Invertek Drives Optidrive Eco (BACnet MS/TP) BACnet points list
Updated 6 November 2026
The Optidrive Eco has BACnet MS/TP built in on its RJ45 RS-485 port, enabled by setting P1-12 = 6. It exposes 34 binary values (drive status flags, digital inputs, relay states, and commandable run/stop, fast stop, coast stop, trip reset and relay commands) and 25 analog values (frequency, speed, current, power, bus voltage, temperature, trip code, I/O levels, energy and hour meters, plus writable speed reference, ramp time and PID values).
This page lists 59 BACnet objects for the Invertek Drives Optidrive Eco (BACnet MS/TP) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Invertek Drives’s own free documentation, linked below.
- Manufacturer
- Invertek Drives
- Model
- Optidrive Eco (BACnet MS/TP)
- Equipment
- Variable frequency drive
- Equipment type
- VFDs & pumps
- BACnet objects
- 59 (13 writable)
- Transport
- BACnet MS/TP
- Firmware
- PICS lists application software and firmware 2.00
- Default device instance
- 1 (P5-10 x 65536 + P5-09; defaults P5-09 = 1, P5-10 = 0)
- Also known as
- Optidrive Eco, ODV-3, Invertek Optidrive Eco, Invertek ODV-3, 82-HEMAN-IN
Reference only, provided as-is: verify against Invertek Drives’s current documentation and the live device before use. Not official Invertek Drives information. Terms of use.
BMS integration notes: Invertek Drives Optidrive Eco (BACnet MS/TP)
Set P1-14 = 101 for the extended parameters, give each drive a MAC address (P5-01), baud rate (P5-03), data format (P5-04) and a unique device instance (P5-09/P5-10), then set P1-12 = 6 for BACnet MS/TP control. Command BV 25 run/stop and write the speed reference to AV 15 (Hz). Read BV 0, AV 0, AV 2 and BV 1/AV 8, and reset trips with BV 27.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 25 | Run/Stop CMD | Run/stop command (1 = run) | Command |
| AV 15 | Speed Reference | Speed reference in Hz | Command |
| BV 27 | Trip Reset | Resets a trip on a rising edge | Command |
| BV 0 | Run/Stop State | Running status | Read |
| BV 2 | Hand Mode | Hand or auto mode | Read |
| AV 0 | Motor Frequency | Output frequency in Hz | Read |
| AV 2 | Motor Current | Motor amps | Read |
| BV 1 | Trip State | Drive tripped | Read |
| AV 8 | Trip Code | Active trip code | Read |
Enable & remote start
Set P1-12 Primary Command Source = 6 (BACnet MS/TP mode); the drive then takes run/stop and reference from the network. BV 6 Enable State shows whether the hardware enable signal is present, and BV 3 shows a hardware inhibit.
Heartbeat & communication loss
P5-05 Communications Loss Timeout (0.0-5.0 s, default 1.0 s): if no valid telegram arrives in that time the drive treats it as a comms loss and acts per P5-06: 0 trip and coast to stop (default), 1 ramp to stop then trip, 2 ramp to stop only, 3 run at preset speed 4.
Sensors & values from the BMS
AV 17 User PID Reference and AV 18 User PID Feedback take a PID setpoint and feedback from the BMS when the drive's PID controller is set to use them.
Network setup
- P5-01 sets the MS/TP MAC address (1-63, default 1).
- BACnet baud rates 9600, 19200, 38400 or 76800 in P5-03 (factory 115.2 kbps is for Modbus; auto-baud is not supported).
- P5-04 data format: n-1 (default), n-2, O-1 or E-1.
- Device instance = P5-10 x 65536 + P5-09 (0-4194304); P5-11 max master 1-127 (default 127).
- P5-07 = 1 lets the network set the ramp times (AV 16); the guide recommends leaving ramps to P1-03/P1-04.
- Wire RS-485+/RS-485- and 0 V common through the RJ45 port; terminate the end of the line with 120 ohm.
Watch out for
- AV 15 speed reference is in Hz, not %.
- P5-06 default 0 trips the drive on a comms loss; a trip reset (BV 27) is then needed.
- BV 28 Coast Stop overrides BV 26 Fast Stop.
- Relay commands BV 29-33 need the relay function set to user value first.
