Easy BACnet
  1. Home
  2. BACnet points lists
  3. Leviton
  4. VerifEye Series 8000 multi-circuit meter (3P-08 example)

Power meter (multi-circuit submeter) · BACnet points list

Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example) BACnet points list

Updated 6 November 2026

Short answer

The Series 8000 is a multi-circuit electrical submeter that reports each configured meter over BACnet IP. Every meter gets total active, reactive and apparent power and power factor, per-element current, voltage, power, power factor and phase angle, present and peak demand, and energy accumulators. The object count scales with the meter configuration; this list is Leviton's 3P-08 example with 216 analog inputs and 40 accumulators.

This page lists 256 BACnet objects for the Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Leviton’s own free documentation, linked below.

Manufacturer
Leviton
Model
VerifEye Series 8000 multi-circuit meter (3P-08 example)
Equipment
Power meter (multi-circuit submeter)
Equipment type
Thermostats, sensors & meters
BACnet objects
256 (0 writable)
Transport
BACnet IP
Firmware
BACnet firmware 1.4.0 or later (Meter Shop configuration tool 1.5.0); example unit 1.41/1.42
Default device instance
4194303
Also known as
VerifEye 8000, Series 8000, S8000, PowerHawk, Triacta PowerHawk, PowerHawk 4224-120V-3P-08, 3P-08
Source document
VerifEye Series 8000 BACnet Configuration Guide - 2.1 Points List Summary
Download CSV 256 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Leviton’s current documentation and the live device before use. Not official Leviton information. Terms of use.

BMS integration notes: Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example)

Integration in brief

A read-only meter: poll or trend the per-meter power, demand and energy objects for the circuits you need. Use the accumulators for energy totals and the present demand objects for load. Configure the meter layout first, because the object count and numbering follow it.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 0Meter 1 Active PowerMeter 1 total active powerRead
AI 208Meter 1 Present DemandMeter 1 present demandRead
AI 200Meter 1 Peak DemandMeter 1 peak demandRead
AI 24Meter 1 Power FactorMeter 1 power factorRead
AI 32Meter 1 Element 0 CurrentMeter 1 element 0 currentRead
AI 56Meter 1 Element 0 VoltageMeter 1 element 0 voltageRead
ACC 0Meter 1 Active Power Delivered RegisterMeter 1 delivered active energy, WhRead

