- KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations)
Potable water heater station gateway · BACnet points list
Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) BACnet points list
Updated 12 November 2026
The KTS BACnet Gateway connects Kemper KTS fresh-water (potable hot water) stations to a BMS over BACnet IP; it also offers Modbus RTU. It exposes the system's thermal disinfection controls, the hot water setpoint and device clock, buffer and circulation temperatures, and for each of up to 8 cascaded stations the temperatures, flow, primary pump output, faults and operating mode.
This page lists 46 BACnet objects for the Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Kemper’s own free documentation, linked below.
- Manufacturer
- Kemper
- Model
- KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations)
- Equipment
- Potable water heater station gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 46 (13 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- Fig. 916 02 022, 916 02 022, KTS Gateway, Kemper KTS, KTS BACnet
Reference only, provided as-is: verify against Kemper’s current documentation and the live device before use. Not official Kemper information. Terms of use.
BMS integration notes: Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations)
Map the station operating mode (BV x27), hot water setpoint (AV 100) and the per-station temperatures, then the common fault and coded fault per station. Thermal disinfection is started and cancelled through BV 5, with its status on MI 6. Scale temperatures by 0.1.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 127 | Betriebsart | Station 1 mode, 0 = off, 1 = auto (BV 227-827 others) | Write |
| AV 100 | Temperatur PWH Soll | Hot water setpoint, °C x10 | Write |
| BV 5 | Starten / abbrechen | Thermal disinfection, 1 = start, 0 = cancel | Write |
| AI 109 | S2 - PWH Temperatur | Station 1 hot water outlet temp, °C x10 | Read |
| AI 117 | V - PWH Volumenstrom | Station 1 hot water flow, l/min x10 | Read |
| MI 6 | Status | Thermal disinfection status | Read |
| BI 125 | Sammelstörung | Station 1 common fault; write 0 to acknowledge | Write |
| AI 126 | Codierte Fehlermeldung | Station 1 bit-coded fault messages | Read |
| BI 1 | Kommunikationsstörung zum Regler | Gateway lost communication with the controller | Read |
Enable & remote start
Each station's BV x27 Betriebsart sets it to off (0) or automatic (1).
Network setup
- Physical interfaces: Ethernet (BACnet IP) and RS485 (Modbus RTU, 9600 / 8 / N / 1).
- The device clock can be set through AV 101-106.
Watch out for
- Values are scaled integers: divide temperatures and flow by 10, firmware version by 100.
- Thermal disinfection points only read once the function is enabled in the controller.
- The station 2 relay numbering (R1, R2) differs from the single-unit block (R3, R4).
Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 1 | Kommunikationsstörung zum Regler | Communication fault to the controller | Read | 0=Normal, 1=Fault | |
| AV | 2 | Solltemperatur | Thermal disinfection setpoint, 70-90 °C, default 75 | °C x10 | Write | |
| AV | 3 | Gesamtdauer pro Station | Disinfection total time per station, 60-1440 min | min | Write | |
| AV | 4 | Einwirkzeit | Disinfection hold time, 30-1080 min, default 60 | min | Write | |
| BVmin | 5 | Starten / abbrechen | Start or cancel thermal disinfection | Write | 0=Cancel, 1=Start | |
| MImin | 6 | Status | Thermal disinfection status | Read | 0=Deactivated, 1=Idle, 2=Preparation, 3=Heating, 4=Disinfected, 5=Result, 6=Run-on, 7=Finished | |
| BI | 13 | S6 - Überlaufsensor Spülgruppe | Single unit: flush group overflow sensor | Read | 0=No overflow, 1=Overflow | |
| BI | 20 | R3 - Spülventil | Single unit: flush valve | Read | 0=Closed, 1=Open | |
| BI | 21 | R4 - Zirkulationspumpe | Single unit: circulation pump | Read | 0=Off, 1=On | |
