Boiler gateway (fire tube combi/heating boiler) · BACnet points list

Navien NFB-C Fire Tube Boiler - Single Boiler (Modbus/BACnet Gateway) BACnet points list

Updated 11 November 2026

Short answer

The Navien Modbus/BACnet gateway reads an NFB-C boiler over Modbus RTU and presents it as a BACnet IP or BACnet MS/TP device (or Modbus TCP). The single-boiler profile gives on/off and enable commands, space-heat and DHW setpoints, temperatures, pump and thermostat states, error codes and run counters.

This page lists 66 BACnet objects for the Navien NFB-C Fire Tube Boiler - Single Boiler (Modbus/BACnet Gateway) — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Navien’s own free documentation, linked below.

Manufacturer
Navien
Model
NFB-C Fire Tube Boiler - Single Boiler (Modbus/BACnet Gateway)
Equipment
Boiler gateway (fire tube combi/heating boiler)
Equipment type
Boilers & water heaters
BACnet objects
66 (21 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
NFB-C, NFB-301C, NFB-399C, Navien Modbus/BACnet Gateway, GXXX001932
Source document
Modbus/BACnet Gateway Start-up Guide (Installation & Operation Manual) for interfacing Navien products to building automation systems · rev. Effective October 1, 2019
Download CSV 66 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Navien’s current documentation and the live device before use. Not official Navien information. Terms of use.

BMS integration notes: Navien NFB-C Fire Tube Boiler - Single Boiler (Modbus/BACnet Gateway)

Integration in brief

Enable the boiler and space heating from the BMS, write the supply and DHW setpoints, then read the operating status, temperatures and error codes. Error reset is an AV command.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1Boiler On/Off commandBoiler on/off commandWrite
BV 1SH operation on/off controlSpace heating on/offWrite
AV 2SH supply setpoint settingSpace-heat supply water setpointWrite
AV 4DHW setpoint settingDomestic hot water setpointWrite
AV 5Error reset commandResets the boiler errorWrite
AI 12Boiler Operation StatusBoiler operating statusRead
BI 1Burner operation stateBurner firingRead
AI 4Supply temperatureBoiler supply water temperatureRead
AI 5Return temperatureBoiler return water temperatureRead
AI 1Main Error codeActive main error codeRead

Enable & remote start

Boiler On/Off command (AV 1) and SH operation on/off control (BV 1) switch the boiler and space heating; DHW operation ON/OFF control (BV 4) does the same for hot water.

Network setup

Watch out for

Navien NFB-C Fire Tube Boiler - Single Boiler (Modbus/BACnet Gateway) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

