Power and energy meter (BACnet MS/TP) · BACnet points list

Leviton VerifEye Series 4100 bi-directional power and energy meter (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The Series 4100 is a compact DIN-rail three-phase meter that measures power and energy in both directions (import and export), for example on sites with solar. Over BACnet MS/TP it serves 83 Analog Inputs for net, import and export energy (total and per phase, real, reactive by quadrant and apparent), power, power factor, voltage, current, frequency and demand, 11 writable Analog Values for setup and commands, and 15 Binary Input alerts.

This page lists 109 BACnet objects for the Leviton VerifEye Series 4100 bi-directional power and energy meter (BACnet MS/TP) — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Leviton’s own free documentation, linked below.

Manufacturer
Leviton
Model
VerifEye Series 4100 bi-directional power and energy meter (BACnet MS/TP)
Equipment
Power and energy meter (BACnet MS/TP)
Equipment type
Thermostats, sensors & meters
BACnet objects
109 (11 writable)
Transport
BACnet MS/TP
Firmware
Application S4100-C
Default device instance
Pseudo-random, 1,000,000-3,097,151
Also known as
Series 4100, S4100, 4DUBM, 41OUB, VerifEye 4100, Leviton 4100 BACnet, Leviton S4100 Energy Meter
Source document
Series 4100 Bi-Directional Compact Power and Energy Meter, BACnet MS/TP Support - Installation Guide
Download CSV 109 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Leviton’s current documentation and the live device before use. Not official Leviton information. Terms of use.

BMS integration notes: Leviton VerifEye Series 4100 bi-directional power and energy meter (BACnet MS/TP)

Integration in brief

Set the MAC address and baud at the meter display, write AV2 System_Type, AV3/AV4 CT settings, AV5 PT ratio and AV6 system voltage, then read net and import/export energy, total power, demand and voltage/current. Read AI83 Alarm_Bitmap (or the BIs) for alerts.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1KWh_NetNet energy (import minus export), kWhRead
AI 2KWh_ImportImported energy, kWhRead
AI 3KWh_ExportExported energy, kWhRead
AI 11KW_TotalTotal real power, kWRead
AI 19KW_Present_DemandPresent real power demand, kWRead
AI 14PF_TotalTotal power factorRead
AI 15Volts_LL_AvgAverage line-to-line voltageRead
AI 17Current AverageAverage phase current, ARead
AI 83Alarm_BitmapAlert bits BI1-BI15 as one numberRead

Network setup

Watch out for

Leviton VerifEye Series 4100 bi-directional power and energy meter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

