Boiler gateway (cascaded fire tube boilers) · BACnet points list

Navien NFB-C Fire Tube Boiler - Cascade Main + Sub 1-31 (Modbus/BACnet Gateway) BACnet points list

Updated 11 November 2026

Short answer

With the cascade profile, the Navien Modbus/BACnet gateway presents a whole NFB-C cascade (Main plus Sub 1-31) as one BACnet IP or BACnet MS/TP device. It exposes the cascade commands and setpoints, cascade state, and a block of status, temperature, error and counter points for the Main and each Sub boiler.

This page lists 580 BACnet objects for the Navien NFB-C Fire Tube Boiler - Cascade Main + Sub 1-31 (Modbus/BACnet Gateway) — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Navien’s own free documentation, linked below.

Manufacturer
Navien
Model
NFB-C Fire Tube Boiler - Cascade Main + Sub 1-31 (Modbus/BACnet Gateway)
Equipment
Boiler gateway (cascaded fire tube boilers)
Equipment type
Boilers & water heaters
BACnet objects
580 (21 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
NFB-C cascade, NFB-301C, NFB-399C, Navien Modbus/BACnet Gateway, GXXX001932
Source document
Modbus/BACnet Gateway Start-up Guide (Installation & Operation Manual) for interfacing Navien products to building automation systems · rev. Effective October 1, 2019
Download CSV 580 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Navien’s current documentation and the live device before use. Not official Navien information. Terms of use.

BMS integration notes: Navien NFB-C Fire Tube Boiler - Cascade Main + Sub 1-31 (Modbus/BACnet Gateway)

Integration in brief

Command the cascade from the BMS (on/off, space heating, setpoints) and read cascade state plus the Main and Sub boiler status and error points. Map only the Sub blocks that exist on site.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1Boiler On/Off commandCascade on/off commandWrite
BV 1SH operation on/off controlSpace heating on/offWrite
AV 2SH supply setpoint settingSpace-heat supply water setpointWrite
AV 4DHW setpoint settingDomestic hot water setpointWrite
AV 5Error reset commandResets boiler errorsWrite
BI 101Cascade system enable stateCascade system enabledRead
BI 102Cascade burning stateCascade burner firingRead
BI 6Main Error stateMain boiler in errorRead

Enable & remote start

Boiler On/Off command (AV 1) and SH operation on/off control (BV 1) switch the cascade and space heating; DHW operation ON/OFF control (BV 4) does the same for hot water.

Network setup

Watch out for

Navien NFB-C Fire Tube Boiler - Cascade Main + Sub 1-31 (Modbus/BACnet Gateway) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

