- Home
- BACnet points lists
- Leviton
- VerifEye Series 8000 multi-circuit meter (3P-08 example)
Power meter (multi-circuit submeter) · BACnet points list
Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example) BACnet points list
Updated 6 November 2026
The Series 8000 is a multi-circuit electrical submeter that reports each configured meter over BACnet IP. Every meter gets total active, reactive and apparent power and power factor, per-element current, voltage, power, power factor and phase angle, present and peak demand, and energy accumulators. The object count scales with the meter configuration; this list is Leviton's 3P-08 example with 216 analog inputs and 40 accumulators.
This page lists 256 BACnet objects for the Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Leviton’s own free documentation, linked below.
- Manufacturer
- Leviton
- Model
- VerifEye Series 8000 multi-circuit meter (3P-08 example)
- Equipment
- Power meter (multi-circuit submeter)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 256 (0 writable)
- Transport
- BACnet IP
- Firmware
- BACnet firmware 1.4.0 or later (Meter Shop configuration tool 1.5.0); example unit 1.41/1.42
- Default device instance
- 4194303
- Also known as
- VerifEye 8000, Series 8000, S8000, PowerHawk, Triacta PowerHawk, PowerHawk 4224-120V-3P-08, 3P-08
Reference only, provided as-is: verify against Leviton’s current documentation and the live device before use. Not official Leviton information. Terms of use.
BMS integration notes: Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example)
A read-only meter: poll or trend the per-meter power, demand and energy objects for the circuits you need. Use the accumulators for energy totals and the present demand objects for load. Configure the meter layout first, because the object count and numbering follow it.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 0 | Meter 1 Active Power | Meter 1 total active power | Read |
| AI 208 | Meter 1 Present Demand | Meter 1 present demand | Read |
| AI 200 | Meter 1 Peak Demand | Meter 1 peak demand | Read |
| AI 24 | Meter 1 Power Factor | Meter 1 power factor | Read |
| AI 32 | Meter 1 Element 0 Current | Meter 1 element 0 current | Read |
| AI 56 | Meter 1 Element 0 Voltage | Meter 1 element 0 voltage | Read |
| ACC 0 | Meter 1 Active Power Delivered Register | Meter 1 delivered active energy, Wh | Read |
Network setup
- BACnet IP on UDP port 47808 by default; BBMD address and timeout (default 60000) are set in the configuration tool.
- Device ID, description, location and object name are set in the Meter Shop / factory configuration tool; the default device ID shown is 4194303.
- The example unit lists vendor ID 425 (Triacta Power Technologies).
Watch out for
- Every meter ships with device ID 4194303; give each one a unique device ID before adding several to a network.
- Writing property 1501 on the device object clears peak demand on every meter at once.
- Object numbering changes with the meter configuration; re-discover objects after changing it.
Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | Meter 1 Active Power | Meter 1 active power, meter total | Read | ||
| AI | 1 | Meter 2 Active Power | Meter 2 active power, meter total | Read | ||
| AI | 2 | Meter 3 Active Power | Meter 3 active power, meter total | Read | ||
| AI | 3 | Meter 4 Active Power | Meter 4 active power, meter total | Read | ||
| AI | 4 | Meter 5 Active Power | Meter 5 active power, meter total | Read | ||
| AI | 5 | Meter 6 Active Power | Meter 6 active power, meter total | Read | ||
| AI | 6 | Meter 7 Active Power | Meter 7 active power, meter total | Read | ||
| AI | 7 | Meter 8 Active Power | Meter 8 active power, meter total | Read | ||
| AI | 8 | Meter 1 Reactive Power | Meter 1 reactive power, meter total | Read | ||
| AI | 9 | Meter 2 Reactive Power | Meter 2 reactive power, meter total | Read | ||
| AI | 10 | Meter 3 Reactive Power | Meter 3 reactive power, meter total | Read | ||
| AI | 11 | Meter 4 Reactive Power | Meter 4 reactive power, meter total | Read | ||
| AI | 12 | Meter 5 Reactive Power | Meter 5 reactive power, meter total | Read | ||
| AI | 13 | Meter 6 Reactive Power | Meter 6 reactive power, meter total | Read | ||
| AI | 14 | Meter 7 Reactive Power | Meter 7 reactive power, meter total | Read | ||
| AI | 15 | Meter 8 Reactive Power | Meter 8 reactive power, meter total | Read | ||
| AI | 16 | Meter 1 Apparent Power | Meter 1 apparent power, meter total | Read | ||
| AI | 17 | Meter 2 Apparent Power | Meter 2 apparent power, meter total | Read | ||
| AI | 18 | Meter 3 Apparent Power | Meter 3 apparent power, meter total | Read | ||
| AI | 19 | Meter 4 Apparent Power | Meter 4 apparent power, meter total | Read | ||
| AI | 20 | Meter 5 Apparent Power | Meter 5 apparent power, meter total | Read | ||
| AI | 21 | Meter 6 Apparent Power | Meter 6 apparent power, meter total | Read | ||