109 of 109 shown
Type
Binary
Access
Show
Leviton VerifEye Series 4100 bi-directional power and energy meter (BACnet MS/TP) BACnet Points List
DescriptionStates
AV1ConfigCommand register; reads 0Write30078=clear all energy accumulators, 21211=start new demand sub-interval (sync-to-comms), 21212=reset max demand, 16498=clear pulse counters
AV2System_TypeWiring system type (default 40)Write10=Single-phase A+N, 11=Single-phase A+B, 12=Split-phase A+B+N, 31=3-phase A+B+C no N, 40=3-phase Y A+B+C+N
AV3CT_Ratio_PrimaryCT primary current, 5-32000 (default 100)AWrite
AV4CT_Ratio_SecondaryCT secondary: 1 = 1 V CTs (default), 3 = 1/3 V CTsWrite
AV5PT_RatioPT ratio, 0.01-320.0 (default 1 = no PT)Write
AV6System_VoltageSystem voltage, L-L (L-N in type 10), default 600VWrite
AV7Display_UnitsDisplay unitsWrite0=IEC, 1=IEEE (default)
AV8Phase_Loss_Voltage_ThresholdPhase loss voltage threshold, 1-99 (default 10)%Write
AV9Phase_Loss_Imbalance_ThresholdPhase loss imbalance threshold, 1-99 (default 25)%Write
AV10SubintervalsSub-intervals per demand interval, 1-6 (default 1)Write
AV11Subinterval_LengthSub-interval length in 1/100 s; 0 = sync-to-comms (default 90000)Write
AImin1KWh_NetAccumulated Real Energy: Net (Import - Export)kWhRead
AImin2KWh_ImportReal Energy ImportkWhRead
AImin3KWh_ExportReal Energy ExportkWhRead
AI4KVARh_Q1Reactive Energy Quadrant 1kVARhRead
AI5KVARh_Q2Reactive Energy Quadrant 2kVARhRead
AI6KVARh_Q3Reactive Energy Quadrant 3kVARhRead
AI7KVARh_Q4Reactive Energy Quadrant 4kVARhRead
AI8Net_KVAhApparent Energy: Net (Import - Export)kVAhRead
AI9KVAh_ImportApparent Energy ImportkVAhRead
AI10KVAh_ExportApparent Energy ExportkVAhRead
AImin11KW_TotalTotal Instantaneous Real PowerkWRead
AI12KVAR_TotalTotal Instantaneous Reactive PowerkVARRead
AI13KVA_TotalTotal Instantaneous Apparent PowerkVARead
AImin14PF_TotalTotal Power Factor (-1.00 to 1.00)Read
AImin15Volts_LL_AvgVoltage, L-L, Average of Active PhasesVRead
AI16Volts_LN_AvgVoltage, L-N, Average of Active PhasesVRead
AImin17Current AverageCurrent, Average of Active PhasesARead
AI18FrequencyFrequencyHzRead
AImin19KW_Present_DemandTotal Real Power Present DemandkWRead
AI20KVAR_Present_DemandTotal Reactive Power Present DemandkVARRead
AI21KVA_Present_DemandTotal Apparent Power Present DemandkVARead
AI22KW_Max_Demand_ImportTotal Real Power Max Demand ImportkWRead
AI23KVAR_Max_Demand_ImportTotal Reactive Power Max Demand ImportkVARRead
AI24KVA_Max_Demand_ImportTotal Apparent Power Max Demand ImportkVARead
AI25KW_Max_Demand_ExportTotal Real Power Max Demand ExportkWRead
AI26KVAR_Max_Demand_ExportTotal Reactive Power Max Demand ExportkVARRead
AI27KVA_Max_Demand_ExportTotal Apparent Power Max Demand ExportkVARead
AI28Reserved_AI28ReservedRead
AI29Pulse CountPulse count (0-4294967040)Read
AI30ReservedReservedRead
AI31KWh_Import_AReal Energy Import Phase AkWhRead
AI32KWh_Import_BReal Energy Import Phase BkWhRead
AI33KWh_Import_CReal Energy Import Phase CkWhRead
AI34KWh_Export_AReal Energy Export Phase AkWhRead
AI35KWh_Export_BReal Energy Export Phase BkWhRead
AI36KWh_Export_CReal Energy Export Phase CkWhRead
AI37KVARh_Q1_AReactive Energy Q1 Phase AkVARhRead
AI38KVARh_Q1_BReactive Energy Q1 Phase bkVARhRead
AI39KVARh_Q1_CReactive Energy Q1 Phase CkVARhRead
AI40KVARh_Q2_AReactive Energy Q2 Phase AkVARhRead
AI41KVARh_Q2_BReactive Energy Q2 Phase BkVARhRead
AI42KVARh_Q2_CReactive Energy Q2 Phase CkVARhRead
AI43KVARh_Q3_AReactive Energy Q3 Phase AkVARhRead
AI44KVARh_Q3_BReactive Energy Q3 Phase BkVARhRead
AI45KVARh_Q3_CReactive Energy Q3 Phase CkVARhRead
AI46KVARh_Q4_AReactive Energy Q4 Phase AkVARhRead
AI47KVARh_Q4_BReactive Energy Q4 Phase bkVARhRead
AI48KVARh_Q4_CReactive Energy Q4 Phase CkVARhRead
AI49KVAh_Import_AApparent Energy Import Phase AkVAhRead
AI50KVAh_Import_BApparent Energy Import Phase BkVAhRead
AI51KVAh_Import_CApparent Energy Import Phase CkVAhRead
AI52KVAh_Export_AApparent Energy Export Phase AkVAhRead
AI53KVAh_Export_BApparent Energy Export Phase BkVAhRead
AI54KVAh_Export_CApparent Energy Export Phase CkVAhRead
AI55KW_AReal Power Phase AkWRead
AI56KW_BReal Power Phase BkWRead
AI57KW_CReal Power Phase CkWRead
AI58KVAR_AReactive Power Phase AkVARRead
AI59KVAR_BReactive Power Phase BkVARRead
AI60KVAR_CReactive Power Phase CkVARRead
AI61KVA_AApparent Power Phase AkVARead
AI62KVA_BApparent Power Phase BkVARead
AI63KVA_CApparent Power Phase CkVARead
AI64PF_APower Factor Phase ARead
AI65PF_BPower Factor Phase BRead
AI66PF_CPower Factor Phase CRead
AI67Volts_ABVoltage Phase A-BVRead
AI68Volts_BCVoltage Phase B-CVRead
AI69Volts_ACVoltage Phase A-CVRead
AI70Volts_ANVoltage Phase A-NVRead
AI71Volts_BNVoltage Phase B-NVRead
AI72Volts_CNVoltage Phase C-NVRead
AI73Current_ACurrent Phase AARead
AI74Current_BCurrent Phase BARead
AI75Current_CCurrent Phase CARead
AI76Max_PowerMax power (full scale from AV2, AV3, AV5, AV6)kWRead
AI77Reserved_AI77ReservedRead
AI78Energy_ResetsCount of energy resetsRead
AI79Reserved_AI79ReservedRead
AI80Reserved_AI80ReservedRead
AI81Power_Up_CountCount of power-up cyclesRead
AI82Output_ConfigOutput configuration (returns 11)Read
AImin83Alarm_BitmapAlarm bitmap of BI1-BI15Read
BI1Volts_Error_AVoltage out of range, phase ARead0=INACTIVE, 1=ACTIVE
BI2Volts_Error_BVoltage out of range, phase BRead0=INACTIVE, 1=ACTIVE
BI3Volts_Error_CVoltage out of range, phase CRead0=INACTIVE, 1=ACTIVE
BI4Current_Error_ACurrent out of range, phase ARead0=INACTIVE, 1=ACTIVE
BI5Current_Error_ACurrent out of range, phase BRead0=INACTIVE, 1=ACTIVE
BI6Current_Error_ACurrent out of range, phase CRead0=INACTIVE, 1=ACTIVE
BI7Frequency_ErrorFrequency out of rangeRead0=INACTIVE, 1=ACTIVE
BI8Reserved_BI8Reserved, returns INACTIVERead0=INACTIVE, 1=ACTIVE
BI9Phase_Loss_APhase loss, phase ARead0=INACTIVE, 1=ACTIVE
BI10Phase_Loss_BPhase loss, phase BRead0=INACTIVE, 1=ACTIVE
BI11Phase_Loss_CPhase loss, phase CRead0=INACTIVE, 1=ACTIVE
BI12Power_Factor_ALow power factor (<50 %), phase ARead0=INACTIVE, 1=ACTIVE
BI13Power_Factor_BLow power factor (<50 %), phase BRead0=INACTIVE, 1=ACTIVE
BI14Power_Factor_CLow power factor (<50 %), phase CRead0=INACTIVE, 1=ACTIVE
BI15RTC_ResetReal-time clock was reset; time not valid until syncedRead0=INACTIVE, 1=ACTIVE
Object ID lookup: Leviton VerifEye Series 4100 bi-directional power and energy meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VerifEye Series 4100 bi-directional power and energy meter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Leviton VerifEye Series 4100 bi-directional power and energy meter (BACnet MS/TP)

