- BZ122-LX configurable VAV controller (Onyxx LX)
VAV box controller · BACnet points list
Lynxspring BZ122-LX configurable VAV controller (Onyxx LX) BACnet points list
Updated 12 November 2026Unofficial source
The BZ122-LX is a configurable (not programmable) VAV controller with an integrated actuator and airflow sensor that works with TZ series room sensors. Its BACnet MS/TP map is fixed: airflow and damper I/O, room and supply temperatures, occupied/unoccupied setpoints, airflow limits, five auxiliary outputs for reheat or fans, PID loops and configuration multi-states.
This page lists 112 BACnet objects for the Lynxspring BZ122-LX configurable VAV controller (Onyxx LX) — 75 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Lynxspring’s documentation hosted by Cochrane Supply, not by Lynxspring itself, so treat it as unofficial.
- Manufacturer
- Lynxspring
- Model
- BZ122-LX configurable VAV controller (Onyxx LX)
- Equipment
- VAV box controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 112 (75 writable)
- Transport
- BACnet MS/TP
- Firmware
- Onyxx LX UI software 4.0 or later, firmware 2.182 or later
- Also known as
- BZ122-LX, BZ122, Onyxx LX BZ122, Onyxx LX VAV controller
- Source document
- BZ122-LX Configurable VAV MS/TP - Installation and Wiring Guide (unofficial copy, hosted by Cochrane Supply)
Reference only, provided as-is: verify against Lynxspring’s current documentation and the live device before use. Not official Lynxspring information. Terms of use.
BMS integration notes: Lynxspring BZ122-LX configurable VAV controller (Onyxx LX)
Set the address and baud on the DIP switches, configure box type, airflow limits and auxiliary outputs, then command occupancy (MSV 24) and the occupied setpoints. Read room temperature, airflow, damper position and the validation error code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 24 | OccMode | Occupancy command | Write |
| AV 12 | RTSPclg_Occ | Occupied cooling setpoint | Write |
| AV 13 | RTSPhtg_Occ | Occupied heating setpoint | Write |
| AV 41 | RoomT | Room temperature | Read |
| AI 5 | zAirFlow | Measured airflow | Read |
| AV 2 | zActiveFlowSP | Active airflow setpoint | Read |
| AO 2 | zActMod | Damper position, % | Read |
| AV 44 | DSsupplyT | Discharge air temp after reheat | Read |
| AV 39 | ValidationErr | Configuration error code (0 = none) | Read |
Network setup
- MS/TP address is set on DIP switch bank DS2 (1-127); baud on DS1: 010 = 9600, 110 = 19200, 001 = 38400, 011 = 76800.
- An EOL jumper terminates the MS/TP trunk on the last controller; a second jumper terminates the TZ sensor bus.
- Firmware updates use a USB-COM adapter or a USB to MS/TP converter cable.
Watch out for
- K-factor (AV 30) and duct area (AV 31) must match the box for airflow to read right.
- BV 10 saves objects to flash and restarts the controller; do not write it cyclically.