| AI | 22 | Meter 7 Apparent Power | Meter 7 apparent power, meter total | Read | ||
| AI | 23 | Meter 8 Apparent Power | Meter 8 apparent power, meter total | Read | ||
| AImin | 24 | Meter 1 Power Factor | Meter 1 power factor, meter total | Read | ||
| AI | 25 | Meter 2 Power Factor | Meter 2 power factor, meter total | Read | ||
| AI | 26 | Meter 3 Power Factor | Meter 3 power factor, meter total | Read | ||
| AI | 27 | Meter 4 Power Factor | Meter 4 power factor, meter total | Read | ||
| AI | 28 | Meter 5 Power Factor | Meter 5 power factor, meter total | Read | ||
| AI | 29 | Meter 6 Power Factor | Meter 6 power factor, meter total | Read | ||
| AI | 30 | Meter 7 Power Factor | Meter 7 power factor, meter total | Read | ||
| AI | 31 | Meter 8 Power Factor | Meter 8 power factor, meter total | Read | ||
| AImin | 32 | Meter 1 Element 0 Current | Meter 1, element 0 (phase) current | Read | ||
| AI | 33 | Meter 2 Element 0 Current | Meter 2, element 0 (phase) current | Read | ||
| AI | 34 | Meter 3 Element 0 Current | Meter 3, element 0 (phase) current | Read | ||
| AI | 35 | Meter 4 Element 0 Current | Meter 4, element 0 (phase) current | Read | ||
| AI | 36 | Meter 5 Element 0 Current | Meter 5, element 0 (phase) current | Read | ||
| AI | 37 | Meter 6 Element 0 Current | Meter 6, element 0 (phase) current | Read | ||
| AI | 38 | Meter 7 Element 0 Current | Meter 7, element 0 (phase) current | Read | ||
| AI | 39 | Meter 8 Element 0 Current | Meter 8, element 0 (phase) current | Read | ||
| AI | 40 | Meter 1 Element 1 Current | Meter 1, element 1 (phase) current | Read | ||
| AI | 41 | Meter 2 Element 1 Current | Meter 2, element 1 (phase) current | Read | ||
| AI | 42 | Meter 3 Element 1 Current | Meter 3, element 1 (phase) current | Read | ||
| AI | 43 | Meter 4 Element 1 Current | Meter 4, element 1 (phase) current | Read | ||
| AI | 44 | Meter 5 Element 1 Current | Meter 5, element 1 (phase) current | Read | ||
| AI | 45 | Meter 6 Element 1 Current | Meter 6, element 1 (phase) current | Read | ||
| AI | 46 | Meter 7 Element 1 Current | Meter 7, element 1 (phase) current | Read | ||
| AI | 47 | Meter 8 Element 1 Current | Meter 8, element 1 (phase) current | Read | ||
| AI | 48 | Meter 1 Element 2 Current | Meter 1, element 2 (phase) current | Read | ||
| AI | 49 | Meter 2 Element 2 Current | Meter 2, element 2 (phase) current | Read | ||
| AI | 50 | Meter 3 Element 2 Current | Meter 3, element 2 (phase) current | Read | ||
| AI | 51 | Meter 4 Element 2 Current | Meter 4, element 2 (phase) current | Read | ||
| AI | 52 | Meter 5 Element 2 Current | Meter 5, element 2 (phase) current | Read | ||
| AI | 53 | Meter 6 Element 2 Current | Meter 6, element 2 (phase) current | Read | ||
| AI | 54 | Meter 7 Element 2 Current | Meter 7, element 2 (phase) current | Read | ||
| AI | 55 | Meter 8 Element 2 Current | Meter 8, element 2 (phase) current | Read | ||
| AImin | 56 | Meter 1 Element 0 Voltage | Meter 1, element 0 (phase) voltage | Read | ||
| AI | 57 | Meter 2 Element 0 Voltage | Meter 2, element 0 (phase) voltage | Read | ||
| AI | 58 | Meter 3 Element 0 Voltage | Meter 3, element 0 (phase) voltage | Read | ||
| AI | 59 | Meter 4 Element 0 Voltage | Meter 4, element 0 (phase) voltage | Read | ||
| AI | 60 | Meter 5 Element 0 Voltage | Meter 5, element 0 (phase) voltage | Read | ||
| AI | 61 | Meter 6 Element 0 Voltage | Meter 6, element 0 (phase) voltage | Read | ||
| AI | 62 | Meter 7 Element 0 Voltage | Meter 7, element 0 (phase) voltage | Read | ||
| AI | 63 | Meter 8 Element 0 Voltage | Meter 8, element 0 (phase) voltage | Read | ||
| AI | 64 | Meter 1 Element 1 Voltage | Meter 1, element 1 (phase) voltage | Read | ||
| AI | 65 | Meter 2 Element 1 Voltage | Meter 2, element 1 (phase) voltage | Read | ||
| AI | 66 | Meter 3 Element 1 Voltage | Meter 3, element 1 (phase) voltage | Read | ||
| AI | 67 | Meter 4 Element 1 Voltage | Meter 4, element 1 (phase) voltage | Read | ||
| AI | 68 | Meter 5 Element 1 Voltage | Meter 5, element 1 (phase) voltage | Read | ||
| AI | 69 | Meter 6 Element 1 Voltage | Meter 6, element 1 (phase) voltage | Read | ||
| AI | 70 | Meter 7 Element 1 Voltage | Meter 7, element 1 (phase) voltage | Read | ||
| AI | 71 | Meter 8 Element 1 Voltage | Meter 8, element 1 (phase) voltage | Read | ||
| AI | 72 | Meter 1 Element 2 Voltage | Meter 1, element 2 (phase) voltage | Read | ||
| AI | 73 | Meter 2 Element 2 Voltage | Meter 2, element 2 (phase) voltage | Read | ||
| AI | 74 | Meter 3 Element 2 Voltage | Meter 3, element 2 (phase) voltage | Read | ||
| AI | 75 | Meter 4 Element 2 Voltage | Meter 4, element 2 (phase) voltage | Read | ||
| AI | 76 | Meter 5 Element 2 Voltage | Meter 5, element 2 (phase) voltage | Read | ||
| AI | 77 | Meter 6 Element 2 Voltage | Meter 6, element 2 (phase) voltage | Read | ||
| AI | 78 | Meter 7 Element 2 Voltage | Meter 7, element 2 (phase) voltage | Read | ||