580 of 580 shown
Type
Access
Show
Navien NFB-C Fire Tube Boiler - Cascade Main + Sub 1-31 (Modbus/BACnet Gateway) BACnet Points List
DescriptionStates
AI1Main Operation StatusRead
AI2Main Error codeRead
AI4Main Current Heat capacityRead
AI5Main Supply temperatureRead
AI6Main Return temperatureRead
AI8Main Maximum Heat capacityRead
AI9Main Exhaust temperatureRead
AI10Main Total time after installationRead
AI11Main Number of CH operationRead
AI12Main Total time of CH operationRead
AI13Main Current amount of gasRead
AI14Main Total amount of gasRead
AI101Cascade total unitsRead
AI102Cascade Operating unitsRead
AI103Cascade On/Off stateRead
AI104CC Average Heating capacityRead
AI105CC Maximum Heating capacityRead
AI106Primary total flowRead
AI107Average primary Supply temperatureRead
AI108Average primary return temperatureRead
AI109System Supply temperatureRead
AI110System Return temperatureRead
AI111Error occurrence unit numberRead
AI112Main Error codeRead
AI1001Sub01 Operation StatusRead
AI1002Sub01 Main Error codeRead
AI1004Sub01 Current Heat capacityRead
AI1005Sub01 Supply temperatureRead
AI1006Sub01 Return temperatureRead
AI1008Sub01 Maximum Heat capacityRead
AI1009Sub01 Exhaust temperatureRead
AI1010Sub01 Total time after installationRead
AI1011Sub01 Number of CH operationRead
AI1012Sub01 Total time of CH operationRead
AI1013Sub01 Current amount of gasRead
AI1014Sub01 Total amount of gasRead
AI2001Sub02 Operation StatusRead
AI2002Sub02 Main Error codeRead
AI2004Sub02 Current Heat capacityRead
AI2005Sub02 Supply temperatureRead
AI2006Sub02 Return temperatureRead
AI2008Sub02 Maximum Heat capacityRead
AI2009Sub02 Exhaust temperatureRead
AI2010Sub02 Total time after installationRead
AI2011Sub02 Number of CH operationRead
AI2012Sub02 Total time of CH operationRead
AI2013Sub02 Current amount of gasRead
AI2014Sub02 Total amount of gasRead
AI3001Sub03 Operation StatusRead
AI3002Sub03 Main Error codeRead
AI3004Sub03 Current Heat capacityRead
AI3005Sub03 Supply temperatureRead
AI3006Sub03 Return temperatureRead
AI3008Sub03 Maximum Heat capacityRead
AI3009Sub03 Exhaust temperatureRead
AI3010Sub03 Total time after installationRead
AI3011Sub03 Number of CH operationRead
AI3012Sub03 Total time of CH operationRead
AI3013Sub03 Current amount of gasRead
AI3014Sub03 Total amount of gasRead
AI4001Sub04 Operation StatusRead
AI4002Sub04 Main Error codeRead
AI4004Sub04 Current Heat capacityRead
AI4005Sub04 Supply temperatureRead
AI4006Sub04 Return temperatureRead
AI4008Sub04 Maximum Heat capacityRead
AI4009Sub04 Exhaust temperatureRead
AI4010Sub04 Total time after installationRead
AI4011Sub04 Number of CH operationRead
AI4012Sub04 Total time of CH operationRead
AI4013Sub04 Current amount of gasRead
AI4014Sub04 Total amount of gasRead
AI5001Sub05 Operation StatusRead
AI5002Sub05 Main Error codeRead
AI5004Sub05 Current Heat capacityRead
AI5005Sub05 Supply temperatureRead
AI5006Sub05 Return temperatureRead
AI5008Sub05 Maximum Heat capacityRead
AI5009Sub05 Exhaust temperatureRead
AI5010Sub05 Total time after installationRead
AI5011Sub05 Number of CH operationRead
AI5012Sub05 Total time of CH operationRead
AI5013Sub05 Current amount of gasRead
AI5014Sub05 Total amount of gasRead
AI6001Sub06 Operation StatusRead
AI6002Sub06 Main Error codeRead
AI6004Sub06 Current Heat capacityRead
AI6005Sub06 Supply temperatureRead
AI6006Sub06 Return temperatureRead
AI6008Sub06 Maximum Heat capacityRead
AI6009Sub06 Exhaust temperatureRead
AI6010Sub06 Total time after installationRead
AI6011Sub06 Number of CH operationRead
AI6012Sub06 Total time of CH operationRead
AI6013Sub06 Current amount of gasRead
AI6014Sub06 Total amount of gasRead