Lynxspring BZ122-LX configurable VAV controller (Onyxx LX) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | AI_1 | Analog input 1 | Read | ||
| AImin | 5 | zAirFlow | Air flow sensor | Read | ||
| AO | 0 | AO_1 | Analog output 1 | % | Read | |
| AO | 1 | AO_2 | Analog output 2 | % | Read | |
| AOmin | 2 | zActMod | Damper actuator (modulating) | % | Read | |
| AO | 3 | BO_1 | Binary output 1 | Read | ||
| AO | 4 | BO_2 | Binary output 2 | Read | ||
| AV | 0 | zRunTime | Running time of the actuator (floating) | s | Write | |
| AVmin | 2 | zActiveFlowSP | Active flow setpoint | Read | ||
| AV | 3 | MaxAFpos | Maximum airflow (or position) | Write | ||
| AV | 4 | MinAFpos | Minmum airflow (or position) | Write | ||
| AV | 5 | MinAFpos_Htg | Min. AF (or position) @ 100% heating | Write | ||
| AV | 6 | MinAFpos_Clg | Min. AF (or position) @ 100% cooling | Write | ||
| AV | 10 | RTSPmin_Occ | Minimum Room temp. setpoint | °F | Write | |
| AV | 11 | RTSPmax_Occ | Maximum Room temp. setpoint | °F | Write | |
| AVmin | 12 | RTSPclg_Occ | Room temp. cooling setpoint, occupied | °F | Write | |
| AVmin | 13 | RTSPhtg_Occ | Room temp. heating setpoint, occupied | °F | Write | |
| AV | 14 | RTSP_DeadBand | RTSP deadband between Clg and Htg | °F | Write | |
| AV | 15 | RTSPclg_Unocc | Room temp. cooling setpoint, unoccupied | °F | Write | |
| AV | 16 | RTSPhtg_Unocc | Room temp. heating setpoint, unoccupied | °F | Write | |
| AV | 17 | RTSPclg_STBdt | Standby mode, RTSP clg offset (pos.) | °F | Write | |
| AV | 18 | RTSPhtg_STBdt | Standby mode, RTSP htg offset (neg.) | °F | Write | |
| AV | 19 | ActiveRTSP_Clg | Active cooling room temp. setpoint | Read | ||
| AV | 20 | ActiveRTSP_Htg | Active heating room temp. setpoint | Read | ||
| AV | 21 | DSHL_SP | Downstream high limit setpoint | °F | Write | |
| AV | 22 | DSLL_SP | Downstream low limit setpoint | °F | Write | |
| AV | 23 | ChOver_SP | ChOver temp. SP (constant or RoomT+X) | °F | Write | |
| AV | 25 | Calib_RoomT | Room temp. calibration | °F | Write | |
| AV | 26 | Calib_RoomSP | Room temp. Setpoint calibration | °F | Write | |
| AV | 27 | Calib_usT | Upstream temp. calibration | °F | Write | |
| AV | 28 | Calib_dsT | Downstream temp. calibration | °F | Write | |
| AV | 30 | K_Factor | Constant from Pitot characteristics | Write | ||
| AV | 31 | DuctArea | Duct area | Write | ||
| AV | 33 | MinOffTime_Htg | Minimum OFF time, heating (BO) | s | Write | |
| AV | 34 | MinOffTime_Clg | Minimum OFF time, cooling (BO) | s | Write | |
| AV | 35 | MotionTime | Motion sensor active time | min | Write | |
| AV | 36 | OvrTime | Occupancy override active time | min | Write | |
| AV | 37 | MaxPower | Maximum power allowed | % | Write | |
| AV | 38 | OvrRemainTime | Override remaining time | s | Read | |
| AVmin | 39 | ValidationErr | 0 = no error | Read | ||
| AVmin | 41 | RoomT | Room Temperature | °F | Read | |
| AV | 42 | RoomSP | Room Temperature Setpoint | °F | Write | |
| AV | 43 | USsupplyT | Upstream supply temp. (from main fan) | °F | Read | |
| AVmin | 44 | DSsupplyT | Downstream supply temp. (after reheat) | °F | Read | |
| AV | 46 | AuxA_Out | Auxiliary output A | % | Read | |
| AV | 47 | AuxB_Out | Auxiliary output B | % | Read | |
| AV | 48 | AuxC_Out | Auxiliary output C | % | Read | |
| AV | 49 | AuxD_Out | Auxiliary output D, (Tzone #2) | % | Read | |
| AV | 50 | AuxE_Out | Auxiliary output E, (Tzone #3) | % | Read | |
| AV | 52 | EncodedVal1 | Internal Use | Read | ||
| AV | 53 | EncodedVal2 | Internal Use | Read | ||
