Fan coil unit thermostat-controller · BACnet points list

Nailor EZstat Fan Coil Controller (EC-EZstat) BACnet points list

Updated 28 October 2026

Short answer

The EZstat is a BACnet MS/TP application-specific controller (built on a KMC platform) that runs fan coil sequences either stand-alone or networked. The manual lists the objects most useful for monitoring: inputs, outputs, setpoint and status values, a schedule object and four PID loops. Output object names change between the two-pipe and four-pipe applications, and not every input object is present in every model.

This page lists 59 BACnet objects for the Nailor EZstat Fan Coil Controller (EC-EZstat) — 52 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Nailor’s own free documentation, linked below.

Manufacturer
Nailor
Model
EZstat Fan Coil Controller (EC-EZstat)
Equipment
Fan coil unit thermostat-controller
Equipment type
VAV boxes & fan coils
BACnet objects
59 (52 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
EZstat, EC-EZstat, Engineered Comfort EZstat
Source document
Fan Coil Controller EZstat Installation and Operation Manual · EC-EZstat · rev. 2020-11
Download CSV 59 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Nailor EZstat Fan Coil Controller (EC-EZstat)

Integration in brief

Set device instance, MAC and baud from the COMM menu, then map space temperature, the occupied setpoints, system and occupied modes and the fan points. Occupancy normally follows the internal BACnet schedule (SCHED_1 writing BV5), which a workstation can edit, or another BACnet device can command occupancy directly.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 2SYSTEM_MODEHeat / cool / auto / offWrite
BV 5OCC_SCHEDULEOccupancy command; the internal schedule also writes itWrite
MV 1OCCUPIED_MODEOccupied modeWrite
AV 5OCC_CL_STPTOccupied cooling setpointWrite
AV 6OCC_HT_STPTOccupied heating setpointWrite
AV 34FAN_SPEEDFan speed, %Write
BV 14FAN_STATUSFan proof statusWrite
AV 1SPACE_TEMPSpace temperature used for controlRead

Enable & remote start

The EZstat runs stand-alone; occupancy comes from its internal schedule (SCH 1 writing BV5 OCC_SCHEDULE) and can also be commanded by another BACnet device or workstation. Without the schedule enabled it starts occupied.

Network setup

Watch out for

Nailor EZstat Fan Coil Controller (EC-EZstat) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

