Water treatment controller · BACnet points list

Marley MarleyGard CD controller (BACnet) BACnet points list

Updated 4 November 2026

Short answer

The MarleyGard CD is a cooling-tower water treatment controller. It is a BACnet IP device that reports conductivity, pH, ORP, temperatures, water and flow meter totals, flow rates and 4-20 mA inputs for up to four systems, the setpoints and alarm limits, relay states and a large set of alarm flags. Every object in this list is read-only.

This page lists 453 BACnet objects for the Marley MarleyGard CD controller (BACnet) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Marley’s own free documentation, linked below.

Manufacturer
Marley
Model
MarleyGard CD controller (BACnet)
Equipment
Water treatment controller
Equipment type
Other equipment
BACnet objects
453 (0 writable)
Transport
BACnet IP
Firmware
JA.12.1 and higher
Also known as
MarleyGard CD, MarleyGard, Marley water treatment controller, SPX Cooling, Z1069147
Source document
MarleyGard CD controller supplemental - BACnet Communications user manual · Z1069147 · rev. 2018-04
Download CSV 453 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Marley’s current documentation and the live device before use. Not official Marley information. Terms of use.

BMS integration notes: Marley MarleyGard CD controller (BACnet)

Integration in brief

Treat the MarleyGard CD as a monitoring device: read the chemistry inputs (conductivity, pH, ORP) and the flow switch for each system in use, and map the per-system All Alarms flags (BV 11, 80, 149, 218) as summary alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 0AI-000System 1 conductivityRead
AI 8AI-008System 1 pHRead
AI 12AI-012System 1 ORPRead
BI 0BI-000System 1 flow switchRead
BV 11BV-011System 1: any active alarmRead

Network setup

Watch out for

Marley MarleyGard CD controller (BACnet) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

