Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The endicator (PT-NT4-BAC-E) is a power and energy meter with a BACnet MS/TP interface. Analog Inputs carry power, power factor, volts, amps, frequency and import/export energy totals per phase; Analog Values hold the meter set-up (system type, CT type and pairing, pulse contacts, alarms, display); two AO/BO pairs clear the totalizers and the peak demand.

This page lists 104 BACnet objects for the Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP) — 37 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Kele’s own free documentation, linked below.

Manufacturer
Kele
Model
endicator PT-NT4-BAC-E power meter (BACnet MS/TP)
Equipment
Power meter
Equipment type
Thermostats, sensors & meters
BACnet objects
104 (37 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
endicator, PT-NT4-BAC-E, PT-NT4-BAC, Kele endicator power meter
Source document
BACnet MS/TP Point Mapping for the endicator Power Meter
Download CSV 104 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Kele’s current documentation and the live device before use. Not official Kele information. Terms of use.

BMS integration notes: Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP)

Integration in brief

Read total kW, kWh and the per-phase volts and amps; set system type, full-scale volts/amps and CT type once at commissioning.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 4Total KWTotal real power, kWRead
AI 36Total Net KWHNet energy, kWhRead
AI 33Total Pos KWHImported energy, kWhRead
AI 17Total Power FactorTotal power factorRead
AI 21Average LL VoltsAverage line-line voltsRead
AI 29Average AmpsAverage currentRead
AI 58FrequencyLine frequency, HzRead

