  3. Nailor
  4. EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36)

VAV terminal unit controller · BACnet points list

Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) BACnet points list

Updated 6 November 2026

Short answer

EZvav is Nailor's factory-mounted VAV controller family, BTL-listed BACnet application specific controllers on BACnet MS/TP (up to 76.8 kbaud). Device instance, MAC and baud are set from the STE-8001W36 wall sensor without software. The object list covers space temperature and setpoints, occupied and unoccupied cooling and heating setpoints, airflow limits and calibration, fan and reheat outputs, discharge air control, AHU request flags, occupancy mode and the cooling, heating and DAT loops.

This page lists 74 BACnet objects for the Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) — 36 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Nailor’s own free documentation, linked below.

Manufacturer
Nailor
Model
EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36)
Equipment
VAV terminal unit controller
Equipment type
VAV boxes & fan coils
BACnet objects
74 (36 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
EZvav, EZVAVINST, IOM-EZVAVINST, BAC-8001-36, BAC-8005-36, BAC-8007-36, BAC-8205-36, STE-8001W36, KMC SimplyVAV
Source document
EZvav Digital Controls - Installation and Operation Manual · IOM-EZVAVINST · rev. 2016-10 (cover dated 7-2016)
Download CSV 74 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Nailor’s current documentation and the live device before use. Not official Nailor information. Terms of use.

BMS integration notes: Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36)

Integration in brief

Set the device instance, MAC and baud from the STE-8001W36 COMM menu. Monitor AV 1 space temperature, AV 3/AV 4 active setpoints, AV 24 actual airflow and AV 50 damper position (BAC-8205-36); the occupied setpoints are AV 5/AV 6 and MSV 1 is the occupancy mode. BV 1-3 and BV 7 are requests to the air handler.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1OCCUPIED MODEOccupancy mode of the boxWrite
AV 5OCC CL STPTOccupied cooling setpointWrite
AV 6OCC HT SPTOccupied heating setpointWrite
AV 1SPACE TEMPSpace temperatureRead
AV 3ACT COOL STPTCooling setpoint in useRead
AV 4ACT HEAT STPTHeating setpoint in useRead
AV 24PRI ACTUAL FLOWMeasured primary airflowRead
AV 50DAMPER POSITIONDamper positionRead
BV 1NEED AHUBox needs the air handler runningRead