| AI | 79 | Meter 8 Element 2 Voltage | Meter 8, element 2 (phase) voltage | Read | ||
| AI | 80 | Meter 1 Element 0 Active Power | Meter 1, element 0 (phase) active power | Read | ||
| AI | 81 | Meter 2 Element 0 Active Power | Meter 2, element 0 (phase) active power | Read | ||
| AI | 82 | Meter 3 Element 0 Active Power | Meter 3, element 0 (phase) active power | Read | ||
| AI | 83 | Meter 4 Element 0 Active Power | Meter 4, element 0 (phase) active power | Read | ||
| AI | 84 | Meter 5 Element 0 Active Power | Meter 5, element 0 (phase) active power | Read | ||
| AI | 85 | Meter 6 Element 0 Active Power | Meter 6, element 0 (phase) active power | Read | ||
| AI | 86 | Meter 7 Element 0 Active Power | Meter 7, element 0 (phase) active power | Read | ||
| AI | 87 | Meter 8 Element 0 Active Power | Meter 8, element 0 (phase) active power | Read | ||
| AI | 88 | Meter 1 Element 1 Active Power | Meter 1, element 1 (phase) active power | Read | ||
| AI | 89 | Meter 2 Element 1 Active Power | Meter 2, element 1 (phase) active power | Read | ||
| AI | 90 | Meter 3 Element 1 Active Power | Meter 3, element 1 (phase) active power | Read | ||
| AI | 91 | Meter 4 Element 1 Active Power | Meter 4, element 1 (phase) active power | Read | ||
| AI | 92 | Meter 5 Element 1 Active Power | Meter 5, element 1 (phase) active power | Read | ||
| AI | 93 | Meter 6 Element 1 Active Power | Meter 6, element 1 (phase) active power | Read | ||
| AI | 94 | Meter 7 Element 1 Active Power | Meter 7, element 1 (phase) active power | Read | ||
| AI | 95 | Meter 8 Element 1 Active Power | Meter 8, element 1 (phase) active power | Read | ||
| AI | 96 | Meter 1 Element 2 Active Power | Meter 1, element 2 (phase) active power | Read | ||
| AI | 97 | Meter 2 Element 2 Active Power | Meter 2, element 2 (phase) active power | Read | ||
| AI | 98 | Meter 3 Element 2 Active Power | Meter 3, element 2 (phase) active power | Read | ||
| AI | 99 | Meter 4 Element 2 Active Power | Meter 4, element 2 (phase) active power | Read | ||
| AI | 100 | Meter 5 Element 2 Active Power | Meter 5, element 2 (phase) active power | Read | ||
| AI | 101 | Meter 6 Element 2 Active Power | Meter 6, element 2 (phase) active power | Read | ||
| AI | 102 | Meter 7 Element 2 Active Power | Meter 7, element 2 (phase) active power | Read | ||
| AI | 103 | Meter 8 Element 2 Active Power | Meter 8, element 2 (phase) active power | Read | ||
| AI | 104 | Meter 1 Element 0 Reactive Power | Meter 1, element 0 (phase) reactive power | Read | ||
| AI | 105 | Meter 2 Element 0 Reactive Power | Meter 2, element 0 (phase) reactive power | Read | ||
| AI | 106 | Meter 3 Element 0 Reactive Power | Meter 3, element 0 (phase) reactive power | Read | ||
| AI | 107 | Meter 4 Element 0 Reactive Power | Meter 4, element 0 (phase) reactive power | Read | ||
| AI | 108 | Meter 5 Element 0 Reactive Power | Meter 5, element 0 (phase) reactive power | Read | ||
| AI | 109 | Meter 6 Element 0 Reactive Power | Meter 6, element 0 (phase) reactive power | Read | ||
| AI | 110 | Meter 7 Element 0 Reactive Power | Meter 7, element 0 (phase) reactive power | Read | ||
| AI | 111 | Meter 8 Element 0 Reactive Power | Meter 8, element 0 (phase) reactive power | Read | ||
| AI | 112 | Meter 1 Element 1 Reactive Power | Meter 1, element 1 (phase) reactive power | Read | ||
| AI | 113 | Meter 2 Element 1 Reactive Power | Meter 2, element 1 (phase) reactive power | Read | ||
| AI | 114 | Meter 3 Element 1 Reactive Power | Meter 3, element 1 (phase) reactive power | Read | ||
| AI | 115 | Meter 4 Element 1 Reactive Power | Meter 4, element 1 (phase) reactive power | Read | ||
| AI | 116 | Meter 5 Element 1 Reactive Power | Meter 5, element 1 (phase) reactive power | Read | ||
| AI | 117 | Meter 6 Element 1 Reactive Power | Meter 6, element 1 (phase) reactive power | Read | ||
| AI | 118 | Meter 7 Element 1 Reactive Power | Meter 7, element 1 (phase) reactive power | Read | ||
| AI | 119 | Meter 8 Element 1 Reactive Power | Meter 8, element 1 (phase) reactive power | Read | ||
| AI | 120 | Meter 1 Element 2 Reactive Power | Meter 1, element 2 (phase) reactive power | Read | ||
| AI | 121 | Meter 2 Element 2 Reactive Power | Meter 2, element 2 (phase) reactive power | Read | ||
| AI | 122 | Meter 3 Element 2 Reactive Power | Meter 3, element 2 (phase) reactive power | Read | ||
| AI | 123 | Meter 4 Element 2 Reactive Power | Meter 4, element 2 (phase) reactive power | Read | ||
| AI | 124 | Meter 5 Element 2 Reactive Power | Meter 5, element 2 (phase) reactive power | Read | ||
| AI | 125 | Meter 6 Element 2 Reactive Power | Meter 6, element 2 (phase) reactive power | Read | ||
| AI | 126 | Meter 7 Element 2 Reactive Power | Meter 7, element 2 (phase) reactive power | Read | ||
| AI | 127 | Meter 8 Element 2 Reactive Power | Meter 8, element 2 (phase) reactive power | Read | ||