453 of 453 shown
Type
Multi-state
Show
Marley MarleyGard CD controller (BACnet) BACnet Points List
DescriptionStates
BImin0BI-000System #1 – Flow SwitchRead
BI1BI-001System #2 – Flow SwitchRead
BI2BI-002System #3 – Flow SwitchRead
BI3BI-003System #4 – Flow SwitchRead
BV0BV-000System #1 – Conductivity AlarmRead
BV1BV-001System #1 – pH AlarmRead
BV2BV-002System #1 – ORP AlarmRead
BV3BV-003System #1 – S. Temp AlarmRead
BV4BV-004System #1 – M. Temp AlarmRead
BV5BV-005System #1 – D. Temp AlarmRead
BV6BV-006System #1 – Timer 1 AlarmRead
BV7BV-007System #1 – Timer 2 AlarmRead
BV8BV-008System #1 – Timer 3 AlarmRead
BV9BV-009System #1 – Timer 4 AlarmRead
BV10BV-010System #1 – Timer 5 AlarmRead
BVmin11BV-011System #1 – All AlarmsRead
BV12BV-012System #1 – Conductivity High AlarmRead
BV13BV-013System #1 – Conductivity Low AlarmRead
BV14BV-014System #1 – Conductivity Limit AlarmRead
BV15BV-015System #1 – pH High AlarmRead
BV16BV-016System #1 – pH Low AlarmRead
BV17BV-017System #1 – pH Limit AlarmRead
BV18BV-018System #1 – ORP High AlarmRead
BV19BV-019System #1 – ORP Low AlarmRead
BV20BV-020System #1 – ORP Limit AlarmRead
BV21BV-021System #1 – S. Temp High AlarmRead
BV22BV-022System #1 – S. Temp Low AlarmRead
BV23BV-023System #1 – M. Temp High AlarmRead
BV24BV-024System #1 – M. Temp Low AlarmRead
BV25BV-025System #1 – D. Temp High AlarmRead
BV26BV-026System #1 – D. Temp Low AlarmRead
BV27BV-027System #1 – No Flow AlarmRead
BV28BV-028System #1 – Digital Input 1 AlarmRead
BV29BV-029System #1 – Digital Input 2 AlarmRead
BV30BV-030System #1 – Digital Input 3 AlarmRead
BV31BV-031System #1 – Digital Input 4 AlarmRead
BV32BV-032System #1 – Digital Input 5 AlarmRead
BV33BV-033System #1 – M. Conductivity AlarmRead
BV34BV-034System #1 – M. Conductivity High AlarmRead
BV35BV-035System #1 – M. Conductivity Low AlarmRead
BV36BV-036System #1 – M. Conductivity Limit AlarmRead
BV37BV-037System #1 – Notepad 1 High AlarmRead
BV38BV-038System #1 – Notepad 2 High AlarmRead
BV39BV-039System #1 – Notepad 3 High AlarmRead
BV40BV-040System #1 – Notepad 4 High AlarmRead
BV41BV-041System #1 – Notepad 5 High AlarmRead
BV42BV-042System #1 – Notepad 6 High AlarmRead
BV43BV-043System #1 – Notepad 7 High AlarmRead
BV44BV-044System #1 – Notepad 8 High AlarmRead
BV45BV-045System #1 – Notepad 9 High AlarmRead
BV46BV-046System #1 – Notepad 10 High AlarmRead
BV47BV-047System #1 – Notepad 1 Low AlarmRead
BV48BV-048System #1 – Notepad 2 Low AlarmRead
BV49BV-049System #1 – Notepad 3 Low AlarmRead
BV50BV-050System #1 – Notepad 4 Low AlarmRead
BV51BV-051System #1 – Notepad 5 Low AlarmRead
BV52BV-052System #1 – Notepad 6 Low AlarmRead
BV53BV-053System #1 – Notepad 7 Low AlarmRead
BV54BV-054System #1 – Notepad 8 Low AlarmRead
BV55BV-055System #1 – Notepad 9 Low AlarmRead
BV56BV-056System #1 – Notepad 10 Low AlarmRead
BV57BV-057System #1 – Notepad 1 Time AlarmRead
BV58BV-058System #1 – Notepad 2 Time AlarmRead
BV59BV-059System #1 – Notepad 3 Time AlarmRead
BV60BV-060System #1 – Notepad 4 Time AlarmRead