Network setup

Watch out for

Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

256 of 256 shown
Type
AnalogOther
Show
Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example) BACnet Points List
DescriptionStates
AImin0Meter 1 Active PowerMeter 1 active power, meter totalRead
AI1Meter 2 Active PowerMeter 2 active power, meter totalRead
AI2Meter 3 Active PowerMeter 3 active power, meter totalRead
AI3Meter 4 Active PowerMeter 4 active power, meter totalRead
AI4Meter 5 Active PowerMeter 5 active power, meter totalRead
AI5Meter 6 Active PowerMeter 6 active power, meter totalRead
AI6Meter 7 Active PowerMeter 7 active power, meter totalRead
AI7Meter 8 Active PowerMeter 8 active power, meter totalRead
AI8Meter 1 Reactive PowerMeter 1 reactive power, meter totalRead
AI9Meter 2 Reactive PowerMeter 2 reactive power, meter totalRead
AI10Meter 3 Reactive PowerMeter 3 reactive power, meter totalRead
AI11Meter 4 Reactive PowerMeter 4 reactive power, meter totalRead
AI12Meter 5 Reactive PowerMeter 5 reactive power, meter totalRead
AI13Meter 6 Reactive PowerMeter 6 reactive power, meter totalRead
AI14Meter 7 Reactive PowerMeter 7 reactive power, meter totalRead
AI15Meter 8 Reactive PowerMeter 8 reactive power, meter totalRead
AI16Meter 1 Apparent PowerMeter 1 apparent power, meter totalRead
AI17Meter 2 Apparent PowerMeter 2 apparent power, meter totalRead
AI18Meter 3 Apparent PowerMeter 3 apparent power, meter totalRead
AI19Meter 4 Apparent PowerMeter 4 apparent power, meter totalRead
AI20Meter 5 Apparent PowerMeter 5 apparent power, meter totalRead
AI21Meter 6 Apparent PowerMeter 6 apparent power, meter totalRead
AI22Meter 7 Apparent PowerMeter 7 apparent power, meter totalRead
AI23Meter 8 Apparent PowerMeter 8 apparent power, meter totalRead
AImin24Meter 1 Power FactorMeter 1 power factor, meter totalRead
AI25Meter 2 Power FactorMeter 2 power factor, meter totalRead
AI26Meter 3 Power FactorMeter 3 power factor, meter totalRead
AI27Meter 4 Power FactorMeter 4 power factor, meter totalRead
AI28Meter 5 Power FactorMeter 5 power factor, meter totalRead
AI29Meter 6 Power FactorMeter 6 power factor, meter totalRead
AI30Meter 7 Power FactorMeter 7 power factor, meter totalRead
AI31Meter 8 Power FactorMeter 8 power factor, meter totalRead
AImin32Meter 1 Element 0 CurrentMeter 1, element 0 (phase) currentRead
AI33Meter 2 Element 0 CurrentMeter 2, element 0 (phase) currentRead
AI34Meter 3 Element 0 CurrentMeter 3, element 0 (phase) currentRead
AI35Meter 4 Element 0 CurrentMeter 4, element 0 (phase) currentRead
AI36Meter 5 Element 0 CurrentMeter 5, element 0 (phase) currentRead
AI37Meter 6 Element 0 CurrentMeter 6, element 0 (phase) currentRead
AI38Meter 7 Element 0 CurrentMeter 7, element 0 (phase) currentRead
AI39Meter 8 Element 0 CurrentMeter 8, element 0 (phase) currentRead
AI40Meter 1 Element 1 CurrentMeter 1, element 1 (phase) currentRead
AI41Meter 2 Element 1 CurrentMeter 2, element 1 (phase) currentRead
AI42Meter 3 Element 1 CurrentMeter 3, element 1 (phase) currentRead
AI43Meter 4 Element 1 CurrentMeter 4, element 1 (phase) currentRead
AI44Meter 5 Element 1 CurrentMeter 5, element 1 (phase) currentRead
AI45Meter 6 Element 1 CurrentMeter 6, element 1 (phase) currentRead
AI46Meter 7 Element 1 CurrentMeter 7, element 1 (phase) currentRead
AI47Meter 8 Element 1 CurrentMeter 8, element 1 (phase) currentRead
AI48Meter 1 Element 2 CurrentMeter 1, element 2 (phase) currentRead
AI49Meter 2 Element 2 CurrentMeter 2, element 2 (phase) currentRead
AI50Meter 3 Element 2 CurrentMeter 3, element 2 (phase) currentRead
AI51Meter 4 Element 2 CurrentMeter 4, element 2 (phase) currentRead
AI52Meter 5 Element 2 CurrentMeter 5, element 2 (phase) currentRead
AI53Meter 6 Element 2 CurrentMeter 6, element 2 (phase) currentRead
AI54Meter 7 Element 2 CurrentMeter 7, element 2 (phase) currentRead
AI55Meter 8 Element 2 CurrentMeter 8, element 2 (phase) currentRead
AImin56Meter 1 Element 0 VoltageMeter 1, element 0 (phase) voltageRead
AI57Meter 2 Element 0 VoltageMeter 2, element 0 (phase) voltageRead
