Power meter · BACnet points list
Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP) BACnet points list
Updated 12 November 2026
The endicator (PT-NT4-BAC-E) is a power and energy meter with a BACnet MS/TP interface. Analog Inputs carry power, power factor, volts, amps, frequency and import/export energy totals per phase; Analog Values hold the meter set-up (system type, CT type and pairing, pulse contacts, alarms, display); two AO/BO pairs clear the totalizers and the peak demand.
This page lists 104 BACnet objects for the Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP) — 37 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Kele’s own free documentation, linked below.
- Manufacturer
- Kele
- Model
- endicator PT-NT4-BAC-E power meter (BACnet MS/TP)
- Equipment
- Power meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 104 (37 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- endicator, PT-NT4-BAC-E, PT-NT4-BAC, Kele endicator power meter
- Source document
- BACnet MS/TP Point Mapping for the endicator Power Meter
Reference only, provided as-is: verify against Kele’s current documentation and the live device before use. Not official Kele information. Terms of use.
BMS integration notes: Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP)
Read total kW, kWh and the per-phase volts and amps; set system type, full-scale volts/amps and CT type once at commissioning.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 4 | Total KW | Total real power, kW | Read |
| AI 36 | Total Net KWH | Net energy, kWh | Read |
| AI 33 | Total Pos KWH | Imported energy, kWh | Read |
| AI 17 | Total Power Factor | Total power factor | Read |
| AI 21 | Average LL Volts | Average line-line volts | Read |
| AI 29 | Average Amps | Average current | Read |
| AI 58 | Frequency | Line frequency, Hz | Read |
Network setup
- Set AV 1 (power system type), AV 2/AV 3 (full-scale volts/amps) and AV 4 (CT type) to match the installation.
Watch out for
- AO 1 / BO 1 clear all energy totalizers; don't write them from routine logic.
Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Serial Number | Serial Number | Read | ||
| AI | 2 | Firmware Version | Firmware Version | Read | ||
| AI | 3 | Auto/Manual Wiring Configuration | Wiring set up manually (0) or auto-configured (1) | Read | 0=Manual, 1=Auto-configured | |
| AImin | 4 | Total KW | Total KW | kW | Read | |
| AI | 5 | Sliding Window KW | Sliding Window KW | kW | Read | |
| AI | 6 | Total KVAR | Total KVAR | kvar | Read | |
| AI | 7 | Total KVA | Total KVA | kVA | Read | |
| AI | 8 | Phase A KW | Phase A KW | kW | Read | |
| AI | 9 | Phase B KW | Phase B KW | kW | Read | |
| AI | 10 | Phase C KW | Phase C KW | kW | Read | |
| AI | 11 | Phase A KVAR | Phase A KVAR | kvar | Read | |
| AI | 12 | Phase B KVAR | Phase B KVAR | kvar | Read | |
| AI | 13 | Phase C KVAR | Phase C KVAR | kvar | Read | |
| AI | 14 | Phase A KVA | Phase A KVA | kVA | Read | |
| AI | 15 | Phase B KVA | Phase B KVA | kVA | Read | |
| AI | 16 | Phase C KVA | Phase C KVA | kVA | Read | |
| AImin | 17 | Total Power Factor | Total Power Factor | PF | Read | |
| AI | 18 | Phase A Power Factor | Phase A Power Factor | PF | Read | |
| AI | 19 | Phase B Power Factor | Phase B Power Factor | PF | Read | |
| AI | 20 | Phase C Power Factor | Phase C Power Factor | PF | Read | |
| AImin | 21 | Average LL Volts | Average LL Volts | V | Read | |
| AI | 22 | Average LN Volts | Average LN Volts | V | Read | |
| AI | 23 | L1-L2 Volts | L1-L2 Volts | V | Read | |
