 "manufacturer": "Kele",
 "manufacturer_slug": "kele",
 "model": "endicator PT-NT4-BAC-E power meter (BACnet MS/TP)",
 "model_slug": "endicator-pt-nt4-bac-e",
 "aliases": [
  "endicator",
  "PT-NT4-BAC-E",
  "PT-NT4-BAC",
  "Kele endicator power meter"
 ],
 "equipment_type": "Power meter",
 "applies_to": "Kele endicator PT-NT4-BAC-E power and energy meter (single- or three-phase systems) with BACnet MS/TP.",
 "summary": "The endicator (PT-NT4-BAC-E) is a power and energy meter with a BACnet MS/TP interface. Analog Inputs carry power, power factor, volts, amps, frequency and import/export energy totals per phase; Analog Values hold the meter set-up (system type, CT type and pairing, pulse contacts, alarms, display); two AO/BO pairs clear the totalizers and the peak demand.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "Object names are the printed descriptions; the mapping has no separate object-name column.",
  "All Analog Inputs are read-only. AVs are set-up values; access for AV/AO/BO is not printed and is taken as writable from the notes and object type.",
  "Dates and times (clear totalizers, peak window, meter clock) are packed: low byte day or minutes, next byte month or hours.",
  "AV 20-25 hold the meter's name tag as pairs of ASCII characters; AV 26-29 are bit flags choosing what the display shows."
 ],
 "source": {
  "title": "BACnet MS/TP Point Mapping for the endicator Power Meter",
  "doc_number": null,
  "revision_date": null,
  "url": "https://assets.kele.com/Catalog/17%20Power%20Monitoring/PDFs/PT-NT4-BAC-E%20Point%20Mapping.pdf"
 },
 "integration": {
  "summary": "Read total kW, kWh and the per-phase volts and amps; set system type, full-scale volts/amps and CT type once at commissioning.",
  "minimum_points": [
   {
    "ref": "AI 4",
    "name": "Total KW",
    "why": "Total real power, kW"
   },
   {
    "ref": "AI 36",
    "name": "Total Net KWH",
    "why": "Net energy, kWh"
   },
   {
    "ref": "AI 33",
    "name": "Total Pos KWH",
    "why": "Imported energy, kWh"
   },
   {
    "ref": "AI 17",
    "name": "Total Power Factor",
    "why": "Total power factor"
   },
   {
    "ref": "AI 21",
    "name": "Average LL Volts",
    "why": "Average line-line volts"
   },
   {
    "ref": "AI 29",
    "name": "Average Amps",
    "why": "Average current"
   },
   {
    "ref": "AI 58",
    "name": "Frequency",
    "why": "Line frequency, Hz"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "Set AV 1 (power system type), AV 2/AV 3 (full-scale volts/amps) and AV 4 (CT type) to match the installation."
  ],
  "gotchas": [
   "AO 1 / BO 1 clear all energy totalizers; don't write them from routine logic."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Serial Number",
   "description": "Serial Number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Firmware Version",
   "description": "Firmware Version",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Auto/Manual Wiring Configuration",
   "description": "Wiring set up manually (0) or auto-configured (1)",
   "units": "",
   "access": "R",
   "states": "0=Manual, 1=Auto-configured"
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Total KW",
   "description": "Total KW",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Sliding Window KW",
   "description": "Sliding Window KW",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Total KVAR",
   "description": "Total KVAR",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Total KVA",
   "description": "Total KVA",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Phase A KW",
   "description": "Phase A KW",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Phase B KW",
   "description": "Phase B KW",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Phase C KW",
   "description": "Phase C KW",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Phase A KVAR",
   "description": "Phase A KVAR",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "Phase B KVAR",
   "description": "Phase B KVAR",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Phase C KVAR",
   "description": "Phase C KVAR",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "Phase A KVA",
   "description": "Phase A KVA",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Phase B KVA",
   "description": "Phase B KVA",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Phase C KVA",
   "description": "Phase C KVA",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Total Power Factor",
   "description": "Total Power Factor",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "Phase A Power Factor",
   "description": "Phase A Power Factor",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "Phase B Power Factor",
   "description": "Phase B Power Factor",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Phase C Power Factor",
   "description": "Phase C Power Factor",
   "units": "PF",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "Average LL Volts",
   "description": "Average LL Volts",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "Average LN Volts",
   "description": "Average LN Volts",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "L1-L2 Volts",
   "description": "L1-L2 Volts",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "L2-L3 Volts",
   "description": "L2-L3 Volts",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "L3-L1 Volts",
   "description": "L3-L1 Volts",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "L1-N Volts",
   "description": "L1-N Volts",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "L2-N Volts",
   "description": "L2-N Volts",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "L3-N Volts",
   "description": "L3-N Volts",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "Average Amps",
   "description": "Average Amps",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "Phase A Amps",
   "description": "Phase A Amps",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "Phase B Amps",
   "description": "Phase B Amps",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "Phase C Amps",
   "description": "Phase C Amps",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "Total Pos KWH",
   "description": "Total Pos KWH",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "Total Neg KWH",
   "description": "Total Neg KWH",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "Total Abs KWH",