BV61BV-061System #1 – Notepad 5 Time AlarmRead
BV62BV-062System #1 – Notepad 6 Time AlarmRead
BV63BV-063System #1 – Notepad 7 Time AlarmRead
BV64BV-064System #1 – Notepad 8 Time AlarmRead
BV65BV-065System #1 – Notepad 9 Time AlarmRead
BV66BV-066System #1 – Notepad 10 Time AlarmRead
BV67BV-067System #1 – pH 2 AlarmRead
BV68BV-068System #1 – ORP 2 AlarmRead
BV69BV-069System #2 – Conductivity AlarmRead
BV70BV-070System #2 – pH AlarmRead
BV71BV-071System #2 – ORP AlarmRead
BV72BV-072System #2 – S. Temp AlarmRead
BV73BV-073System #2 – M. Temp AlarmRead
BV74BV-074System #2 – D. Temp AlarmRead
BV75BV-075System #2 – Timer 1 AlarmRead
BV76BV-076System #2 – Timer 2 AlarmRead
BV77BV-077System #2 – Timer 3 AlarmRead
BV78BV-078System #2 – Timer 4 AlarmRead
BV79BV-079System #2 – Timer 5 AlarmRead
BV80BV-080System #2 – All AlarmsRead
BV81BV-081System #2 – Conductivity High AlarmRead
BV82BV-082System #2 – Conductivity Low AlarmRead
BV83BV-083System #2 – Conductivity Limit AlarmRead
BV84BV-084System #2 – pH High AlarmRead
BV85BV-085System #2 – pH Low AlarmRead
BV86BV-086System #2 – pH Limit AlarmRead
BV87BV-087System #2 – ORP High AlarmRead
BV88BV-088System #2 – ORP Low AlarmRead
BV89BV-089System #2 – ORP Limit AlarmRead
BV90BV-090System #2 – S. Temp High AlarmRead
BV91BV-091System #2 – S. Temp Low AlarmRead
BV92BV-092System #2 – M. Temp High AlarmRead
BV134BV-134System #2 – Notepad 9 Time AlarmRead
BV135BV-135System #2 – Notepad 10 Time AlarmRead
BV136BV-136System #2 – pH 2 AlarmRead
BV137BV-137System #2 – ORP 2 AlarmRead
BV138BV-138System #3 – Conductivity AlarmRead
BV139BV-139System #3 – pH AlarmRead
BV140BV-140System #3 – ORP AlarmRead
BV141BV-141System #3 – S. Temp AlarmRead
BV142BV-142System #3 – M. Temp AlarmRead
BV143BV-143System #3 – D. Temp AlarmRead
BV144BV-144System #3 – Timer 1 AlarmRead
BV145BV-145System #3 – Timer 2 AlarmRead
BV146BV-146System #3 – Timer 3 AlarmRead
BV147BV-147System #3 – Timer 4 AlarmRead
BV148BV-148System #3 – Timer 5 AlarmRead
BV149BV-149System #3 – All AlarmsRead
BV150BV-150System #3 – Conductivity High AlarmRead
BV151BV-151System #3 – Conductivity Low AlarmRead
BV152BV-152System #3 – Conductivity Limit AlarmRead
BV153BV-153System #3 – pH High AlarmRead
BV154BV-154System #3 – pH Low AlarmRead
BV155BV-155System #3 – pH Limit AlarmRead
BV156BV-156System #3 – ORP High AlarmRead
BV157BV-157System #3 – ORP Low AlarmRead
BV158BV-158System #3 – ORP Limit AlarmRead
BV159BV-159System #3 – S. Temp High AlarmRead
BV160BV-160System #3 – S. Temp Low AlarmRead
BV161BV-161System #3 – M. Temp High AlarmRead
BV162BV-162System #3 – M. Temp Low AlarmRead
BV163BV-163System #3 – D. Temp High AlarmRead
BV164BV-164System #3 – D. Temp Low AlarmRead
BV165BV-165System #3 – No Flow AlarmRead
BV166BV-166System #3 – Digital Input 1 AlarmRead
BV167BV-167System #3 – Digital Input 2 AlarmRead
BV168BV-168System #3 – Digital Input 3 AlarmRead
BV169BV-169System #3 – Digital Input 4 AlarmRead
BV170BV-170System #3 – Digital Input 5 AlarmRead
BV171BV-171System #3 – M. Conductivity AlarmRead