Invertek Drives Optidrive Eco (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 0 | Motor Frequency | Motor output frequency | Hz | Read | |
| AV | 1 | Motor Speed | Motor output speed (0 if P1-10=0) | rpm | Read | |
| AVmin | 2 | Motor Current | Motor output current | A | Read | |
| AV | 3 | Motor Power | Motor output power | kW | Read | |
| AV | 4 | Motor torque | Reserved | % | Read | |
| AV | 5 | DC Bus Voltage | DC bus voltage | V | Read | |
| AV | 6 | Drive temperature | Drive temperature value | °C | Read | |
| AV | 7 | Drive Status | Drive status word | Read | ||
| AVmin | 8 | Trip Code | Drive trip code | Read | ||
| AV | 9 | Analog input 1 | Value of analog input 1 | % | Read | |
| AV | 10 | Analog input 2 | Value of analog input 2 | % | Read | |
| AV | 11 | Analog output 1 | Value of analog output 1 | % | Read | |
| AV | 12 | Analog output 2 | Value of analog output 2 | % | Read | |
| AV | 13 | PID Reference | PID controller reference value | % | Read | |
| AV | 14 | PID feedback | PID controller feedback value | % | Read | |
| AVmin | 15 | Speed Reference | Speed reference value | Hz | Command | |
| AV | 16 | User Ramp Time | User ramp value | s | Write | |
| AV | 17 | User PID Reference | PID controller user reference | % | Write | |
| AV | 18 | User PID Feedback | PID controller user feedback | % | Write | |
| AV | 19 | Kilowatt Hours | Kilowatt hours (can be reset by user) | kWh | Read | |
| AV | 20 | Megawatt Hours | Megawatt hours (can be reset by user) | MWh | Read | |
| AV | 21 | KWh meter | Kilowatt hours meter (cannot be reset) | kWh | Read | |
| AV | 22 | MWh meter | Megawatt hours meter (cannot be reset) | MWh | Read | |
| AV | 23 | Total Run Hours | Total run hours since date of manufacture | h | Read | |
| AV | 24 | Current Run Hours | Run hours since last time enable | h | Read | |
| BVmin | 0 | Run/Stop State | Drive run status | Read | 0=STOP, 1=RUN | |
| BVmin | 1 | Trip State | Drive is tripped | Read | 0=OK, 1=TRIP | |
| BVmin | 2 | Hand Mode | Drive is in hand or auto mode | Read | 0=AUTO, 1=HAND | |
| BV | 3 | Inhibit Mode | Drive hardware inhibit active | Read | 0=OK, 1=INHIBIT | |
| BV | 4 | Mains Loss | Mains loss happened | Read | 0=NO, 1=YES | |
| BV | 5 | Fire Mode | Drive is in fire mode | Read | 0=OFF, 1=ON | |
| BV | 6 | Enable State | Drive has enable signal | Read | 0=NO, 1=YES | |
| BV | 7 | External 24V Mode | Drive is in external 24V mode | Read | 0=NO, 1=YES | |
| BV | 8 | Maintenance Due | Maintenance service is due | Read | 0=NO, 1=YES | |
| BV | 9 | Clean Mode | Pump clean function is on | Read | 0=OFF, 1=ON | |
| BV | 10 | Terminal Mode | Drive is in terminal control mode | Read | 0=OFF, 1=ON | |
| BV | 11 | Bypass Mode | Drive is in bypass mode | Read | 0=OFF, 1=ON | |
| BV | 12 | Digital Input 1 | Status of digital input 1 | Read | 0=OFF, 1=ON | |
| BV | 13 | Digital Input 2 | Status of digital input 2 | Read | 0=OFF, 1=ON | |
| BV | 14 | Digital Input 3 | Status of digital input 3 | Read | 0=OFF, 1=ON | |
| BV | 15 | Digital Input 4 | Status of digital input 4 | Read | 0=OFF, 1=ON | |
| BV | 16 | Digital Input 5 | Status of digital input 5 | Read | 0=OFF, 1=ON | |
| BV | 17 | Digital Input 6 | Status of digital input 6 | Read | 0=OFF, 1=ON | |
| BV | 18 | Digital Input 7 | Status of digital input 7 | Read | 0=OFF, 1=ON | |
| BV | 19 | Digital Input 8 | Status of digital input 8 | Read | 0=OFF, 1=ON | |
| BV | 20 | Relay Output 1 | Status of relay output 1 | Read | 0=OPEN, 1=CLOSED | |
| BV | 21 | Relay Output 2 | Status of relay output 2 | Read | 0=OPEN, 1=CLOSED | |
| BV | 22 | Relay Output 3 | Status of relay output 3 | Read | 0=OPEN, 1=CLOSED | |
| BV | 23 | Relay Output 4 | Status of relay output 4 | Read | 0=OPEN, 1=CLOSED | |
| BV | 24 | Relay Output 5 | Status of relay output 5 | Read | 0=OPEN, 1=CLOSED | |
| BVmin | 25 | Run/Stop CMD | Drive run command | Command | 0=STOP, 1=RUN | |
| BV | 26 | Fast Stop | Fast stop enable | Command | 0=OFF, 1=ON | |
| BVmin | 27 | Trip Reset | Trip reset (rising edge active) | Command | 0=OFF, 1=ON | |
| BV | 28 | Coast Stop | Coast stop enable (overrides fast stop) | Command | 0=OFF, 1=ON | |
| BV | 29 | Relay 1 CMD | Relay output 1 command (relay set to user value) | Command | 0=OPEN, 1=CLOSED | |
| BV | 30 | Relay 2 CMD | Relay output 2 command (relay set to user value) | Command | 0=OPEN, 1=CLOSED | |
| BV | 31 | Relay 3 CMD | Relay output 3 command (relay set to user value) | Command | 0=OPEN, 1=CLOSED | |
| BV | 32 | Relay 4 CMD | Relay output 4 command (relay set to user value) | Command | 0=OPEN, 1=CLOSED | |
| BV | 33 | Relay 5 CMD | Relay output 5 command (relay set to user value) | Command | 0=OPEN, 1=CLOSED |
No points match these filters.
