  4. KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations)

Potable water heater station gateway · BACnet points list

Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) BACnet points list

Updated 12 November 2026

Short answer

The KTS BACnet Gateway connects Kemper KTS fresh-water (potable hot water) stations to a BMS over BACnet IP; it also offers Modbus RTU. It exposes the system's thermal disinfection controls, the hot water setpoint and device clock, buffer and circulation temperatures, and for each of up to 8 cascaded stations the temperatures, flow, primary pump output, faults and operating mode.

This page lists 46 BACnet objects for the Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Kemper’s own free documentation, linked below.

Manufacturer
Kemper
Model
KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations)
Equipment
Potable water heater station gateway
Equipment type
Boilers & water heaters
BACnet objects
46 (13 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Fig. 916 02 022, 916 02 022, KTS Gateway, Kemper KTS, KTS BACnet
Source document
Datenpunktliste KTS BACnet Gateway Fig. 916 02 022 · dok_tin_me130144 · rev. 10.2023
Download CSV 46 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Kemper’s current documentation and the live device before use. Not official Kemper information. Terms of use.

BMS integration notes: Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations)

Integration in brief

Map the station operating mode (BV x27), hot water setpoint (AV 100) and the per-station temperatures, then the common fault and coded fault per station. Thermal disinfection is started and cancelled through BV 5, with its status on MI 6. Scale temperatures by 0.1.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 127BetriebsartStation 1 mode, 0 = off, 1 = auto (BV 227-827 others)Write
AV 100Temperatur PWH SollHot water setpoint, °C x10Write
BV 5Starten / abbrechenThermal disinfection, 1 = start, 0 = cancelWrite
AI 109S2 - PWH TemperaturStation 1 hot water outlet temp, °C x10Read
AI 117V - PWH VolumenstromStation 1 hot water flow, l/min x10Read
MI 6StatusThermal disinfection statusRead
BI 125SammelstörungStation 1 common fault; write 0 to acknowledgeWrite
AI 126Codierte FehlermeldungStation 1 bit-coded fault messagesRead
BI 1Kommunikationsstörung zum ReglerGateway lost communication with the controllerRead

Enable & remote start

Each station's BV x27 Betriebsart sets it to off (0) or automatic (1).

