Drinking-water hygiene system gateway (KHS flushing valves) · BACnet points list

Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 BACnet points list

Updated 6 November 2026

Short answer

BACnet IP gateway (MS/TP optional) for the Kemper KHS MASTER 2.0/2.1 drinking-water hygiene controller. It exposes system objects (restart, mode, clock, SD-card logging, software version) and one block per MASTER/SLAVE device with temperature, flow, volume, cycle count, manual valve mode, error acknowledge and leak/backflow/flow alarms.

This page lists 31 BACnet objects for the Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Kemper’s own free documentation, linked below.

Manufacturer
Kemper
Model
KHS BACnet Gateway L / XL for MASTER 2.0/2.1
Equipment
Drinking-water hygiene system gateway (KHS flushing valves)
Equipment type
Valves & actuators
BACnet objects
31 (11 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
V2.20 or later
Also known as
KHS BACnet Gateway L, KHS BACnet Gateway XL, Figur 686 02 023, Figur 686 02 024, Kemper MASTER 2.0 BACnet, Gebr. Kemper KHS BACnet
Source document
Data Point List - KHS BACnet Gateway L / XL for MASTER 2.0|2.1 · dok_tin_me120090 · rev. 05.2022
Download CSV 31 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Kemper’s current documentation and the live device before use. Not official Kemper information. Terms of use.

BMS integration notes: Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1

Integration in brief

Set the IP or MS/TP settings on the gateway web server, then read each device block (temperature, flow, alarms) and use the MASTER system objects for mode and clock. Acknowledge latched errors with BV x25.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 102ModeSystem mode (1 = locked, 2 = P1, 3 = P2)Write
MV 124Manual modeAutomatic or manual valve operationWrite
BV 125Acknowledge errorGroup error; write to acknowledgeWrite
BI 137Open ValveValve open statusRead
AI 120Current temperatureWater temperature, °CRead
AI 121Current flowFlow, L/minRead
BI 133Leak pendingLeak alarmRead
BI 127Backflow pendingBackflow alarmRead
BI 130Communication failure Bus AMASTER bus A comm failureRead

Network setup

Watch out for

Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

31 of 31 shown
Type
Multi-state
Access
Show
Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 BACnet Points List
DescriptionStates
BV101System restartRestart the system on 1; reads 0Write1=Restart
MVmin102ModeSystem modeWrite1=System locked, 2=P1, 3=P2
AV103Time HourClock hourWrite
AV104Time MinuteClock minuteWrite
AV105Time SecondsClock secondsWrite
AV106Date DayDate dayWrite
AV107Date MonthDate monthWrite
AV108Date YearDate yearWrite
MV109Create file on Micro SD cardWrite a log or config file to the SD cardWrite0=Ready/complete, 1=Create log, 2=Create flushing log, 3=Create current datalog, 4=Save configuration
AI138Main Revision of Software VersionSoftware main revisionRead
AI139Minor Revision of Software VersionSoftware minor revisionRead
AI140Software versionThird digit of the software versionRead
AI110Serial numberDevice serial numberRead
AImin120Current temperatureWater temperature at the device°CRead
AImin121Current flowFlow, one decimalL/minRead
AI122Current volumeVolume, one decimalLRead
AI123Operating cycle counterNumber of operating cyclesRead
MVmin124Manual modeAutomatic or manual valve operationWrite1=Automatic operation, 2=Manual operation Open, 3=Manual operation Close, 5=Open B valve with A valve, 6=Close B valve with A valve
BVmin125Acknowledge errorGroup error; write to acknowledgeWrite
BI126Runtime temperature timer exceededTemperature runtime timer exceededRead0=no, 1=yes
BImin127Backflow pendingBackflow activeRead0=no, 1=yes
BI128Backflow error notedBackflow error latchedRead0=no, 1=yes
BI129Operating cycles >10000More than 10,000 operating cyclesRead0=no, 1=yes
BImin130Communication failure Bus ABus A communication failure (MASTER only)Read0=no, 1=yes
BI131Communication failure Bus BBus B communication failure (MASTER only)Read0=no, 1=yes
BI232Bus communication errorBus communication error (SLAVE 1 shown)Read0=no, 1=yes
BImin133Leak pendingLeak activeRead0=no, 1=yes
BI134Leak error notedLeak error latchedRead0=no, 1=yes
BI135Flow despite closed valveFlow detected with valve closedRead0=no, 1=yes
BI136No flow despite open valveNo flow with valve openRead0=no, 1=yes
BImin137Open ValveValve openRead0=no, 1=yes
Object ID lookup: Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the KHS BACnet Gateway L / XL for MASTER 2.0/2.1 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1

How many BACnet points does the Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 have?

This list has 31 BACnet objects: 8 analog inputs, 6 analog values, 12 binary inputs, 2 binary values, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 BACnet points are writable?

11 of the 31 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 BACnet documentation?

The source is Data Point List - KHS BACnet Gateway L / XL for MASTER 2.0|2.1 (dok_tin_me120090), revision 05.2022, published free by Kemper at https://www.kemper-group.com/media/global-media/pim-daten/dok/tin/dok_tin_me120090_sall_ain_v100.pdf.

What are the minimum BACnet points to integrate the Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1?

Start with MV 102 Mode (System mode (1 = locked, 2 = P1, 3 = P2)); MV 124 Manual mode (Automatic or manual valve operation); BV 125 Acknowledge error (Group error; write to acknowledge); BI 137 Open Valve (Valve open status); AI 120 Current temperature (Water temperature, °C); AI 121 Current flow (Flow, L/min); BI 133 Leak pending (Leak alarm); BI 127 Backflow pending (Backflow alarm); BI 130 Communication failure Bus A (MASTER bus A comm failure).

How do I check these points on the real KHS BACnet Gateway L / XL for MASTER 2.0/2.1?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Data Point List - KHS BACnet Gateway L / XL for MASTER 2.0|2.1 · dok_tin_me120090 · rev. 05.2022. Object names, instances and units are reproduced as published; descriptions are our own.