AI58Meter 3 Element 0 VoltageMeter 3, element 0 (phase) voltageRead
AI59Meter 4 Element 0 VoltageMeter 4, element 0 (phase) voltageRead
AI60Meter 5 Element 0 VoltageMeter 5, element 0 (phase) voltageRead
AI61Meter 6 Element 0 VoltageMeter 6, element 0 (phase) voltageRead
AI62Meter 7 Element 0 VoltageMeter 7, element 0 (phase) voltageRead
AI63Meter 8 Element 0 VoltageMeter 8, element 0 (phase) voltageRead
AI64Meter 1 Element 1 VoltageMeter 1, element 1 (phase) voltageRead
AI65Meter 2 Element 1 VoltageMeter 2, element 1 (phase) voltageRead
AI66Meter 3 Element 1 VoltageMeter 3, element 1 (phase) voltageRead
AI67Meter 4 Element 1 VoltageMeter 4, element 1 (phase) voltageRead
AI68Meter 5 Element 1 VoltageMeter 5, element 1 (phase) voltageRead
AI69Meter 6 Element 1 VoltageMeter 6, element 1 (phase) voltageRead
AI70Meter 7 Element 1 VoltageMeter 7, element 1 (phase) voltageRead
AI71Meter 8 Element 1 VoltageMeter 8, element 1 (phase) voltageRead
AI72Meter 1 Element 2 VoltageMeter 1, element 2 (phase) voltageRead
AI73Meter 2 Element 2 VoltageMeter 2, element 2 (phase) voltageRead
AI74Meter 3 Element 2 VoltageMeter 3, element 2 (phase) voltageRead
AI75Meter 4 Element 2 VoltageMeter 4, element 2 (phase) voltageRead
AI76Meter 5 Element 2 VoltageMeter 5, element 2 (phase) voltageRead
AI77Meter 6 Element 2 VoltageMeter 6, element 2 (phase) voltageRead
AI78Meter 7 Element 2 VoltageMeter 7, element 2 (phase) voltageRead
AI79Meter 8 Element 2 VoltageMeter 8, element 2 (phase) voltageRead
AI80Meter 1 Element 0 Active PowerMeter 1, element 0 (phase) active powerRead
AI81Meter 2 Element 0 Active PowerMeter 2, element 0 (phase) active powerRead
AI82Meter 3 Element 0 Active PowerMeter 3, element 0 (phase) active powerRead
AI83Meter 4 Element 0 Active PowerMeter 4, element 0 (phase) active powerRead
AI84Meter 5 Element 0 Active PowerMeter 5, element 0 (phase) active powerRead
AI85Meter 6 Element 0 Active PowerMeter 6, element 0 (phase) active powerRead
AI86Meter 7 Element 0 Active PowerMeter 7, element 0 (phase) active powerRead
AI87Meter 8 Element 0 Active PowerMeter 8, element 0 (phase) active powerRead
AI88Meter 1 Element 1 Active PowerMeter 1, element 1 (phase) active powerRead
AI89Meter 2 Element 1 Active PowerMeter 2, element 1 (phase) active powerRead
AI90Meter 3 Element 1 Active PowerMeter 3, element 1 (phase) active powerRead
AI91Meter 4 Element 1 Active PowerMeter 4, element 1 (phase) active powerRead
AI92Meter 5 Element 1 Active PowerMeter 5, element 1 (phase) active powerRead
AI93Meter 6 Element 1 Active PowerMeter 6, element 1 (phase) active powerRead
AI94Meter 7 Element 1 Active PowerMeter 7, element 1 (phase) active powerRead
AI95Meter 8 Element 1 Active PowerMeter 8, element 1 (phase) active powerRead
AI96Meter 1 Element 2 Active PowerMeter 1, element 2 (phase) active powerRead
AI97Meter 2 Element 2 Active PowerMeter 2, element 2 (phase) active powerRead
AI98Meter 3 Element 2 Active PowerMeter 3, element 2 (phase) active powerRead
AI99Meter 4 Element 2 Active PowerMeter 4, element 2 (phase) active powerRead
AI100Meter 5 Element 2 Active PowerMeter 5, element 2 (phase) active powerRead
AI101Meter 6 Element 2 Active PowerMeter 6, element 2 (phase) active powerRead
AI102Meter 7 Element 2 Active PowerMeter 7, element 2 (phase) active powerRead
AI103Meter 8 Element 2 Active PowerMeter 8, element 2 (phase) active powerRead
AI104Meter 1 Element 0 Reactive PowerMeter 1, element 0 (phase) reactive powerRead
AI105Meter 2 Element 0 Reactive PowerMeter 2, element 0 (phase) reactive powerRead
AI106Meter 3 Element 0 Reactive PowerMeter 3, element 0 (phase) reactive powerRead
AI107Meter 4 Element 0 Reactive PowerMeter 4, element 0 (phase) reactive powerRead
AI108Meter 5 Element 0 Reactive PowerMeter 5, element 0 (phase) reactive powerRead
AI109Meter 6 Element 0 Reactive PowerMeter 6, element 0 (phase) reactive powerRead
AI110Meter 7 Element 0 Reactive PowerMeter 7, element 0 (phase) reactive powerRead
AI111Meter 8 Element 0 Reactive PowerMeter 8, element 0 (phase) reactive powerRead
AI112Meter 1 Element 1 Reactive PowerMeter 1, element 1 (phase) reactive powerRead