BV172BV-172System #3 – M. Conductivity High AlarmRead
BV173BV-173System #3 – M. Conductivity Low AlarmRead
BV174BV-174System #3 – M. Conductivity Limit AlarmRead
BV175BV-175System #3 – Notepad 1 High AlarmRead
BV176BV-176System #3 – Notepad 2 High AlarmRead
BV177BV-177System #3 – Notepad 3 High AlarmRead
BV178BV-178System #3 – Notepad 4 High AlarmRead
BV179BV-179System #3 – Notepad 5 High AlarmRead
BV180BV-180System #3 – Notepad 6 High AlarmRead
BV181BV-181System #3 – Notepad 7 High AlarmRead
BV182BV-182System #3 – Notepad 8 High AlarmRead
BV183BV-183System #3 – Notepad 9 High AlarmRead
BV184BV-184System #3 – Notepad 10 High AlarmRead
BV185BV-185System #3 – Notepad 1 Low AlarmRead
BV186BV-186System #3 – Notepad 2 Low AlarmRead
BV187BV-187System #3 – Notepad 3 Low AlarmRead
BV188BV-188System #3 – Notepad 4 Low AlarmRead
BV189BV-189System #3 – Notepad 5 Low AlarmRead
BV190BV-190System #3 – Notepad 6 Low AlarmRead
BV191BV-191System #3 – Notepad 7 Low AlarmRead
BV192BV-192System #3 – Notepad 8 Low AlarmRead
BV193BV-193System #3 – Notepad 9 Low AlarmRead
BV194BV-194System #3 – Notepad 10 Low AlarmRead
BV195BV-195System #3 – Notepad 1 Time AlarmRead
BV196BV-196System #3 – Notepad 2 Time AlarmRead
BV197BV-197System #3 – Notepad 3 Time AlarmRead
BV198BV-198System #3 – Notepad 4 Time AlarmRead
BV199BV-199System #3 – Notepad 5 Time AlarmRead
BV200BV-200System #3 – Notepad 6 Time AlarmRead
BV201BV-201System #3 – Notepad 7 Time AlarmRead
BV202BV-202System #3 – Notepad 8 Time AlarmRead
BV203BV-203System #3 – Notepad 9 Time AlarmRead
BV204BV-204System #3 – Notepad 10 Time AlarmRead
BV205BV-205System #3 – pH 2 AlarmRead
BV206BV-206System #3 – ORP 2 AlarmRead
BV207BV-207System #4 – Conductivity AlarmRead
BV208BV-208System #4 – pH AlarmRead
BV209BV-209System #4 – ORP AlarmRead
BV210BV-210System #4 – S. Temp AlarmRead
BV211BV-211System #4 – M. Temp AlarmRead
BV212BV-212System #4 – D. Temp AlarmRead
BV213BV-213System #4 – Timer 1 AlarmRead
BV214BV-214System #4 – Timer 2 AlarmRead
BV215BV-215System #4 – Timer 3 AlarmRead
BV216BV-216System #4 – Timer 4 AlarmRead
BV217BV-217System #4 – Timer 5 AlarmRead
BV218BV-218System #4 – All AlarmsRead
BV219BV-219System #4 – Conductivity High AlarmRead
BV220BV-220System #4 – Conductivity Low AlarmRead
BV221BV-221System #4 – Conductivity Limit AlarmRead
BV222BV-222System #4 – pH High AlarmRead
BV223BV-223System #4 – pH Low AlarmRead
BV224BV-224System #4 – pH Limit AlarmRead
BV225BV-225System #4 – ORP High AlarmRead
BV226BV-226System #4 – ORP Low AlarmRead
BV227BV-227System #4 – ORP Limit AlarmRead
BV228BV-228System #4 – S. Temp High AlarmRead
BV229BV-229System #4 – S. Temp Low AlarmRead
BV230BV-230System #4 – M. Temp High AlarmRead
BV231BV-231System #4 – M. Temp Low AlarmRead
BV232BV-232System #4 – D. Temp High AlarmRead
BV233BV-233System #4 – D. Temp Low AlarmRead
BV234BV-234System #4 – No Flow AlarmRead
BV235BV-235System #4 – Digital Input 1 AlarmRead
BV236BV-236System #4 – Digital Input 2 AlarmRead
BV237BV-237System #4 – Digital Input 3 AlarmRead