How many BACnet points does the Leviton VerifEye Series 4100 bi-directional power and energy meter (BACnet MS/TP) have?

This list has 109 BACnet objects: 83 analog inputs, 11 analog values, 15 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Leviton VerifEye Series 4100 bi-directional power and energy meter (BACnet MS/TP) BACnet points are writable?

11 of the 109 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Leviton VerifEye Series 4100 bi-directional power and energy meter (BACnet MS/TP) BACnet documentation?

The source is Series 4100 Bi-Directional Compact Power and Energy Meter, BACnet MS/TP Support - Installation Guide, published free by Leviton at https://leviton.com/content/dam/leviton/lighting-controls/controls/product_documents/instruction_sheet/VerifEye-Submetering-Series-4100-BACnet-41OUB-4DUBM-English-User-Guide.pdf.

What are the minimum BACnet points to integrate the Leviton VerifEye Series 4100 bi-directional power and energy meter (BACnet MS/TP)?

Start with AI 1 KWh_Net (Net energy (import minus export), kWh); AI 2 KWh_Import (Imported energy, kWh); AI 3 KWh_Export (Exported energy, kWh); AI 11 KW_Total (Total real power, kW); AI 19 KW_Present_Demand (Present real power demand, kW); AI 14 PF_Total (Total power factor); AI 15 Volts_LL_Avg (Average line-to-line voltage); AI 17 Current Average (Average phase current, A); AI 83 Alarm_Bitmap (Alert bits BI1-BI15 as one number).

How do I check these points on the real VerifEye Series 4100 bi-directional power and energy meter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Leviton BACnet points lists