Variable frequency drive · BACnet points list

Invertek Drives Optidrive Eco (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The Optidrive Eco has BACnet MS/TP built in on its RJ45 RS-485 port, enabled by setting P1-12 = 6. It exposes 34 binary values (drive status flags, digital inputs, relay states, and commandable run/stop, fast stop, coast stop, trip reset and relay commands) and 25 analog values (frequency, speed, current, power, bus voltage, temperature, trip code, I/O levels, energy and hour meters, plus writable speed reference, ramp time and PID values).

This page lists 59 BACnet objects for the Invertek Drives Optidrive Eco (BACnet MS/TP) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Invertek Drives’s own free documentation, linked below.

Manufacturer
Invertek Drives
Model
Optidrive Eco (BACnet MS/TP)
Equipment
Variable frequency drive
Equipment type
VFDs & pumps
BACnet objects
59 (13 writable)
Transport
BACnet MS/TP
Firmware
PICS lists application software and firmware 2.00
Default device instance
1 (P5-10 x 65536 + P5-09; defaults P5-09 = 1, P5-10 = 0)
Also known as
Optidrive Eco, ODV-3, Invertek Optidrive Eco, Invertek ODV-3, 82-HEMAN-IN
Source document
Optidrive Eco User Guide · 82-HEMAN-IN Version 3.13 · rev. 2024
Download CSV 59 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Invertek Drives’s current documentation and the live device before use. Not official Invertek Drives information. Terms of use.

BMS integration notes: Invertek Drives Optidrive Eco (BACnet MS/TP)

Integration in brief

Set P1-14 = 101 for the extended parameters, give each drive a MAC address (P5-01), baud rate (P5-03), data format (P5-04) and a unique device instance (P5-09/P5-10), then set P1-12 = 6 for BACnet MS/TP control. Command BV 25 run/stop and write the speed reference to AV 15 (Hz). Read BV 0, AV 0, AV 2 and BV 1/AV 8, and reset trips with BV 27.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 25Run/Stop CMDRun/stop command (1 = run)Command
AV 15Speed ReferenceSpeed reference in HzCommand
BV 27Trip ResetResets a trip on a rising edgeCommand
BV 0Run/Stop StateRunning statusRead
BV 2Hand ModeHand or auto modeRead
AV 0Motor FrequencyOutput frequency in HzRead
AV 2Motor CurrentMotor ampsRead
BV 1Trip StateDrive trippedRead
AV 8Trip CodeActive trip codeRead

Enable & remote start

Set P1-12 Primary Command Source = 6 (BACnet MS/TP mode); the drive then takes run/stop and reference from the network. BV 6 Enable State shows whether the hardware enable signal is present, and BV 3 shows a hardware inhibit.

Heartbeat & communication loss

P5-05 Communications Loss Timeout (0.0-5.0 s, default 1.0 s): if no valid telegram arrives in that time the drive treats it as a comms loss and acts per P5-06: 0 trip and coast to stop (default), 1 ramp to stop then trip, 2 ramp to stop only, 3 run at preset speed 4.

Sensors & values from the BMS

AV 17 User PID Reference and AV 18 User PID Feedback take a PID setpoint and feedback from the BMS when the drive's PID controller is set to use them.

Network setup

Watch out for

Invertek Drives Optidrive Eco (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

