Cooling tower BACnet interface panel · BACnet points list

Marley MarleyGard LINK BACnet/IP Panel BACnet points list

Updated 28 October 2026

Short answer

The MarleyGard LINK is an add-on enclosure with a Contemporary Controls BAScontrol22C I/O module that turns status contacts and 4-20 mA signals from a Marley tower control panel into BACnet/IP objects. It is a monitoring interface: inputs cover vibration, gearbox oil level, basin level and temperature, makeup water, basin heater, and on CoolBoost fluid coolers the spray pumps and dampers. Marley VFDs with a LINK interface connect over Ethernet separately.

This page lists 24 BACnet objects for the Marley MarleyGard LINK BACnet/IP Panel — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Marley’s own free documentation, linked below.

Manufacturer
Marley
Model
MarleyGard LINK BACnet/IP Panel
Equipment
Cooling tower BACnet interface panel
Equipment type
Cooling towers & fluid coolers
BACnet objects
24 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
MarleyGard LINK, Marley LINK, SPX Cooling LINK panel, BAScontrol22C, Z1126362
Source document
MarleyGard LINK BACnet/IP Communication Panel - User Manual (Installation - Operation) · Z1126362 · rev. 2020-09
Download CSV 24 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Marley MarleyGard LINK BACnet/IP Panel

Integration in brief

Plug the BMS into the LINK panel's RJ45 port, browse to the module (default 192.168.92.68), set the IP settings and a unique BACnet device instance and name, then discover and read the inputs. The panel only monitors; start/stop and speed stay with the Marley control panel or VFD.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 6WATER_TEMP_CWBBasin water temp; raw 4-20 mA, scale in the BMSRead
BI 12VIB_SW_TRIPHigh-vibration shutdownRead
BI 10OIL_LVL_ALMGearbox low oilRead
BI 3WATER_LOW_ALMBasin low waterRead
BI 5WATER_HIGH_ALMBasin high waterRead
BI 1BASIN_HEATER_FAILBasin heater failureRead

Network setup

Watch out for

Marley MarleyGard LINK BACnet/IP Panel BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

24 of 24 shown
Type
AnalogBinary
Show
Marley MarleyGard LINK BACnet/IP Panel BACnet Points List
DescriptionStates
BImin12VIB_SW_TRIPVibration switch trip (tower shutdown, high vibration)Read
BI11VIB_SW_ALMVibration switch alarm (rising vibration notice)Read
AI8VIB_LVL_XMTRVibration level transmitter, loop powered by panel or switchmARead
BImin10OIL_LVL_ALMGearbox low oil levelRead
AI7WATER_LVL_CWBCold water basin level transmittermARead
AImin6WATER_TEMP_CWBCold water basin temperature transmittermARead
BImin5WATER_HIGH_ALMCold water basin high levelRead
BI4WATER_MAKEUP_ONMakeup water solenoid valve openRead
BImin3WATER_LOW_ALMCold water basin low levelRead
BI9BASIN_HEATER_ONBasin heater drawing currentRead
BImin1BASIN_HEATER_FAILBasin heater failed (no current)Read
BI2SPARESpare binary inputRead
BI9SPRAY_PUMP_1_ONModule 2: spray pump 1 contactor energizedRead
BI10SPRAY_PUMP_1_TRIPModule 2: spray pump 1 motor overload tripRead
BI11SPRAY_PUMP_2_ONModule 2: spray pump 2 contactor energizedRead
BI12SPRAY_PUMP_2_TRIPModule 2: spray pump 2 motor overload tripRead
BI1SPRAY_PUMP_SAFETY_TRIPModule 2: spray pump low or freezing water tripRead
BI2DAMPER_1_OPENModule 2: damper 1 contactor energizedRead
BI3DAMPER_1_OPEN_END_SWModule 2: damper 1 open end switch closedRead
BI4DAMPER_1_CLOSED_END_SWModule 2: damper 1 closed end switch closedRead
BI5DAMPER_2_OPENModule 2: damper 2 contactor energizedRead
BI6DAMPER_2_OPEN_END_SWModule 2: damper 2 open end switch closedRead
BI7DAMPER_2_CLOSED_END_SWModule 2: damper 2 closed end switch closedRead
BI8SPAREModule 2: spare binary inputRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MarleyGard LINK BACnet/IP Panel and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Marley MarleyGard LINK BACnet/IP Panel

How many BACnet points does the Marley MarleyGard LINK BACnet/IP Panel have?

This list has 24 BACnet objects: 3 analog inputs, 21 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Marley MarleyGard LINK BACnet/IP Panel BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Marley MarleyGard LINK BACnet/IP Panel BACnet documentation?

The source is MarleyGard LINK BACnet/IP Communication Panel - User Manual (Installation - Operation) (Z1126362), revision 2020-09, published free by Marley at https://spxcooling.com/wp-content/uploads/Z1126362.pdf.

What are the minimum BACnet points to integrate the Marley MarleyGard LINK BACnet/IP Panel?

Start with AI 6 WATER_TEMP_CWB (Basin water temp; raw 4-20 mA, scale in the BMS); BI 12 VIB_SW_TRIP (High-vibration shutdown); BI 10 OIL_LVL_ALM (Gearbox low oil); BI 3 WATER_LOW_ALM (Basin low water); BI 5 WATER_HIGH_ALM (Basin high water); BI 1 BASIN_HEATER_FAIL (Basin heater failure).

How do I check these points on the real MarleyGard LINK BACnet/IP Panel?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: MarleyGard LINK BACnet/IP Communication Panel - User Manual (Installation - Operation) · Z1126362 · rev. 2020-09. Object names, instances and units are reproduced as published; descriptions are our own.