| AI | 24 | L2-L3 Volts | L2-L3 Volts | V | Read | |
| AI | 25 | L3-L1 Volts | L3-L1 Volts | V | Read | |
| AI | 26 | L1-N Volts | L1-N Volts | V | Read | |
| AI | 27 | L2-N Volts | L2-N Volts | V | Read | |
| AI | 28 | L3-N Volts | L3-N Volts | V | Read | |
| AImin | 29 | Average Amps | Average Amps | A | Read | |
| AI | 30 | Phase A Amps | Phase A Amps | A | Read | |
| AI | 31 | Phase B Amps | Phase B Amps | A | Read | |
| AI | 32 | Phase C Amps | Phase C Amps | A | Read | |
| AImin | 33 | Total Pos KWH | Total Pos KWH | kWh | Read | |
| AI | 34 | Total Neg KWH | Total Neg KWH | kWh | Read | |
| AI | 35 | Total Abs KWH | Total Abs KWH | kWh | Read | |
| AImin | 36 | Total Net KWH | Total Net KWH | kWh | Read | |
| AI | 37 | Total Pos KVARH | Total Pos KVARH | kvarh | Read | |
| AI | 38 | Total Neg KVARH | Total Neg KVARH | kvarh | Read | |
| AI | 39 | Total Abs KVARH | Total Abs KVARH | kvarh | Read | |
| AI | 40 | Total Net KVARH | Total Net KVARH | kvarh | Read | |
| AI | 41 | Total KVAH | Total KVAH | kVAh | Read | |
| AI | 42 | Phase A Pos KWH | Phase A Pos KWH | kWh | Read | |
| AI | 43 | Phase B Pos KWH | Phase B Pos KWH | kWh | Read | |
| AI | 44 | Phase C Pos KWH | Phase C Pos KWH | kWh | Read | |
| AI | 45 | Phase A Neg KWH | Phase A Neg KWH | kWh | Read | |
| AI | 46 | Phase B Neg KWH | Phase B Neg KWH | kWh | Read | |
| AI | 47 | Phase C Neg KWH | Phase C Neg KWH | kWh | Read | |
| AI | 48 | Phase A Pos KVARH | Phase A Pos KVARH | kvarh | Read | |
| AI | 49 | Phase B Pos KVARH | Phase B Pos KVARH | kvarh | Read | |
| AI | 50 | Phase C Pos KVARH | Phase C Pos KVARH | kvarh | Read | |
| AI | 51 | Phase A Neg KVARH | Phase A Neg KVARH | kvarh | Read | |
| AI | 52 | Phase B Neg KVARH | Phase B Neg KVARH | kvarh | Read | |
| AI | 53 | Phase C Neg KVARH | Phase C Neg KVARH | kvarh | Read | |
| AI | 54 | Phase A Pos KVAH | Phase A Pos KVAH | kVAh | Read | |
| AI | 55 | Phase B Pos KVAH | Phase B Pos KVAH | kVAh | Read | |
| AI | 56 | Phase C Pos KVAH | Phase C Pos KVAH | kVAh | Read | |
| AI | 57 | Peak Sliding Window KW | Peak Sliding Window KW | kW | Read | |
| AImin | 58 | Frequency | Frequency | Hz | Read | |
| AI | 59 | Clear Totalizers Year | Year totalizers were last cleared | Read | ||
| AI | 60 | Clear Totalizers Day Month | Day/month totalizers cleared (LSB day, next byte month) | Read | ||
| AI | 61 | Clear Totalizers Time | Time totalizers cleared (LSB minutes, next byte hours) | Read | ||
| AI | 62 | Peak Window KW Year | Year of peak window kW | Read | ||
| AI | 63 | Peak Window KW Day Month | Day/month of peak window kW (LSB day, next byte month) | Read | ||
| AI | 64 | Peak Window KW Time | Time of peak window kW (LSB minutes, next byte hours) | Read | ||
| AI | 65 | Clear Peak KW Year | Year peak kW was last cleared | Read | ||
| AI | 66 | Clear Peak KW Day Month | Day/month peak kW cleared (LSB day, next byte month) | Read | ||
| AI | 67 | Clear Peak KW Time | Time peak kW cleared (LSB minutes, next byte hours) | Read | ||
| AV | 1 | Power System Type | Power system type | Write | 0=3-Wire Delta, 1=4-Wire Wye, 2=2-Wire Single Phase, 3=3-Wire Single Phase, 4=4-Wire Delta | |
| AV | 2 | Full Scale Volts | Full scale volts, 120-32000 | V | Write | |
| AV | 3 | Full Scale Amps | Full scale amps, 5-6000 | A | Write | |
| AV | 4 | CT Type | CT type | Write | 0=Safe-CTs non-matched, 1=5A CTs non-matched, 2=Safe-CTs matched set, 3=5A CTs matched set | |
| AV | 5 | ‘A’ Phase Cal Number | Phase A calibration number, 9500-10500 | Write | ||
| AV | 6 | ‘B’ Phase Cal Number | Phase B calibration number, 9500-10500 | Write | ||