59 of 59 shown
Type
AnalogBinary
Access
Show
Invertek Drives Optidrive Eco (BACnet MS/TP) BACnet Points List
DescriptionStates
AVmin0Motor FrequencyMotor output frequencyHzRead
AV1Motor SpeedMotor output speed (0 if P1-10=0)rpmRead
AVmin2Motor CurrentMotor output currentARead
AV3Motor PowerMotor output powerkWRead
AV4Motor torqueReserved%Read
AV5DC Bus VoltageDC bus voltageVRead
AV6Drive temperatureDrive temperature value°CRead
AV7Drive StatusDrive status wordRead
AVmin8Trip CodeDrive trip codeRead
AV9Analog input 1Value of analog input 1%Read
AV10Analog input 2Value of analog input 2%Read
AV11Analog output 1Value of analog output 1%Read
AV12Analog output 2Value of analog output 2%Read
AV13PID ReferencePID controller reference value%Read
AV14PID feedbackPID controller feedback value%Read
AVmin15Speed ReferenceSpeed reference valueHzCommand
AV16User Ramp TimeUser ramp valuesWrite
AV17User PID ReferencePID controller user reference%Write
AV18User PID FeedbackPID controller user feedback%Write
AV19Kilowatt HoursKilowatt hours (can be reset by user)kWhRead
AV20Megawatt HoursMegawatt hours (can be reset by user)MWhRead
AV21KWh meterKilowatt hours meter (cannot be reset)kWhRead
AV22MWh meterMegawatt hours meter (cannot be reset)MWhRead
AV23Total Run HoursTotal run hours since date of manufacturehRead
AV24Current Run HoursRun hours since last time enablehRead
BVmin0Run/Stop StateDrive run statusRead0=STOP, 1=RUN
BVmin1Trip StateDrive is trippedRead0=OK, 1=TRIP
BVmin2Hand ModeDrive is in hand or auto modeRead0=AUTO, 1=HAND
BV3Inhibit ModeDrive hardware inhibit activeRead0=OK, 1=INHIBIT
BV4Mains LossMains loss happenedRead0=NO, 1=YES
BV5Fire ModeDrive is in fire modeRead0=OFF, 1=ON
BV6Enable StateDrive has enable signalRead0=NO, 1=YES
BV7External 24V ModeDrive is in external 24V modeRead0=NO, 1=YES
BV8Maintenance DueMaintenance service is dueRead0=NO, 1=YES
BV9Clean ModePump clean function is onRead0=OFF, 1=ON
BV10Terminal ModeDrive is in terminal control modeRead0=OFF, 1=ON
BV11Bypass ModeDrive is in bypass modeRead0=OFF, 1=ON
BV12Digital Input 1Status of digital input 1Read0=OFF, 1=ON
BV13Digital Input 2Status of digital input 2Read0=OFF, 1=ON
BV14Digital Input 3Status of digital input 3Read0=OFF, 1=ON
BV15Digital Input 4Status of digital input 4Read0=OFF, 1=ON
BV16Digital Input 5Status of digital input 5Read0=OFF, 1=ON
BV17Digital Input 6Status of digital input 6Read0=OFF, 1=ON
BV18Digital Input 7Status of digital input 7Read0=OFF, 1=ON
BV19Digital Input 8Status of digital input 8Read0=OFF, 1=ON
BV20Relay Output 1Status of relay output 1Read0=OPEN, 1=CLOSED
BV21Relay Output 2Status of relay output 2Read0=OPEN, 1=CLOSED
BV22Relay Output 3Status of relay output 3Read0=OPEN, 1=CLOSED
BV23Relay Output 4Status of relay output 4Read0=OPEN, 1=CLOSED
BV24Relay Output 5Status of relay output 5Read0=OPEN, 1=CLOSED
BVmin25Run/Stop CMDDrive run commandCommand0=STOP, 1=RUN
BV26Fast StopFast stop enableCommand0=OFF, 1=ON
BVmin27Trip ResetTrip reset (rising edge active)Command0=OFF, 1=ON
BV28Coast StopCoast stop enable (overrides fast stop)Command0=OFF, 1=ON
BV29Relay 1 CMDRelay output 1 command (relay set to user value)Command0=OPEN, 1=CLOSED
BV30Relay 2 CMDRelay output 2 command (relay set to user value)Command0=OPEN, 1=CLOSED
BV31Relay 3 CMDRelay output 3 command (relay set to user value)Command0=OPEN, 1=CLOSED
BV32Relay 4 CMDRelay output 4 command (relay set to user value)Command0=OPEN, 1=CLOSED
BV33Relay 5 CMDRelay output 5 command (relay set to user value)Command0=OPEN, 1=CLOSED
Object ID lookup: Invertek Drives Optidrive Eco point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Optidrive Eco (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Invertek Drives Optidrive Eco (BACnet MS/TP)

How many BACnet points does the Invertek Drives Optidrive Eco (BACnet MS/TP) have?

This list has 59 BACnet objects: 25 analog values, 34 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Invertek Drives Optidrive Eco (BACnet MS/TP) BACnet points are writable?

13 of the 59 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Invertek Drives Optidrive Eco (BACnet MS/TP) BACnet documentation?

The source is Optidrive Eco User Guide (82-HEMAN-IN Version 3.13), revision 2024, published free by Invertek Drives at https://admin.invertekdrives.com/assets/56AFAD3C-CE1A-4D9D-A91D-F893F86B59D2/82-HEMAN-IN_V3.13%20Optidrive%20Eco%20User%20Guide.pdf.

What are the minimum BACnet points to integrate the Invertek Drives Optidrive Eco (BACnet MS/TP)?

Start with BV 25 Run/Stop CMD (Run/stop command (1 = run)); AV 15 Speed Reference (Speed reference in Hz); BV 27 Trip Reset (Resets a trip on a rising edge); BV 0 Run/Stop State (Running status); BV 2 Hand Mode (Hand or auto mode); AV 0 Motor Frequency (Output frequency in Hz); AV 2 Motor Current (Motor amps); BV 1 Trip State (Drive tripped); AV 8 Trip Code (Active trip code).

How do I enable BMS control of the Invertek Drives Optidrive Eco (BACnet MS/TP)?

Set P1-12 Primary Command Source = 6 (BACnet MS/TP mode); the drive then takes run/stop and reference from the network. BV 6 Enable State shows whether the hardware enable signal is present, and BV 3 shows a hardware inhibit.

Does the Invertek Drives Optidrive Eco (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

P5-05 Communications Loss Timeout (0.0-5.0 s, default 1.0 s): if no valid telegram arrives in that time the drive treats it as a comms loss and acts per P5-06: 0 trip and coast to stop (default), 1 ramp to stop then trip, 2 ramp to stop only, 3 run at preset speed 4.

Can the BMS supply sensor values to the Invertek Drives Optidrive Eco (BACnet MS/TP)?

AV 17 User PID Reference and AV 18 User PID Feedback take a PID setpoint and feedback from the BMS when the drive's PID controller is set to use them.

How do I check these points on the real Optidrive Eco (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Optidrive Eco User Guide · 82-HEMAN-IN Version 3.13 · rev. 2024. Object names, instances and units are reproduced as published; descriptions are our own.