- EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36)
VAV terminal unit controller · BACnet points list
Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) BACnet points list
Updated 6 November 2026
EZvav is Nailor's factory-mounted VAV controller family, BTL-listed BACnet application specific controllers on BACnet MS/TP (up to 76.8 kbaud). Device instance, MAC and baud are set from the STE-8001W36 wall sensor without software. The object list covers space temperature and setpoints, occupied and unoccupied cooling and heating setpoints, airflow limits and calibration, fan and reheat outputs, discharge air control, AHU request flags, occupancy mode and the cooling, heating and DAT loops.
This page lists 74 BACnet objects for the Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) — 36 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Nailor’s own free documentation, linked below.
- Manufacturer
- Nailor
- Model
- EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36)
- Equipment
- VAV terminal unit controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 74 (36 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- EZvav, EZVAVINST, IOM-EZVAVINST, BAC-8001-36, BAC-8005-36, BAC-8007-36, BAC-8205-36, STE-8001W36, KMC SimplyVAV
Reference only, provided as-is: verify against Nailor’s current documentation and the live device before use. Not official Nailor information. Terms of use.
BMS integration notes: Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36)
Set the device instance, MAC and baud from the STE-8001W36 COMM menu. Monitor AV 1 space temperature, AV 3/AV 4 active setpoints, AV 24 actual airflow and AV 50 damper position (BAC-8205-36); the occupied setpoints are AV 5/AV 6 and MSV 1 is the occupancy mode. BV 1-3 and BV 7 are requests to the air handler.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1 | OCCUPIED MODE | Occupancy mode of the box | Write |
| AV 5 | OCC CL STPT | Occupied cooling setpoint | Write |
| AV 6 | OCC HT SPT | Occupied heating setpoint | Write |
| AV 1 | SPACE TEMP | Space temperature | Read |
| AV 3 | ACT COOL STPT | Cooling setpoint in use | Read |
| AV 4 | ACT HEAT STPT | Heating setpoint in use | Read |
| AV 24 | PRI ACTUAL FLOW | Measured primary airflow | Read |
| AV 50 | DAMPER POSITION | Damper position | Read |
| BV 1 | NEED AHU | Box needs the air handler running | Read |
Network setup
- Device instance (seven digits), MAC address and baud are entered from the STE-8001W36 sensor: CNFG > COMM > DID, MAC, BAUD.
- BACnet MS/TP at up to 76.8 kbaud on EIA-485.
Watch out for
- Changing airflow calibration objects (K factor, correction slope/offset) changes measured flow; leave them to the balancer.
- Multistate state texts are not printed in the manual; read them from the controller.
Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | DISCHARGE AIR | Discharge Air Temperature (input type KMC10K_Type_III) | Read | ||
| AI | 2 | SPACE SENSOR | Space Sensor (input type KMC Type II Deg F) | Read | ||
| AI | 3 | SPACE SET POINT | Space Set point (input type TABLE_4) | Read | ||
| AI | 4 | PRIMARY DUCT | Primary Duct Pressure | Read | ||
| AI | 5 | SECONDARY DUCT | Secondary Duct Pressure | Read | ||
| AO | 3 | ANALOG HEAT | Analog Heat | % | Read | |
| AO | 4 | FAN SPEED | Fan Speed | % | Read | |
| BO | 1 | DAMPER CW | Damper Clockwise | Read | ||
| BO | 2 | DAMPER CCW | Damper Counter Clockwise | Read | ||
| BO | 5 | FAN | Fan | Read | ||
| BO | 6 | HT STAGE 1 | Heating Stage 1 | Read | ||
| BO | 7 | HT STAGE 2 | Heating Stage 2 | Read | ||
| BO | 8 | HT STAGE 3 | Heating Stage3 | Read | ||
| AVmin | 1 | SPACE TEMP | Space Temperature | Read | ||
| AV | 2 | STPT REFERENCE | Set point Reference | Read | ||