59 of 59 shown
Type
Multi-state
Access
Show
Nailor EZstat Fan Coil Controller (EC-EZstat) BACnet Points List
DescriptionStates
AI1REMOTE_SENSORRemote room sensor input (KMC 10K Type II)Read
AI2WATER_TEMPWater temperature input (KMC 10K Type III)Read
AI3DATDischarge air temperature input (KMC 10K Type II)Read
AI4LOCAL_SENSORBuilt-in space temperature sensorRead
AO6ANALOG VALVEAnalog valve output, 0-10 V (4-pipe: ANALOG_COOLING)%Command
AO7ANALOG AUX HEATAuxiliary heat output, 0-10 V (4-pipe: ANALOG_HEATING)%Command
AO8ANALOG FANFan speed control, 0-10 V (4-pipe: ANALOG_FAN)%Command
BO1LOWFan low speedCommand
BO2MEDIUMFan medium speedCommand
BO3HIGHFan high speedCommand
BO4STAGE_2_HEATStage 2 heat (4-pipe: BINARY_COOLING, cooling valve)Command
BO5STAGE_1_HEATStage 1 heat (4-pipe: BINARY_HEATING, heating valve)Command
AV3ACT_COOL_STPTActive cooling setpointWrite
AV4ACT_HEAT_STPTActive heating setpointWrite
AVmin5OCC_CL_STPTOccupied cooling setpointWrite
AVmin6OCC_HT_STPTOccupied heating setpointWrite
AV7UNOCC_CL_STPTUnoccupied cooling setpointWrite
AV8UNOCC_HT_STPTUnoccupied heating setpointWrite
AV9MAX_CL_STPTCooling setpoint limit (listed as Minimum Cooling Setpoint)Write
AV10MAX_HT_STPTMaximum heating setpointWrite
AV11MIN_STPT_DIFFMinimum heating/cooling setpoint differentialWrite
AV12STBY_OFFSETStandby offsetWrite
AV25FAN_OFF_DELAYFan off delayWrite
AV31Max_VLV_LOWMaximum valve at low fan speed%Write
AV32Max_VLV_MEDMaximum valve at medium fan speed%Write
AV33Max_VLV_HIGHMaximum valve at high fan speed%Write
AVmin34FAN_SPEEDFan speed%Write
AV35FAN_COOL_MAXFan cooling maximum speed%Write
AV36FAN_MINIMUMFan minimum speed%Write
AV37FAN_HEAT_MAXFan heating maximum speed%Write
AV38OVRD_TIMELocal override timerminWrite
AVmin1SPACE_TEMPSpace temperature used for controlRead
AV19WATER_TEMPWater temperatureRead
AV20DISCHARGE_TEMPDischarge air temperatureRead
BVmin5OCC_SCHEDULEOccupancy from schedule (schedule reference)Write
BV6DAT_ENABLEDischarge air temperature control enableWrite
BV7DAT_SENSORDischarge air sensor presentWrite
BV9FAN_NEEDCall for fanWrite
BV10COOL_HEAT_NEEDCooling or heating neededWrite
BV11SPEED_UPSpeed up timers x15Write
BV13OCCUPIED_FANFan on during occupied modeWrite
BVmin14FAN_STATUSFan proofWrite
BV15MOD_FAN_ACTIONModulating or stepped fan actionWrite
BV16AUTO_FAN_RESETReset fan back to autoWrite
BV18CL_VLV_ACTIONCooling valve normally closed/openWrite
BV19HT_VLV_ACTIONHeating valve normally closed/openWrite
BV20COOL_STG_1Cooling stage 1Write
BV22HEAT_STG_1Heating stage 1Write
BV28LOCAL_OVRDLocal override modeWrite
BV36STPT_HOLDHold temperature setpointWrite
MVmin1OCCUPIED_MODEOccupied modeWrite
MVmin2SYSTEM_MODEControl (system) modeWrite
MV3FAN_MODEFan auto/manual modeWrite
MV4AVAILABLE_SPEEDSNumber of fan speeds availableWrite
SCH1SCHED_1Occupancy schedule #1, writes BV5Write
LO1CL LOOPCooling loop (fan, on room temperature)Write
LO2HT LOOPHeating loop (fan, on room temperature)Write
LO3CL_DAT LOOPCooling loop on DAT setpoint (valves)Write
LO4HT_DAT LOOPHeating loop on DAT setpoint (valves)Write

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EZstat Fan Coil Controller (EC-EZstat) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Nailor EZstat Fan Coil Controller (EC-EZstat)

How many BACnet points does the Nailor EZstat Fan Coil Controller (EC-EZstat) have?

This list has 59 BACnet objects: 4 analog inputs, 3 analog outputs, 22 analog values, 5 binary outputs, 16 binary values, 4 loops, 1 schedule, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Nailor EZstat Fan Coil Controller (EC-EZstat) BACnet points are writable?

52 of the 59 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Nailor EZstat Fan Coil Controller (EC-EZstat) BACnet documentation?

The source is Fan Coil Controller EZstat Installation and Operation Manual (EC-EZstat), revision 2020-11, published free by Nailor at https://nailor.com/sites/default/files/documents/EC-EZSTATINST.pdf.

What are the minimum BACnet points to integrate the Nailor EZstat Fan Coil Controller (EC-EZstat)?

Start with MV 2 SYSTEM_MODE (Heat / cool / auto / off); BV 5 OCC_SCHEDULE (Occupancy command; the internal schedule also writes it); MV 1 OCCUPIED_MODE (Occupied mode); AV 5 OCC_CL_STPT (Occupied cooling setpoint); AV 6 OCC_HT_STPT (Occupied heating setpoint); AV 34 FAN_SPEED (Fan speed, %); BV 14 FAN_STATUS (Fan proof status); AV 1 SPACE_TEMP (Space temperature used for control).

How do I enable BMS control of the Nailor EZstat Fan Coil Controller (EC-EZstat)?

The EZstat runs stand-alone; occupancy comes from its internal schedule (SCH 1 writing BV5 OCC_SCHEDULE) and can also be commanded by another BACnet device or workstation. Without the schedule enabled it starts occupied.

How do I check these points on the real EZstat Fan Coil Controller (EC-EZstat)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Fan Coil Controller EZstat Installation and Operation Manual · EC-EZstat · rev. 2020-11. Object names, instances and units are reproduced as published; descriptions are our own.