  4. BW437-FCU-LX fan coil unit wall controller (Onyxx LX)

Fan coil unit controller (wall-mount) · BACnet points list

Lynxspring BW437-FCU-LX fan coil unit wall controller (Onyxx LX) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The BW437-FCU-LX is a wall-mounted fan coil controller with built-in room sensing and three fan speed relays, valve outputs and an auxiliary/reheat output. On BACnet MS/TP it exposes room temperature, humidity and CO2, setpoints by occupancy mode, demands, status flags such as window, filter and service alarms, and configuration multi-states for sequence, fan and input options.

This page lists 87 BACnet objects for the Lynxspring BW437-FCU-LX fan coil unit wall controller (Onyxx LX) — 44 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Lynxspring’s documentation hosted by Cochrane Supply, not by Lynxspring itself, so treat it as unofficial.

Manufacturer
Lynxspring
Model
BW437-FCU-LX fan coil unit wall controller (Onyxx LX)
Equipment
Fan coil unit controller (wall-mount)
Equipment type
VAV boxes & fan coils
BACnet objects
87 (44 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
BW437-FCU-LX, BW437-FCU, BW437FCU, Onyxx LX BW437 FCU, Onyxx LX fan coil wall controller
Source document
BW437-FCU-LX Wall Controller Quick Guide (unofficial copy, hosted by Cochrane Supply)
Download CSV 87 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Lynxspring’s current documentation and the live device before use. Not official Lynxspring information. Terms of use.

BMS integration notes: Lynxspring BW437-FCU-LX fan coil unit wall controller (Onyxx LX)

Integration in brief

Set the sequence of operation and pipe configuration, then command occupancy (MSV 18), system mode (MSV 16) and fan mode (MSV 17) and adjust the occupied setpoints. Read room temperature, effective occupancy, fan status and the filter/service alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 16MODESystem mode (Off/Auto/Cool/Heat)Write
MV 18Occ_CmdOccupancy commandWrite
MV 17FANFan mode (Lo/Med/Hi/Auto)Write
AV 40OccCLSPOccupied cooling setpointWrite
AV 39OccHTSPOccupied heating setpointWrite
MV 33Eff_OccEffective occupancy modeRead
MV 28FanStatFan speed statusRead
AI 5RoomTRoom temperatureRead
BV 36FilterFilter alarmRead
BV 37ServALMService alarmRead

Network setup

Watch out for

Lynxspring BW437-FCU-LX fan coil unit wall controller (Onyxx LX) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