AI113Meter 2 Element 1 Reactive PowerMeter 2, element 1 (phase) reactive powerRead
AI114Meter 3 Element 1 Reactive PowerMeter 3, element 1 (phase) reactive powerRead
AI115Meter 4 Element 1 Reactive PowerMeter 4, element 1 (phase) reactive powerRead
AI116Meter 5 Element 1 Reactive PowerMeter 5, element 1 (phase) reactive powerRead
AI117Meter 6 Element 1 Reactive PowerMeter 6, element 1 (phase) reactive powerRead
AI118Meter 7 Element 1 Reactive PowerMeter 7, element 1 (phase) reactive powerRead
AI119Meter 8 Element 1 Reactive PowerMeter 8, element 1 (phase) reactive powerRead
AI120Meter 1 Element 2 Reactive PowerMeter 1, element 2 (phase) reactive powerRead
AI121Meter 2 Element 2 Reactive PowerMeter 2, element 2 (phase) reactive powerRead
AI122Meter 3 Element 2 Reactive PowerMeter 3, element 2 (phase) reactive powerRead
AI123Meter 4 Element 2 Reactive PowerMeter 4, element 2 (phase) reactive powerRead
AI124Meter 5 Element 2 Reactive PowerMeter 5, element 2 (phase) reactive powerRead
AI125Meter 6 Element 2 Reactive PowerMeter 6, element 2 (phase) reactive powerRead
AI126Meter 7 Element 2 Reactive PowerMeter 7, element 2 (phase) reactive powerRead
AI127Meter 8 Element 2 Reactive PowerMeter 8, element 2 (phase) reactive powerRead
AI128Meter 1 Element 0 Apparent PowerMeter 1, element 0 (phase) apparent powerRead
AI129Meter 2 Element 0 Apparent PowerMeter 2, element 0 (phase) apparent powerRead
AI130Meter 3 Element 0 Apparent PowerMeter 3, element 0 (phase) apparent powerRead
AI131Meter 4 Element 0 Apparent PowerMeter 4, element 0 (phase) apparent powerRead
AI132Meter 5 Element 0 Apparent PowerMeter 5, element 0 (phase) apparent powerRead
AI133Meter 6 Element 0 Apparent PowerMeter 6, element 0 (phase) apparent powerRead
AI134Meter 7 Element 0 Apparent PowerMeter 7, element 0 (phase) apparent powerRead
AI135Meter 8 Element 0 Apparent PowerMeter 8, element 0 (phase) apparent powerRead
AI136Meter 1 Element 1 Apparent PowerMeter 1, element 1 (phase) apparent powerRead
AI137Meter 2 Element 1 Apparent PowerMeter 2, element 1 (phase) apparent powerRead
AI138Meter 3 Element 1 Apparent PowerMeter 3, element 1 (phase) apparent powerRead
AI139Meter 4 Element 1 Apparent PowerMeter 4, element 1 (phase) apparent powerRead
AI140Meter 5 Element 1 Apparent PowerMeter 5, element 1 (phase) apparent powerRead
AI141Meter 6 Element 1 Apparent PowerMeter 6, element 1 (phase) apparent powerRead
AI142Meter 7 Element 1 Apparent PowerMeter 7, element 1 (phase) apparent powerRead
AI143Meter 8 Element 1 Apparent PowerMeter 8, element 1 (phase) apparent powerRead
AI144Meter 1 Element 2 Apparent PowerMeter 1, element 2 (phase) apparent powerRead
AI145Meter 2 Element 2 Apparent PowerMeter 2, element 2 (phase) apparent powerRead
AI146Meter 3 Element 2 Apparent PowerMeter 3, element 2 (phase) apparent powerRead
AI147Meter 4 Element 2 Apparent PowerMeter 4, element 2 (phase) apparent powerRead
AI148Meter 5 Element 2 Apparent PowerMeter 5, element 2 (phase) apparent powerRead
AI149Meter 6 Element 2 Apparent PowerMeter 6, element 2 (phase) apparent powerRead
AI150Meter 7 Element 2 Apparent PowerMeter 7, element 2 (phase) apparent powerRead
AI151Meter 8 Element 2 Apparent PowerMeter 8, element 2 (phase) apparent powerRead
AI152Meter 1 Element 0 Power FactorMeter 1, element 0 (phase) power factorRead
AI153Meter 2 Element 0 Power FactorMeter 2, element 0 (phase) power factorRead
AI154Meter 3 Element 0 Power FactorMeter 3, element 0 (phase) power factorRead
AI155Meter 4 Element 0 Power FactorMeter 4, element 0 (phase) power factorRead
AI156Meter 5 Element 0 Power FactorMeter 5, element 0 (phase) power factorRead
AI157Meter 6 Element 0 Power FactorMeter 6, element 0 (phase) power factorRead
AI158Meter 7 Element 0 Power FactorMeter 7, element 0 (phase) power factorRead
AI159Meter 8 Element 0 Power FactorMeter 8, element 0 (phase) power factorRead
AI160Meter 1 Element 1 Power FactorMeter 1, element 1 (phase) power factorRead
AI161Meter 2 Element 1 Power FactorMeter 2, element 1 (phase) power factorRead
