- KHS BACnet Gateway L / XL for MASTER 2.0/2.1
Drinking-water hygiene system gateway (KHS flushing valves) · BACnet points list
Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 BACnet points list
Updated 6 November 2026
BACnet IP gateway (MS/TP optional) for the Kemper KHS MASTER 2.0/2.1 drinking-water hygiene controller. It exposes system objects (restart, mode, clock, SD-card logging, software version) and one block per MASTER/SLAVE device with temperature, flow, volume, cycle count, manual valve mode, error acknowledge and leak/backflow/flow alarms.
This page lists 31 BACnet objects for the Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Kemper’s own free documentation, linked below.
- Manufacturer
- Kemper
- Model
- KHS BACnet Gateway L / XL for MASTER 2.0/2.1
- Equipment
- Drinking-water hygiene system gateway (KHS flushing valves)
- Equipment type
- Valves & actuators
- BACnet objects
- 31 (11 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- V2.20 or later
- Also known as
- KHS BACnet Gateway L, KHS BACnet Gateway XL, Figur 686 02 023, Figur 686 02 024, Kemper MASTER 2.0 BACnet, Gebr. Kemper KHS BACnet
Reference only, provided as-is: verify against Kemper’s current documentation and the live device before use. Not official Kemper information. Terms of use.
BMS integration notes: Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1
Set the IP or MS/TP settings on the gateway web server, then read each device block (temperature, flow, alarms) and use the MASTER system objects for mode and clock. Acknowledge latched errors with BV x25.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 102 | Mode | System mode (1 = locked, 2 = P1, 3 = P2) | Write |
| MV 124 | Manual mode | Automatic or manual valve operation | Write |
| BV 125 | Acknowledge error | Group error; write to acknowledge | Write |
| BI 137 | Open Valve | Valve open status | Read |
| AI 120 | Current temperature | Water temperature, °C | Read |
| AI 121 | Current flow | Flow, L/min | Read |
| BI 133 | Leak pending | Leak alarm | Read |
| BI 127 | Backflow pending | Backflow alarm | Read |
| BI 130 | Communication failure Bus A | MASTER bus A comm failure | Read |
Network setup
- Default gateway IP 10.1.23.151 / 255.255.255.0, gateway 10.1.23.1.
- Network number, UDP port, IP mode, MS/TP address and baud rate are set on the gateway web server.
- Software version V2.20 or later (as stated on the list).
Watch out for
- While MV 109 is creating a file the MASTER does not answer requests; MV 109 returns to 0 when done.
- Manual modes 5 and 6 follow the valve sequence and waiting times.
Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BV | 101 | System restart | Restart the system on 1; reads 0 | Write | 1=Restart | |
| MVmin | 102 | Mode | System mode | Write | 1=System locked, 2=P1, 3=P2 | |
| AV | 103 | Time Hour | Clock hour | Write | ||
| AV | 104 | Time Minute | Clock minute | Write | ||
| AV | 105 | Time Seconds | Clock seconds | Write | ||
| AV | 106 | Date Day | Date day | Write | ||
| AV | 107 | Date Month | Date month | Write | ||
| AV | 108 | Date Year | Date year | Write | ||
| MV | 109 | Create file on Micro SD card | Write a log or config file to the SD card | Write | 0=Ready/complete, 1=Create log, 2=Create flushing log, 3=Create current datalog, 4=Save configuration | |
| AI | 138 | Main Revision of Software Version | Software main revision | Read | ||
| AI | 139 | Minor Revision of Software Version | Software minor revision | Read | ||
| AI | 140 | Software version | Third digit of the software version | Read | ||
| AI | 110 | Serial number | Device serial number | Read | ||
| AImin | 120 | Current temperature | Water temperature at the device | °C | Read | |
| AImin | 121 | Current flow | Flow, one decimal | L/min | Read | |
| AI | 122 | Current volume | Volume, one decimal | L | Read | |
| AI | 123 | Operating cycle counter | Number of operating cycles | Read | ||
| MVmin | 124 | Manual mode | Automatic or manual valve operation | Write | 1=Automatic operation, 2=Manual operation Open, 3=Manual operation Close, 5=Open B valve with A valve, 6=Close B valve with A valve | |