Network setup

Watch out for

Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

104 of 104 shown
Type
Binary
Access
Show
Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP) BACnet Points List
DescriptionStates
AI1Serial NumberSerial NumberRead
AI2Firmware VersionFirmware VersionRead
AI3Auto/Manual Wiring ConfigurationWiring set up manually (0) or auto-configured (1)Read0=Manual, 1=Auto-configured
AImin4Total KWTotal KWkWRead
AI5Sliding Window KWSliding Window KWkWRead
AI6Total KVARTotal KVARkvarRead
AI7Total KVATotal KVAkVARead
AI8Phase A KWPhase A KWkWRead
AI9Phase B KWPhase B KWkWRead
AI10Phase C KWPhase C KWkWRead
AI11Phase A KVARPhase A KVARkvarRead
AI12Phase B KVARPhase B KVARkvarRead
AI13Phase C KVARPhase C KVARkvarRead
AI14Phase A KVAPhase A KVAkVARead
AI15Phase B KVAPhase B KVAkVARead
AI16Phase C KVAPhase C KVAkVARead
AImin17Total Power FactorTotal Power FactorPFRead
AI18Phase A Power FactorPhase A Power FactorPFRead
AI19Phase B Power FactorPhase B Power FactorPFRead
AI20Phase C Power FactorPhase C Power FactorPFRead
AImin21Average LL VoltsAverage LL VoltsVRead
AI22Average LN VoltsAverage LN VoltsVRead
AI23L1-L2 VoltsL1-L2 VoltsVRead
AI24L2-L3 VoltsL2-L3 VoltsVRead
AI25L3-L1 VoltsL3-L1 VoltsVRead
AI26L1-N VoltsL1-N VoltsVRead
AI27L2-N VoltsL2-N VoltsVRead
AI28L3-N VoltsL3-N VoltsVRead
AImin29Average AmpsAverage AmpsARead
AI30Phase A AmpsPhase A AmpsARead
AI31Phase B AmpsPhase B AmpsARead
AI32Phase C AmpsPhase C AmpsARead
AImin33Total Pos KWHTotal Pos KWHkWhRead
AI34Total Neg KWHTotal Neg KWHkWhRead
AI35Total Abs KWHTotal Abs KWHkWhRead
AImin36Total Net KWHTotal Net KWHkWhRead
AI37Total Pos KVARHTotal Pos KVARHkvarhRead
AI38Total Neg KVARHTotal Neg KVARHkvarhRead
AI39Total Abs KVARHTotal Abs KVARHkvarhRead
AI40Total Net KVARHTotal Net KVARHkvarhRead
AI41Total KVAHTotal KVAHkVAhRead
AI42Phase A Pos KWHPhase A Pos KWHkWhRead
AI43Phase B Pos KWHPhase B Pos KWHkWhRead
AI44Phase C Pos KWHPhase C Pos KWHkWhRead
AI45Phase A Neg KWHPhase A Neg KWHkWhRead
AI46Phase B Neg KWHPhase B Neg KWHkWhRead
AI47Phase C Neg KWHPhase C Neg KWHkWhRead
AI48Phase A Pos KVARHPhase A Pos KVARHkvarhRead
AI49Phase B Pos KVARHPhase B Pos KVARHkvarhRead
AI50Phase C Pos KVARHPhase C Pos KVARHkvarhRead
AI51Phase A Neg KVARHPhase A Neg KVARHkvarhRead
AI52Phase B Neg KVARHPhase B Neg KVARHkvarhRead
AI53Phase C Neg KVARHPhase C Neg KVARHkvarhRead
AI54Phase A Pos KVAHPhase A Pos KVAHkVAhRead
AI55Phase B Pos KVAHPhase B Pos KVAHkVAhRead
AI56Phase C Pos KVAHPhase C Pos KVAHkVAhRead
AI57Peak Sliding Window KWPeak Sliding Window KWkWRead
AImin58FrequencyFrequencyHzRead
AI59Clear Totalizers YearYear totalizers were last clearedRead
AI60Clear Totalizers Day MonthDay/month totalizers cleared (LSB day, next byte month)Read
AI61Clear Totalizers TimeTime totalizers cleared (LSB minutes, next byte hours)Read
AI62Peak Window KW YearYear of peak window kWRead
AI63Peak Window KW Day MonthDay/month of peak window kW (LSB day, next byte month)Read
AI64Peak Window KW TimeTime of peak window kW (LSB minutes, next byte hours)Read
AI65Clear Peak KW YearYear peak kW was last clearedRead
AI66Clear Peak KW Day MonthDay/month peak kW cleared (LSB day, next byte month)Read
AI67Clear Peak KW TimeTime peak kW cleared (LSB minutes, next byte hours)Read
AV1Power System TypePower system typeWrite0=3-Wire Delta, 1=4-Wire Wye, 2=2-Wire Single Phase, 3=3-Wire Single Phase, 4=4-Wire Delta
AV2Full Scale VoltsFull scale volts, 120-32000VWrite
AV3Full Scale AmpsFull scale amps, 5-6000AWrite
AV4CT TypeCT typeWrite0=Safe-CTs non-matched, 1=5A CTs non-matched, 2=Safe-CTs matched set, 3=5A CTs matched set
AV5‘A’ Phase Cal NumberPhase A calibration number, 9500-10500Write
AV6‘B’ Phase Cal NumberPhase B calibration number, 9500-10500Write
AV7‘C’ Phase Cal NumberPhase C calibration number, 9500-10500Write
AV8Volt-Amp PairingVolt-amp (voltage/CT) pairingWrite0=L1/CTA L2/CTB L3/CTC (normal), 1=L1/CTB L2/CTA L3/CTC, 2=L1/CTA L2/CTC L3/CTB, 3=L1/CTC L2/CTB L3/CTA, 4=L1/CTC L2/CTA L3/CTB, 5=L1/CTB L2/CTC L3/CTA