Object ID lookup: Invertek Drives Optidrive Eco point IDs by name
AV0Motor FrequencyAV1Motor SpeedAV2Motor CurrentAV3Motor PowerAV4Motor torqueAV5DC Bus VoltageAV6Drive temperatureAV7Drive StatusAV8Trip CodeAV9Analog input 1AV10Analog input 2AV11Analog output 1AV12Analog output 2AV13PID ReferenceAV14PID feedbackAV15Speed ReferenceAV16User Ramp TimeAV17User PID ReferenceAV18User PID FeedbackAV19Kilowatt HoursAV20Megawatt HoursAV21KWh meterAV22MWh meterAV23Total Run HoursAV24Current Run HoursBV0Run/Stop StateBV1Trip StateBV2Hand ModeBV3Inhibit ModeBV4Mains LossBV5Fire ModeBV6Enable StateBV7External 24V ModeBV8Maintenance DueBV9Clean ModeBV10Terminal ModeBV11Bypass ModeBV12Digital Input 1BV13Digital Input 2BV14Digital Input 3BV15Digital Input 4BV16Digital Input 5BV17Digital Input 6BV18Digital Input 7BV19Digital Input 8BV20Relay Output 1BV21Relay Output 2BV22Relay Output 3BV23Relay Output 4BV24Relay Output 5BV25Run/Stop CMDBV26Fast StopBV27Trip ResetBV28Coast StopBV29Relay 1 CMDBV30Relay 2 CMDBV31Relay 3 CMDBV32Relay 4 CMDBV33Relay 5 CMD
Integration notes
- Object dictionary from section 10.3.5 of the user guide (pages 73-74); the guide has no other BACnet object types besides the Device object.
- Access codes as printed: R read only, W read or write, C commandable.
- Relay commands BV 29-33 only act when that relay output is set to be driven by a user value.
- AV 4 Motor torque is described as Reserved in the table.
- AV 19/AV 20 energy counters can be reset by the user; AV 21/AV 22 meters cannot.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Optidrive Eco (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Invertek Drives Optidrive Eco (BACnet MS/TP)
How many BACnet points does the Invertek Drives Optidrive Eco (BACnet MS/TP) have?
This list has 59 BACnet objects: 25 analog values, 34 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Invertek Drives Optidrive Eco (BACnet MS/TP) BACnet points are writable?
13 of the 59 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Invertek Drives Optidrive Eco (BACnet MS/TP) BACnet documentation?
The source is Optidrive Eco User Guide (82-HEMAN-IN Version 3.13), revision 2024, published free by Invertek Drives at https://admin.invertekdrives.com/assets/56AFAD3C-CE1A-4D9D-A91D-F893F86B59D2/82-HEMAN-IN_V3.13%20Optidrive%20Eco%20User%20Guide.pdf.
What are the minimum BACnet points to integrate the Invertek Drives Optidrive Eco (BACnet MS/TP)?
Start with BV 25 Run/Stop CMD (Run/stop command (1 = run)); AV 15 Speed Reference (Speed reference in Hz); BV 27 Trip Reset (Resets a trip on a rising edge); BV 0 Run/Stop State (Running status); BV 2 Hand Mode (Hand or auto mode); AV 0 Motor Frequency (Output frequency in Hz); AV 2 Motor Current (Motor amps); BV 1 Trip State (Drive tripped); AV 8 Trip Code (Active trip code).
How do I enable BMS control of the Invertek Drives Optidrive Eco (BACnet MS/TP)?
Set P1-12 Primary Command Source = 6 (BACnet MS/TP mode); the drive then takes run/stop and reference from the network. BV 6 Enable State shows whether the hardware enable signal is present, and BV 3 shows a hardware inhibit.
Does the Invertek Drives Optidrive Eco (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?
P5-05 Communications Loss Timeout (0.0-5.0 s, default 1.0 s): if no valid telegram arrives in that time the drive treats it as a comms loss and acts per P5-06: 0 trip and coast to stop (default), 1 ramp to stop then trip, 2 ramp to stop only, 3 run at preset speed 4.
Can the BMS supply sensor values to the Invertek Drives Optidrive Eco (BACnet MS/TP)?
AV 17 User PID Reference and AV 18 User PID Feedback take a PID setpoint and feedback from the BMS when the drive's PID controller is set to use them.
How do I check these points on the real Optidrive Eco (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: Optidrive Eco User Guide · 82-HEMAN-IN Version 3.13 · rev. 2024. Object names, instances and units are reproduced as published; descriptions are our own.