Variable frequency drive communication card (VFD) · BACnet points list

INVT EC-TX107 BACnet/IP communication card (Goodrive drives) BACnet points list

Updated 12 November 2026

Short answer

The EC-TX107 card puts an INVT Goodrive drive on BACnet IP as 32 Analog Values. AV 0 is the control word and AV 12 the state word; the PZD send and receive words carry whatever the drive's P15 parameters assign to them (for example set frequency in, running frequency out). AV 24-31 are a parameter read/write channel.

This page lists 32 BACnet objects for the INVT EC-TX107 BACnet/IP communication card (Goodrive drives) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from INVT’s own free documentation, linked below.

Manufacturer
INVT
Model
EC-TX107 BACnet/IP communication card (Goodrive drives)
Equipment
Variable frequency drive communication card (VFD)
Equipment type
VFDs & pumps
BACnet objects
32 (16 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
1
Also known as
EC-TX107, ECTX107, INVT BACnet IP card, GD300-16 BACnet, Goodrive300-16 BACnet
Source document
EC-TX107 BACnet/IP Communication Card Manual
Download CSV 32 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against INVT’s current documentation and the live device before use. Not official INVT information. Terms of use.

BMS integration notes: INVT EC-TX107 BACnet/IP communication card (Goodrive drives)

Integration in brief

Set the drive to take commands and frequency from the communication card (P00.01 = 2, P00.02 = 1 on the GD300-16), assign P15.02 = 1 so AV 1 is the set frequency, and assign the P15.13+ words you want back (running frequency, current, fault code). Then write AV 0 = 1 to run forward and 5 to stop.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0CONTROL_WORDControl word: 1 = run fwd, 5 = stop, 7 = fault resetCommand
AV 1PZD2_SENDSet frequency x100 Hz when P15.02 = 1Command
AV 12STATUS_WORDState word: 1 = fwd run, 3 = stopped, 4 = faultRead
AV 13PZD2_RECEIVERunning frequency x100 Hz when P15.13 = 1Read

Enable & remote start

Run commands and frequency must come from the communication card: P00.01 = 2 and P00.02 = 1 on the GD300-16.

Heartbeat & communication loss

P15.41 sets a communication timeout; 0 (default) disables timeout detection.

Network setup

Watch out for

INVT EC-TX107 BACnet/IP communication card (Goodrive drives) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

32 of 32 shown
Type
Analog
Access
Show
INVT EC-TX107 BACnet/IP communication card (Goodrive drives) BACnet Points List
DescriptionStates
AVmin0CONTROL_WORDDrive control word (1 = run forward, 5 = decel stop, 7 = fault reset)Command
AVmin1PZD2_SENDProcess data word to the drive; meaning set by P15.02Command
AV2PZD3_SENDProcess data word to the drive; meaning set by P15.03Command
AV3PZD4_SENDProcess data word to the drive; meaning set by P15.04Command
AV4PZD5_SENDProcess data word to the drive; meaning set by P15.05Command
AV5PZD6_SENDProcess data word to the drive; meaning set by P15.06Command
AV6PZD7_SENDProcess data word to the drive; meaning set by P15.07Command
AV7PZD8_SENDProcess data word to the drive; meaning set by P15.08Command
AV8PZD9_SENDProcess data word to the drive; meaning set by P15.09Command
AV9PZD10_SENDProcess data word to the drive; meaning set by P15.10Command
AV10PZD11_SENDProcess data word to the drive; meaning set by P15.11Command
AV11PZD12_SENDProcess data word to the drive; meaning set by P15.12Command
AVmin12STATUS_WORDDrive state word (1 = fwd run, 3 = stopped, 4 = fault)Read
AVmin13PZD2_RECEIVEProcess data word from the drive; meaning set by P15.13Read
AV14PZD3_RECEIVEProcess data word from the drive; meaning set by P15.14Read
AV15PZD4_RECEIVEProcess data word from the drive; meaning set by P15.15Read
AV16PZD5_RECEIVEProcess data word from the drive; meaning set by P15.16Read
AV17PZD6_RECEIVEProcess data word from the drive; meaning set by P15.17Read
AV18PZD7_RECEIVEProcess data word from the drive; meaning set by P15.18Read
AV19PZD8_RECEIVEProcess data word from the drive; meaning set by P15.19Read
AV20PZD9_RECEIVEProcess data word from the drive; meaning set by P15.20Read
AV21PZD10_RECEIVEProcess data word from the drive; meaning set by P15.21Read
AV22PZD11_RECEIVEProcess data word from the drive; meaning set by P15.22Read
AV23PZD12_RECEIVEProcess data word from the drive; meaning set by P15.23Read
AV24PKW1_SENDTask identity (request)Command
AV25PKW2_SENDParameter address (request)Command
AV26PKW3_SENDParameter value MSBs (request)Command
AV27PKW4_SENDParameter value LSBs (request)Command
AV28PKW1_RECEIVEResponse identityRead
AV29PKW2_RECEIVEParameter address (response)Read
AV30PKW3_RECEIVEParameter value MSBs or error code (response)Read
AV31PKW4_RECEIVEParameter value LSBs (response)Read
Object ID lookup: INVT EC-TX107 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EC-TX107 BACnet/IP communication card (Goodrive drives) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the INVT EC-TX107 BACnet/IP communication card (Goodrive drives)

How many BACnet points does the INVT EC-TX107 BACnet/IP communication card (Goodrive drives) have?

This list has 32 BACnet objects: 32 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which INVT EC-TX107 BACnet/IP communication card (Goodrive drives) BACnet points are writable?

16 of the 32 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official INVT EC-TX107 BACnet/IP communication card (Goodrive drives) BACnet documentation?

The source is EC-TX107 BACnet/IP Communication Card Manual, published free by INVT at https://www.invt.com/uploads/file1/20220826/EC-TX107%20BACnetIP%20Communication%20Card%20Manual.pdf.

What are the minimum BACnet points to integrate the INVT EC-TX107 BACnet/IP communication card (Goodrive drives)?

Start with AV 0 CONTROL_WORD (Control word: 1 = run fwd, 5 = stop, 7 = fault reset); AV 1 PZD2_SEND (Set frequency x100 Hz when P15.02 = 1); AV 12 STATUS_WORD (State word: 1 = fwd run, 3 = stopped, 4 = fault); AV 13 PZD2_RECEIVE (Running frequency x100 Hz when P15.13 = 1).

How do I enable BMS control of the INVT EC-TX107 BACnet/IP communication card (Goodrive drives)?

Run commands and frequency must come from the communication card: P00.01 = 2 and P00.02 = 1 on the GD300-16.

Does the INVT EC-TX107 BACnet/IP communication card (Goodrive drives) need a BACnet heartbeat or have a communication timeout?

P15.41 sets a communication timeout; 0 (default) disables timeout detection.

How do I check these points on the real EC-TX107 BACnet/IP communication card (Goodrive drives)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: EC-TX107 BACnet/IP Communication Card Manual. Object names, instances and units are reproduced as published; descriptions are our own.