AI7001Sub07 Operation StatusRead
AI7002Sub07 Main Error codeRead
AI7004Sub07 Current Heat capacityRead
AI7005Sub07 Supply temperatureRead
AI7006Sub07 Return temperatureRead
AI7008Sub07 Maximum Heat capacityRead
AI7009Sub07 Exhaust temperatureRead
AI7010Sub07 Total time after installationRead
AI7011Sub07 Number of CH operationRead
AI7012Sub07 Total time of CH operationRead
AI7013Sub07 Current amount of gasRead
AI7014Sub07 Total amount of gasRead
AI8001Sub08 Operation StatusRead
AI8002Sub08 Main Error codeRead
AI8004Sub08 Current Heat capacityRead
AI8005Sub08 Supply temperatureRead
AI8006Sub08 Return temperatureRead
AI8008Sub08 Maximum Heat capacityRead
AI8009Sub08 Exhaust temperatureRead
AI8010Sub08 Total time after installationRead
AI8011Sub08 Number of CH operationRead
AI8012Sub08 Total time of CH operationRead
AI8013Sub08 Current amount of gasRead
AI8014Sub08 Total amount of gasRead
AI9001Sub09 Operation StatusRead
AI9002Sub09 Main Error codeRead
AI9004Sub09 Current Heat capacityRead
AI9005Sub09 Supply temperatureRead
AI9006Sub09 Return temperatureRead
AI9008Sub09 Maximum Heat capacityRead
AI9009Sub09 Exhaust temperatureRead
AI9010Sub09 Total time after installationRead
AI9011Sub09 Number of CH operationRead
AI9012Sub09 Total time of CH operationRead
AI9013Sub09 Current amount of gasRead
AI9014Sub09 Total amount of gasRead
AI10001Sub10 Operation StatusRead
AI10002Sub10 Main Error codeRead
AI10004Sub10 Current Heat capacityRead
AI10005Sub10 Supply temperatureRead
AI10006Sub10 Return temperatureRead
AI10008Sub10 Maximum Heat capacityRead
AI10009Sub10 Exhaust temperatureRead
AI10010Sub10 Total time after installationRead
AI10011Sub10 Number of CH operationRead
AI10012Sub10 Total time of CH operationRead
AI10013Sub10 Current amount of gasRead
AI10014Sub10 Total amount of gasRead
AI11001Sub11 Operation StatusRead
AI11002Sub11 Main Error codeRead
AI11004Sub11 Current Heat capacityRead
AI11005Sub11 Supply temperatureRead
AI11006Sub11 Return temperatureRead
AI11008Sub11 Maximum Heat capacityRead
AI11009Sub11 Exhaust temperatureRead
AI11010Sub11 Total time after installationRead
AI11011Sub11 Number of CH operationRead
AI11012Sub11 Total time of CH operationRead
AI11013Sub11 Current amount of gasRead
AI11014Sub11 Total amount of gasRead
AI12001Sub12 Operation StatusRead
AI12002Sub12 Main Error codeRead
AI12004Sub12 Current Heat capacityRead
AI12005Sub12 Supply temperatureRead
AI12006Sub12 Return temperatureRead
AI12008Sub12 Maximum Heat capacityRead
AI12009Sub12 Exhaust temperatureRead
AI12010Sub12 Total time after installationRead
AI12011Sub12 Number of CH operationRead
AI12012Sub12 Total time of CH operationRead
AI12013Sub12 Current amount of gasRead
AI12014Sub12 Total amount of gasRead
AI13001Sub13 Operation StatusRead
AI13002Sub13 Main Error codeRead
AI13004Sub13 Current Heat capacityRead
AI13005Sub13 Supply temperatureRead
AI13006Sub13 Return temperatureRead
AI13008Sub13 Maximum Heat capacityRead
AI13009Sub13 Exhaust temperatureRead
AI13010Sub13 Total time after installationRead
AI13011Sub13 Number of CH operationRead
AI13012Sub13 Total time of CH operationRead
AI13013Sub13 Current amount of gasRead
AI13014Sub13 Total amount of gasRead
AI14001Sub14 Operation StatusRead
AI14002Sub14 Main Error codeRead
AI14004Sub14 Current Heat capacityRead
AI14005Sub14 Supply temperatureRead
AI14006Sub14 Return temperatureRead
AI14008Sub14 Maximum Heat capacityRead
AI14009Sub14 Exhaust temperatureRead
AI14010Sub14 Total time after installationRead
AI14011Sub14 Number of CH operationRead
AI14012Sub14 Total time of CH operationRead
AI14013Sub14 Current amount of gasRead
AI14014Sub14 Total amount of gasRead
AI15001Sub15 Operation StatusRead
