Easy BACnet
  1. Home
  2. BACnet points lists
  3. Patterson-Kelley
  4. ENVI boiler control (ProtoNode FPC-N34/N35)

Boiler controller gateway · BACnet points list

Patterson-Kelley ENVI boiler control (ProtoNode FPC-N34/N35) BACnet points list

Updated 6 November 2026

Short answer

The ProtoNode maps the Patterson-Kelley ENVI boiler control to 53 objects: state, temperatures, firing rate, flame signal, error code, counters, safety input states and a second block of "ET" values, plus writable CH/DHW setpoints, boiler operation and outdoor reset settings.

This page lists 53 BACnet objects for the Patterson-Kelley ENVI boiler control (ProtoNode FPC-N34/N35) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Patterson-Kelley’s own free documentation, linked below.

Manufacturer
Patterson-Kelley
Model
ENVI boiler control (ProtoNode FPC-N34/N35)
Equipment
Boiler controller gateway
Equipment type
Boilers & water heaters
BACnet objects
53 (9 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
ENVI, P-K ENVI, Patterson-Kelley ENVI, ProtoNode FPC-N34
Source document
ProtoNode FPC-N34 and FPC-N35 Startup Guide For Interfacing Products: ENVI, LOVE, NURO, Appendix B.1 ENVI · Document Revision 14.B · rev. 2016-04 (effective date)
Download CSV 53 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Patterson-Kelley’s current documentation and the live device before use. Not official Patterson-Kelley information. Terms of use.

BMS integration notes: Patterson-Kelley ENVI boiler control (ProtoNode FPC-N34/N35)

Integration in brief

Run the boiler with Boiler Operation (AV 13) and send CH and DHW setpoints (AV 11/12). Read State, supply and return temperatures, firing rate, flame signal and the error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 13Boiler Operation0 off, 1 on/pump auto, 2 off/pump on, 3 on/pump onWrite
AV 11CH SetpointCentral heating setpointWrite
AV 12DHW SetpointDHW setpointWrite
AI 1StateBurner state; 9 = burning, 16-17 and 19-21 = errorsRead
AI 2Supply TempSupply water temperatureRead
AI 6Firing RateFiring rateRead
AI 10Flame SignalFlame signal; 128 = flameRead
AI 20Error CodeError code; see the manual notesRead

Enable & remote start

AV 13 Boiler Operation: 0 = boiler off & pump off, 1 = boiler on & pump auto, 2 = boiler off & pump on, 3 = boiler on & pump on. AV 11/12 are the CH and DHW setpoints; AV 14-19 set the outdoor reset curve and night setback.

Network setup

Watch out for

Patterson-Kelley ENVI boiler control (ProtoNode FPC-N34/N35) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

53 of 53 shown
Type
Binary
Access
Show
Patterson-Kelley ENVI boiler control (ProtoNode FPC-N34/N35) BACnet Points List
DescriptionStates
AImin1StateBurner state codeRead1=resetting, 2=standby, 3-4=relay circuit check, 5-6=pre-purging, 7=pre-ignition, 8=ignition, 9=burning, 10-11=post purging, 12=post pumping CH, 13=pumping CH, 14=post pumping DHW, 15=pumping DHW, 16=locking, 17=blocking, 18=restarting, 19-21=error handling
AImin2Supply TempRead
AI3Return TempRead
AI4DHW TempRead
AI5Header TempRead
AImin6Firing RateFiring rateRead
AI7Flue Gas TempRead
AI8HX TempRead
AI9Outside TempRead
AImin10Flame SignalFlame signal codeRead0=no flame, 128=flame
AVmin11CH SetpointWrite
AVmin12DHW SetpointWrite
AVmin13Boiler OperationWrite0=boiler off & pump off, 1=boiler on & pump auto, 2=boiler off & pump on, 3=boiler on & pump on
AV14High Outdoor Air TempWrite
AV15Min Outdoor Air SetpointWrite
AV16Low Outdoor Air TempWrite
AV17Max Outdoor Air SetpointWrite
AV18Outdoor Air Shutdown TempWrite
AV19Night SetbackWrite
AImin20Error CodeError code; see the manual notesRead
AI21Analog InRead
AI22Analog OutRead
AI23IgnitionsRead
AI24Burner High HoursRead
AI25Burner Medium HoursRead
AI26Burner Low HoursRead
BI27Water LevelRead
BI28Low Gas PressureRead
BI29Air PressureRead
BI30Blocked FlueRead
BI31CH PumpRead
BI32DHW PumpRead
BI33Air DamperRead
BI34High Gas PressureRead
AI35ET Error NumberRead
AI36ET Supply TempRead
AI37ET Return TempRead
AI38ET DHW TempRead
AI39ET Flue Gas TempRead
AI40ET HX TempRead
AI41ET Outside TempRead
AI42Boiler StateRead
BI43Frost ProtectionRead
BI44DHW ModeRead
BI45CH ModeRead
AI46ET MonthRead
AI47ET DayRead
AI48ET YearRead
AI49ET HoursRead
AI50ET MinutesRead
AI51ET Day Count HighRead
AI52ET Day Count LowRead
AI53ET Run HoursRead
Object ID lookup: Patterson-Kelley ENVI boiler control point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ENVI boiler control (ProtoNode FPC-N34/N35) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Patterson-Kelley ENVI boiler control (ProtoNode FPC-N34/N35)

How many BACnet points does the Patterson-Kelley ENVI boiler control (ProtoNode FPC-N34/N35) have?

This list has 53 BACnet objects: 33 analog inputs, 9 analog values, 11 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Patterson-Kelley ENVI boiler control (ProtoNode FPC-N34/N35) BACnet points are writable?

9 of the 53 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Patterson-Kelley ENVI boiler control (ProtoNode FPC-N34/N35) BACnet documentation?

The source is ProtoNode FPC-N34 and FPC-N35 Startup Guide For Interfacing Products: ENVI, LOVE, NURO, Appendix B.1 ENVI (Document Revision 14.B), revision 2016-04 (effective date), published free by Patterson-Kelley at https://www.weil-mclain.com/wp-content/uploads/Nuro-Controller-ProtoNode-Startup-Guide_1.pdf.

What are the minimum BACnet points to integrate the Patterson-Kelley ENVI boiler control (ProtoNode FPC-N34/N35)?

Start with AV 13 Boiler Operation (0 off, 1 on/pump auto, 2 off/pump on, 3 on/pump on); AV 11 CH Setpoint (Central heating setpoint); AV 12 DHW Setpoint (DHW setpoint); AI 1 State (Burner state; 9 = burning, 16-17 and 19-21 = errors); AI 2 Supply Temp (Supply water temperature); AI 6 Firing Rate (Firing rate); AI 10 Flame Signal (Flame signal; 128 = flame); AI 20 Error Code (Error code; see the manual notes).

How do I enable BMS control of the Patterson-Kelley ENVI boiler control (ProtoNode FPC-N34/N35)?

AV 13 Boiler Operation: 0 = boiler off & pump off, 1 = boiler on & pump auto, 2 = boiler off & pump on, 3 = boiler on & pump on. AV 11/12 are the CH and DHW setpoints; AV 14-19 set the outdoor reset curve and night setback.

How do I check these points on the real ENVI boiler control (ProtoNode FPC-N34/N35)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Patterson-Kelley BACnet points lists

Source: ProtoNode FPC-N34 and FPC-N35 Startup Guide For Interfacing Products: ENVI, LOVE, NURO, Appendix B.1 ENVI · Document Revision 14.B · rev. 2016-04 (effective date). Object names, instances and units are reproduced as published; descriptions are our own.