| AI | 32 | Anzahl Schaltspiele R3 - Spülventil | Single unit: flush valve switching cycles | Read | ||
| AI | 33 | Anzahl Schaltspiele R4 - Zirkulationspumpe | Single unit: circulation pump switching cycles | Read | ||
| AVmin | 100 | Temperatur PWH Soll | Hot water (PWH) setpoint, default 60 °C | °C x10 | Write | |
| AV | 101 | Datum Tag | Device clock: day, 1-31 | Write | ||
| AV | 102 | Datum Monat | Device clock: month, 1-12 | Write | ||
| AV | 103 | Datum Jahr | Device clock: year, 0-99 | Write | ||
| AV | 104 | Uhrzeit Stunde | Device clock: hour, 0-23 | h | Write | |
| AV | 105 | Uhrzeit Minute | Device clock: minute, 0-59 | min | Write | |
| AV | 106 | Uhrzeit Sekunde | Device clock: second, 0-59 | s | Write | |
| AI | 107 | Firmware-Version | Firmware version x100 | Read | ||
| AI | 111 | S4 - Puffertemperatur unten | Buffer tank temperature, bottom | °C x10 | Read | |
| AI | 112 | S5 - Puffertemperatur mitte | Buffer tank temperature, middle | °C x10 | Read | |
| AI | 114 | S7 - HzRL Temperatur | Heating return temperature (return stratification) | °C x10 | Read | |
| AI | 115 | S8 - PWH-C Temperatur Zirkulationseintritt | Building circulation return temperature | °C x10 | Read | |
| AI | 116 | S9 - PWC Temperatur | Cold water temperature | °C x10 | Read | |
| BI | 119 | R2 - Rücklaufeinschichtung | Return stratification valve position | Read | 0=Valve bottom, 1=Valve middle | |
| BI | 122 | R5 - Nachladung | Buffer recharge | Read | 0=Recharge off, 1=Recharge active | |
| BI | 123 | R6 - Fehler | Fault relay | Read | 0=No fault, 1=Fault | |
| AI | 131 | Anzahl Schaltspiele R2 - Rücklaufeinschichtung | Return stratification valve switching cycles | Read | ||
| AI | 134 | Anzahl Schaltspiele R5 - Nachladung | Recharge switching cycles | Read | ||
| BI | 213 | S6 - Überlaufsensor Spülgruppe | Station 2: flush group overflow sensor | Read | 0=No overflow, 1=Overflow | |
| BI | 218 | R1 - Spülventil | Station 2: flush valve | Read | 0=Closed, 1=Open | |
| BI | 219 | R2 - Zirkulationspumpe | Station 2: circulation pump | Read | 0=Off, 1=On | |
| AI | 230 | Anzahl Schaltspiele R1 - Spülventil | Station 2: flush valve switching cycles | Read | ||
| AI | 231 | Anzahl Schaltspiele R2 - Zirkulationspumpe | Station 2: circulation pump switching cycles | Read | ||
| AI | 108 | S1 - HzVL Temperatur | Station 1: heating flow temp before the heat exchanger | °C x10 | Read | |
| AImin | 109 | S2 - PWH Temperatur | Station 1: hot water temp at heat exchanger outlet | °C x10 | Read | |
| AI | 110 | S3 - PWH-C / PWC Temperatur | Station 1: circulation / cold water temp at flow sensor | °C x10 | Read | |
| AImin | 117 | V - PWH Volumenstrom | Station 1: hot water flow | l/min x10 | Read | |
| BI | 121 | R4 - Kaskadenventil | Station 1: cascade valve | Read | 0=Closed, 1=Open | |
| AI | 124 | PWM - Ansteuerung der Primärpumpe | Station 1: primary pump PWM output, 0-100 % | % | Read | |
| BImin | 125 | Sammelstörung | Station 1: common fault; write 0 to acknowledge | Write | 0=No fault, 1=Fault | |
| AImin | 126 | Codierte Fehlermeldung | Station 1: bit-coded fault messages | Read | bit 0=All OK, 1=Date/time, 2=Sensor fault, 3=Cascade config, 4=Valve open, 5=Valve closed, 6=Software update, 7=Hot water emergency mode, 8=Single controller, 9-16=Timeout station 1-8, 17=Buffer >95 °C, 18=Buffer temperature, 19=Flow temp reduction possible, 20=Flush lock, 21=Overflow, 22=Modbus module, 23=Manual mode via Modbus, 24=Station variant | |
| BVmin | 127 | Betriebsart | Station 1: operating mode | Write | 0=Off, 1=Automatic | |
| AI | 128 | Kemper Seriennummer | Station 1: Kemper serial number | Read | ||
| AI | 133 | Anzahl Schaltspiele R4 - Kaskadenventil | Station 1: cascade valve switching cycles | Read | ||
| AI | 135 | Betriebsstunden Primärpumpe | Station 1: primary pump run hours | h | Read |
No points match these filters.