| BVmin | 125 | Acknowledge error | Group error; write to acknowledge | Write | ||
| BI | 126 | Runtime temperature timer exceeded | Temperature runtime timer exceeded | Read | 0=no, 1=yes | |
| BImin | 127 | Backflow pending | Backflow active | Read | 0=no, 1=yes | |
| BI | 128 | Backflow error noted | Backflow error latched | Read | 0=no, 1=yes | |
| BI | 129 | Operating cycles >10000 | More than 10,000 operating cycles | Read | 0=no, 1=yes | |
| BImin | 130 | Communication failure Bus A | Bus A communication failure (MASTER only) | Read | 0=no, 1=yes | |
| BI | 131 | Communication failure Bus B | Bus B communication failure (MASTER only) | Read | 0=no, 1=yes | |
| BI | 232 | Bus communication error | Bus communication error (SLAVE 1 shown) | Read | 0=no, 1=yes | |
| BImin | 133 | Leak pending | Leak active | Read | 0=no, 1=yes | |
| BI | 134 | Leak error noted | Leak error latched | Read | 0=no, 1=yes | |
| BI | 135 | Flow despite closed valve | Flow detected with valve closed | Read | 0=no, 1=yes | |
| BI | 136 | No flow despite open valve | No flow with valve open | Read | 0=no, 1=yes | |
| BImin | 137 | Open Valve | Valve open | Read | 0=no, 1=yes |
No points match these filters.
Object ID lookup: Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 point IDs by name
BV101System restartMV102ModeAV103Time HourAV104Time MinuteAV105Time SecondsAV106Date DayAV107Date MonthAV108Date YearMV109Create file on Micro SD cardAI138Main Revision of Software VersionAI139Minor Revision of Software VersionAI140Software versionAI110Serial numberAI120Current temperatureAI121Current flowAI122Current volumeAI123Operating cycle counterMV124Manual modeBV125Acknowledge errorBI126Runtime temperature timer exceededBI127Backflow pendingBI128Backflow error notedBI129Operating cycles >10000BI130Communication failure Bus ABI131Communication failure Bus BBI232Bus communication errorBI133Leak pendingBI134Leak error notedBI135Flow despite closed valveBI136No flow despite open valveBI137Open Valve
Integration notes
- System objects (BV 101 to AI 140) exist once, in the MASTER.
- Device objects repeat for up to 62 devices: the hundreds digit is the device (1xx = MASTER, 2xx = SLAVE 1, 3xx = SLAVE 2 ...). The MASTER block is shown; BI 232 is printed in its SLAVE 1 form.
- Names are the list's data point labels. Units and other object details can be read from the EDE file the gateway creates.
- Read/write objects use data points of Gateway 2 (per the document).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the KHS BACnet Gateway L / XL for MASTER 2.0/2.1 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1
How many BACnet points does the Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 have?
This list has 31 BACnet objects: 8 analog inputs, 6 analog values, 12 binary inputs, 2 binary values, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 BACnet points are writable?
11 of the 31 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1 BACnet documentation?
The source is Data Point List - KHS BACnet Gateway L / XL for MASTER 2.0|2.1 (dok_tin_me120090), revision 05.2022, published free by Kemper at https://www.kemper-group.com/media/global-media/pim-daten/dok/tin/dok_tin_me120090_sall_ain_v100.pdf.
What are the minimum BACnet points to integrate the Kemper KHS BACnet Gateway L / XL for MASTER 2.0/2.1?
Start with MV 102 Mode (System mode (1 = locked, 2 = P1, 3 = P2)); MV 124 Manual mode (Automatic or manual valve operation); BV 125 Acknowledge error (Group error; write to acknowledge); BI 137 Open Valve (Valve open status); AI 120 Current temperature (Water temperature, °C); AI 121 Current flow (Flow, L/min); BI 133 Leak pending (Leak alarm); BI 127 Backflow pending (Backflow alarm); BI 130 Communication failure Bus A (MASTER bus A comm failure).
How do I check these points on the real KHS BACnet Gateway L / XL for MASTER 2.0/2.1?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: Data Point List - KHS BACnet Gateway L / XL for MASTER 2.0|2.1 · dok_tin_me120090 · rev. 05.2022. Object names, instances and units are reproduced as published; descriptions are our own.