| AI | 128 | Meter 1 Element 0 Apparent Power | Meter 1, element 0 (phase) apparent power | Read | ||
| AI | 129 | Meter 2 Element 0 Apparent Power | Meter 2, element 0 (phase) apparent power | Read | ||
| AI | 130 | Meter 3 Element 0 Apparent Power | Meter 3, element 0 (phase) apparent power | Read | ||
| AI | 131 | Meter 4 Element 0 Apparent Power | Meter 4, element 0 (phase) apparent power | Read | ||
| AI | 132 | Meter 5 Element 0 Apparent Power | Meter 5, element 0 (phase) apparent power | Read | ||
| AI | 133 | Meter 6 Element 0 Apparent Power | Meter 6, element 0 (phase) apparent power | Read | ||
| AI | 134 | Meter 7 Element 0 Apparent Power | Meter 7, element 0 (phase) apparent power | Read | ||
| AI | 135 | Meter 8 Element 0 Apparent Power | Meter 8, element 0 (phase) apparent power | Read | ||
| AI | 136 | Meter 1 Element 1 Apparent Power | Meter 1, element 1 (phase) apparent power | Read | ||
| AI | 137 | Meter 2 Element 1 Apparent Power | Meter 2, element 1 (phase) apparent power | Read | ||
| AI | 138 | Meter 3 Element 1 Apparent Power | Meter 3, element 1 (phase) apparent power | Read | ||
| AI | 139 | Meter 4 Element 1 Apparent Power | Meter 4, element 1 (phase) apparent power | Read | ||
| AI | 140 | Meter 5 Element 1 Apparent Power | Meter 5, element 1 (phase) apparent power | Read | ||
| AI | 141 | Meter 6 Element 1 Apparent Power | Meter 6, element 1 (phase) apparent power | Read | ||
| AI | 142 | Meter 7 Element 1 Apparent Power | Meter 7, element 1 (phase) apparent power | Read | ||
| AI | 143 | Meter 8 Element 1 Apparent Power | Meter 8, element 1 (phase) apparent power | Read | ||
| AI | 144 | Meter 1 Element 2 Apparent Power | Meter 1, element 2 (phase) apparent power | Read | ||
| AI | 145 | Meter 2 Element 2 Apparent Power | Meter 2, element 2 (phase) apparent power | Read | ||
| AI | 146 | Meter 3 Element 2 Apparent Power | Meter 3, element 2 (phase) apparent power | Read | ||
| AI | 147 | Meter 4 Element 2 Apparent Power | Meter 4, element 2 (phase) apparent power | Read | ||
| AI | 148 | Meter 5 Element 2 Apparent Power | Meter 5, element 2 (phase) apparent power | Read | ||
| AI | 149 | Meter 6 Element 2 Apparent Power | Meter 6, element 2 (phase) apparent power | Read | ||
| AI | 150 | Meter 7 Element 2 Apparent Power | Meter 7, element 2 (phase) apparent power | Read | ||
| AI | 151 | Meter 8 Element 2 Apparent Power | Meter 8, element 2 (phase) apparent power | Read | ||
| AI | 152 | Meter 1 Element 0 Power Factor | Meter 1, element 0 (phase) power factor | Read | ||
| AI | 153 | Meter 2 Element 0 Power Factor | Meter 2, element 0 (phase) power factor | Read | ||
| AI | 154 | Meter 3 Element 0 Power Factor | Meter 3, element 0 (phase) power factor | Read | ||
| AI | 155 | Meter 4 Element 0 Power Factor | Meter 4, element 0 (phase) power factor | Read | ||
| AI | 156 | Meter 5 Element 0 Power Factor | Meter 5, element 0 (phase) power factor | Read | ||
| AI | 157 | Meter 6 Element 0 Power Factor | Meter 6, element 0 (phase) power factor | Read | ||
| AI | 158 | Meter 7 Element 0 Power Factor | Meter 7, element 0 (phase) power factor | Read | ||
| AI | 159 | Meter 8 Element 0 Power Factor | Meter 8, element 0 (phase) power factor | Read | ||
| AI | 160 | Meter 1 Element 1 Power Factor | Meter 1, element 1 (phase) power factor | Read | ||
| AI | 161 | Meter 2 Element 1 Power Factor | Meter 2, element 1 (phase) power factor | Read | ||
| AI | 162 | Meter 3 Element 1 Power Factor | Meter 3, element 1 (phase) power factor | Read | ||
| AI | 163 | Meter 4 Element 1 Power Factor | Meter 4, element 1 (phase) power factor | Read | ||
| AI | 164 | Meter 5 Element 1 Power Factor | Meter 5, element 1 (phase) power factor | Read | ||
| AI | 165 | Meter 6 Element 1 Power Factor | Meter 6, element 1 (phase) power factor | Read | ||
| AI | 166 | Meter 7 Element 1 Power Factor | Meter 7, element 1 (phase) power factor | Read | ||
| AI | 167 | Meter 8 Element 1 Power Factor | Meter 8, element 1 (phase) power factor | Read | ||
| AI | 168 | Meter 1 Element 2 Power Factor | Meter 1, element 2 (phase) power factor | Read | ||
| AI | 169 | Meter 2 Element 2 Power Factor | Meter 2, element 2 (phase) power factor | Read | ||
| AI | 170 | Meter 3 Element 2 Power Factor | Meter 3, element 2 (phase) power factor | Read | ||
| AI | 171 | Meter 4 Element 2 Power Factor | Meter 4, element 2 (phase) power factor | Read | ||
| AI | 172 | Meter 5 Element 2 Power Factor | Meter 5, element 2 (phase) power factor | Read | ||
| AI | 173 | Meter 6 Element 2 Power Factor | Meter 6, element 2 (phase) power factor | Read | ||
| AI | 174 | Meter 7 Element 2 Power Factor | Meter 7, element 2 (phase) power factor | Read | ||
| AI | 175 | Meter 8 Element 2 Power Factor | Meter 8, element 2 (phase) power factor | Read | ||
| AI | 176 | Meter 1 Element 0 Phase Angle | Meter 1, element 0 (phase) phase angle | Read | ||
| AI | 177 | Meter 2 Element 0 Phase Angle | Meter 2, element 0 (phase) phase angle | Read | ||