AI15002Sub15 Main Error codeRead
AI15004Sub15 Current Heat capacityRead
AI15005Sub15 Supply temperatureRead
AI15006Sub15 Return temperatureRead
AI15008Sub15 Maximum Heat capacityRead
AI15009Sub15 Exhaust temperatureRead
AI15010Sub15 Total time after installationRead
AI15011Sub15 Number of CH operationRead
AI15012Sub15 Total time of CH operationRead
AI15013Sub15 Current amount of gasRead
AI15014Sub15 Total amount of gasRead
AI16001Sub16 Operation StatusRead
AI16002Sub16 Main Error codeRead
AI16004Sub16 Current Heat capacityRead
AI16005Sub16 Supply temperatureRead
AI16006Sub16 Return temperatureRead
AI16008Sub16 Maximum Heat capacityRead
AI16009Sub16 Exhaust temperatureRead
AI16010Sub16 Total time after installationRead
AI16011Sub16 Number of CH operationRead
AI16012Sub16 Total time of CH operationRead
AI16013Sub16 Current amount of gasRead
AI16014Sub16 Total amount of gasRead
AI17001Sub17 Operation StatusRead
AI17002Sub17 Main Error codeRead
AI17004Sub17 Current Heat capacityRead
AI17005Sub17 Supply temperatureRead
AI17006Sub17 Return temperatureRead
AI17008Sub17 Maximum Heat capacityRead
AI17009Sub17 Exhaust temperatureRead
AI17010Sub17 Total time after installationRead
AI17011Sub17 Number of CH operationRead
AI17012Sub17 Total time of CH operationRead
AI17013Sub17 Current amount of gasRead
AI17014Sub17 Total amount of gasRead
AI18001Sub18 Operation StatusRead
AI18002Sub18 Main Error codeRead
AI18004Sub18 Current Heat capacityRead
AI18005Sub18 Supply temperatureRead
AI18006Sub18 Return temperatureRead
AI18008Sub18 Maximum Heat capacityRead
AI18009Sub18 Exhaust temperatureRead
AI18010Sub18 Total time after installationRead
AI18011Sub18 Number of CH operationRead
AI18012Sub18 Total time of CH operationRead
AI18013Sub18 Current amount of gasRead
AI18014Sub18 Total amount of gasRead
AI19001Sub19 Operation StatusRead
AI19002Sub19 Main Error codeRead
AI19004Sub19 Current Heat capacityRead
AI19005Sub19 Supply temperatureRead
AI19006Sub19 Return temperatureRead
AI19008Sub19 Maximum Heat capacityRead
AI19009Sub19 Exhaust temperatureRead
AI19010Sub19 Total time after installationRead
AI19011Sub19 Number of CH operationRead
AI19012Sub19 Total time of CH operationRead
AI19013Sub19 Current amount of gasRead
AI19014Sub19 Total amount of gasRead
AI20001Sub20 Operation StatusRead
AI20002Sub20 Main Error codeRead
AI20004Sub20 Current Heat capacityRead
AI20005Sub20 Supply temperatureRead
AI20006Sub20 Return temperatureRead
AI20008Sub20 Maximum Heat capacityRead
AI20009Sub20 Exhaust temperatureRead
AI20010Sub20 Total time after installationRead
AI20011Sub20 Number of CH operationRead
AI20012Sub20 Total time of CH operationRead
AI20013Sub20 Current amount of gasRead
AI20014Sub20 Total amount of gasRead
AI21001Sub21 Operation StatusRead
AI21002Sub21 Main Error codeRead
AI21004Sub21 Current Heat capacityRead
AI21005Sub21 Supply temperatureRead
AI21006Sub21 Return temperatureRead
AI21008Sub21 Maximum Heat capacityRead
AI21009Sub21 Exhaust temperatureRead
AI21010Sub21 Total time after installationRead
AI21011Sub21 Number of CH operationRead
AI21012Sub21 Total time of CH operationRead
AI21013Sub21 Current amount of gasRead
AI21014Sub21 Total amount of gasRead
AI22001Sub22 Operation StatusRead
AI22002Sub22 Main Error codeRead
AI22004Sub22 Current Heat capacityRead
AI22005Sub22 Supply temperatureRead
AI22006Sub22 Return temperatureRead
AI22008Sub22 Maximum Heat capacityRead
AI22009Sub22 Exhaust temperatureRead
AI22010Sub22 Total time after installationRead
AI22011Sub22 Number of CH operationRead
AI22012Sub22 Total time of CH operationRead
AI22013Sub22 Current amount of gasRead
AI22014Sub22 Total amount of gasRead