   "description": "Total Abs KWH",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "Total Net KWH",
   "description": "Total Net KWH",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "Total Pos KVARH",
   "description": "Total Pos KVARH",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "Total Neg KVARH",
   "description": "Total Neg KVARH",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "Total Abs KVARH",
   "description": "Total Abs KVARH",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "Total Net KVARH",
   "description": "Total Net KVARH",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "Total KVAH",
   "description": "Total KVAH",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "Phase A Pos KWH",
   "description": "Phase A Pos KWH",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "Phase B Pos KWH",
   "description": "Phase B Pos KWH",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "Phase C Pos KWH",
   "description": "Phase C Pos KWH",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "Phase A Neg KWH",
   "description": "Phase A Neg KWH",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "Phase B Neg KWH",
   "description": "Phase B Neg KWH",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "Phase C Neg KWH",
   "description": "Phase C Neg KWH",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "Phase A Pos KVARH",
   "description": "Phase A Pos KVARH",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "Phase B Pos KVARH",
   "description": "Phase B Pos KVARH",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "Phase C Pos KVARH",
   "description": "Phase C Pos KVARH",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "Phase A Neg KVARH",
   "description": "Phase A Neg KVARH",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "Phase B Neg KVARH",
   "description": "Phase B Neg KVARH",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "Phase C Neg KVARH",
   "description": "Phase C Neg KVARH",
   "units": "kvarh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "Phase A Pos KVAH",
   "description": "Phase A Pos KVAH",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "Phase B Pos KVAH",
   "description": "Phase B Pos KVAH",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "Phase C Pos KVAH",
   "description": "Phase C Pos KVAH",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 57,
   "name": "Peak Sliding Window KW",
   "description": "Peak Sliding Window KW",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "Frequency",
   "description": "Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 59,
   "name": "Clear Totalizers Year",
   "description": "Year totalizers were last cleared",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 60,
   "name": "Clear Totalizers Day Month",
   "description": "Day/month totalizers cleared (LSB day, next byte month)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "Clear Totalizers Time",
   "description": "Time totalizers cleared (LSB minutes, next byte hours)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 62,
   "name": "Peak Window KW Year",
   "description": "Year of peak window kW",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "Peak Window KW Day Month",
   "description": "Day/month of peak window kW (LSB day, next byte month)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "Peak Window KW Time",
   "description": "Time of peak window kW (LSB minutes, next byte hours)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "Clear Peak KW Year",
   "description": "Year peak kW was last cleared",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "Clear Peak KW Day Month",
   "description": "Day/month peak kW cleared (LSB day, next byte month)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "Clear Peak KW Time",
   "description": "Time peak kW cleared (LSB minutes, next byte hours)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Power System Type",
   "description": "Power system type",
   "units": "",
   "access": "W",
   "states": "0=3-Wire Delta, 1=4-Wire Wye, 2=2-Wire Single Phase, 3=3-Wire Single Phase, 4=4-Wire Delta"
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Full Scale Volts",
   "description": "Full scale volts, 120-32000",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Full Scale Amps",
   "description": "Full scale amps, 5-6000",
   "units": "A",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "CT Type",
   "description": "CT type",
   "units": "",
   "access": "W",
   "states": "0=Safe-CTs non-matched, 1=5A CTs non-matched, 2=Safe-CTs matched set, 3=5A CTs matched set"
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "‘A’ Phase Cal Number",
   "description": "Phase A calibration number, 9500-10500",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "‘B’ Phase Cal Number",
   "description": "Phase B calibration number, 9500-10500",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "‘C’ Phase Cal Number",
   "description": "Phase C calibration number, 9500-10500",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Volt-Amp Pairing",
   "description": "Volt-amp (voltage/CT) pairing",
   "units": "",
   "access": "W",
   "states": "0=L1/CTA L2/CTB L3/CTC (normal), 1=L1/CTB L2/CTA L3/CTC, 2=L1/CTA L2/CTC L3/CTB, 3=L1/CTC L2/CTB L3/CTA, 4=L1/CTC L2/CTA L3/CTB, 5=L1/CTB L2/CTC L3/CTA"
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "CTA Polarity",
   "description": "CT A polarity",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Reversed"
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "CTB Polarity",
   "description": "CT B polarity",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Reversed"
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "CTC Polarity",
   "description": "CT C polarity",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Reversed"
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "KW Sliding Window Period",
   "description": "kW sliding window period, 5-60 min",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Contact 1 Function",
   "description": "Contact 1 function (pulse or alarm)",
   "units": "",
   "access": "W",
   "states": "0=Positive KWH pulse, 1=Negative KWH pulse, 2=Low Volts alarm N.O, 3=Low Volts alarm N.C., 4=Unbalanced Volts alarm N.O., 5=Unbalanced Volts alarm N.C., 6=Low OR Unbal Volts alarm N.O., 7=Low OR Unbal Volts alarm N.C."
