Easy BACnet
  1. Home
  2. BACnet points lists
  3. Kaiterra
  4. Sensedge SE-100 smart air quality monitor (BACnet IP)

Indoor air quality sensor (PM, TVOC, CO2, temperature, humidity) · BACnet points list

Kaiterra Sensedge SE-100 smart air quality monitor (BACnet IP) BACnet points list

Updated 6 November 2026

Short answer

The Sensedge monitor serves its readings on BACnet IP (IPv4 and IPv6, UDP 47808) as nine Analog Inputs: PM2.5, PM10, TVOC, temperature, humidity, CO2, an unassigned slot and two sensor-module lifespans. All objects support COV.

This page lists 9 BACnet objects for the Kaiterra Sensedge SE-100 smart air quality monitor (BACnet IP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Kaiterra’s own free documentation, linked below.

Manufacturer
Kaiterra
Model
Sensedge SE-100 smart air quality monitor (BACnet IP)
Equipment
Indoor air quality sensor (PM, TVOC, CO2, temperature, humidity)
Equipment type
Thermostats, sensors & meters
BACnet objects
9 (0 writable)
Transport
BACnet IP
Firmware
1.15.12
Default device instance
User-specified
Also known as
Sensedge, SE-100, Kaiterra Sensedge, Sensedge air quality monitor
Source document
Kaiterra Sensedge BACnet Protocol Implementation Conformance Statement (PICS) · rev. 2024-02-27
Download CSV 9 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Kaiterra’s current documentation and the live device before use. Not official Kaiterra information. Terms of use.

BMS integration notes: Kaiterra Sensedge SE-100 smart air quality monitor (BACnet IP)

Integration in brief

Enable BACnet IP on the monitor, give it a unique device instance, then read CO2, PM2.5, TVOC, temperature and humidity. COV subscriptions are supported.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 5CO2CO2 concentrationRead
AI 0PM2.5PM2.5 concentrationRead
AI 2TVOCTotal VOC levelRead
AI 3TemperatureAir temperatureRead
AI 4HumidityRelative humidityRead

Network setup

Watch out for

Kaiterra Sensedge SE-100 smart air quality monitor (BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

9 of 9 shown
Type
Analog
Show
Kaiterra Sensedge SE-100 smart air quality monitor (BACnet IP) BACnet Points List
DescriptionStates
AImin0PM2.5PM2.5 concentrationRead
AI1PM10PM10 concentrationRead
AImin2TVOCTotal VOCRead
AImin3TemperatureAir temperatureRead
AImin4HumidityRelative humidityRead
AImin5CO2CO2 concentrationRead
AI6UnassignedNot usedRead
AI7KM10X Module LifespanSensor module lifespanRead
AI8KM10X Module LifespanSensor module lifespan (second module)Read
Object ID lookup: Kaiterra Sensedge SE-100 smart air quality monitor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Sensedge SE-100 smart air quality monitor (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Kaiterra Sensedge SE-100 smart air quality monitor (BACnet IP)

How many BACnet points does the Kaiterra Sensedge SE-100 smart air quality monitor (BACnet IP) have?

This list has 9 BACnet objects: 9 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Kaiterra Sensedge SE-100 smart air quality monitor (BACnet IP) BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Kaiterra Sensedge SE-100 smart air quality monitor (BACnet IP) BACnet documentation?

The source is Kaiterra Sensedge BACnet Protocol Implementation Conformance Statement (PICS), revision 2024-02-27, published free by Kaiterra at https://support.kaiterra.com/hubfs/CS%20Documentation/Kaiterra%20Sensedge%20BACnet%20Protocol%20Implementation%20Conformance%20Statement%20-%20February%202024.pdf?hsLang=en.

What are the minimum BACnet points to integrate the Kaiterra Sensedge SE-100 smart air quality monitor (BACnet IP)?

Start with AI 5 CO2 (CO2 concentration); AI 0 PM2.5 (PM2.5 concentration); AI 2 TVOC (Total VOC level); AI 3 Temperature (Air temperature); AI 4 Humidity (Relative humidity).

How do I check these points on the real Sensedge SE-100 smart air quality monitor (BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Kaiterra BACnet points lists

Source: Kaiterra Sensedge BACnet Protocol Implementation Conformance Statement (PICS) · rev. 2024-02-27. Object names, instances and units are reproduced as published; descriptions are our own.