Network setup

Watch out for

Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

74 of 74 shown
Type
Multi-stateOther
Access
Show
Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) BACnet Points List
DescriptionStates
AI1DISCHARGE AIRDischarge Air Temperature (input type KMC10K_Type_III)Read
AI2SPACE SENSORSpace Sensor (input type KMC Type II Deg F)Read
AI3SPACE SET POINTSpace Set point (input type TABLE_4)Read
AI4PRIMARY DUCTPrimary Duct PressureRead
AI5SECONDARY DUCTSecondary Duct PressureRead
AO3ANALOG HEATAnalog Heat%Read
AO4FAN SPEEDFan Speed%Read
BO1DAMPER CWDamper ClockwiseRead
BO2DAMPER CCWDamper Counter ClockwiseRead
BO5FANFanRead
BO6HT STAGE 1Heating Stage 1Read
BO7HT STAGE 2Heating Stage 2Read
BO8HT STAGE 3Heating Stage3Read
AVmin1SPACE TEMPSpace TemperatureRead
AV2STPT REFERENCESet point ReferenceRead
AVmin3ACT COOL STPTActive Cooling Set pointRead
AVmin4ACT HEAT STPTActive Heating Set pointRead
AVmin5OCC CL STPTOccupied Cooling Set pointWrite
AVmin6OCC HT SPTOccupied Heating Set pointWrite
AV7UNOCC CL STPTUnoccupied Cooling Set pointWrite
AV8UNOCC HT STPTUnoccupied Heating Set pointWrite
AV9MIN CL STPTMinimum Cooling Set pointWrite
AV10MAX HT STPTMaximum Heating Set pointWrite
AV11MIN STPT DIFFMinimum Set point DifferentialWrite
AV12STBY DIFFStandby DifferentialWrite
AV13MIN COOL FLOWMinimum Cooling FlowWrite
AV14MAX COOL FLOWMaximum Cooling FlowWrite
AV15MIN HEAT FLOWMinimum Heating FlowWrite
AV16MAX HEAT FLOWMaximum Heating FlowWrite
AV17AUXILIARY FLOWAuxiliary FlowWrite
AV18PRI K FACTPrimary K FactorWrite
AV19PRI CORR SLOPEPrimary Correction SlopeWrite
AV20PRI CORR OFFSTPrimary Correction OffsetWrite
AV21PRI LO FLOW CORRPrimary Low Flow CorrectionWrite
AV22PRI FLOW STPTPrimary Flow Set pointWrite
AV23PRI RAW FLOWPrimary Raw FlowRead
AVmin24PRI ACTUAL FLOWPrimary Actual FlowRead
AV32MIN FAN SPEEDMinimum Fan SpeedWrite
AV33MAX FAN SPEEDMaximum Fan SpeedWrite
AV36DAT STPTDischarge Air Temp Set pointWrite
AV37SAT CHANGEOVERSAT Changeover TemperatureWrite
AV38LOCAL OVRD TIMELocal Override TimerRead
AV39STANDBY TIMEStandby Timer (motion)Write
AV40STANDBY TRIGGERStandby TriggerWrite
AV43MEASURED MAXMeasured MaximumRead
AV44MEASURED MINMeasured MinimumRead
AV45PRI SAVE MIN FLOPrimary Saved Minimum AirflowRead
AV47DAT MAXIMUMMaximum DAT Set pointWrite
AV48CW DMP POSCW Damper Position (BAC-8205-36 only)Read
AV49CCW DMP POSCCW Damper Position (BAC-8205-36 only)Read
AVmin50DAMPER POSITIONDamper Position (BAC-8205-36 only)Read
AV55CHNG_OVER_DELAYCooling Change Over DelayWrite
AV56LOW AUTO OCCLow Limit for Auto OccupyWrite
BVmin1NEED AHUNeed For AHURead
BV2NEED COLDER SPLYNeed For Colder Air SupplyRead
BV3NEED MORE STATICNeed For AHURead
BV4LOCAL OVRDLocal Override ModeRead
BV5MOTION OVRDMotion Override ModeRead
BV6MOTION SENSORMotion Sensor (Wall Stat)Read
BV7NEED HOTTER SPLYNeed For Hotter Air SupplyRead
BV8CHANGE OVER MODESAT Changeover ModeRead
BV9DAT LIMITINGDischarge Air Temp LimitingRead
BV10CLOCKWISE CLOSEClockwise CloseWrite
BV11AUTO OCCUPANCYAuto Occupancy DetectionWrite
BV12BALANCE MODEBalance ModeWrite
BV13DAT SENSORDAT Sensor PresentWrite
BV14PRI BAL TRIGGERPrimary Balance TriggerWrite
MVmin1OCCUPIED MODEOccupied ModeWrite
MV2FAN CONFIGFantype ConfigurationWrite
MV3REHEATReheat TypeWrite
MV6WALL SENSORMulti-state Value #6Write
LO1CL LOOPCooling LoopRead
LO2HT LOOPHeating LoopRead
LO3DAT LoopDischarge Air Temp LoopRead
Object ID lookup: Nailor EZvav Digital VAV Controls point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36)

How many BACnet points does the Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) have?

This list has 74 BACnet objects: 5 analog inputs, 2 analog outputs, 40 analog values, 6 binary outputs, 14 binary values, 3 loops, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) BACnet points are writable?

36 of the 74 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36) BACnet documentation?

The source is EZvav Digital Controls - Installation and Operation Manual (IOM-EZVAVINST), revision 2016-10 (cover dated 7-2016), published free by Nailor at https://nailor.com/sites/default/files/documents/EZVAVINST_2.pdf.

What are the minimum BACnet points to integrate the Nailor EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36)?

Start with MV 1 OCCUPIED MODE (Occupancy mode of the box); AV 5 OCC CL STPT (Occupied cooling setpoint); AV 6 OCC HT SPT (Occupied heating setpoint); AV 1 SPACE TEMP (Space temperature); AV 3 ACT COOL STPT (Cooling setpoint in use); AV 4 ACT HEAT STPT (Heating setpoint in use); AV 24 PRI ACTUAL FLOW (Measured primary airflow); AV 50 DAMPER POSITION (Damper position); BV 1 NEED AHU (Box needs the air handler running).

How do I check these points on the real EZvav Digital VAV Controls (BAC-8001-36 / 8005-36 / 8007-36 / 8205-36)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Nailor BACnet points lists

Source: EZvav Digital Controls - Installation and Operation Manual · IOM-EZVAVINST · rev. 2016-10 (cover dated 7-2016). Object names, instances and units are reproduced as published; descriptions are our own.