected"
  },
  {
   "type": "BV",
   "instance": 2000,
   "name": "Boiler##_AAHighFire",
   "description": "AA/High Fire Input",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 2001,
   "name": "Boiler##_HeatDemand",
   "description": "Heat Demand (Local Override) Input",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 2002,
   "name": "Boiler##_4to20Remote",
   "description": "4 to 20ma Remote Input",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 2003,
   "name": "Boiler##_OAROverride",
   "description": "Outside Air Reset Override Input",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 2004,
   "name": "Boiler##_T1",
   "description": "T1 Input",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 2005,
   "name": "Boiler##_T2",
   "description": "T2 Input",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 2006,
   "name": "Boiler##_T3",
   "description": "T3 Input",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 2007,
   "name": "Boiler##_T4",
   "description": "T4 Input",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed"
  },
  {
   "type": "BV",
   "instance": 3000,
   "name": "Boiler##_DHWEnabled",
   "description": "DHW enabled status (menus)",
   "units": "",
   "access": "R",
   "states": "0=disabled, 1=enabled"
  },
  {
   "type": "BV",
   "instance": 3001,
   "name": "Boiler##_DamperProve2",
   "description": "Damper Prove (J12B)",
   "units": "",
   "access": "R",
   "states": "0=open, 1=closed (proven)"
  },
  {
   "type": "BV",
   "instance": 3002,
   "name": "Boiler##_ServiceFault",
   "description": "Call service fault",
   "units": "",
   "access": "R",
   "states": "0=ok, 1=fault"
  },
  {
   "type": "BV",
   "instance": 3003,
   "name": "Boiler##_BlowerFault",
   "description": "Air Switch Blower fault",
   "units": "",
   "access": "R",
   "states": "0=ok, 1=fault"
  },
  {
   "type": "BV",
   "instance": 3009,
   "name": "Boiler##_DHWSensorNA",
   "description": "DHW Sensor is not available (detected)",
   "units": "",
   "access": "R",
   "states": "0=detected, 1=not available"
  },
  {
   "type": "BV",
   "instance": 3010,
   "name": "Boiler##_DHWBoiler",
   "description": "DHW Boiler",
   "units": "",
   "access": "R",
   "states": "0=no, 1=yes"
  },
  {
   "type": "BV",
   "instance": 3011,
   "name": "Boiler##_OpLimitClamp",
   "description": "Input limited (clamped) by high supply temperature",
   "units": "",
   "access": "R",
   "states": "0=not clamped, 1=clamped"
  },
  {
   "type": "BV",
   "instance": 3012,
   "name": "Boiler01_BoilersFlowLimited",
   "description": "Boilers limited by the BMS flow rate value",
   "units": "",
   "access": "R",
   "states": "0=not limited, 1=limited"
  },
  {
   "type": "BV",
   "instance": 3013,
   "name": "Boiler01_BoilersBMSLimited",
   "description": "Boilers limited by the BMS limit-boilers value",
   "units": "",
   "access": "R",
   "states": "0=not limited, 1=limited"
  },
  {
   "type": "BV",
   "instance": 3014,
   "name": "Boiler##_StackSensorNA",
   "description": "Stack Sensor is not available (detected) (firmware 2.00+)",
   "units": "",
   "access": "R",
   "states": "0=detected, 1=not available"
  },
  {
   "type": "BV",
   "instance": 3015,
   "name": "Boiler##_SysReturnSensorNA",
   "description": "System Return Sensor is not available (detected) (firmware 2.00+)",
   "units": "",
   "access": "R",
   "states": "0=detected, 1=not available"
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "BoilersOn",
   "description": "Boilers currently running",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Modulation",
   "description": "System target modulation level",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "HeaderTemp",
   "description": "Header / system temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "SupplyTemp",
   "description": "Supply temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "ReturnTemp",
   "description": "Return temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "OutsideTemp",
   "description": "Outside air temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Spare1",
   "description": "Raw A/D value, spare input 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Spare2",
   "description": "Raw A/D value, spare input 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Month",
   "description": "Clock month (0 = January)",
   "units": "months",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Day",
   "description": "Clock day",
   "units": "days",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Year",
   "description": "Clock year (0-99)",
   "units": "years",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "Hour",
   "description": "Clock hour",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Minute",
   "description": "Clock minute",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "Second",
   "description": "Clock second",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Weekday",
   "description": "Clock weekday (0 = Monday)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "DHWTemp",
   "description": "DHW temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "Boiler01_Runtime",
   "description": "Boiler 1 run time with the current control board",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "Boiler01_Cycles",
   "description": "Boiler 1 cycles with the current control board",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 80,
   "name": "Boiler01_SupplyTemp",
   "description": "Boiler 1 supply (outlet) temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 96,
   "name": "Boiler01_ReturnTemp",
   "description": "Boiler 1 return (inlet) temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 112,
   "name": "Boiler01_DHWTemp",
   "description": "Boiler 1 DHW sensor temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 128,
   "name": "Boiler01_Modulation",
   "description": "Boiler 1 modulation (not in AA/High Fire, T1 or T2 modes)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 144,
   "name": "OperatingSetpoint",
   "description": "Active setpoint: normal, DHW, outdoor reset or 4-20 mA",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 145,
   "name": "AvailableBoilers",
   "description": "Boilers available",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 146,
   "name": "BTUH",
   "description": "Estimated plant output (firmware 2.00+)",
   "units": "BTU/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 147,
   "name": "SystemReturnTemp",
   "description": "System return temperature, if fitted (firmware 2.00+)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 148,
   "name": "SystemFlow",
   "description": "System flow: meter reading or BMSFlowRateGPM (firmware 2.00+)",
   "units": "gpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 149,
   "name": "HeatingBoilersOn",
   "description": "Boilers running for heating (firmware 2.00+)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 150,
   "name": "DHWBoilersOn",
   "description": "Boilers running for DHW (firmware 2.00+)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 151,
   "name": "ManualBoilersOn",
   "description": "Boilers running on local override, T1, T2, AA (firmware 2.00+)",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/rbi/heatnet-v3-fiii-fusion-ck",