| AV | 7 | ‘C’ Phase Cal Number | Phase C calibration number, 9500-10500 | Write | ||
| AV | 8 | Volt-Amp Pairing | Volt-amp (voltage/CT) pairing | Write | 0=L1/CTA L2/CTB L3/CTC (normal), 1=L1/CTB L2/CTA L3/CTC, 2=L1/CTA L2/CTC L3/CTB, 3=L1/CTC L2/CTB L3/CTA, 4=L1/CTC L2/CTA L3/CTB, 5=L1/CTB L2/CTC L3/CTA | |
| AV | 9 | CTA Polarity | CT A polarity | Write | 0=Normal, 1=Reversed | |
| AV | 10 | CTB Polarity | CT B polarity | Write | 0=Normal, 1=Reversed | |
| AV | 11 | CTC Polarity | CT C polarity | Write | 0=Normal, 1=Reversed | |
| AV | 12 | KW Sliding Window Period | kW sliding window period, 5-60 min | min | Write | |
| AV | 13 | Contact 1 Function | Contact 1 function (pulse or alarm) | Write | 0=Positive KWH pulse, 1=Negative KWH pulse, 2=Low Volts alarm N.O, 3=Low Volts alarm N.C., 4=Unbalanced Volts alarm N.O., 5=Unbalanced Volts alarm N.C., 6=Low OR Unbal Volts alarm N.O., 7=Low OR Unbal Volts alarm N.C. | |
| AV | 14 | Contact 2 Function | Contact 2 function (pulse or alarm) | Write | 0=Positive KWH pulse, 1=Negative KWH pulse, 2=Low Volts alarm N.O, 3=Low Volts alarm N.C., 4=Unbalanced Volts alarm N.O., 5=Unbalanced Volts alarm N.C., 6=Low OR Unbal Volts alarm N.O., 7=Low OR Unbal Volts alarm N.C. | |
| AV | 15 | Minimum KWH Pulse Width | kWh pulse width, 50-2000 ms in 50 ms steps | ms | Write | |
| AV | 16 | KWH Per Puls | kWh per pulse | kWh | Write | 0=0.01 KWH/pulse, 1=0.1 KWH/pulse, 2=1 KWH/pulse, 3=10 KWH/pulse |
| AV | 17 | Low Volts Alarm Threshold | Low volts alarm threshold, 0-99 (0 = off) | % | Write | |
| AV | 18 | Unbalanced Volts Alarm Threshold | Unbalanced volts alarm threshold, 0-99 (0 = off) | % | Write | |
| AV | 19 | mA Output Function | mA output function | Write | 1=Total Bidirectional KW, 2=Sliding Window KW, 3=Peak Window KW, 4=Total KVA, 5=Total Power Factor, 6=Average amps, 7=Average volts | |
| AV | 20 | Name Tag Part 1 | Name tag characters, part 1 (two ASCII bytes) | Write | ||
| AV | 21 | Name Tag Part 2 | Name tag characters, part 2 (two ASCII bytes) | Write | ||
| AV | 22 | Name Tag Part 3 | Name tag characters, part 3 (two ASCII bytes) | Write | ||
| AV | 23 | Name Tag Part 4 | Name tag characters, part 4 (two ASCII bytes) | Write | ||
| AV | 24 | Name Tag Part 5 | Name tag characters, part 5 (two ASCII bytes) | Write | ||
| AV | 25 | Name Tag Part 6 | Name tag characters, part 6 (two ASCII bytes) | Write | ||
| AV | 26 | Displayed Values 1 | Display item bit flags, set 1 | Write | ||
| AV | 27 | Displayed Values 2 | Display item bit flags, set 2 | Write | ||
| AV | 28 | Displayed Values 3 | Display item bit flags, set 3 | Write | ||
| AV | 29 | Displayed Values 4 | Display item bit flags, set 4 | Write | ||
| AV | 30 | Display Action | Display icons / rotation | Write | 0=No icons, no rotate, 1=Show icons, no rotate, 2=No icons, rotate, 3=Show icons, rotate display | |
| AV | 31 | Year | Meter clock year | Write | ||
| AV | 32 | Day Month | Meter clock day/month (LSB day, next byte month) | Write | ||
| AV | 33 | Time | Meter clock time (LSB minutes, next byte hours) | Write | ||
| AO | 1 | Clear Totalizers | Write any value to clear totalizers; self-resets to 0 | Write | ||
| AO | 2 | Clear Peak Sliding Window | Write any value to clear peak sliding window kW; self-resets | Write | ||
| BO | 1 | Clear Totalizers | Set active to clear totalizers; self-resets | Write | ||
| BO | 2 | Clear Peak Sliding Window | Set active to clear peak sliding window kW; self-resets | Write |
No points match these filters.