| AI | 178 | Meter 3 Element 0 Phase Angle | Meter 3, element 0 (phase) phase angle | Read | ||
| AI | 179 | Meter 4 Element 0 Phase Angle | Meter 4, element 0 (phase) phase angle | Read | ||
| AI | 180 | Meter 5 Element 0 Phase Angle | Meter 5, element 0 (phase) phase angle | Read | ||
| AI | 181 | Meter 6 Element 0 Phase Angle | Meter 6, element 0 (phase) phase angle | Read | ||
| AI | 182 | Meter 7 Element 0 Phase Angle | Meter 7, element 0 (phase) phase angle | Read | ||
| AI | 183 | Meter 8 Element 0 Phase Angle | Meter 8, element 0 (phase) phase angle | Read | ||
| AI | 184 | Meter 1 Element 1 Phase Angle | Meter 1, element 1 (phase) phase angle | Read | ||
| AI | 185 | Meter 2 Element 1 Phase Angle | Meter 2, element 1 (phase) phase angle | Read | ||
| AI | 186 | Meter 3 Element 1 Phase Angle | Meter 3, element 1 (phase) phase angle | Read | ||
| AI | 187 | Meter 4 Element 1 Phase Angle | Meter 4, element 1 (phase) phase angle | Read | ||
| AI | 188 | Meter 5 Element 1 Phase Angle | Meter 5, element 1 (phase) phase angle | Read | ||
| AI | 189 | Meter 6 Element 1 Phase Angle | Meter 6, element 1 (phase) phase angle | Read | ||
| AI | 190 | Meter 7 Element 1 Phase Angle | Meter 7, element 1 (phase) phase angle | Read | ||
| AI | 191 | Meter 8 Element 1 Phase Angle | Meter 8, element 1 (phase) phase angle | Read | ||
| AI | 192 | Meter 1 Element 2 Phase Angle | Meter 1, element 2 (phase) phase angle | Read | ||
| AI | 193 | Meter 2 Element 2 Phase Angle | Meter 2, element 2 (phase) phase angle | Read | ||
| AI | 194 | Meter 3 Element 2 Phase Angle | Meter 3, element 2 (phase) phase angle | Read | ||
| AI | 195 | Meter 4 Element 2 Phase Angle | Meter 4, element 2 (phase) phase angle | Read | ||
| AI | 196 | Meter 5 Element 2 Phase Angle | Meter 5, element 2 (phase) phase angle | Read | ||
| AI | 197 | Meter 6 Element 2 Phase Angle | Meter 6, element 2 (phase) phase angle | Read | ||
| AI | 198 | Meter 7 Element 2 Phase Angle | Meter 7, element 2 (phase) phase angle | Read | ||
| AI | 199 | Meter 8 Element 2 Phase Angle | Meter 8, element 2 (phase) phase angle | Read | ||
| AImin | 200 | Meter 1 Peak Demand | Meter 1 peak demand (timestamp in property 1500) | Read | ||
| AI | 201 | Meter 2 Peak Demand | Meter 2 peak demand (timestamp in property 1500) | Read | ||
| AI | 202 | Meter 3 Peak Demand | Meter 3 peak demand (timestamp in property 1500) | Read | ||
| AI | 203 | Meter 4 Peak Demand | Meter 4 peak demand (timestamp in property 1500) | Read | ||
| AI | 204 | Meter 5 Peak Demand | Meter 5 peak demand (timestamp in property 1500) | Read | ||
| AI | 205 | Meter 6 Peak Demand | Meter 6 peak demand (timestamp in property 1500) | Read | ||
| AI | 206 | Meter 7 Peak Demand | Meter 7 peak demand (timestamp in property 1500) | Read | ||
| AI | 207 | Meter 8 Peak Demand | Meter 8 peak demand (timestamp in property 1500) | Read | ||
| AImin | 208 | Meter 1 Present Demand | Meter 1 present demand interval value | Read | ||
| AI | 209 | Meter 2 Present Demand | Meter 2 present demand interval value | Read | ||
| AI | 210 | Meter 3 Present Demand | Meter 3 present demand interval value | Read | ||
| AI | 211 | Meter 4 Present Demand | Meter 4 present demand interval value | Read | ||
| AI | 212 | Meter 5 Present Demand | Meter 5 present demand interval value | Read | ||
| AI | 213 | Meter 6 Present Demand | Meter 6 present demand interval value | Read | ||
| AI | 214 | Meter 7 Present Demand | Meter 7 present demand interval value | Read | ||
| AI | 215 | Meter 8 Present Demand | Meter 8 present demand interval value | Read | ||
| ACCmin | 0 | Meter 1 Active Power Delivered Register | Meter 1 energy register: active power delivered | Wh | Read | |
| ACC | 1 | Meter 2 Active Power Delivered Register | Meter 2 energy register: active power delivered | Wh | Read | |
| ACC | 2 | Meter 3 Active Power Delivered Register | Meter 3 energy register: active power delivered | Wh | Read | |
| ACC | 3 | Meter 4 Active Power Delivered Register | Meter 4 energy register: active power delivered | Wh | Read | |
| ACC | 4 | Meter 5 Active Power Delivered Register | Meter 5 energy register: active power delivered | Wh | Read | |
| ACC | 5 | Meter 6 Active Power Delivered Register | Meter 6 energy register: active power delivered | Wh | Read | |
| ACC | 6 | Meter 7 Active Power Delivered Register | Meter 7 energy register: active power delivered | Wh | Read | |
| ACC | 7 | Meter 8 Active Power Delivered Register | Meter 8 energy register: active power delivered | Wh | Read | |
| ACC | 8 | Meter 1 Active Power Received Register | Meter 1 energy register: active power received | Wh | Read | |
| ACC | 9 | Meter 2 Active Power Received Register | Meter 2 energy register: active power received | Wh | Read | |
| ACC | 10 | Meter 3 Active Power Received Register | Meter 3 energy register: active power received | Wh | Read | |