87 of 87 shown
Type
Multi-state
Access
Show
Lynxspring BW437-FCU-LX fan coil unit wall controller (Onyxx LX) BACnet Points List
DescriptionStates
AI1AI_1Analog input 1Read
AI2AI_2Analog input 2Read
AI3AI_3Analog input 3Read
AI4AI_4Remote sensorRead
AImin5RoomTRoom temperature°FRead
AI6RoomRHRoom humidity%Read
AI7RoomCO2Room CO2ppmRead
AO1AO_ECMFan ECM output%Read
AO2AO_2Analog output 2%Read
AO3AO_3Analog output 3%Read
AO4AO_4Auxiliary / Reheat output%Read
BI1MotionMotion detectionRead0=Off, 1=Active
BO1BO_1Binary output 1Read0=Off, 1=On
BO2BO_2Binary output 2Read0=Off, 1=On
BO3BO_3Binary output 3Read0=Off, 1=On
BO4BO_4Binary output 4Read0=Off, 1=On
BO5BO_HighHigh speed fan outputRead0=Off, 1=On
BO6BO_MedMedium speed fan outputRead0=Off, 1=On
BO7BO_LowLow speed fan outputRead0=Off, 1=On
AV1RoomTSPRoom Temperature setpoint°FWrite
AV7Eff_TEffective temperature used for control°FRead
AV9OATempOutdoor air temperature°FRead
AV12SATempSupply air temperature°FRead
AV13CHOV_TChangeover temperature°FRead
AV21HTG_DemHeating demand%Read
AV22CLG_DemCooling demand%Read
AV23Fan_HT__DemandFan heating demand%Read
AV24Fan_CL__DemandFan cooling demand%Read
AV25ECM_MinECM minimum speed output%Write
AV30EffHTSPEffective heating setpoint°FRead
AV31EffCLSPEffective cooling setpoint°FRead
AVmin39OccHTSPOccupied heating setpoint°FWrite
AVmin40OccCLSPOccupied cooling setpoint°FWrite
AV41STBHTSPStandby heating setpoint°FWrite
AV42STBCLSPStandby cooling setpoint°FWrite
AV43Unoc_HT_SPUnoccupied heating setpoint°FWrite
AV44Unoc_CL_SPUnoccupied cooling setpoint°FWrite
AV50RT_CalRoom temperature calibWrite
AV58MaxHTSPMaximum heating setpoint°FWrite
AV59MinCLSPMinimum cooling setpoint°FWrite
AV63SP_DBSetpoint deadband°FWrite
AV67StandbyDLY_HrsStandby time delayhWrite
AV68Unoc_T_DLY_HrsUnoccupied time delayhWrite
BV1SaveObjSave all objects to flashWrite0=Normal, 1=Save
BV8OVRSTATOccupancy override statusRead0=Normal, 1=Overrid
BV14Aux_CmdAuxiliary network commandWrite0=Off, 1=On
BV25AuxStatAuxiliary output statusRead0=Off, 1=On
BV29AI1StatAnalog input 1 binary contact statusRead0=Deactivated, 1=Activated
BV30AI2StatAnalog input 2 binary contact statusRead0=Deactivated, 1=Activated
BV31AI3StatAnalog input 3 binary contact statusRead0=Deactivated, 1=Activated
BV32Mot_DetMotion detectionRead0=None, 1=Moving
BV35WindowWindow detection statusRead0=Close, 1=Open
BVmin36FilterFilter sensor statusRead0=Normal, 1=Alarm
BVmin37ServALMService alarm statusRead0=Normal, 1=Alarm
BV40Ch_OverChange over statusRead0=Cool, 1=Heat
BV50AutoModAuto mode authorisedWrite0=No, 1=Yes
BV51T_UnitsTemperature unitsWrite0=Imper, 1=Metric
BV64Reh_OptReheat control optionWrite0=Pulse1S, 1=On/Off
BV66KeepFanFan auto modeWrite0=Fan Low, 1=Fan Off
BV75VALVCTLValve motors control typeWrite0=On/Off, 1=Floatng
BV78AO2_DirAO2 actionWrite0=Direct, 1=Reverse
BV79AO3_DirAO3 actionWrite0=Direct, 1=Reverse
MV2TsourceTemperature input locationWrite1=AutoDet, 2=Intern, 3=Extern
MV15SeqOperControl sequence of operationWrite1=Cooling, 2=Heating, 3=Cool-Rt, 4=Heat-Rt, 5=Cl-Ht, 6=Cl-Ht-R
MVmin16MODESystem modeWrite1=Off, 2=Auto, 3=Cool, 4=Heat
MVmin17FANFan modeWrite1=Lo, 2=Med, 3=Hi, 4=Auto
MVmin18Occ_CmdOccupancy commandWrite1=Loc_Occ, 2=Occupied, 3=Unoccup
MV19KeyLockKeypad lock levelWrite1=None, 2=Fan, 3=Mode, 4=FanMode, 5=All
MV26BO3_BO4BO3/BO4 statusRead1=Stopped, 2=Open, 3=Close
MV27BO1_BO2BO1/BO2 statusRead1=Stopped, 2=Open, 3=Close
MVmin28FanStatFan statusRead1=Off, 2=Low, 3=Med, 4=High
MVmin33Eff_OccEffective occupancy modeRead1=Occupied, 2=Unoccup, 3=TempOcc, 4=Standby
MV46AI1_CFGAnalog input 1 configurationWrite1=None, 2=Rem NSB, 3=Mot-NO, 4=Mot-NC, 5=Window
MV47AI2_CFGAnalog input 2 configurationWrite1=None, 2=Door Dry (door switch), 3=Overrid (remote local override switch), 4=Filter, 5=Service
MV48AI3_CFGAnalog input 3 configurationWrite1=None, 2=COC/NH (normally heat changeover contact), 3=COC/NH (normally cool changeover contact), 4=COS (changeover sensor), 5=SS (remote monitoring 10K sensor)
MV52PipeNumPipe numberWrite1=2 Pipes, 2=4 Pipes
MV54Aux_CFGAuxiliary output configurationWrite1=Reheat, 2=Occ-NO, 3=Occ-NC, 4=Fan-NO, 5=Fan-NC, 6=Network
MV55ReheatReheat typeWrite1=Basebrd, 2=Coil
MV58Fan_SeqControl fan sequenceWrite1=L-M-H, 2=L-H, 3=L-M-H-A, 4=L-M-H, 5=On-Auto
MV61Occ_OptOccupancy options schedule or motionWrite1=No, 2=S_and_M, 3=S_or_M, 4=Sc-Only
MV62OvrTimeOverride time delayWriteRange 0-24 hours
MV65PBHeating / cooling proportional bandWriteRange 3 F (1.2 C) - 10 F (5.6 C)
MV70SP_AUTOZone Temperature setpoint in auto modeWrite1=Heating, 2=Center, 3=Cooling
MV75BO3TimeBO3/BO4 travel time for 3 states valveWriteRange 0.5-6 min
MV76BO1TimeBO1/BO2 travel time for 3 states valveWriteRange 0.5-6 min
MV77CL_CPHCooling output cycle per hourWriteRange 3-8 CPH
MV78HT_CPHHeating output cycle per hourWriteRange 3-8 CPH
Object ID lookup: Lynxspring BW437-FCU-LX fan coil unit wall controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BW437-FCU-LX fan coil unit wall controller (Onyxx LX) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lynxspring BW437-FCU-LX fan coil unit wall controller (Onyxx LX)