66 of 66 shown
Type
Access
Show
Navien NFB-C Fire Tube Boiler - Single Boiler (Modbus/BACnet Gateway) BACnet Points List
DescriptionStates
AImin1Main Error codeRead
AI2Sub Error codeRead
AI3Current Heat capacityRead
AImin4Supply temperatureRead
AImin5Return temperatureRead
AI6System Supply temperatureRead
AI7System Return temperatureRead
AI8Water pressureRead
AI9Exhaust temperatureRead
AI10DHW Tank temperatureRead
AI11Outdoor temperatureRead
AImin12Boiler Operation StatusRead
AI13Maximum Heat capacityRead
AI14Total time of CH operationRead
AI15Number of CH operationRead
AI16Total time after installationRead
AI27Maximum outdoor temperature statusRead
AI28Minimum outdoor temperature statusRead
AI29CH supply minimum temperatureRead
AI30CH supply maximum temperatureRead
AI31CH return minimum temperatureRead
AI32CH return maximum temperatureRead
AI33DHW minimum temperatureRead
AI34DHW maximum temperatureRead
AI35SH control methodRead
AI36DHW control methodRead
AI38Gas typeRead
AI41Current amount of gasRead
AI42Total amount of gasRead
AVmin1Boiler On/Off commandWrite
AVmin2SH supply setpoint settingWrite
AV3SH return setpoint settingWrite
AVmin4DHW setpoint settingWrite
AVmin5Error reset commandWrite
AV7Boiler setpoint in DHW operationWrite
AV9Outdoor reset curve heatload settingWrite
AV10Maximum outdoor temperature settingWrite
AV11Minimum outdoor temperature settingWrite
AV12WWSD temperature settingWrite
AV13WWSD On differential settingWrite
AV14Boost interval time settingWrite
AV15Cascade Initial op units settingWrite
AV16CH supply min temperature settingWrite
AV17CH supply max temperature settingWrite
AV18CH return min temperature settingWrite
AV19CH return max temperature settingWrite
BImin1Burner operation stateRead
BI2SH operation stateRead
BI4DHW tank mode operation stateRead
BI5Error stateRead
BI7Boiler enable statusRead
BI8Boiler pump Operation StatusRead
BI9DHW/Zone1 pump Operation StatusRead
BI10Zone2 pump status Operation StatusRead
BI11System/Zone3 pump Operation StatusRead
BI12SH1 Thermostat input StatusRead
BI13SH2 Thermostat input StatusRead
BI14SH3 Thermostat input StatusRead
BI15DHW call signalRead
BI16DHW Thermostat input StatusRead
BI17LWCO input statusRead
BI24Frozen protection modeRead
BVmin1SH operation on/off controlWrite
BV2Outdoor reset curve usage enableWrite
BV3WWSD enableWrite
BV4DHW operation ON/OFF controlWrite
Object ID lookup: Navien NFB-C Single Boiler Gateway point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the NFB-C Fire Tube Boiler - Single Boiler (Modbus/BACnet Gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Navien NFB-C Fire Tube Boiler - Single Boiler (Modbus/BACnet Gateway)

How many BACnet points does the Navien NFB-C Fire Tube Boiler - Single Boiler (Modbus/BACnet Gateway) have?

This list has 66 BACnet objects: 29 analog inputs, 17 analog values, 16 binary inputs, 4 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Navien NFB-C Fire Tube Boiler - Single Boiler (Modbus/BACnet Gateway) BACnet points are writable?

21 of the 66 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Navien NFB-C Fire Tube Boiler - Single Boiler (Modbus/BACnet Gateway) BACnet documentation?

The source is Modbus/BACnet Gateway Start-up Guide (Installation & Operation Manual) for interfacing Navien products to building automation systems, revision Effective October 1, 2019, published free by Navien at https://www.navieninc.com/downloads/modbus-bacnet-installation-and-operation-manual-en/download.

What are the minimum BACnet points to integrate the Navien NFB-C Fire Tube Boiler - Single Boiler (Modbus/BACnet Gateway)?

Start with AV 1 Boiler On/Off command (Boiler on/off command); BV 1 SH operation on/off control (Space heating on/off); AV 2 SH supply setpoint setting (Space-heat supply water setpoint); AV 4 DHW setpoint setting (Domestic hot water setpoint); AV 5 Error reset command (Resets the boiler error); AI 12 Boiler Operation Status (Boiler operating status); BI 1 Burner operation state (Burner firing); AI 4 Supply temperature (Boiler supply water temperature); AI 5 Return temperature (Boiler return water temperature); AI 1 Main Error code (Active main error code).

How do I enable BMS control of the Navien NFB-C Fire Tube Boiler - Single Boiler (Modbus/BACnet Gateway)?

Boiler On/Off command (AV 1) and SH operation on/off control (BV 1) switch the boiler and space heating; DHW operation ON/OFF control (BV 4) does the same for hot water.

How do I check these points on the real NFB-C Fire Tube Boiler - Single Boiler (Modbus/BACnet Gateway)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Navien BACnet points lists

Source: Modbus/BACnet Gateway Start-up Guide (Installation & Operation Manual) for interfacing Navien products to building automation systems · rev. Effective October 1, 2019. Object names, instances and units are reproduced as published; descriptions are our own.