Network setup

Watch out for

Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

46 of 46 shown
Type
Multi-state
Access
Show
Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) BACnet Points List
DescriptionStates
BImin1Kommunikationsstörung zum ReglerCommunication fault to the controllerRead0=Normal, 1=Fault
AV2SolltemperaturThermal disinfection setpoint, 70-90 °C, default 75°C x10Write
AV3Gesamtdauer pro StationDisinfection total time per station, 60-1440 minminWrite
AV4EinwirkzeitDisinfection hold time, 30-1080 min, default 60minWrite
BVmin5Starten / abbrechenStart or cancel thermal disinfectionWrite0=Cancel, 1=Start
MImin6StatusThermal disinfection statusRead0=Deactivated, 1=Idle, 2=Preparation, 3=Heating, 4=Disinfected, 5=Result, 6=Run-on, 7=Finished
BI13S6 - Überlaufsensor SpülgruppeSingle unit: flush group overflow sensorRead0=No overflow, 1=Overflow
BI20R3 - SpülventilSingle unit: flush valveRead0=Closed, 1=Open
BI21R4 - ZirkulationspumpeSingle unit: circulation pumpRead0=Off, 1=On
AI32Anzahl Schaltspiele R3 - SpülventilSingle unit: flush valve switching cyclesRead
AI33Anzahl Schaltspiele R4 - ZirkulationspumpeSingle unit: circulation pump switching cyclesRead
AVmin100Temperatur PWH SollHot water (PWH) setpoint, default 60 °C°C x10Write
AV101Datum TagDevice clock: day, 1-31Write
AV102Datum MonatDevice clock: month, 1-12Write
AV103Datum JahrDevice clock: year, 0-99Write
AV104Uhrzeit StundeDevice clock: hour, 0-23hWrite
AV105Uhrzeit MinuteDevice clock: minute, 0-59minWrite
AV106Uhrzeit SekundeDevice clock: second, 0-59sWrite
AI107Firmware-VersionFirmware version x100Read
AI111S4 - Puffertemperatur untenBuffer tank temperature, bottom°C x10Read
AI112S5 - Puffertemperatur mitteBuffer tank temperature, middle°C x10Read
AI114S7 - HzRL TemperaturHeating return temperature (return stratification)°C x10Read
AI115S8 - PWH-C Temperatur ZirkulationseintrittBuilding circulation return temperature°C x10Read
AI116S9 - PWC TemperaturCold water temperature°C x10Read
BI119R2 - RücklaufeinschichtungReturn stratification valve positionRead0=Valve bottom, 1=Valve middle
BI122R5 - NachladungBuffer rechargeRead0=Recharge off, 1=Recharge active
BI123R6 - FehlerFault relayRead0=No fault, 1=Fault
AI131Anzahl Schaltspiele R2 - RücklaufeinschichtungReturn stratification valve switching cyclesRead
AI134Anzahl Schaltspiele R5 - NachladungRecharge switching cyclesRead
BI213S6 - Überlaufsensor SpülgruppeStation 2: flush group overflow sensorRead0=No overflow, 1=Overflow
BI218R1 - SpülventilStation 2: flush valveRead0=Closed, 1=Open
BI219R2 - ZirkulationspumpeStation 2: circulation pumpRead0=Off, 1=On
AI230Anzahl Schaltspiele R1 - SpülventilStation 2: flush valve switching cyclesRead
AI231Anzahl Schaltspiele R2 - ZirkulationspumpeStation 2: circulation pump switching cyclesRead
AI108S1 - HzVL TemperaturStation 1: heating flow temp before the heat exchanger°C x10Read
AImin109S2 - PWH TemperaturStation 1: hot water temp at heat exchanger outlet°C x10Read
AI110S3 - PWH-C / PWC TemperaturStation 1: circulation / cold water temp at flow sensor°C x10Read
AImin117V - PWH VolumenstromStation 1: hot water flowl/min x10Read
BI121R4 - KaskadenventilStation 1: cascade valveRead0=Closed, 1=Open
AI124PWM - Ansteuerung der PrimärpumpeStation 1: primary pump PWM output, 0-100 %%Read
BImin125SammelstörungStation 1: common fault; write 0 to acknowledgeWrite0=No fault, 1=Fault
AImin126Codierte FehlermeldungStation 1: bit-coded fault messagesReadbit 0=All OK, 1=Date/time, 2=Sensor fault, 3=Cascade config, 4=Valve open, 5=Valve closed, 6=Software update, 7=Hot water emergency mode, 8=Single controller, 9-16=Timeout station 1-8, 17=Buffer >95 °C, 18=Buffer temperature, 19=Flow temp reduction possible, 20=Flush lock, 21=Overflow, 22=Modbus module, 23=Manual mode via Modbus, 24=Station variant
BVmin127BetriebsartStation 1: operating modeWrite0=Off, 1=Automatic
AI128Kemper SeriennummerStation 1: Kemper serial numberRead
AI133Anzahl Schaltspiele R4 - KaskadenventilStation 1: cascade valve switching cyclesRead
AI135Betriebsstunden PrimärpumpeStation 1: primary pump run hourshRead
Object ID lookup: Kemper KTS BACnet Gateway point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations)

How many BACnet points does the Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) have?

This list has 46 BACnet objects: 21 analog inputs, 10 analog values, 12 binary inputs, 2 binary values, 1 multi-state input. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) BACnet points are writable?

13 of the 46 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) BACnet documentation?

The source is Datenpunktliste KTS BACnet Gateway Fig. 916 02 022 (dok_tin_me130144), revision 10.2023, published free by Kemper at https://www.kemper-group.com/media/global-media/pim-daten/dok/tin/dok_tin_me130144_sde_ain_v100.pdf.

What are the minimum BACnet points to integrate the Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations)?

Start with BV 127 Betriebsart (Station 1 mode, 0 = off, 1 = auto (BV 227-827 others)); AV 100 Temperatur PWH Soll (Hot water setpoint, °C x10); BV 5 Starten / abbrechen (Thermal disinfection, 1 = start, 0 = cancel); AI 109 S2 - PWH Temperatur (Station 1 hot water outlet temp, °C x10); AI 117 V - PWH Volumenstrom (Station 1 hot water flow, l/min x10); MI 6 Status (Thermal disinfection status); BI 125 Sammelstörung (Station 1 common fault; write 0 to acknowledge); AI 126 Codierte Fehlermeldung (Station 1 bit-coded fault messages); BI 1 Kommunikationsstörung zum Regler (Gateway lost communication with the controller).

How do I enable BMS control of the Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations)?

Each station's BV x27 Betriebsart sets it to off (0) or automatic (1).

How do I check these points on the real KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.