| AV | 55 | ActiveTz2SPHtg | Active heating Tzone #2 setpoint | Write | ||
| AV | 56 | ActiveTz2SPClg | Active cooling Tzone #2 setpoint | Write | ||
| AV | 57 | ActiveTz3SPHtg | Active heating Tzone #3 setpoint | Write | ||
| AV | 58 | ActiveTz3SPClg | Active cooling Tzone #3 setpoint | Write | ||
| AV | 64 | RoomRH | Room relative humidity | % | Read | |
| AV | 65 | RoomCO2 | Room carbin dioxide (CO2) | ppm | Read | |
| AV | 66 | RoomCO2SP | Room CO2 Setpoint | ppm | Write | |
| AV | 67 | RoomCO2Dem | Room CO2 demand | % | Read | |
| BV | 0 | ActRotation | Actuator rotation direction | Write | 0=Direct, 1=Reverse | |
| BV | 1 | FanStatus | FanStatus | Read | 0=Off, 1=On | |
| BV | 2 | DewPtHL | Dewpoint Temperature High Limit | Write | 0=32°F (0°C), 1=122°F (50°C) | |
| BV | 3 | OccSched | Occupancy schedule | Write | 0=Night, 1=Day | |
| BV | 4 | OvrStatus | Occupancy override status | Read | 0=Inactive, 1=Active | |
| BV | 10 | SaveAndRestart | Saves Objects to Flash and restart | Write | 0=Off, 1=On | |
| BV | 24 | TZstatus | TZxxx communications status | Read | 0=Normal, 1=Fault | |
| MV | 1 | Units_Type | Units configuration (temp. & Airflow) | Write | 1=°F, CFM, 2=°C, CFM, 3=°F, LS, 4=°C, LS | |
| MV | 2 | Tstor10K_Type | Thermistors type (std type 3 or type 2) | Write | 1=Type 3 (std), 2=Type 2 | |
| MV | 4 | AuxA_Loc | Auxiliary output A physical location | Write | 1=None, 2=AO-1, 3=AO-2, 4=BO-1, 5=BO-2, 6=Float BO-1,2 | |
| MV | 5 | AuxA_Type | Auxiliary output A control type | Write | 1=None, 2=Elect. Reheat, 3=Water Reheat, 4=Elect. Bboard, 5=Water Bboard, 6=DX Cool, 7=Water Cool | |
| MV | 6 | AuxA_Formula | Auxiliary output A formula | Write | 1=0-10 VDC, Dir., 2=0-10 VDC, Rev., 3=2-10 VDC, Dir., 4=2-10 VDC, Rev, 5=On-Off, 6=Pulse, Dir., 7=Pulse, Rev. | |
| MV | 7 | AuxA_Auto | Auxiliary output A authorization | Write | 1=Never, 2=Always, 3=FanStatus, 4=MaxPower, 5=Fan+MaxPwr | |
| MV | 8 | AuxB_Loc | Auxiliary output B physical location | Write | 1=None, 2=AO-1, 3=AO-2, 4=BO-1, 5=BO-2, 6=Float BO-1,2 | |
| MV | 9 | AuxB_Type | Auxiliary output B control type | Write | 1=None, 2=Elect. Reheat, 3=Water Reheat, 4=Elect. Bboard, 5=Water Bboard, 6=DX Cool, 7=Water Cool | |
| MV | 10 | AuxB_Formula | Auxiliary output B formula | Write | 1=0-10 VDC, Dir., 2=0-10 VDC, Rev., 3=2-10 VDC, Dir., 4=2-10 VDC, Rev, 5=On-Off, 6=Pulse, Dir., 7=Pulse, Rev. | |
| MV | 11 | AuxB_Auto | Auxiliary output B authorization | Write | 1=Never, 2=Always, 3=FanStatus, 4=MaxPower, 5=Fan+MaxPwr | |
| MV | 12 | AuxC_Loc | Auxiliary output C physical location | Write | 1=None, 2=AO-1, 3=AO-2, 4=BO-1, 5=BO-2, 6=BO-3, 7=BO-4, 8=Float BO-1,2 | |
| MV | 13 | AuxC_Type | Auxiliary output C control type | Write | 1=None, 2=Elect. Reheat, 3=Water Reheat, 4=Elect. Bboard, 5=Water Bboard, 6=DX Cool, 7=Water Cool, 8=Parallel Fan, 9=Series Fan | |
| MV | 14 | AuxC_Formula | Auxiliary output C formula | Write | 1=0-10 VDC, Dir., 2=0-10 VDC, Rev., 3=2-10 VDC, Dir., 4=2-10 VDC, Rev, 5=On-Off, 6=Pulse, Dir., 7=Pulse, Rev. | |
| MV | 15 | AuxC_Auto | Auxiliary output C authorization | Write | 1=Never, 2=Always, 3=FanStatus, 4=MaxPower, 5=Fan+MaxPwr | |
| MV | 17 | RoomT_Loc | Room temp. physical location | Write | 1=None, 2=Elect. Reheat, 3=Water Reheat, 4=Elect. Bboard, 5=Water Bboard, 6=DX Cool, 7=Water Cool | |
| MV | 18 | RoomSP_Loc | Room setpoint location (occupied) | Write | 1=None, 2=AI-1, 3=Tzone, 4=External | |