| ACC | 11 | Meter 4 Active Power Received Register | Meter 4 energy register: active power received | Wh | Read | |
| ACC | 12 | Meter 5 Active Power Received Register | Meter 5 energy register: active power received | Wh | Read | |
| ACC | 13 | Meter 6 Active Power Received Register | Meter 6 energy register: active power received | Wh | Read | |
| ACC | 14 | Meter 7 Active Power Received Register | Meter 7 energy register: active power received | Wh | Read | |
| ACC | 15 | Meter 8 Active Power Received Register | Meter 8 energy register: active power received | Wh | Read | |
| ACC | 16 | Meter 1 Reactive Power Delivered Register | Meter 1 energy register: reactive power delivered | Wh | Read | |
| ACC | 17 | Meter 2 Reactive Power Delivered Register | Meter 2 energy register: reactive power delivered | Wh | Read | |
| ACC | 18 | Meter 3 Reactive Power Delivered Register | Meter 3 energy register: reactive power delivered | Wh | Read | |
| ACC | 19 | Meter 4 Reactive Power Delivered Register | Meter 4 energy register: reactive power delivered | Wh | Read | |
| ACC | 20 | Meter 5 Reactive Power Delivered Register | Meter 5 energy register: reactive power delivered | Wh | Read | |
| ACC | 21 | Meter 6 Reactive Power Delivered Register | Meter 6 energy register: reactive power delivered | Wh | Read | |
| ACC | 22 | Meter 7 Reactive Power Delivered Register | Meter 7 energy register: reactive power delivered | Wh | Read | |
| ACC | 23 | Meter 8 Reactive Power Delivered Register | Meter 8 energy register: reactive power delivered | Wh | Read | |
| ACC | 24 | Meter 1 Reactive Power Received Register | Meter 1 energy register: reactive power received | Wh | Read | |
| ACC | 25 | Meter 2 Reactive Power Received Register | Meter 2 energy register: reactive power received | Wh | Read | |
| ACC | 26 | Meter 3 Reactive Power Received Register | Meter 3 energy register: reactive power received | Wh | Read | |
| ACC | 27 | Meter 4 Reactive Power Received Register | Meter 4 energy register: reactive power received | Wh | Read | |
| ACC | 28 | Meter 5 Reactive Power Received Register | Meter 5 energy register: reactive power received | Wh | Read | |
| ACC | 29 | Meter 6 Reactive Power Received Register | Meter 6 energy register: reactive power received | Wh | Read | |
| ACC | 30 | Meter 7 Reactive Power Received Register | Meter 7 energy register: reactive power received | Wh | Read | |
| ACC | 31 | Meter 8 Reactive Power Received Register | Meter 8 energy register: reactive power received | Wh | Read | |
| ACC | 32 | Meter 1 Apparent Power Register | Meter 1 energy register: apparent power | Wh | Read | |
| ACC | 33 | Meter 2 Apparent Power Register | Meter 2 energy register: apparent power | Wh | Read | |
| ACC | 34 | Meter 3 Apparent Power Register | Meter 3 energy register: apparent power | Wh | Read | |
| ACC | 35 | Meter 4 Apparent Power Register | Meter 4 energy register: apparent power | Wh | Read | |
| ACC | 36 | Meter 5 Apparent Power Register | Meter 5 energy register: apparent power | Wh | Read | |
| ACC | 37 | Meter 6 Apparent Power Register | Meter 6 energy register: apparent power | Wh | Read | |
| ACC | 38 | Meter 7 Apparent Power Register | Meter 7 energy register: apparent power | Wh | Read | |
| ACC | 39 | Meter 8 Apparent Power Register | Meter 8 energy register: apparent power | Wh | Read |
No points match these filters.
Object ID lookup: Leviton VerifEye Series 8000 multi-circuit meter point IDs by name
AI0Meter 1 Active PowerAI1Meter 2 Active PowerAI2Meter 3 Active PowerAI3Meter 4 Active PowerAI4Meter 5 Active PowerAI5Meter 6 Active PowerAI6Meter 7 Active PowerAI7Meter 8 Active PowerAI8Meter 1 Reactive PowerAI9Meter 2 Reactive PowerAI10Meter 3 Reactive PowerAI11Meter 4 Reactive PowerAI12Meter 5 Reactive PowerAI13Meter 6 Reactive PowerAI14Meter 7 Reactive PowerAI15Meter 8 Reactive PowerAI16Meter 1 Apparent PowerAI17Meter 2 Apparent PowerAI18Meter 3 Apparent PowerAI19Meter 4 Apparent PowerAI20Meter 5 Apparent PowerAI21Meter 6 Apparent PowerAI22Meter 7 Apparent PowerAI23Meter 8 Apparent PowerAI24Meter 1 Power FactorAI25Meter 2 Power FactorAI26Meter 3 Power FactorAI27Meter 4 Power FactorAI28Meter 5 Power FactorAI29Meter 6 Power FactorAI30Meter 7 Power FactorAI31Meter 8 Power FactorAI32Meter 1 Element 0 CurrentAI33Meter 2 Element 0 CurrentAI34Meter 3 Element 0 CurrentAI35Meter 4 Element 0 CurrentAI36Meter 5 Element 0 CurrentAI37Meter 6 Element 0 CurrentAI38Meter 7 Element 0 CurrentAI39Meter 8 Element 0 CurrentAI40Meter 1 Element 1 CurrentAI41Meter 2 Element 1 CurrentAI42Meter 3 Element 1 CurrentAI43Meter 4 Element 1 CurrentAI44Meter 5 Element 1 CurrentAI45Meter 6 Element 1 CurrentAI46Meter 7 Element 1 CurrentAI47Meter 8 Element 1 CurrentAI48Meter 1 Element 2 CurrentAI49Meter 2 Element 2 CurrentAI50Meter 3 Element 2 CurrentAI51Meter 4 Element 2 CurrentAI52Meter 5 Element 2 CurrentAI53Meter 6 Element 2 CurrentAI54Meter 7 Element 2 