Object ID lookup: Kele endicator PT-NT4-BAC-E power meter point IDs by name
AI1Serial NumberAI2Firmware VersionAI3Auto/Manual Wiring ConfigurationAI4Total KWAI5Sliding Window KWAI6Total KVARAI7Total KVAAI8Phase A KWAI9Phase B KWAI10Phase C KWAI11Phase A KVARAI12Phase B KVARAI13Phase C KVARAI14Phase A KVAAI15Phase B KVAAI16Phase C KVAAI17Total Power FactorAI18Phase A Power FactorAI19Phase B Power FactorAI20Phase C Power FactorAI21Average LL VoltsAI22Average LN VoltsAI23L1-L2 VoltsAI24L2-L3 VoltsAI25L3-L1 VoltsAI26L1-N VoltsAI27L2-N VoltsAI28L3-N VoltsAI29Average AmpsAI30Phase A AmpsAI31Phase B AmpsAI32Phase C AmpsAI33Total Pos KWHAI34Total Neg KWHAI35Total Abs KWHAI36Total Net KWHAI37Total Pos KVARHAI38Total Neg KVARHAI39Total Abs KVARHAI40Total Net KVARHAI41Total KVAHAI42Phase A Pos KWHAI43Phase B Pos KWHAI44Phase C Pos KWHAI45Phase A Neg KWHAI46Phase B Neg KWHAI47Phase C Neg KWHAI48Phase A Pos KVARHAI49Phase B Pos KVARHAI50Phase C Pos KVARHAI51Phase A Neg KVARHAI52Phase B Neg KVARHAI53Phase C Neg KVARHAI54Phase A Pos KVAHAI55Phase B Pos KVAHAI56Phase C Pos KVAHAI57Peak Sliding Window KWAI58FrequencyAI59Clear Totalizers YearAI60Clear Totalizers Day MonthAI61Clear Totalizers TimeAI62Peak Window KW YearAI63Peak Window KW Day MonthAI64Peak Window KW TimeAI65Clear Peak KW YearAI66Clear Peak KW Day MonthAI67Clear Peak KW TimeAV1Power System TypeAV2Full Scale VoltsAV3Full Scale AmpsAV4CT TypeAV5‘A’ Phase Cal NumberAV6‘B’ Phase Cal NumberAV7‘C’ Phase Cal NumberAV8Volt-Amp PairingAV9CTA PolarityAV10CTB PolarityAV11CTC PolarityAV12KW Sliding Window PeriodAV13Contact 1 FunctionAV14Contact 2 FunctionAV15Minimum KWH Pulse WidthAV16KWH Per PulsAV17Low Volts Alarm ThresholdAV18Unbalanced Volts Alarm ThresholdAV19mA Output FunctionAV20Name Tag Part 1AV21Name Tag Part 2AV22Name Tag Part 3AV23Name Tag Part 4AV24Name Tag Part 5AV25Name Tag Part 6AV26Displayed Values 1AV27Displayed Values 2AV28Displayed Values 3AV29Displayed Values 4AV30Display ActionAV31YearAV32Day MonthAV33TimeAO1Clear TotalizersAO2Clear Peak Sliding WindowBO1Clear TotalizersBO2Clear Peak Sliding Window
Integration notes
- Object names are the printed descriptions; the mapping has no separate object-name column.
- All Analog Inputs are read-only. AVs are set-up values; access for AV/AO/BO is not printed and is taken as writable from the notes and object type.
- Dates and times (clear totalizers, peak window, meter clock) are packed: low byte day or minutes, next byte month or hours.
- AV 20-25 hold the meter's name tag as pairs of ASCII characters; AV 26-29 are bit flags choosing what the display shows.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the endicator PT-NT4-BAC-E power meter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP)
How many BACnet points does the Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP) have?
This list has 104 BACnet objects: 67 analog inputs, 2 analog outputs, 33 analog values, 2 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP) BACnet points are writable?
37 of the 104 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP) BACnet documentation?
The source is BACnet MS/TP Point Mapping for the endicator Power Meter, published free by Kele at https://assets.kele.com/Catalog/17%20Power%20Monitoring/PDFs/PT-NT4-BAC-E%20Point%20Mapping.pdf.
What are the minimum BACnet points to integrate the Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP)?
Start with AI 4 Total KW (Total real power, kW); AI 36 Total Net KWH (Net energy, kWh); AI 33 Total Pos KWH (Imported energy, kWh); AI 17 Total Power Factor (Total power factor); AI 21 Average LL Volts (Average line-line volts); AI 29 Average Amps (Average current); AI 58 Frequency (Line frequency, Hz).
How do I check these points on the real endicator PT-NT4-BAC-E power meter (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: BACnet MS/TP Point Mapping for the endicator Power Meter. Object names, instances and units are reproduced as published; descriptions are our own.