BV238BV-238System #4 – Digital Input 4 AlarmRead
BV239BV-239System #4 – Digital Input 5 AlarmRead
BV240BV-240System #4 – M. Conductivity AlarmRead
BV241BV-241System #4 – M. Conductivity High AlarmRead
BV242BV-242System #4 – M. Conductivity Low AlarmRead
BV243BV-243System #4 – M. Conductivity Limit AlarmRead
BV244BV-244System #4 – Notepad 1 High AlarmRead
BV245BV-245System #4 – Notepad 2 High AlarmRead
BV246BV-246System #4 – Notepad 3 High AlarmRead
BV247BV-247System #4 – Notepad 4 High AlarmRead
BV248BV-248System #4 – Notepad 5 High AlarmRead
BV249BV-249System #4 – Notepad 6 High AlarmRead
BV250BV-250System #4 – Notepad 7 High AlarmRead
BV251BV-251System #4 – Notepad 8 High AlarmRead
BV252BV-252System #4 – Notepad 9 High AlarmRead
BV253BV-253System #4 – Notepad 10 High AlarmRead
BV254BV-254System #4 – Notepad 1 Low AlarmRead
BV255BV-255System #4 – Notepad 2 Low AlarmRead
BV256BV-256System #4 – Notepad 3 Low AlarmRead
BV257BV-257System #4 – Notepad 4 Low AlarmRead
BV258BV-258System #4 – Notepad 5 Low AlarmRead
BV259BV-259System #4 – Notepad 6 Low AlarmRead
BV260BV-260System #4 – Notepad 7 Low AlarmRead
BV261BV-261System #4 – Notepad 8 Low AlarmRead
BV262BV-262System #4 – Notepad 9 Low AlarmRead
BV263BV-263System #4 – Notepad 10 Low AlarmRead
BV264BV-264System #4 – Notepad 1 Time AlarmRead
BV265BV-265System #4 – Notepad 2 Time AlarmRead
BV266BV-266System #4 – Notepad 3 Time AlarmRead
BV267BV-267System #4 – Notepad 4 Time AlarmRead
BV268BV-268System #4 – Notepad 5 Time AlarmRead
BV269BV-269System #4 – Notepad 6 Time AlarmRead
BV270BV-270System #4 – Notepad 7 Time AlarmRead
BV271BV-271System #4 – Notepad 8 Time AlarmRead
BV272BV-272System #4 – Notepad 9 Time AlarmRead
BV273BV-273System #4 – Notepad 10 Time AlarmRead
BV274BV-274System #4 – pH 2 AlarmRead
BV275BV-275System #4 – ORP 2 AlarmRead
BV276BV-276ma Input 1 AlarmRead
BV277BV-277ma Input 1 High AlarmRead
BV278BV-278ma Input 1 Low AlarmRead
BV279BV-279ma Input 2 AlarmRead
BV280BV-280ma Input 2 High AlarmRead
BV281BV-281ma Input 2 Low AlarmRead
BV282BV-282ma Input 3 AlarmRead
BV283BV-283ma Input 3 High AlarmRead
BV284BV-284ma Input 3 Low AlarmRead
BV285BV-285ma Input 4 AlarmRead
BV286BV-286ma Input 4 High AlarmRead
BV287BV-287ma Input 4 Low AlarmRead
BV288BV-288ma Input 5 AlarmRead
BV289BV-289ma Input 5 High AlarmRead
BV290BV-290ma Input 5 Low AlarmRead
BV291BV-291ma Input 6 AlarmRead
BV292BV-292ma Input 6 High AlarmRead
BV293BV-293ma Input 6 Low AlarmRead
BV294BV-294ma Input 7 AlarmRead
BV295BV-295ma Input 7 High AlarmRead
BV296BV-296ma Input 7 Low AlarmRead
BV297BV-297ma Input 8 AlarmRead
BV298BV-298ma Input 8 High AlarmRead
BV299BV-299ma Input 8 Low AlarmRead
AImin0AI-000System #1 – ConductivityRead
AI1AI-001System #2 – ConductivityRead
AI2AI-002System #3 – ConductivityRead
AI3AI-003System #4 – ConductivityRead
AI4AI-004System #1 – M. ConductivityRead
AI5AI-005System #2 – M. ConductivityRead
AI6AI-006System #3 – M. ConductivityRead
AI7AI-007System #4 – M. ConductivityRead
AImin8AI-008System #1 – pHRead
AI9AI-009System #2 – pHRead