AI23001Sub23 Operation StatusRead
AI23002Sub23 Main Error codeRead
AI23004Sub23 Current Heat capacityRead
AI23005Sub23 Supply temperatureRead
AI23006Sub23 Return temperatureRead
AI23008Sub23 Maximum Heat capacityRead
AI23009Sub23 Exhaust temperatureRead
AI23010Sub23 Total time after installationRead
AI23011Sub23 Number of CH operationRead
AI23012Sub23 Total time of CH operationRead
AI23013Sub23 Current amount of gasRead
AI23014Sub23 Total amount of gasRead
AI24001Sub24 Operation StatusRead
AI24002Sub24 Main Error codeRead
AI24004Sub24 Current Heat capacityRead
AI24005Sub24 Supply temperatureRead
AI24006Sub24 Return temperatureRead
AI24008Sub24 Maximum Heat capacityRead
AI24009Sub24 Exhaust temperatureRead
AI24010Sub24 Total time after installationRead
AI24011Sub24 Number of CH operationRead
AI24012Sub24 Total time of CH operationRead
AI24013Sub24 Current amount of gasRead
AI24014Sub24 Total amount of gasRead
AI25001Sub25 Operation StatusRead
AI25002Sub25 Main Error codeRead
AI25004Sub25 Current Heat capacityRead
AI25005Sub25 Supply temperatureRead
AI25006Sub25 Return temperatureRead
AI25008Sub25 Maximum Heat capacityRead
AI25009Sub25 Exhaust temperatureRead
AI25010Sub25 Total time after installationRead
AI25011Sub25 Number of CH operationRead
AI25012Sub25 Total time of CH operationRead
AI25013Sub25 Current amount of gasRead
AI25014Sub25 Total amount of gasRead
AI26001Sub26 Operation StatusRead
AI26002Sub26 Main Error codeRead
AI26004Sub26 Current Heat capacityRead
AI26005Sub26 Supply temperatureRead
AI26006Sub26 Return temperatureRead
AI26008Sub26 Maximum Heat capacityRead
AI26009Sub26 Exhaust temperatureRead
AI26010Sub26 Total time after installationRead
AI26011Sub26 Number of CH operationRead
AI26012Sub26 Total time of CH operationRead
AI26013Sub26 Current amount of gasRead
AI26014Sub26 Total amount of gasRead
AI27001Sub27 Operation StatusRead
AI27002Sub27 Main Error codeRead
AI27004Sub27 Current Heat capacityRead
AI27005Sub27 Supply temperatureRead
AI27006Sub27 Return temperatureRead
AI27008Sub27 Maximum Heat capacityRead
AI27009Sub27 Exhaust temperatureRead
AI27010Sub27 Total time after installationRead
AI27011Sub27 Number of CH operationRead
AI27012Sub27 Total time of CH operationRead
AI27013Sub27 Current amount of gasRead
AI27014Sub27 Total amount of gasRead
AI28001Sub28 Operation StatusRead
AI28002Sub28 Main Error codeRead
AI28004Sub28 Current Heat capacityRead
AI28005Sub28 Supply temperatureRead
AI28006Sub28 Return temperatureRead
AI28008Sub28 Maximum Heat capacityRead
AI28009Sub28 Exhaust temperatureRead
AI28010Sub28 Total time after installationRead
AI28011Sub28 Number of CH operationRead
AI28012Sub28 Total time of CH operationRead
AI28013Sub28 Current amount of gasRead
AI28014Sub28 Total amount of gasRead
AI29001Sub29 Operation StatusRead
AI29002Sub29 Main Error codeRead
AI29004Sub29 Current Heat capacityRead
AI29005Sub29 Supply temperatureRead
AI29006Sub29 Return temperatureRead
AI29008Sub29 Maximum Heat capacityRead
AI29009Sub29 Exhaust temperatureRead
AI29010Sub29 Total time after installationRead
AI29011Sub29 Number of CH operationRead
AI29012Sub29 Total time of CH operationRead
AI29013Sub29 Current amount of gasRead
AI29014Sub29 Total amount of gasRead
AI30001Sub30 Operation StatusRead
AI30002Sub30 Main Error codeRead
AI30004Sub30 Current Heat capacityRead
AI30005Sub30 Supply temperatureRead
AI30006Sub30 Return temperatureRead
AI30008Sub30 Maximum Heat capacityRead
AI30009Sub30 Exhaust temperatureRead
AI30010Sub30 Total time after installationRead
AI30011Sub30 Number of CH operationRead
AI30012Sub30 Total time of CH operationRead
AI30013Sub30 Current amount of gasRead
AI30014Sub30 Total amount of gasRead