AI162Meter 3 Element 1 Power FactorMeter 3, element 1 (phase) power factorRead
AI163Meter 4 Element 1 Power FactorMeter 4, element 1 (phase) power factorRead
AI164Meter 5 Element 1 Power FactorMeter 5, element 1 (phase) power factorRead
AI165Meter 6 Element 1 Power FactorMeter 6, element 1 (phase) power factorRead
AI166Meter 7 Element 1 Power FactorMeter 7, element 1 (phase) power factorRead
AI167Meter 8 Element 1 Power FactorMeter 8, element 1 (phase) power factorRead
AI168Meter 1 Element 2 Power FactorMeter 1, element 2 (phase) power factorRead
AI169Meter 2 Element 2 Power FactorMeter 2, element 2 (phase) power factorRead
AI170Meter 3 Element 2 Power FactorMeter 3, element 2 (phase) power factorRead
AI171Meter 4 Element 2 Power FactorMeter 4, element 2 (phase) power factorRead
AI172Meter 5 Element 2 Power FactorMeter 5, element 2 (phase) power factorRead
AI173Meter 6 Element 2 Power FactorMeter 6, element 2 (phase) power factorRead
AI174Meter 7 Element 2 Power FactorMeter 7, element 2 (phase) power factorRead
AI175Meter 8 Element 2 Power FactorMeter 8, element 2 (phase) power factorRead
AI176Meter 1 Element 0 Phase AngleMeter 1, element 0 (phase) phase angleRead
AI177Meter 2 Element 0 Phase AngleMeter 2, element 0 (phase) phase angleRead
AI178Meter 3 Element 0 Phase AngleMeter 3, element 0 (phase) phase angleRead
AI179Meter 4 Element 0 Phase AngleMeter 4, element 0 (phase) phase angleRead
AI180Meter 5 Element 0 Phase AngleMeter 5, element 0 (phase) phase angleRead
AI181Meter 6 Element 0 Phase AngleMeter 6, element 0 (phase) phase angleRead
AI182Meter 7 Element 0 Phase AngleMeter 7, element 0 (phase) phase angleRead
AI183Meter 8 Element 0 Phase AngleMeter 8, element 0 (phase) phase angleRead
AI184Meter 1 Element 1 Phase AngleMeter 1, element 1 (phase) phase angleRead
AI185Meter 2 Element 1 Phase AngleMeter 2, element 1 (phase) phase angleRead
AI186Meter 3 Element 1 Phase AngleMeter 3, element 1 (phase) phase angleRead
AI187Meter 4 Element 1 Phase AngleMeter 4, element 1 (phase) phase angleRead
AI188Meter 5 Element 1 Phase AngleMeter 5, element 1 (phase) phase angleRead
AI189Meter 6 Element 1 Phase AngleMeter 6, element 1 (phase) phase angleRead
AI190Meter 7 Element 1 Phase AngleMeter 7, element 1 (phase) phase angleRead
AI191Meter 8 Element 1 Phase AngleMeter 8, element 1 (phase) phase angleRead
AI192Meter 1 Element 2 Phase AngleMeter 1, element 2 (phase) phase angleRead
AI193Meter 2 Element 2 Phase AngleMeter 2, element 2 (phase) phase angleRead
AI194Meter 3 Element 2 Phase AngleMeter 3, element 2 (phase) phase angleRead
AI195Meter 4 Element 2 Phase AngleMeter 4, element 2 (phase) phase angleRead
AI196Meter 5 Element 2 Phase AngleMeter 5, element 2 (phase) phase angleRead
AI197Meter 6 Element 2 Phase AngleMeter 6, element 2 (phase) phase angleRead
AI198Meter 7 Element 2 Phase AngleMeter 7, element 2 (phase) phase angleRead
AI199Meter 8 Element 2 Phase AngleMeter 8, element 2 (phase) phase angleRead
AImin200Meter 1 Peak DemandMeter 1 peak demand (timestamp in property 1500)Read
AI201Meter 2 Peak DemandMeter 2 peak demand (timestamp in property 1500)Read
AI202Meter 3 Peak DemandMeter 3 peak demand (timestamp in property 1500)Read
AI203Meter 4 Peak DemandMeter 4 peak demand (timestamp in property 1500)Read
AI204Meter 5 Peak DemandMeter 5 peak demand (timestamp in property 1500)Read
AI205Meter 6 Peak DemandMeter 6 peak demand (timestamp in property 1500)Read
AI206Meter 7 Peak DemandMeter 7 peak demand (timestamp in property 1500)Read
AI207Meter 8 Peak DemandMeter 8 peak demand (timestamp in property 1500)Read
AImin208Meter 1 Present DemandMeter 1 present demand interval valueRead
AI209Meter 2 Present DemandMeter 2 present demand interval valueRead
AI210Meter 3 Present DemandMeter 3 present demand interval valueRead
AI211Meter 4 Present DemandMeter 4 present demand interval valueRead
AI212Meter 5 Present DemandMeter 5 present demand interval valueRead
AI213Meter 6 Present DemandMeter 6 present demand interval valueRead
AI214Meter 7 Present DemandMeter 7 present demand interval valueRead
AI215Meter 8 Present DemandMeter 8 present demand interval valueRead