AI10AI-010System #3 – pHRead
AI11AI-011System #4 – pHRead
AImin12AI-012System #1 – ORPRead
AI13AI-013System #2 – ORPRead
AI14AI-014System #3 – ORPRead
AI15AI-015System #4 – ORPRead
AI16AI-016System #1 – S. TempRead
AI17AI-017System #2 – S. TempRead
AI18AI-018System #3 – S. TempRead
AI19AI-019System #4 – S. TempRead
AI20AI-020System #1 – M. TempRead
AI21AI-021System #2 – M. TempRead
AI22AI-022System #3 – M. TempRead
AI23AI-023System #4 – M. TempRead
AI24AI-024Sys #1 – Water Meter #1 - Total ValueRead
AI25AI-025Sys #2 – Water Meter #1 - Total ValueRead
AI26AI-026Sys #3 – Water Meter #1 - Total ValueRead
AI27AI-027Sys #4 – Water Meter #1 - Total ValueRead
AI28AI-028Sys #1 – Water Meter #2 - Total ValueRead
AI29AI-029Sys #2 – Water Meter #2 - Total ValueRead
AI30AI-030Sys #3 – Water Meter #2 - Total ValueRead
AI31AI-031Sys #4 – Water Meter #2 - Total ValueRead
AI32AI-032System #1 – M.CyclesRead
AI33AI-033System #2 – M.CyclesRead
AI34AI-034System #3 – M.CyclesRead
AI35AI-035System #4 – M.CyclesRead
AI36AI-0364-20 mA / 0-5V Input #1 - ValueRead
AI37AI-0374-20 mA / 0-5V Input #2 - ValueRead
AI38AI-0384-20 mA / 0-5V Input #3 - ValueRead
AI39AI-0394-20 mA / 0-5V Input #4 - ValueRead
AI40AI-0404-20 mA / 0-5V Input #5 - ValueRead
AI41AI-0414-20 mA / 0-5V Input #6 - ValueRead
AI42AI-0424-20 mA / 0-5V Input #7 - ValueRead
AI43AI-0434-20 mA / 0-5V Input #8 - ValueRead
AI44AI-044Flow Meter #1 – Total ValueRead
AI45AI-045Flow Meter #2 – Total ValueRead
AI46AI-046Flow Meter #3 – Total ValueRead
AI47AI-047Flow Meter #4 – Total ValueRead
AI48AI-048Flow Meter #5 – Total ValueRead
AI49AI-049Flow Meter #6 – Total ValueRead
AI50AI-050Flow Meter #7 – Total ValueRead
AI51AI-051Flow Meter #8 – Total ValueRead
AI52AI-052Flow Meter #9 – Total ValueRead
AI53AI-053Flow Meter #10 – Total ValueRead
AI54AI-054Flow Meter #1 – Flow Rate (per MIN)Read
AI55AI-055Flow Meter #2 – Flow Rate (per MIN)Read
AI56AI-056Flow Meter #3 – Flow Rate (per MIN)Read
AI57AI-057Flow Meter #4 – Flow Rate (per MIN)Read
AI58AI-058Flow Meter #5 – Flow Rate (per MIN)Read
AI59AI-059Flow Meter #6 – Flow Rate (per MIN)Read
AI60AI-060Flow Meter #7 – Flow Rate (per MIN)Read
AI61AI-061Flow Meter #8 – Flow Rate (per MIN)Read
AI62AI-062Flow Meter #9 – Flow Rate (per MIN)Read
AI63AI-063Flow Meter #10 – Flow Rate (per MIN)Read
AV0AV-000System #1 – Conductivity Setpoint #1Read
AV1AV-001System #2 – Conductivity Setpoint #1Read
AV2AV-002System #3 – Conductivity Setpoint #1Read
AV3AV-003System #4 – Conductivity Setpoint #1Read
AV4AV-004System #1 – Conductivity Setpoint #2Read
AV5AV-005System #2 – Conductivity Setpoint #2Read
AV6AV-006System #3 – Conductivity Setpoint #2Read
AV7AV-007System #4 – Conductivity Setpoint #2Read
AV8AV-008System #1 – Conductivity High AlarmRead
AV9AV-009System #2 – Conductivity High AlarmRead
AV10AV-010System #3 – Conductivity High AlarmRead
AV11AV-011System #4 – Conductivity High AlarmRead
AV12AV-012System #1 – Conductivity Low AlarmRead
AV13AV-013System #2 – Conductivity Low AlarmRead
