Easy BACnet
  1. Home
  2. BACnet points lists
  3. Patterson-Kelley
  4. LOVE controller (ProtoNode FPC-N34/N35)

Boiler controller gateway · BACnet points list

Patterson-Kelley LOVE controller (ProtoNode FPC-N34/N35) BACnet points list

Updated 6 November 2026

Short answer

The ProtoNode maps the LOVE temperature (PID) controller used on Patterson-Kelley equipment to 40 objects: process value, setpoint and range, PID tuning, output limits, alarm types and limits, lock and write-in status, run/stop commands and error flags.

This page lists 40 BACnet objects for the Patterson-Kelley LOVE controller (ProtoNode FPC-N34/N35) — 25 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Patterson-Kelley’s own free documentation, linked below.

Manufacturer
Patterson-Kelley
Model
LOVE controller (ProtoNode FPC-N34/N35)
Equipment
Boiler controller gateway
Equipment type
Boilers & water heaters
BACnet objects
40 (25 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
LOVE, P-K LOVE, Patterson-Kelley LOVE, ProtoNode FPC-N34
Source document
ProtoNode FPC-N34 and FPC-N35 Startup Guide For Interfacing Products: ENVI, LOVE, NURO, Appendix B.2 LOVE · Document Revision 14.B · rev. 2016-04 (effective date)
Download CSV 40 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Patterson-Kelley’s current documentation and the live device before use. Not official Patterson-Kelley information. Terms of use.

BMS integration notes: Patterson-Kelley LOVE controller (ProtoNode FPC-N34/N35)

Integration in brief

Use Control RUN/STOP (BV 27) and the Setpoint (AV 2). Read the process value and output value, and watch the error objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 27Control RUN/STOP SettingControl run command: 0 = STOP, 1 = RUNWrite
AV 2SetpointTemperature setpointWrite
AI 25Communication Write-in SelectionComms write-in must be 1 = enabled to writeRead
AI 1Process ValueProcess value (measured temperature)Read
AV 9Output ValueControl output valueWrite
AI 33Input Sensor Did Not ConnectInput sensor not connectedRead

Enable & remote start

BV 27 Control RUN/STOP Setting (0 = STOP, 1 = RUN) and AV 2 Setpoint. AI 25 Communication Write-in Selection must read 1 (enabled) for network writes; AV 24 Setting Lock Status can lock settings.

Network setup

Watch out for

Patterson-Kelley LOVE controller (ProtoNode FPC-N34/N35) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

40 of 40 shown
Type
Binary
Access
Show
Patterson-Kelley LOVE controller (ProtoNode FPC-N34/N35) BACnet Points List
DescriptionStates
AImin1Process ValueProcess value (temperature); error codes 8002H-8007HRead
AVmin2SetpointTemperature setpointWrite
AI3Upper-Limit of Temp RangeRead
AI4Lower-Limit of Temp RangeRead
AV5Control MethodWrite0=PID, 1=On/Off, 2=manual tuning, 3=PID program control
AV6PB Proportional BandWrite
AV7Ti Integral TimeWrite
AV8Td Derivative TimeWrite
AVmin9Output ValueControl output valueWrite
AV10Upper-Limit RegulationWrite
AV11Lower-Limit RegulationWrite
AV12Analog Decimal SettingWrite
AV13PID Parameter SelectionWrite
AV14SV ValueWrite
AV15Alarm 1 TypeWrite
AV16Alarm 2 TypeWrite
AV17Alarm 3 TypeWrite
AV18Upper-Limit Alarm 1Write
AV19Lower-Limit Alarm 1Write
AV20Upper-Limit Alarm 2Write
AV21Lower-Limit Alarm 2Write
AV22Upper-Limit Alarm 3Write
AV23Lower-Limit Alarm 3Write
AV24Setting Lock StatusWrite0=normal, 1=all setting lock, 11=lock others than SV value
AImin25Communication Write-in SelectionRead0=disabled, 1=enabled
BV26Temp Unit Display SelectionWrite0=°F, 1=°C
BVmin27Control RUN/STOP SettingWrite0=STOP, 1=RUN
BV28STOP Setting for PIDWrite0=RUN, 1=STOP
BV29Temp STOP for PIDWrite0=RUN, 1=temporary STOP
AI30PV UnstableRead
AI31Re-initializeRead
AI32PV Value for Error 0002HRead
AImin33Input Sensor Did Not ConnectRead
AI34PV Value for error 0003HRead
AI35Input Signal ErrorRead
AI36PV Value for Error 0004HRead
AI37Over Input RangeRead
AI38ADC FailRead
AI39PV Value for Error 0006HRead
AI40EEPROM Read/Write errorRead
Object ID lookup: Patterson-Kelley LOVE controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the LOVE controller (ProtoNode FPC-N34/N35) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Patterson-Kelley LOVE controller (ProtoNode FPC-N34/N35)

How many BACnet points does the Patterson-Kelley LOVE controller (ProtoNode FPC-N34/N35) have?

This list has 40 BACnet objects: 15 analog inputs, 21 analog values, 4 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Patterson-Kelley LOVE controller (ProtoNode FPC-N34/N35) BACnet points are writable?

25 of the 40 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Patterson-Kelley LOVE controller (ProtoNode FPC-N34/N35) BACnet documentation?

The source is ProtoNode FPC-N34 and FPC-N35 Startup Guide For Interfacing Products: ENVI, LOVE, NURO, Appendix B.2 LOVE (Document Revision 14.B), revision 2016-04 (effective date), published free by Patterson-Kelley at https://www.weil-mclain.com/wp-content/uploads/Nuro-Controller-ProtoNode-Startup-Guide_1.pdf.

What are the minimum BACnet points to integrate the Patterson-Kelley LOVE controller (ProtoNode FPC-N34/N35)?

Start with BV 27 Control RUN/STOP Setting (Control run command: 0 = STOP, 1 = RUN); AV 2 Setpoint (Temperature setpoint); AI 25 Communication Write-in Selection (Comms write-in must be 1 = enabled to write); AI 1 Process Value (Process value (measured temperature)); AV 9 Output Value (Control output value); AI 33 Input Sensor Did Not Connect (Input sensor not connected).

How do I enable BMS control of the Patterson-Kelley LOVE controller (ProtoNode FPC-N34/N35)?

BV 27 Control RUN/STOP Setting (0 = STOP, 1 = RUN) and AV 2 Setpoint. AI 25 Communication Write-in Selection must read 1 (enabled) for network writes; AV 24 Setting Lock Status can lock settings.

How do I check these points on the real LOVE controller (ProtoNode FPC-N34/N35)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Patterson-Kelley BACnet points lists

Source: ProtoNode FPC-N34 and FPC-N35 Startup Guide For Interfacing Products: ENVI, LOVE, NURO, Appendix B.2 LOVE · Document Revision 14.B · rev. 2016-04 (effective date). Object names, instances and units are reproduced as published; descriptions are our own.