Object ID lookup: Kemper KTS BACnet Gateway point IDs by name
BI1Kommunikationsstörung zum ReglerAV2SolltemperaturAV3Gesamtdauer pro StationAV4EinwirkzeitBV5Starten / abbrechenMI6StatusBI13S6 - Überlaufsensor SpülgruppeBI20R3 - SpülventilBI21R4 - ZirkulationspumpeAI32Anzahl Schaltspiele R3 - SpülventilAI33Anzahl Schaltspiele R4 - ZirkulationspumpeAV100Temperatur PWH SollAV101Datum TagAV102Datum MonatAV103Datum JahrAV104Uhrzeit StundeAV105Uhrzeit MinuteAV106Uhrzeit SekundeAI107Firmware-VersionAI111S4 - Puffertemperatur untenAI112S5 - Puffertemperatur mitteAI114S7 - HzRL TemperaturAI115S8 - PWH-C Temperatur ZirkulationseintrittAI116S9 - PWC TemperaturBI119R2 - RücklaufeinschichtungBI122R5 - NachladungBI123R6 - FehlerAI131Anzahl Schaltspiele R2 - RücklaufeinschichtungAI134Anzahl Schaltspiele R5 - NachladungBI213S6 - Überlaufsensor SpülgruppeBI218R1 - SpülventilBI219R2 - ZirkulationspumpeAI230Anzahl Schaltspiele R1 - SpülventilAI231Anzahl Schaltspiele R2 - ZirkulationspumpeAI108S1 - HzVL TemperaturAI109S2 - PWH TemperaturAI110S3 - PWH-C / PWC TemperaturAI117V - PWH VolumenstromBI121R4 - KaskadenventilAI124PWM - Ansteuerung der PrimärpumpeBI125SammelstörungAI126Codierte FehlermeldungBV127BetriebsartAI128Kemper SeriennummerAI133Anzahl Schaltspiele R4 - KaskadenventilAI135Betriebsstunden Primärpumpe
Integration notes
- Point list is in German; object names are kept as printed and descriptions are English.
- Per-station objects are printed as ranges, for example AI-108 … AI-808: the hundreds digit is the station number (1-8). Only the station 1 instances are listed; add 100 per station.
- Temperatures and the setpoints are sent as °C x10 and flow as l/min x10.
- BI 13-AI 33 are for a single (non-cascade) unit and BI 213-AI 231 for station 2, as printed.
- Thermal disinfection must be enabled in the controller, otherwise AV 2-MI 6 cannot be read.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations)
How many BACnet points does the Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) have?
This list has 46 BACnet objects: 21 analog inputs, 10 analog values, 12 binary inputs, 2 binary values, 1 multi-state input. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) BACnet points are writable?
13 of the 46 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations) BACnet documentation?
The source is Datenpunktliste KTS BACnet Gateway Fig. 916 02 022 (dok_tin_me130144), revision 10.2023, published free by Kemper at https://www.kemper-group.com/media/global-media/pim-daten/dok/tin/dok_tin_me130144_sde_ain_v100.pdf.
What are the minimum BACnet points to integrate the Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations)?
Start with BV 127 Betriebsart (Station 1 mode, 0 = off, 1 = auto (BV 227-827 others)); AV 100 Temperatur PWH Soll (Hot water setpoint, °C x10); BV 5 Starten / abbrechen (Thermal disinfection, 1 = start, 0 = cancel); AI 109 S2 - PWH Temperatur (Station 1 hot water outlet temp, °C x10); AI 117 V - PWH Volumenstrom (Station 1 hot water flow, l/min x10); MI 6 Status (Thermal disinfection status); BI 125 Sammelstörung (Station 1 common fault; write 0 to acknowledge); AI 126 Codierte Fehlermeldung (Station 1 bit-coded fault messages); BI 1 Kommunikationsstörung zum Regler (Gateway lost communication with the controller).
How do I enable BMS control of the Kemper KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations)?
Each station's BV x27 Betriebsart sets it to off (0) or automatic (1).
How do I check these points on the real KTS BACnet Gateway Fig. 916 02 022 (KTS hot water stations)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Kemper BACnet points lists