CurrentAI55Meter 8 Element 2 CurrentAI56Meter 1 Element 0 VoltageAI57Meter 2 Element 0 VoltageAI58Meter 3 Element 0 VoltageAI59Meter 4 Element 0 VoltageAI60Meter 5 Element 0 VoltageAI61Meter 6 Element 0 VoltageAI62Meter 7 Element 0 VoltageAI63Meter 8 Element 0 VoltageAI64Meter 1 Element 1 VoltageAI65Meter 2 Element 1 VoltageAI66Meter 3 Element 1 VoltageAI67Meter 4 Element 1 VoltageAI68Meter 5 Element 1 VoltageAI69Meter 6 Element 1 VoltageAI70Meter 7 Element 1 VoltageAI71Meter 8 Element 1 VoltageAI72Meter 1 Element 2 VoltageAI73Meter 2 Element 2 VoltageAI74Meter 3 Element 2 VoltageAI75Meter 4 Element 2 VoltageAI76Meter 5 Element 2 VoltageAI77Meter 6 Element 2 VoltageAI78Meter 7 Element 2 VoltageAI79Meter 8 Element 2 VoltageAI80Meter 1 Element 0 Active PowerAI81Meter 2 Element 0 Active PowerAI82Meter 3 Element 0 Active PowerAI83Meter 4 Element 0 Active PowerAI84Meter 5 Element 0 Active PowerAI85Meter 6 Element 0 Active PowerAI86Meter 7 Element 0 Active PowerAI87Meter 8 Element 0 Active PowerAI88Meter 1 Element 1 Active PowerAI89Meter 2 Element 1 Active PowerAI90Meter 3 Element 1 Active PowerAI91Meter 4 Element 1 Active PowerAI92Meter 5 Element 1 Active PowerAI93Meter 6 Element 1 Active PowerAI94Meter 7 Element 1 Active PowerAI95Meter 8 Element 1 Active PowerAI96Meter 1 Element 2 Active PowerAI97Meter 2 Element 2 Active PowerAI98Meter 3 Element 2 Active PowerAI99Meter 4 Element 2 Active PowerAI100Meter 5 Element 2 Active PowerAI101Meter 6 Element 2 Active PowerAI102Meter 7 Element 2 Active PowerAI103Meter 8 Element 2 Active PowerAI104Meter 1 Element 0 Reactive PowerAI105Meter 2 Element 0 Reactive PowerAI106Meter 3 Element 0 Reactive PowerAI107Meter 4 Element 0 Reactive PowerAI108Meter 5 Element 0 Reactive PowerAI109Meter 6 Element 0 Reactive PowerAI110Meter 7 Element 0 Reactive PowerAI111Meter 8 Element 0 Reactive PowerAI112Meter 1 Element 1 Reactive PowerAI113Meter 2 Element 1 Reactive PowerAI114Meter 3 Element 1 Reactive PowerAI115Meter 4 Element 1 Reactive PowerAI116Meter 5 Element 1 Reactive PowerAI117Meter 6 Element 1 Reactive PowerAI118Meter 7 Element 1 Reactive PowerAI119Meter 8 Element 1 Reactive PowerAI120Meter 1 Element 2 Reactive PowerAI121Meter 2 Element 2 Reactive PowerAI122Meter 3 Element 2 Reactive PowerAI123Meter 4 Element 2 Reactive PowerAI124Meter 5 Element 2 Reactive PowerAI125Meter 6 Element 2 Reactive PowerAI126Meter 7 Element 2 Reactive PowerAI127Meter 8 Element 2 Reactive PowerAI128Meter 1 Element 0 Apparent PowerAI129Meter 2 Element 0 Apparent PowerAI130Meter 3 Element 0 Apparent PowerAI131Meter 4 Element 0 Apparent PowerAI132Meter 5 Element 0 Apparent PowerAI133Meter 6 Element 0 Apparent PowerAI134Meter 7 Element 0 Apparent PowerAI135Meter 8 Element 0 Apparent PowerAI136Meter 1 Element 1 Apparent PowerAI137Meter 2 Element 1 Apparent PowerAI138Meter 3 Element 1 Apparent PowerAI139Meter 4 Element 1 Apparent PowerAI140Meter 5 Element 1 Apparent PowerAI141Meter 6 Element 1 Apparent PowerAI142Meter 7 Element 1 Apparent PowerAI143Meter 8 Element 1 Apparent PowerAI144Meter 1 Element 2 Apparent PowerAI145Meter 2 Element 2 Apparent PowerAI146Meter 3 Element 2 Apparent PowerAI147Meter 4 Element 2 Apparent PowerAI148Meter 5 Element 2 Apparent PowerAI149Meter 6 Element 2 Apparent PowerAI150Meter 7 Element 2 Apparent PowerAI151Meter 8 Element 2 Apparent PowerAI152Meter 1 Element 0 Power FactorAI153Meter 2 Element 0 Power FactorAI154Meter 3 Element 0 Power FactorAI155Meter 4 Element 0 Power FactorAI156Meter 5 Element 0 Power FactorAI157Meter 6 Element 0 Power FactorAI158Meter 7 Element 0 Power FactorAI159Meter 8 Element 0 Power FactorAI160Meter 1 Element 1 Power FactorAI161Meter 2 Element 1 Power FactorAI162Meter 3 Element 1 Power FactorAI163Meter 4 Element 1 Power FactorAI164Meter 5 Element 1 Power FactorAI165Meter 6 Element 1 Power FactorAI166Meter 7 Element 1 Power FactorAI167Meter 8 Element 1 Power FactorAI168Meter 1 Element 2 Power FactorAI169Meter 2 Element 2 Power FactorAI170Meter 3 Element 2 Power FactorAI171Meter 4 Element 2 Power FactorAI172Meter 5 Element 2 Power FactorAI173Meter 6 Element 2 Power FactorAI174Meter 7 Element 2 Power FactorAI175Meter 8 Element 2 Power FactorAI176Meter 1 Element 0 Phase AngleAI177Meter 2 Element 0 Phase AngleAI178Meter 3 Element 0 Phase AngleAI179Meter 4 Element 0 Phase AngleAI180Meter 5 Element 0 Phase AngleAI181Meter 6 Element 0 Phase AngleAI182Meter 7 Element 0 Phase AngleAI183Meter 8 Element 0 Phase AngleAI184Meter 1 Element 1 Phase AngleAI185Meter 2 Element 1 Phase AngleAI186Meter 3 Element 1 Phase AngleAI187Meter 4 Element 1 Phase AngleAI188Meter 5 Element 1 Phase AngleAI189Meter 6 Element 1 Phase AngleAI190Meter 7 Element 1 Phase AngleAI191Meter 8 Element 1 Phase AngleAI192Meter 1 Element 2 Phase AngleAI193Meter 2 Element 2 Phase AngleAI194Meter 3 Element 2 Phase AngleAI195Meter 4 Element 2 Phase AngleAI196Meter 5 Element 2 Phase AngleAI197Meter 6 Element 2 Phase AngleAI198Meter 