| AVmin | 3 | ACT COOL STPT | Active Cooling Set point | Read | ||
| AVmin | 4 | ACT HEAT STPT | Active Heating Set point | Read | ||
| AVmin | 5 | OCC CL STPT | Occupied Cooling Set point | Write | ||
| AVmin | 6 | OCC HT SPT | Occupied Heating Set point | Write | ||
| AV | 7 | UNOCC CL STPT | Unoccupied Cooling Set point | Write | ||
| AV | 8 | UNOCC HT STPT | Unoccupied Heating Set point | Write | ||
| AV | 9 | MIN CL STPT | Minimum Cooling Set point | Write | ||
| AV | 10 | MAX HT STPT | Maximum Heating Set point | Write | ||
| AV | 11 | MIN STPT DIFF | Minimum Set point Differential | Write | ||
| AV | 12 | STBY DIFF | Standby Differential | Write | ||
| AV | 13 | MIN COOL FLOW | Minimum Cooling Flow | Write | ||
| AV | 14 | MAX COOL FLOW | Maximum Cooling Flow | Write | ||
| AV | 15 | MIN HEAT FLOW | Minimum Heating Flow | Write | ||
| AV | 16 | MAX HEAT FLOW | Maximum Heating Flow | Write | ||
| AV | 17 | AUXILIARY FLOW | Auxiliary Flow | Write | ||
| AV | 18 | PRI K FACT | Primary K Factor | Write | ||
| AV | 19 | PRI CORR SLOPE | Primary Correction Slope | Write | ||
| AV | 20 | PRI CORR OFFST | Primary Correction Offset | Write | ||
| AV | 21 | PRI LO FLOW CORR | Primary Low Flow Correction | Write | ||
| AV | 22 | PRI FLOW STPT | Primary Flow Set point | Write | ||
| AV | 23 | PRI RAW FLOW | Primary Raw Flow | Read | ||
| AVmin | 24 | PRI ACTUAL FLOW | Primary Actual Flow | Read | ||
| AV | 32 | MIN FAN SPEED | Minimum Fan Speed | Write | ||
| AV | 33 | MAX FAN SPEED | Maximum Fan Speed | Write | ||
| AV | 36 | DAT STPT | Discharge Air Temp Set point | Write | ||
| AV | 37 | SAT CHANGEOVER | SAT Changeover Temperature | Write | ||
| AV | 38 | LOCAL OVRD TIME | Local Override Timer | Read | ||
| AV | 39 | STANDBY TIME | Standby Timer (motion) | Write | ||
| AV | 40 | STANDBY TRIGGER | Standby Trigger | Write | ||
| AV | 43 | MEASURED MAX | Measured Maximum | Read | ||
| AV | 44 | MEASURED MIN | Measured Minimum | Read | ||
| AV | 45 | PRI SAVE MIN FLO | Primary Saved Minimum Airflow | Read | ||
| AV | 47 | DAT MAXIMUM | Maximum DAT Set point | Write | ||
| AV | 48 | CW DMP POS | CW Damper Position (BAC-8205-36 only) | Read | ||
| AV | 49 | CCW DMP POS | CCW Damper Position (BAC-8205-36 only) | Read | ||
| AVmin | 50 | DAMPER POSITION | Damper Position (BAC-8205-36 only) | Read | ||
| AV | 55 | CHNG_OVER_DELAY | Cooling Change Over Delay | Write | ||
| AV | 56 | LOW AUTO OCC | Low Limit for Auto Occupy | Write | ||
| BVmin | 1 | NEED AHU | Need For AHU | Read | ||
| BV | 2 | NEED COLDER SPLY | Need For Colder Air Supply | Read | ||
| BV | 3 | NEED MORE STATIC | Need For AHU | Read | ||
| BV | 4 | LOCAL OVRD | Local Override Mode | Read | ||
| BV | 5 | MOTION OVRD | Motion Override Mode | Read | ||
| BV | 6 | MOTION SENSOR | Motion Sensor (Wall Stat) | Read | ||
| BV | 7 | NEED HOTTER SPLY | Need For Hotter Air Supply | Read | ||
| BV | 8 | CHANGE OVER MODE | SAT Changeover Mode | Read | ||
| BV | 9 | DAT LIMITING | Discharge Air Temp Limiting | Read | ||
| BV | 10 | CLOCKWISE CLOSE | Clockwise Close | Write | ||
| BV | 11 | AUTO OCCUPANCY | Auto Occupancy Detection | Write | ||
| BV | 12 | BALANCE MODE | Balance Mode | Write | ||
| BV | 13 | DAT SENSOR | DAT Sensor Present | Write | ||
| BV | 14 | PRI BAL TRIGGER | Primary Balance Trigger | Write | ||
| MVmin | 1 | OCCUPIED MODE | Occupied Mode | Write | ||
| MV | 2 | FAN CONFIG | Fantype Configuration | Write | ||
| MV | 3 | REHEAT | Reheat Type | Write | ||
| MV | 6 | WALL SENSOR | Multi-state Value #6 | Write | ||
| LO | 1 | CL LOOP | Cooling Loop | Read | ||
| LO | 2 | HT LOOP | Heating Loop | Read | ||
| LO | 3 | DAT Loop | Discharge Air Temp Loop | Read |
No points match these filters.