| MV | 19 | USsupplyT_Loc | Upstream supply temp. loc. (from main fan) | Write | 1=None, 2=AI-1, 3=External | |
| MV | 20 | DSsupplyT_Loc | Downstream supply temp. loc (after reheat) | Write | 1=None, 2=AI-1 | |
| MV | 21 | FanStatus_Loc | Fan status location | Write | 1=None, 2=AI-1(BI), 3=External | |
| MV | 22 | Motion_Loc | Motion sensor location | Write | 1=None, 2=NO, AI-1 (BI), 3=NC, AI-1 (BI), 4=External | |
| MV | 23 | Sched_Loc | Scheduler location | Write | 1=None, 2=AI-1(BI), 3=External | |
| MVmin | 24 | OccMode | Occupancy mode | Write | 1=Unoccupied, 2=Occupied, 3=Standby | |
| MV | 25 | ChOver_Type | Changeover type | Write | 1=None, 2=Constant, 3=RoomT°+Offset | |
| MV | 26 | HtgClgMode | Heating/cooling mode | Write | 1=Heat, 2=Cool, 3=Unused | |
| MV | 27 | VAV_Type | VAV box type (dependent/independent) | Write | 1=Dependent, 2=Independent, 3=Unused | |
| MV | 29 | CoolingWeight | Cooling Weight in demand calculation | Write | 1=0 to 10 | |
| MV | 30 | HeatingWeight | Heating Weight in demand calculation | Write | 1=0 to 10 | |
| MV | 34 | TzControlMode | Control mode with multiple Tzone | Write | 1=Tzone1, 2=Tzone2, 3=Tzone3, 4=Average, 5=Maximum Htg., 6=Maximum Clg. | |
| MV | 35 | AuxD_Loc | Auxiliary output D physical location | Write | 1=None, 2=AO-1, 3=AO-2, 4=BO-1, 5=BO-2, 6=Float BO-1,2 | |
| MV | 36 | AuxD_Type | Auxiliary output D control type | Write | 1=None, 2=Elect. Reheat, 3=Water Reheat, 4=Elect. Bboard, 5=Water Bboard, 6=DX Cool, 7=Water Cool | |
| MV | 37 | AuxD_Formula | Auxiliary output D formula | Write | 1=0-10 VDC, Dir., 2=0-10 VDC, Rev., 3=2-10 VDC, Dir., 4=2-10 VDC, Rev, 5=On-Off, 6=Pulse, Dir., 7=Pulse, Rev. | |
| MV | 38 | AuxD_Auto | Auxiliary output D authorization | Write | 1=Never, 2=Always, 3=FanStatus, 4=MaxPower, 5=Fan+MaxPwr | |
| MV | 39 | AuxE_Loc | Auxiliary output E physical location | Write | 1=None, 2=AO-1, 3=AO-2, 4=BO-1, 5=BO-2, 6=Float BO-1,2 | |
| MV | 40 | AuxE_Type | Auxiliary output E control type | Write | 1=None, 2=Elect. Reheat, 3=Water Reheat, 4=Elect. Bboard, 5=Water Bboard, 6=DX Cool, 7=Water Cool | |
| MV | 41 | AuxE_Formula | Auxiliary output E formula | Write | 1=0-10 VDC, Dir., 2=0-10 VDC, Rev., 3=2-10 VDC, Dir., 4=2-10 VDC, Rev, 5=On-Off, 6=Pulse, Dir., 7=Pulse, Rev. | |
| MV | 42 | AuxE_Auto | Auxiliary output E authorization | Write | 1=Never, 2=Always, 3=FanStatus, 4=MaxPower, 5=Fan+MaxPwr | |
| MV | 62 | RoomTSPType | Room temp setpoint type (in occupied mode) | Write | 1=Heating, 2=Central, 3=Cooling | |
| LO | 0 | zPidFlow | Flow control PID loop (Reverse acting, Kp 0.3, Ki 0.01, bias 50) | Read | ||
| LO | 1 | PidRoomT_Clg | Room temp. control loop, cooling (Direct acting, Kp 20, Ki 0.05, bias 0) | Read | ||
| LO | 2 | PidRoomT_Htg | Room temp. control loop, heating (Reverse acting, Kp 20, Ki 0.05, bias 0) | Read | ||
| LO | 3 | PidHL_DST | Downstream high limit control loop (Reverse acting, Kp 5, Ki 0.1, bias 50) | Read | ||
| LO | 4 | PidLL_DST | Downstream low limit control loop (Direct acting, Kp 5, Ki 0.1, bias 50) | Read | ||
| LO | 6 | PidRoomTz2_Clg | Room temp. control loop, cooling (Direct acting, Kp 20, Ki 0.05, bias 0) | Read | ||
| LO | 7 | PidRoomTz2_Htg | Room temp. control loop, heating (Reverse acting, Kp 20, Ki 0.05, bias 0) | Read | ||
| LO | 8 | PidRoomTz3_Clg | Room temp. control loop, cooling (Direct acting, Kp 20, Ki 0.05, bias 0) | Read | ||
| LO | 9 | PidRoomTz3_Htg | Room temp. control loop, heating (Reverse acting, Kp 20, Ki 0.05, bias 0) | Read |
No points match these filters.