AV9CTA PolarityCT A polarityWrite0=Normal, 1=Reversed
AV10CTB PolarityCT B polarityWrite0=Normal, 1=Reversed
AV11CTC PolarityCT C polarityWrite0=Normal, 1=Reversed
AV12KW Sliding Window PeriodkW sliding window period, 5-60 minminWrite
AV13Contact 1 FunctionContact 1 function (pulse or alarm)Write0=Positive KWH pulse, 1=Negative KWH pulse, 2=Low Volts alarm N.O, 3=Low Volts alarm N.C., 4=Unbalanced Volts alarm N.O., 5=Unbalanced Volts alarm N.C., 6=Low OR Unbal Volts alarm N.O., 7=Low OR Unbal Volts alarm N.C.
AV14Contact 2 FunctionContact 2 function (pulse or alarm)Write0=Positive KWH pulse, 1=Negative KWH pulse, 2=Low Volts alarm N.O, 3=Low Volts alarm N.C., 4=Unbalanced Volts alarm N.O., 5=Unbalanced Volts alarm N.C., 6=Low OR Unbal Volts alarm N.O., 7=Low OR Unbal Volts alarm N.C.
AV15Minimum KWH Pulse WidthkWh pulse width, 50-2000 ms in 50 ms stepsmsWrite
AV16KWH Per PulskWh per pulsekWhWrite0=0.01 KWH/pulse, 1=0.1 KWH/pulse, 2=1 KWH/pulse, 3=10 KWH/pulse
AV17Low Volts Alarm ThresholdLow volts alarm threshold, 0-99 (0 = off)%Write
AV18Unbalanced Volts Alarm ThresholdUnbalanced volts alarm threshold, 0-99 (0 = off)%Write
AV19mA Output FunctionmA output functionWrite1=Total Bidirectional KW, 2=Sliding Window KW, 3=Peak Window KW, 4=Total KVA, 5=Total Power Factor, 6=Average amps, 7=Average volts
AV20Name Tag Part 1Name tag characters, part 1 (two ASCII bytes)Write
AV21Name Tag Part 2Name tag characters, part 2 (two ASCII bytes)Write
AV22Name Tag Part 3Name tag characters, part 3 (two ASCII bytes)Write
AV23Name Tag Part 4Name tag characters, part 4 (two ASCII bytes)Write
AV24Name Tag Part 5Name tag characters, part 5 (two ASCII bytes)Write
AV25Name Tag Part 6Name tag characters, part 6 (two ASCII bytes)Write
AV26Displayed Values 1Display item bit flags, set 1Write
AV27Displayed Values 2Display item bit flags, set 2Write
AV28Displayed Values 3Display item bit flags, set 3Write
AV29Displayed Values 4Display item bit flags, set 4Write
AV30Display ActionDisplay icons / rotationWrite0=No icons, no rotate, 1=Show icons, no rotate, 2=No icons, rotate, 3=Show icons, rotate display
AV31YearMeter clock yearWrite
AV32Day MonthMeter clock day/month (LSB day, next byte month)Write
AV33TimeMeter clock time (LSB minutes, next byte hours)Write
AO1Clear TotalizersWrite any value to clear totalizers; self-resets to 0Write
AO2Clear Peak Sliding WindowWrite any value to clear peak sliding window kW; self-resetsWrite
BO1Clear TotalizersSet active to clear totalizers; self-resetsWrite
BO2Clear Peak Sliding WindowSet active to clear peak sliding window kW; self-resetsWrite
Object ID lookup: Kele endicator PT-NT4-BAC-E power meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the endicator PT-NT4-BAC-E power meter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP)

How many BACnet points does the Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP) have?

This list has 104 BACnet objects: 67 analog inputs, 2 analog outputs, 33 analog values, 2 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP) BACnet points are writable?

37 of the 104 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP) BACnet documentation?

The source is BACnet MS/TP Point Mapping for the endicator Power Meter, published free by Kele at https://assets.kele.com/Catalog/17%20Power%20Monitoring/PDFs/PT-NT4-BAC-E%20Point%20Mapping.pdf.

What are the minimum BACnet points to integrate the Kele endicator PT-NT4-BAC-E power meter (BACnet MS/TP)?

Start with AI 4 Total KW (Total real power, kW); AI 36 Total Net KWH (Net energy, kWh); AI 33 Total Pos KWH (Imported energy, kWh); AI 17 Total Power Factor (Total power factor); AI 21 Average LL Volts (Average line-line volts); AI 29 Average Amps (Average current); AI 58 Frequency (Line frequency, Hz).

How do I check these points on the real endicator PT-NT4-BAC-E power meter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: BACnet MS/TP Point Mapping for the endicator Power Meter. Object names, instances and units are reproduced as published; descriptions are our own.