AI31001Sub31 Operation StatusRead
AI31002Sub31 Main Error codeRead
AI31004Sub31 Current Heat capacityRead
AI31005Sub31 Supply temperatureRead
AI31006Sub31 Return temperatureRead
AI31008Sub31 Maximum Heat capacityRead
AI31009Sub31 Exhaust temperatureRead
AI31010Sub31 Total time after installationRead
AI31011Sub31 Number of CH operationRead
AI31012Sub31 Total time of CH operationRead
AI31013Sub31 Current amount of gasRead
AI31014Sub31 Total amount of gasRead
AVmin1Boiler On/Off commandWrite
AVmin2SH supply setpoint settingWrite
AV3SH return setpoint settingWrite
AVmin4DHW setpoint settingWrite
AVmin5Error reset commandWrite
AV7Boiler setpoint in DHW operationWrite
AV9Outdoor reset curve heatload settingWrite
AV10Maximum outdoor temperature settingWrite
AV11Minimum outdoor temperature settingWrite
AV12WWSD temperature settingWrite
AV13WWSD On differential settingWrite
AV14Boost interval time settingWrite
AV15Cascade Initial op units settingWrite
AV16CH supply min temperature settingWrite
AV17CH supply max temperature settingWrite
AV18CH return min temperature settingWrite
AV19CH return max temperature settingWrite
BI1Main Burner op stateRead
BI2Main Frozen protection modeRead
BImin6Main Error stateRead
BI7Main Boiler enable statusRead
BI8Main Boiler pump op StatusRead
BImin101Cascade system enable stateRead
BImin102Cascade burning stateRead
BI103Cascade SH operation stateRead
BI1001Sub01 Burner op stateRead
BI1002Sub01 Frozen protection modeRead
BI1006Sub01 Error stateRead
BI1007Sub01 Boiler enable statusRead
BI1008Sub01 Boiler pump op StatusRead
BI2001Sub02 Burner op stateRead
BI2002Sub02 Frozen protection modeRead
BI2006Sub02 Error stateRead
BI2007Sub02 Boiler enable statusRead
BI2008Sub02 Boiler pump op StatusRead
BI3001Sub03 Burner op stateRead
BI3002Sub03 Frozen protection modeRead
BI3006Sub03 Error stateRead
BI3007Sub03 Boiler enable statusRead
BI3008Sub03 Boiler pump op StatusRead
BI4001Sub04 Burner op stateRead
BI4002Sub04 Frozen protection modeRead
BI4006Sub04 Error stateRead
BI4007Sub04 Boiler enable statusRead
BI4008Sub04 Boiler pump op StatusRead
BI5001Sub05 Burner op stateRead
BI5002Sub05 Frozen protection modeRead
BI5006Sub05 Error stateRead
BI5007Sub05 Boiler enable statusRead
BI5008Sub05 Boiler pump op StatusRead
BI6001Sub06 Burner op stateRead
BI6002Sub06 Frozen protection modeRead
BI6006Sub06 Error stateRead
BI6007Sub06 Boiler enable statusRead
BI6008Sub06 Boiler pump op StatusRead
BI7001Sub07 Burner op stateRead
BI7002Sub07 Frozen protection modeRead
BI7006Sub07 Error stateRead
BI7007Sub07 Boiler enable statusRead
BI7008Sub07 Boiler pump op StatusRead
BI8001Sub08 Burner op stateRead
BI8002Sub08 Frozen protection modeRead
BI8006Sub08 Error stateRead
BI8007Sub08 Boiler enable statusRead
BI8008Sub08 Boiler pump op StatusRead
BI9001Sub09 Burner op stateRead
BI9002Sub09 Frozen protection modeRead
BI9006Sub09 Error stateRead
BI9007Sub09 Boiler enable statusRead
BI9008Sub09 Boiler pump op StatusRead
BI10001Sub10 Burner op stateRead
BI10002Sub10 Frozen protection modeRead
BI10006Sub10 Error stateRead
BI10007Sub10 Boiler enable statusRead
BI10008Sub10 Boiler pump op StatusRead
BI11001Sub11 Burner op stateRead
BI11002Sub11 Frozen protection modeRead
BI11006Sub11 Error stateRead
BI11007Sub11 Boiler enable statusRead
BI11008Sub11 Boiler pump op StatusRead
BI12001Sub12 Burner op stateRead
BI12002Sub12 Frozen protection modeRead
BI12006Sub12 Error stateRead
BI12007Sub12 Boiler enable statusRead
BI12008Sub12 Boiler pump op StatusRead
BI13001Sub13 Burner op stateRead
BI13002Sub13 Frozen protection modeRead
BI13006Sub13 Error stateRead
BI13007Sub13 Boiler enable statusRead
BI13008Sub13 Boiler pump op StatusRead