Object ID lookup: Lynxspring BZ122-LX configurable VAV controller point IDs by name
AI0AI_1AI5zAirFlowAO0AO_1AO1AO_2AO2zActModAO3BO_1AO4BO_2AV0zRunTimeAV2zActiveFlowSPAV3MaxAFposAV4MinAFposAV5MinAFpos_HtgAV6MinAFpos_ClgAV10RTSPmin_OccAV11RTSPmax_OccAV12RTSPclg_OccAV13RTSPhtg_OccAV14RTSP_DeadBandAV15RTSPclg_UnoccAV16RTSPhtg_UnoccAV17RTSPclg_STBdtAV18RTSPhtg_STBdtAV19ActiveRTSP_ClgAV20ActiveRTSP_HtgAV21DSHL_SPAV22DSLL_SPAV23ChOver_SPAV25Calib_RoomTAV26Calib_RoomSPAV27Calib_usTAV28Calib_dsTAV30K_FactorAV31DuctAreaAV33MinOffTime_HtgAV34MinOffTime_ClgAV35MotionTimeAV36OvrTimeAV37MaxPowerAV38OvrRemainTimeAV39ValidationErrAV41RoomTAV42RoomSPAV43USsupplyTAV44DSsupplyTAV46AuxA_OutAV47AuxB_OutAV48AuxC_OutAV49AuxD_OutAV50AuxE_OutAV52EncodedVal1AV53EncodedVal2AV55ActiveTz2SPHtgAV56ActiveTz2SPClgAV57ActiveTz3SPHtgAV58ActiveTz3SPClgAV64RoomRHAV65RoomCO2AV66RoomCO2SPAV67RoomCO2DemBV0ActRotationBV1FanStatusBV2DewPtHLBV3OccSchedBV4OvrStatusBV10SaveAndRestartBV24TZstatusMV1Units_TypeMV2Tstor10K_TypeMV4AuxA_LocMV5AuxA_TypeMV6AuxA_FormulaMV7AuxA_AutoMV8AuxB_LocMV9AuxB_TypeMV10AuxB_FormulaMV11AuxB_AutoMV12AuxC_LocMV13AuxC_TypeMV14AuxC_FormulaMV15AuxC_AutoMV17RoomT_LocMV18RoomSP_LocMV19USsupplyT_LocMV20DSsupplyT_LocMV21FanStatus_LocMV22Motion_LocMV23Sched_LocMV24OccModeMV25ChOver_TypeMV26HtgClgModeMV27VAV_TypeMV29CoolingWeightMV30HeatingWeightMV34TzControlModeMV35AuxD_LocMV36AuxD_TypeMV37AuxD_FormulaMV38AuxD_AutoMV39AuxE_LocMV40AuxE_TypeMV41AuxE_FormulaMV42AuxE_AutoMV62RoomTSPTypeLO0zPidFlowLO1PidRoomT_ClgLO2PidRoomT_HtgLO3PidHL_DSTLO4PidLL_DSTLO6PidRoomTz2_ClgLO7PidRoomTz2_HtgLO8PidRoomTz3_ClgLO9PidRoomTz3_Htg
Integration notes
- The guide has no read/write column; access is inferred from its tags (Status = read-only; Cfg, User and Cmd = writable).