AV14AV-014System #3 – Conductivity Low AlarmRead
AV15AV-015System #4 – Conductivity Low AlarmRead
AV16AV-016System #1 – M. Conductivity SetpointRead
AV17AV-017System #2 – M. Conductivity SetpointRead
AV18AV-018System #3 – M. Conductivity SetpointRead
AV19AV-019System #4 – M. Conductivity SetpointRead
AV20AV-020System #1 – M. Conductivity High AlarmRead
AV21AV-021System #2 – M. Conductivity High AlarmRead
AV22AV-022System #3 – M. Conductivity High AlarmRead
AV23AV-023System #4 – M. Conductivity High AlarmRead
AV24AV-024System #1 – M. Conductivity Low AlarmRead
AV25AV-025System #2 – M. Conductivity Low AlarmRead
AV26AV-026System #3 – M. Conductivity Low AlarmRead
AV27AV-027System #4 – M. Conductivity Low AlarmRead
AV28AV-028System #1 – pH Setpoint #1Read
AV29AV-029System #2 – pH Setpoint #1Read
AV30AV-030System #3 – pH Setpoint #1Read
AV31AV-031System #4 – pH Setpoint #1Read
AV32AV-032System #1 – pH Setpoint #2Read
AV33AV-033System #2 – pH Setpoint #2Read
AV34AV-034System #3 – pH Setpoint #2Read
AV35AV-035System #4 – pH Setpoint #2Read
AV36AV-036System #1 – pH High AlarmRead
AV37AV-037System #2 – pH High AlarmRead
AV38AV-038System #3 – pH High AlarmRead
AV39AV-039System #4 – pH High AlarmRead
AV40AV-040System #1 – pH Low AlarmRead
AV41AV-041System #2 – pH Low AlarmRead
AV42AV-042System #3 – pH Low AlarmRead
AV43AV-043System #4 – pH Low AlarmRead
AV44AV-044System #1 – ORP Setpoint #1Read
AV45AV-045System #2 – ORP Setpoint #1Read
AV46AV-046System #3 – ORP Setpoint #1Read
AV47AV-047System #4 – ORP Setpoint #1Read
AV48AV-048System #1 – ORP Setpoint #2Read
AV49AV-049System #2 – ORP Setpoint #2Read
AV50AV-050System #3 – ORP Setpoint #2Read
AV51AV-051System #4 – ORP Setpoint #2Read
AV52AV-052System #1 – ORP High AlarmRead
AV53AV-053System #2 – ORP High AlarmRead
AV54AV-054System #3 – ORP High AlarmRead
AV55AV-055System #4 – ORP High AlarmRead
AV56AV-056System #1 – ORP Low AlarmRead
AV57AV-057System #2 – ORP Low AlarmRead
AV58AV-058System #3 – ORP Low AlarmRead
AV59AV-059System #4 – ORP Low AlarmRead
AV60AV-060System #1 – S. Temp SetpointRead
AV61AV-061System #2 – S. Temp SetpointRead
AV62AV-062System #3 – S. Temp SetpointRead
AV63AV-063System #4 – S. Temp SetpointRead
AV64AV-064System #1 – S. Temp High AlarmRead
AV65AV-065System #2 – S. Temp High AlarmRead
AV66AV-066System #3 – S. Temp High AlarmRead
AV67AV-067System #4 – S. Temp High AlarmRead
AV68AV-068System #1 – S. Temp Low AlarmRead
AV69AV-069System #2 – S. Temp Low AlarmRead
AV70AV-070System #3 – S. Temp Low AlarmRead
AV71AV-071System #4 – S. Temp Low AlarmRead
AV72AV-072System #1 – M. Temp SetpointRead
AV73AV-073System #2 – M. Temp SetpointRead
AV74AV-074System #3 – M. Temp SetpointRead
AV75AV-075System #4 – M. Temp SetpointRead
AV76AV-076System #1 – M. Temp High AlarmRead
AV77AV-077System #2 – M. Temp High AlarmRead
AV78AV-078System #3 – M. Temp High AlarmRead
AV79AV-079System #4 – M. Temp High AlarmRead
AV80AV-080System #1 – M. Temp Low AlarmRead
AV81AV-081System #2 – M. Temp Low AlarmRead
AV82AV-082System #3 – M. Temp Low AlarmRead
