Indoor air quality sensor · BACnet points list
Kaiterra Sensedge Mini Indoor Air Quality Monitor (SE-200 / SE-200P) BACnet points list
Updated 6 November 2026
The Sensedge Mini is an indoor air quality monitor built around swappable sensor modules. Over BACnet IP it exposes one Analog Input per measurement (PM2.5, PM10, TVOC, temperature, humidity, CO2, ozone, NO2, CO, differential pressure and module lifespans) at fixed instance numbers.
This page lists 16 BACnet objects for the Kaiterra Sensedge Mini Indoor Air Quality Monitor (SE-200 / SE-200P) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Kaiterra’s own free documentation, linked below.
- Manufacturer
- Kaiterra
- Model
- Sensedge Mini Indoor Air Quality Monitor (SE-200 / SE-200P)
- Equipment
- Indoor air quality sensor
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 16 (0 writable)
- Transport
- BACnet IP
- Firmware
- Firmware 1.0, application software 2.6.5 (PICS)
- Also known as
- Sensedge Mini, SE-200, SE-200P, Kaiterra-SE-200
Reference only, provided as-is: verify against Kaiterra’s current documentation and the live device before use. Not official Kaiterra information. Terms of use.
BMS integration notes: Kaiterra Sensedge Mini Indoor Air Quality Monitor (SE-200 / SE-200P)
Read the AIs for the measurements fitted to the unit. Re-read the object list after sensor modules are added or removed. COV subscriptions are supported.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 6 | CO2 | CO2 concentration | Read |
| AI 1 | PM2.5 | PM2.5 concentration | Read |
| AI 3 | TVOC | Total volatile organic compounds | Read |
| AI 4 | Temperature | Room temperature | Read |
| AI 5 | Humidity | Relative humidity | Read |
Network setup
- BACnet IP over Ethernet or 2.4 GHz Wi-Fi; UDP port 47808 by default and user-configurable.
- The device instance is user-set (Object_Identifier is writable); the default object name is "Kaiterra-SE-200".
- Foreign device registration to a remote BBMD is supported.
Watch out for
- Units can only be changed for TVOC (ppb or µg/m³) and Temperature (°C or °F); other unit writes are rejected.
Kaiterra Sensedge Mini Indoor Air Quality Monitor (SE-200 / SE-200P) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | Sec (Reserved, deprecated) | Reserved, deprecated | Read | ||
| AImin | 1 | PM2.5 | Read | |||
| AI | 2 | PM10 | Read | |||
| AImin | 3 | TVOC | Units ppb or µg/m³ (writable Units) | Read | ||
| AImin | 4 | Temperature | Units °C or °F (writable Units) | Read | ||
| AImin | 5 | Humidity | Read | |||
| AImin | 6 | CO2 | Read | |||
| AI | 7 | Unassigned | Unassigned | Read | ||
| AI | 8 | KM20X Module Lifespan | Read | |||
| AI | 9 | KM20X Module Lifespan | Read | |||
| AI | 10 | O3 | Read | |||
| AI | 11 | Differential Pressure | Read | |||
| AI | 12 | Flow Speed Pressure | Read | |||
| AI | 13 | In-duct Module Lifespan | Read | |||
| AI | 14 | NO2 | Read | |||
| AI | 15 | CO | Read |
No points match these filters.
Object ID lookup: Kaiterra Sensedge Mini Indoor Air Quality Monitor point IDs by name
Integration notes
- From the Analog Input table in the Sensedge Mini PICS (September 2026). Instance numbers are fixed per measurement.
- Only the AIs for the installed sensor modules are present; the device updates Object_List and Database_Revision when modules change.
- AI 8 and AI 9 are both printed as "KM20X Module Lifespan". No units are printed in the table.
- Present_Value is writable only while Out_Of_Service is TRUE; Units, COV_Increment and Out_Of_Service are writable.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Sensedge Mini Indoor Air Quality Monitor (SE-200 / SE-200P) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Kaiterra Sensedge Mini Indoor Air Quality Monitor (SE-200 / SE-200P)
How many BACnet points does the Kaiterra Sensedge Mini Indoor Air Quality Monitor (SE-200 / SE-200P) have?
This list has 16 BACnet objects: 16 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Kaiterra Sensedge Mini Indoor Air Quality Monitor (SE-200 / SE-200P) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Kaiterra Sensedge Mini Indoor Air Quality Monitor (SE-200 / SE-200P) BACnet documentation?
The source is Kaiterra Sensedge Mini BACnet Protocol Implementation Conformance Statement (PICS), revision September 2, 2026, published free by Kaiterra at https://support.kaiterra.com/hubfs/Kaiterra%20Sensedge%20Mini%20BACnet%20Protocol%20Implementation%20Conformance%20Statement%20-%20September%202026.pdf?hsLang=en.
What are the minimum BACnet points to integrate the Kaiterra Sensedge Mini Indoor Air Quality Monitor (SE-200 / SE-200P)?
Start with AI 6 CO2 (CO2 concentration); AI 1 PM2.5 (PM2.5 concentration); AI 3 TVOC (Total volatile organic compounds); AI 4 Temperature (Room temperature); AI 5 Humidity (Relative humidity).
How do I check these points on the real Sensedge Mini Indoor Air Quality Monitor (SE-200 / SE-200P)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Kaiterra BACnet points lists
Source: Kaiterra Sensedge Mini BACnet Protocol Implementation Conformance Statement (PICS) · rev. September 2, 2026. Object names, instances and units are reproduced as published; descriptions are our own.