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Contact 2 Function",
   "description": "Contact 2 function (pulse or alarm)",
   "units": "",
   "access": "W",
   "states": "0=Positive KWH pulse, 1=Negative KWH pulse, 2=Low Volts alarm N.O, 3=Low Volts alarm N.C., 4=Unbalanced Volts alarm N.O., 5=Unbalanced Volts alarm N.C., 6=Low OR Unbal Volts alarm N.O., 7=Low OR Unbal Volts alarm N.C."
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Minimum KWH Pulse Width",
   "description": "kWh pulse width, 50-2000 ms in 50 ms steps",
   "units": "ms",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "KWH Per Puls",
   "description": "kWh per pulse",
   "units": "kWh",
   "access": "W",
   "states": "0=0.01 KWH/pulse, 1=0.1 KWH/pulse, 2=1 KWH/pulse, 3=10 KWH/pulse"
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Low Volts Alarm Threshold",
   "description": "Low volts alarm threshold, 0-99 (0 = off)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "Unbalanced Volts Alarm Threshold",
   "description": "Unbalanced volts alarm threshold, 0-99 (0 = off)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "mA Output Function",
   "description": "mA output function",
   "units": "",
   "access": "W",
   "states": "1=Total Bidirectional KW, 2=Sliding Window KW, 3=Peak Window KW, 4=Total KVA, 5=Total Power Factor, 6=Average amps, 7=Average volts"
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "Name Tag Part 1",
   "description": "Name tag characters, part 1 (two ASCII bytes)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "Name Tag Part 2",
   "description": "Name tag characters, part 2 (two ASCII bytes)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "Name Tag Part 3",
   "description": "Name tag characters, part 3 (two ASCII bytes)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "Name Tag Part 4",
   "description": "Name tag characters, part 4 (two ASCII bytes)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "Name Tag Part 5",
   "description": "Name tag characters, part 5 (two ASCII bytes)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Name Tag Part 6",
   "description": "Name tag characters, part 6 (two ASCII bytes)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "Displayed Values 1",
   "description": "Display item bit flags, set 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "Displayed Values 2",
   "description": "Display item bit flags, set 2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "Displayed Values 3",
   "description": "Display item bit flags, set 3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "Displayed Values 4",
   "description": "Display item bit flags, set 4",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "Display Action",
   "description": "Display icons / rotation",
   "units": "",
   "access": "W",
   "states": "0=No icons, no rotate, 1=Show icons, no rotate, 2=No icons, rotate, 3=Show icons, rotate display"
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "Year",
   "description": "Meter clock year",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "Day Month",
   "description": "Meter clock day/month (LSB day, next byte month)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "Time",
   "description": "Meter clock time (LSB minutes, next byte hours)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "Clear Totalizers",
   "description": "Write any value to clear totalizers; self-resets to 0",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 2,
   "name": "Clear Peak Sliding Window",
   "description": "Write any value to clear peak sliding window kW; self-resets",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "Clear Totalizers",
   "description": "Set active to clear totalizers; self-resets",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "Clear Peak Sliding Window",
   "description": "Set active to clear peak sliding window kW; self-resets",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/kele/endicator-pt-nt4-bac-e",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}