ACCmin0Meter 1 Active Power Delivered RegisterMeter 1 energy register: active power deliveredWhRead
ACC1Meter 2 Active Power Delivered RegisterMeter 2 energy register: active power deliveredWhRead
ACC2Meter 3 Active Power Delivered RegisterMeter 3 energy register: active power deliveredWhRead
ACC3Meter 4 Active Power Delivered RegisterMeter 4 energy register: active power deliveredWhRead
ACC4Meter 5 Active Power Delivered RegisterMeter 5 energy register: active power deliveredWhRead
ACC5Meter 6 Active Power Delivered RegisterMeter 6 energy register: active power deliveredWhRead
ACC6Meter 7 Active Power Delivered RegisterMeter 7 energy register: active power deliveredWhRead
ACC7Meter 8 Active Power Delivered RegisterMeter 8 energy register: active power deliveredWhRead
ACC8Meter 1 Active Power Received RegisterMeter 1 energy register: active power receivedWhRead
ACC9Meter 2 Active Power Received RegisterMeter 2 energy register: active power receivedWhRead
ACC10Meter 3 Active Power Received RegisterMeter 3 energy register: active power receivedWhRead
ACC11Meter 4 Active Power Received RegisterMeter 4 energy register: active power receivedWhRead
ACC12Meter 5 Active Power Received RegisterMeter 5 energy register: active power receivedWhRead
ACC13Meter 6 Active Power Received RegisterMeter 6 energy register: active power receivedWhRead
ACC14Meter 7 Active Power Received RegisterMeter 7 energy register: active power receivedWhRead
ACC15Meter 8 Active Power Received RegisterMeter 8 energy register: active power receivedWhRead
ACC16Meter 1 Reactive Power Delivered RegisterMeter 1 energy register: reactive power deliveredWhRead
ACC17Meter 2 Reactive Power Delivered RegisterMeter 2 energy register: reactive power deliveredWhRead
ACC18Meter 3 Reactive Power Delivered RegisterMeter 3 energy register: reactive power deliveredWhRead
ACC19Meter 4 Reactive Power Delivered RegisterMeter 4 energy register: reactive power deliveredWhRead
ACC20Meter 5 Reactive Power Delivered RegisterMeter 5 energy register: reactive power deliveredWhRead
ACC21Meter 6 Reactive Power Delivered RegisterMeter 6 energy register: reactive power deliveredWhRead
ACC22Meter 7 Reactive Power Delivered RegisterMeter 7 energy register: reactive power deliveredWhRead
ACC23Meter 8 Reactive Power Delivered RegisterMeter 8 energy register: reactive power deliveredWhRead
ACC24Meter 1 Reactive Power Received RegisterMeter 1 energy register: reactive power receivedWhRead
ACC25Meter 2 Reactive Power Received RegisterMeter 2 energy register: reactive power receivedWhRead
ACC26Meter 3 Reactive Power Received RegisterMeter 3 energy register: reactive power receivedWhRead
ACC27Meter 4 Reactive Power Received RegisterMeter 4 energy register: reactive power receivedWhRead
ACC28Meter 5 Reactive Power Received RegisterMeter 5 energy register: reactive power receivedWhRead
ACC29Meter 6 Reactive Power Received RegisterMeter 6 energy register: reactive power receivedWhRead
ACC30Meter 7 Reactive Power Received RegisterMeter 7 energy register: reactive power receivedWhRead
ACC31Meter 8 Reactive Power Received RegisterMeter 8 energy register: reactive power receivedWhRead
ACC32Meter 1 Apparent Power RegisterMeter 1 energy register: apparent powerWhRead
ACC33Meter 2 Apparent Power RegisterMeter 2 energy register: apparent powerWhRead
ACC34Meter 3 Apparent Power RegisterMeter 3 energy register: apparent powerWhRead
ACC35Meter 4 Apparent Power RegisterMeter 4 energy register: apparent powerWhRead
ACC36Meter 5 Apparent Power RegisterMeter 5 energy register: apparent powerWhRead
ACC37Meter 6 Apparent Power RegisterMeter 6 energy register: apparent powerWhRead
ACC38Meter 7 Apparent Power RegisterMeter 7 energy register: apparent powerWhRead
ACC39Meter 8 Apparent Power RegisterMeter 8 energy register: apparent powerWhRead
Object ID lookup: Leviton VerifEye Series 8000 multi-circuit meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VerifEye Series 8000 multi-circuit meter (3P-08 example) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example)