7 Element 2 Phase AngleAI199Meter 8 Element 2 Phase AngleAI200Meter 1 Peak DemandAI201Meter 2 Peak DemandAI202Meter 3 Peak DemandAI203Meter 4 Peak DemandAI204Meter 5 Peak DemandAI205Meter 6 Peak DemandAI206Meter 7 Peak DemandAI207Meter 8 Peak DemandAI208Meter 1 Present DemandAI209Meter 2 Present DemandAI210Meter 3 Present DemandAI211Meter 4 Present DemandAI212Meter 5 Present DemandAI213Meter 6 Present DemandAI214Meter 7 Present DemandAI215Meter 8 Present DemandACC0Meter 1 Active Power Delivered RegisterACC1Meter 2 Active Power Delivered RegisterACC2Meter 3 Active Power Delivered RegisterACC3Meter 4 Active Power Delivered RegisterACC4Meter 5 Active Power Delivered RegisterACC5Meter 6 Active Power Delivered RegisterACC6Meter 7 Active Power Delivered RegisterACC7Meter 8 Active Power Delivered RegisterACC8Meter 1 Active Power Received RegisterACC9Meter 2 Active Power Received RegisterACC10Meter 3 Active Power Received RegisterACC11Meter 4 Active Power Received RegisterACC12Meter 5 Active Power Received RegisterACC13Meter 6 Active Power Received RegisterACC14Meter 7 Active Power Received RegisterACC15Meter 8 Active Power Received RegisterACC16Meter 1 Reactive Power Delivered RegisterACC17Meter 2 Reactive Power Delivered RegisterACC18Meter 3 Reactive Power Delivered RegisterACC19Meter 4 Reactive Power Delivered RegisterACC20Meter 5 Reactive Power Delivered RegisterACC21Meter 6 Reactive Power Delivered RegisterACC22Meter 7 Reactive Power Delivered RegisterACC23Meter 8 Reactive Power Delivered RegisterACC24Meter 1 Reactive Power Received RegisterACC25Meter 2 Reactive Power Received RegisterACC26Meter 3 Reactive Power Received RegisterACC27Meter 4 Reactive Power Received RegisterACC28Meter 5 Reactive Power Received RegisterACC29Meter 6 Reactive Power Received RegisterACC30Meter 7 Reactive Power Received RegisterACC31Meter 8 Reactive Power Received RegisterACC32Meter 1 Apparent Power RegisterACC33Meter 2 Apparent Power RegisterACC34Meter 3 Apparent Power RegisterACC35Meter 4 Apparent Power RegisterACC36Meter 5 Apparent Power RegisterACC37Meter 6 Apparent Power RegisterACC38Meter 7 Apparent Power RegisterACC39Meter 8 Apparent Power Register
Integration notes
- Taken from '2.1 Points List Summary' (pp6-11), printed as an image of a BACnet browser tree; read by OCR and checked against the page. It is the 3P-08 example: other configurations (3P-02, 1P/2P-03, 1P/2P-06, 1P/2P-12, 1P/2P-24) change how many meters and elements exist, so the instance numbers shift.
- Instances run in blocks of eight meters: AI 0-31 per-meter totals, AI 32-199 per-element values (current, voltage, active/reactive/apparent power, power factor, phase angle; elements 0-2), AI 200-215 peak and present demand, ACC 0-39 energy registers.
- Accumulators are BACnet Accumulator objects (type 23). The doc's sample property dump shows watt_hours as the units property on every accumulator, including the reactive and apparent registers; units for the analog inputs are not given.
- Access is inferred: the doc has no read/write column; all objects are inputs or accumulators and are listed read-only.
- Peak demand timestamp: proprietary property 1500 on each peak demand object (Unix 32-bit time). Writing any value to property 1501 on the device object resets peak demand on all meters.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VerifEye Series 8000 multi-circuit meter (3P-08 example) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example)
How many BACnet points does the Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example) have?
This list has 256 BACnet objects: 216 analog inputs, 40 accumulators. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example) BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example) BACnet documentation?
The source is VerifEye Series 8000 BACnet Configuration Guide - 2.1 Points List Summary, published free by Leviton at https://leviton.com/content/dam/leviton/lighting-controls/controls/product_documents/instruction_sheet/VerifEye-Series-8000-BACnet-English-Configuration-Guide.pdf.
What are the minimum BACnet points to integrate the Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example)?
Start with AI 0 Meter 1 Active Power (Meter 1 total active power); AI 208 Meter 1 Present Demand (Meter 1 present demand); AI 200 Meter 1 Peak Demand (Meter 1 peak demand); AI 24 Meter 1 Power Factor (Meter 1 power factor); AI 32 Meter 1 Element 0 Current (Meter 1 element 0 current); AI 56 Meter 1 Element 0 Voltage (Meter 1 element 0 voltage); ACC 0 Meter 1 Active Power Delivered Register (Meter 1 delivered active energy, Wh).
How do I check these points on the real VerifEye Series 8000 multi-circuit meter (3P-08 example)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: VerifEye Series 8000 BACnet Configuration Guide - 2.1 Points List Summary. Object names, instances and units are reproduced as published; descriptions are our own.