- The two binary outputs are printed as AO 3 and AO 4 (named BO_1 and BO_2).
- Some MSV state lists are printed in short form (for example "AI-1, AI-2, AI-3 or AI-4"); those are kept as printed rather than numbered.
- MSV 17 RoomT_Loc prints the reheat type state list (None, Elect. Reheat ...); kept as printed.
- PID loop objects LOOP0-LOOP9 are listed as LO with their printed action and default gains.
- Temperature units are listed as °F; the guide prints °F and °C ranges and the controller can be set to metric.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BZ122-LX configurable VAV controller (Onyxx LX) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Lynxspring BZ122-LX configurable VAV controller (Onyxx LX)
How many BACnet points does the Lynxspring BZ122-LX configurable VAV controller (Onyxx LX) have?
This list has 112 BACnet objects: 2 analog inputs, 5 analog outputs, 52 analog values, 7 binary values, 9 loops, 37 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Lynxspring BZ122-LX configurable VAV controller (Onyxx LX) BACnet points are writable?
75 of the 112 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Lynxspring BZ122-LX configurable VAV controller (Onyxx LX) BACnet documentation?
Lynxspring does not publish it on its own website. This list comes from BZ122-LX Configurable VAV MS/TP - Installation and Wiring Guide, a copy hosted by Cochrane Supply at https://www.cochranesupply.com/media/assets/product/documents/Lynxspring/BZ122%20Installation%20and%20Wiring%20Guide.pdf. Ask Lynxspring or its representative for the current revision.
What are the minimum BACnet points to integrate the Lynxspring BZ122-LX configurable VAV controller (Onyxx LX)?
Start with MV 24 OccMode (Occupancy command); AV 12 RTSPclg_Occ (Occupied cooling setpoint); AV 13 RTSPhtg_Occ (Occupied heating setpoint); AV 41 RoomT (Room temperature); AI 5 zAirFlow (Measured airflow); AV 2 zActiveFlowSP (Active airflow setpoint); AO 2 zActMod (Damper position, %); AV 44 DSsupplyT (Discharge air temp after reheat); AV 39 ValidationErr (Configuration error code (0 = none)).
How do I check these points on the real BZ122-LX configurable VAV controller (Onyxx LX)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Lynxspring BACnet points lists
- Rooftop / air handling unit controller (configurable)
Lynxspring B848-LX / BP848-LX configurable field controller (Onyxx LX)
Lynxspring Onyxx LX B848-LX and BP848-LX configurable MS/TP field controllers (8 UI, 8 BO, 4 AO) set up for RTU, AHU, heat pump or fan coil applications.
Also known as: B848-LX, BP848-LX, B848, BP848, Onyxx LX B848, Onyxx LX BP848 - Fan coil unit controller (wall-mount)
Lynxspring BW437-FCU-LX fan coil unit wall controller (Onyxx LX)
Lynxspring Onyxx LX BW437-FCU-LX wall-mount controllers for 2-pipe and 4-pipe fan coil units over BACnet MS/TP.
Also known as: BW437-FCU-LX, BW437-FCU, BW437FCU, Onyxx LX BW437 FCU, Onyxx LX fan coil wall controller - Rooftop unit controller (wall-mount)
Lynxspring BW437-RTU-LX rooftop unit wall controller (Onyxx LX)
Lynxspring Onyxx LX BW437-RTU-LX wall-mount controllers running packaged rooftop units and heat pumps over BACnet MS/TP.
Also known as: BW437-RTU-LX, BW437-RTU, BW437RTU, Onyxx LX BW437 RTU, Onyxx LX RTU wall controller - VAV box controller
Lynxspring BZ424-LX configurable VAV controller (Onyxx LX)
Lynxspring Onyxx LX BZ424-LX configurable VAV controllers (4 UI, 2 AO, 4 BO, built-in actuator) on BACnet MS/TP.
Also known as: BZ424-LX, BZ424, Onyxx LX BZ424, Onyxx LX VAV controller 4 UI
Source: BZ122-LX Configurable VAV MS/TP - Installation and Wiring Guide. Object names, instances and units are reproduced as published; descriptions are our own.