How many BACnet points does the Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example) have?

This list has 256 BACnet objects: 216 analog inputs, 40 accumulators. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example) BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example) BACnet documentation?

The source is VerifEye Series 8000 BACnet Configuration Guide - 2.1 Points List Summary, published free by Leviton at https://leviton.com/content/dam/leviton/lighting-controls/controls/product_documents/instruction_sheet/VerifEye-Series-8000-BACnet-English-Configuration-Guide.pdf.

What are the minimum BACnet points to integrate the Leviton VerifEye Series 8000 multi-circuit meter (3P-08 example)?

Start with AI 0 Meter 1 Active Power (Meter 1 total active power); AI 208 Meter 1 Present Demand (Meter 1 present demand); AI 200 Meter 1 Peak Demand (Meter 1 peak demand); AI 24 Meter 1 Power Factor (Meter 1 power factor); AI 32 Meter 1 Element 0 Current (Meter 1 element 0 current); AI 56 Meter 1 Element 0 Voltage (Meter 1 element 0 voltage); ACC 0 Meter 1 Active Power Delivered Register (Meter 1 delivered active energy, Wh).

How do I check these points on the real VerifEye Series 8000 multi-circuit meter (3P-08 example)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: VerifEye Series 8000 BACnet Configuration Guide - 2.1 Points List Summary. Object names, instances and units are reproduced as published; descriptions are our own.