Object ID lookup: Nailor EZvav Digital VAV Controls point IDs by name
AI1DISCHARGE AIRAI2SPACE SENSORAI3SPACE SET POINTAI4PRIMARY DUCTAI5SECONDARY DUCTAO3ANALOG HEATAO4FAN SPEEDBO1DAMPER CWBO2DAMPER CCWBO5FANBO6HT STAGE 1BO7HT STAGE 2BO8HT STAGE 3AV1SPACE TEMPAV2STPT REFERENCEAV3ACT COOL STPTAV4ACT HEAT STPTAV5OCC CL STPTAV6OCC HT SPTAV7UNOCC CL STPTAV8UNOCC HT STPTAV9MIN CL STPTAV10MAX HT STPTAV11MIN STPT DIFFAV12STBY DIFFAV13MIN COOL FLOWAV14MAX COOL FLOWAV15MIN HEAT FLOWAV16MAX HEAT FLOWAV17AUXILIARY FLOWAV18PRI K FACTAV19PRI CORR SLOPEAV20PRI CORR OFFSTAV21PRI LO FLOW CORRAV22PRI FLOW STPTAV23PRI RAW FLOWAV24PRI ACTUAL FLOWAV32MIN FAN SPEEDAV33MAX FAN SPEEDAV36DAT STPTAV37SAT CHANGEOVERAV38LOCAL OVRD TIMEAV39STANDBY TIMEAV40STANDBY TRIGGERAV43MEASURED MAXAV44MEASURED MINAV45PRI SAVE MIN FLOAV47DAT MAXIMUMAV48CW DMP POSAV49CCW DMP POSAV50DAMPER POSITIONAV55CHNG_OVER_DELAYAV56LOW AUTO OCCBV1NEED AHUBV2NEED COLDER SPLYBV3NEED MORE STATICBV4LOCAL OVRDBV5MOTION OVRDBV6MOTION SENSORBV7NEED HOTTER SPLYBV8CHANGE OVER MODEBV9DAT LIMITINGBV10CLOCKWISE CLOSEBV11AUTO OCCUPANCYBV12BALANCE MODEBV13DAT SENSORBV14PRI BAL TRIGGERMV1OCCUPIED MODEMV2FAN CONFIGMV3REHEATMV6WALL SENSORLO1CL LOOPLO2HT LOOPLO3DAT Loop
Integration notes
- The controllers are KMC SimplyVAV models sold under the Nailor EZvav name; the list matches KMC's SimplyVAV list apart from a few names (e.g. AV 2 STPT REFERENCE, AV 12 STBY DIFF, AI 3 SPACE SET POINT) and a few objects KMC adds (AV 51, AV 54).
- The manual gives object, name and description only. Access is inferred: setpoint and configuration AVs writable, inputs, outputs and calculated values read-only.
- Not every object exists on every model; AV 48-50 are BAC-8205-36 only.
- Multistate values are printed as MSV1-MSV6 and loops as LOOP1-LOOP3; they are listed as MV and LO objects.
- BV 3 is printed with the description 'Need For AHU' (same as BV 1) and MSV 6 as 'Multi-state Value #6'.
- Source: BACnet objects, manual pages 44-46 (74 objects).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36)
How many BACnet points does the Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) have?
This list has 74 BACnet objects: 5 analog inputs, 2 analog outputs, 40 analog values, 6 binary outputs, 14 binary values, 3 loops, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) BACnet points are writable?
36 of the 74 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) BACnet documentation?
The source is EZvav Digital Controls - Installation and Operation Manual (IOM-EZVAVINST), revision 2016-10 (cover dated 7-2016), published free by Nailor at https://nailor.com/sites/default/files/documents/EZVAVINST_2.pdf.
What are the minimum BACnet points to integrate the Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36)?
Start with MV 1 OCCUPIED MODE (Occupancy mode of the box); AV 5 OCC CL STPT (Occupied cooling setpoint); AV 6 OCC HT SPT (Occupied heating setpoint); AV 1 SPACE TEMP (Space temperature); AV 3 ACT COOL STPT (Cooling setpoint in use); AV 4 ACT HEAT STPT (Heating setpoint in use); AV 24 PRI ACTUAL FLOW (Measured primary airflow); AV 50 DAMPER POSITION (Damper position); BV 1 NEED AHU (Box needs the air handler running).
How do I check these points on the real EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Nailor BACnet points lists
Source: EZvav Digital Controls - Installation and Operation Manual · IOM-EZVAVINST · rev. 2016-10 (cover dated 7-2016). Object names, instances and units are reproduced as published; descriptions are our own.