How many BACnet points does the Lynxspring BW437-FCU-LX fan coil unit wall controller (Onyxx LX) have?

This list has 87 BACnet objects: 7 analog inputs, 4 analog outputs, 24 analog values, 1 binary input, 7 binary outputs, 19 binary values, 25 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lynxspring BW437-FCU-LX fan coil unit wall controller (Onyxx LX) BACnet points are writable?

44 of the 87 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Lynxspring BW437-FCU-LX fan coil unit wall controller (Onyxx LX) BACnet documentation?

Lynxspring does not publish it on its own website. This list comes from BW437-FCU-LX Wall Controller Quick Guide, a copy hosted by Cochrane Supply at https://www.cochranesupply.com/media/assets/product/documents/Lynxspring/BW437-FCU-quick-guide.pdf. Ask Lynxspring or its representative for the current revision.

What are the minimum BACnet points to integrate the Lynxspring BW437-FCU-LX fan coil unit wall controller (Onyxx LX)?

Start with MV 16 MODE (System mode (Off/Auto/Cool/Heat)); MV 18 Occ_Cmd (Occupancy command); MV 17 FAN (Fan mode (Lo/Med/Hi/Auto)); AV 40 OccCLSP (Occupied cooling setpoint); AV 39 OccHTSP (Occupied heating setpoint); MV 33 Eff_Occ (Effective occupancy mode); MV 28 FanStat (Fan speed status); AI 5 RoomT (Room temperature); BV 36 Filter (Filter alarm); BV 37 ServALM (Service alarm).

How do I check these points on the real BW437-FCU-LX fan coil unit wall controller (Onyxx LX)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Lynxspring BACnet points lists

Source: BW437-FCU-LX Wall Controller Quick Guide. Object names, instances and units are reproduced as published; descriptions are our own.