BI14001Sub14 Burner op stateRead
BI14002Sub14 Frozen protection modeRead
BI14006Sub14 Error stateRead
BI14007Sub14 Boiler enable statusRead
BI14008Sub14 Boiler pump op StatusRead
BI15001Sub15 Burner op stateRead
BI15002Sub15 Frozen protection modeRead
BI15006Sub15 Error stateRead
BI15007Sub15 Boiler enable statusRead
BI15008Sub15 Boiler pump op StatusRead
BI16001Sub16 Burner op stateRead
BI16002Sub16 Frozen protection modeRead
BI16006Sub16 Error stateRead
BI16007Sub16 Boiler enable statusRead
BI16008Sub16 Boiler pump op StatusRead
BI17001Sub17 Burner op stateRead
BI17002Sub17 Frozen protection modeRead
BI17006Sub17 Error stateRead
BI17007Sub17 Boiler enable statusRead
BI17008Sub17 Boiler pump op StatusRead
BI18001Sub18 Burner op stateRead
BI18002Sub18 Frozen protection modeRead
BI18006Sub18 Error stateRead
BI18007Sub18 Boiler enable statusRead
BI18008Sub18 Boiler pump op StatusRead
BI19001Sub19 Burner op stateRead
BI19002Sub19 Frozen protection modeRead
BI19006Sub19 Error stateRead
BI19007Sub19 Boiler enable statusRead
BI19008Sub19 Boiler pump op StatusRead
BI20001Sub20 Burner op stateRead
BI20002Sub20 Frozen protection modeRead
BI20006Sub20 Error stateRead
BI20007Sub20 Boiler enable statusRead
BI20008Sub20 Boiler pump op StatusRead
BI21001Sub21 Burner op stateRead
BI21002Sub21 Frozen protection modeRead
BI21006Sub21 Error stateRead
BI21007Sub21 Boiler enable statusRead
BI21008Sub21 Boiler pump op StatusRead
BI22001Sub22 Burner op stateRead
BI22002Sub22 Frozen protection modeRead
BI22006Sub22 Error stateRead
BI22007Sub22 Boiler enable statusRead
BI22008Sub22 Boiler pump op StatusRead
BI23001Sub23 Burner op stateRead
BI23002Sub23 Frozen protection modeRead
BI23006Sub23 Error stateRead
BI23007Sub23 Boiler enable statusRead
BI23008Sub23 Boiler pump op StatusRead
BI24001Sub24 Burner op stateRead
BI24002Sub24 Frozen protection modeRead
BI24006Sub24 Error stateRead
BI24007Sub24 Boiler enable statusRead
BI24008Sub24 Boiler pump op StatusRead
BI25001Sub25 Burner op stateRead
BI25002Sub25 Frozen protection modeRead
BI25006Sub25 Error stateRead
BI25007Sub25 Boiler enable statusRead
BI25008Sub25 Boiler pump op StatusRead
BI26001Sub26 Burner op stateRead
BI26002Sub26 Frozen protection modeRead
BI26006Sub26 Error stateRead
BI26007Sub26 Boiler enable statusRead
BI26008Sub26 Boiler pump op StatusRead
BI27001Sub27 Burner op stateRead
BI27002Sub27 Frozen protection modeRead
BI27006Sub27 Error stateRead
BI27007Sub27 Boiler enable statusRead
BI27008Sub27 Boiler pump op StatusRead
BI28001Sub28 Burner op stateRead
BI28002Sub28 Frozen protection modeRead
BI28006Sub28 Error stateRead
BI28007Sub28 Boiler enable statusRead
BI28008Sub28 Boiler pump op StatusRead
BI29001Sub29 Burner op stateRead
BI29002Sub29 Frozen protection modeRead
BI29006Sub29 Error stateRead
BI29007Sub29 Boiler enable statusRead
BI29008Sub29 Boiler pump op StatusRead
BI30001Sub30 Burner op stateRead
BI30002Sub30 Frozen protection modeRead
BI30006Sub30 Error stateRead
BI30007Sub30 Boiler enable statusRead
BI30008Sub30 Boiler pump op StatusRead
BI31001Sub31 Burner op stateRead
BI31002Sub31 Frozen protection modeRead
BI31006Sub31 Error stateRead
BI31007Sub31 Boiler enable statusRead
BI31008Sub31 Boiler pump op StatusRead
BVmin1SH operation on/off controlWrite
BV2Outdoor reset curve usage enableWrite
BV3WWSD enableWrite
BV4DHW operation ON/OFF controlWrite
Object ID lookup: Navien NFB-C Cascade Gateway point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the NFB-C Fire Tube Boiler - Cascade Main + Sub 1-31 (Modbus/BACnet Gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Navien NFB-C Fire Tube Boiler - Cascade Main + Sub 1-31 (Modbus/BACnet Gateway)