AV83AV-083System #4 – M. Temp Low AlarmRead
AV84AV-084System #1 – D. Temp SetpointRead
AV85AV-085System #2 – D. Temp SetpointRead
AV86AV-086System #3 – D. Temp SetpointRead
AV87AV-087System #4 – D. Temp SetpointRead
AV88AV-088System #1 – D. Temp High AlarmRead
AV89AV-089System #2 – D. Temp High AlarmRead
AV90AV-090System #3 – D. Temp High AlarmRead
AV91AV-091System #4 – D. Temp High AlarmRead
AV92AV-092System #1 – D. Temp Low AlarmRead
AV93AV-093System #2 – D. Temp Low AlarmRead
AV94AV-094System #3 – D. Temp Low AlarmRead
AV95AV-095System #4 – D. Temp Low AlarmRead
AV96AV-096System #1 – Flow Switch Conf.Read
AV97AV-097System #2 – Flow Switch Conf.Read
AV98AV-098System #3 – Flow Switch Conf.Read
AV99AV-099System #4 – Flow Switch Conf.Read
AV100AV-100mA 1 - Output ValueRead
AV101AV-101mA 2 - Output ValueRead
AV102AV-102mA 3 - Output ValueRead
AV103AV-103mA 4 - Output ValueRead
AV104AV-104mA 5 - Output ValueRead
AV105AV-105mA 6 - Output ValueRead
MV0MSV-000Relay 1 – StateRead
MV1MSV-001Relay 2 – StateRead
MV2MSV-002Relay 3 – StateRead
MV3MSV-003Relay 4 – StateRead
MV4MSV-004Relay 5 – StateRead
MV5MSV-005Relay 6 – StateRead
MV6MSV-006Relay 7 – StateRead
MV7MSV-007Relay 8 – StateRead
MV8MSV-008Relay 9 – StateRead
MV9MSV-009Relay 10 – StateRead
MV10MSV-010Relay 11 – StateRead
MV11MSV-011Relay 12 – StateRead
MV12MSV-012Relay 13 – StateRead
MV13MSV-013Relay 14 – StateRead
MV14MSV-014Relay 15 – StateRead
MV15MSV-015Relay 16 – StateRead
MV16MSV-016Relay 17 – StateRead
MV17MSV-017Relay 18 – StateRead
MV18MSV-018Relay 19 – StateRead
MV19MSV-019Relay 20 – StateRead
Object ID lookup: Marley MarleyGard CD controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MarleyGard CD controller (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Marley MarleyGard CD controller (BACnet)

How many BACnet points does the Marley MarleyGard CD controller (BACnet) have?

This list has 453 BACnet objects: 64 analog inputs, 106 analog values, 4 binary inputs, 259 binary values, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Marley MarleyGard CD controller (BACnet) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Marley MarleyGard CD controller (BACnet) BACnet documentation?

The source is MarleyGard CD controller supplemental - BACnet Communications user manual (Z1069147), revision 2018-04, published free by Marley at https://spxcooling.com/pdf/Z1069147.pdf.

What are the minimum BACnet points to integrate the Marley MarleyGard CD controller (BACnet)?

Start with AI 0 AI-000 (System 1 conductivity); AI 8 AI-008 (System 1 pH); AI 12 AI-012 (System 1 ORP); BI 0 BI-000 (System 1 flow switch); BV 11 BV-011 (System 1: any active alarm).

How do I check these points on the real MarleyGard CD controller (BACnet)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Marley BACnet points lists

Source: MarleyGard CD controller supplemental - BACnet Communications user manual · Z1069147 · rev. 2018-04. Object names, instances and units are reproduced as published; descriptions are our own.