How many BACnet points does the Navien NFB-C Fire Tube Boiler - Cascade Main + Sub 1-31 (Modbus/BACnet Gateway) have?

This list has 580 BACnet objects: 396 analog inputs, 17 analog values, 163 binary inputs, 4 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Navien NFB-C Fire Tube Boiler - Cascade Main + Sub 1-31 (Modbus/BACnet Gateway) BACnet points are writable?

21 of the 580 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Navien NFB-C Fire Tube Boiler - Cascade Main + Sub 1-31 (Modbus/BACnet Gateway) BACnet documentation?

The source is Modbus/BACnet Gateway Start-up Guide (Installation & Operation Manual) for interfacing Navien products to building automation systems, revision Effective October 1, 2019, published free by Navien at https://www.navieninc.com/downloads/modbus-bacnet-installation-and-operation-manual-en/download.

What are the minimum BACnet points to integrate the Navien NFB-C Fire Tube Boiler - Cascade Main + Sub 1-31 (Modbus/BACnet Gateway)?

Start with AV 1 Boiler On/Off command (Cascade on/off command); BV 1 SH operation on/off control (Space heating on/off); AV 2 SH supply setpoint setting (Space-heat supply water setpoint); AV 4 DHW setpoint setting (Domestic hot water setpoint); AV 5 Error reset command (Resets boiler errors); BI 101 Cascade system enable state (Cascade system enabled); BI 102 Cascade burning state (Cascade burner firing); BI 6 Main Error state (Main boiler in error).

How do I enable BMS control of the Navien NFB-C Fire Tube Boiler - Cascade Main + Sub 1-31 (Modbus/BACnet Gateway)?

Boiler On/Off command (AV 1) and SH operation on/off control (BV 1) switch the cascade and space heating; DHW operation ON/OFF control (BV 4) does the same for hot water.

How do I check these points on the real NFB-C Fire Tube Boiler - Cascade Main + Sub 1-31 (Modbus/BACnet Gateway)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Navien BACnet points lists

Source: Modbus/BACnet Gateway Start-up Guide (Installation & Operation Manual) for interfacing Navien products to building automation systems · rev. Effective October 1, 2019. Object names, instances and units are reproduced as published; descriptions are our own.